Case - 2.3 Ef (Star TCC)

This document provides protection settings for three pieces of equipment in the 33kV SWGR-A switchgear: a 120MVA transformer, a 33kV circuit breaker, and a 20MVA transformer. It lists the manufacturer and model of the protection relays for each, along with the current transformer ratios and inverse time overcurrent settings, including pickup values and time dials to achieve specified operation times for 3x, 5x, and 8x pickup current.

Uploaded by

josh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
46 views1 page

Case - 2.3 Ef (Star TCC)

This document provides protection settings for three pieces of equipment in the 33kV SWGR-A switchgear: a 120MVA transformer, a 33kV circuit breaker, and a 20MVA transformer. It lists the manufacturer and model of the protection relays for each, along with the current transformer ratios and inverse time overcurrent settings, including pickup values and time dials to achieve specified operation times for 3x, 5x, and 8x pickup current.

Uploaded by

josh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Amps X 100 33kV(BB-2) SWGR-A (Nom. kV=33, Plot Ref.

kV=33)
.5

10

30

50

100

300

500

1K

3K

5K

1K

10K
1K

500

500

300

300

100

100

H08-RP - G
OC1

50

50

120MVA I/C
ABB
REF615
CT Ratio 2500:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.47
3x = 2.96 s, 5x = 2.01 s, 8x = 1.55 s

30

10

30

10

Seconds

H05-RP - G
OC1
5

33kV B/C
ABB
REF615
CT Ratio 2500:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.44
3x = 2.77 s, 5x = 1.88 s, 8x = 1.45 s

.5

.5

.3

.3

H14-RP - G
OC1

.1

.1

20MVA T/F
ABB
REF615
CT Ratio 600:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.06
3x = 0.378 s, 5x = 0.257 s, 8x = 0.198 s

.05

.03

.05

.03

.01
.5

10

30

50

100

300

500

1K

3K

Amps X 100 33kV(BB-2) SWGR-A (Nom. kV=33, Plot Ref. kV=33)


N7733-ZAKHER
Project:
Location:
Contract:
Engineer:
Filename:

220/33/11kV Zakher Grid


Zakher Area of Al Ain
N7733
JM
C:\ETAP 1250\N7733\N7733.OTI

CASE:2.3 EF
Date:
SN:
Rev:
Fault:
Circuit:

21-01-2016
LARSENTRN2
Base
Ground
120MVAI/C,33kVB/C,20MVA

5K

.01
10K

ETAP Star 12.5.0C