Case - 2.2 Ef (Star TCC)

This document contains protection settings for several circuits connected to the 33kV (BB-2) SWGR-A switchgear. It includes overcurrent protection settings for the 33kV bus section, 33kV incoming feeder, 120MVA MV SBEF transformer, and 120MVA incoming circuit. The settings list the device manufacturer, model, CT ratio, protection curve type, pickup value, and time dial multiplier settings to achieve specified protection tripping times.

Uploaded by

josh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
41 views1 page

Case - 2.2 Ef (Star TCC)

This document contains protection settings for several circuits connected to the 33kV (BB-2) SWGR-A switchgear. It includes overcurrent protection settings for the 33kV bus section, 33kV incoming feeder, 120MVA MV SBEF transformer, and 120MVA incoming circuit. The settings list the device manufacturer, model, CT ratio, protection curve type, pickup value, and time dial multiplier settings to achieve specified protection tripping times.

Uploaded by

josh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Amps X 100 33kV(BB-2) SWGR-A (Nom. kV=33, Plot Ref.

kV=33)
.5

10

30

50

100

300

500

1K

3K

5K

1K

10K
1K

500

500

300

300

H17-RP - G
OC1
33kV B/S
ABB
REF615
CT Ratio 2500:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.44
3x = 2.77 s, 5x = 1.88 s, 8x = 1.45 s

100

H08-RP - G
OC1

50

120MVA I/C
ABB
REF615
CT Ratio 2500:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.47
3x = 2.96 s, 5x = 2.01 s, 8x = 1.55 s

30

Seconds

10

100

50

30

10

.5

.5

.3

.3

H03-RP - G
OC1
33kV O/G-SWGR-A
ABB
REF615
CT Ratio 600:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.3
3x = 1.89 s, 5x = 1.28 s, 8x = 0.989 s

.1

.05

.03

T201-MV-SBEF - G
OC1

.1

120MVA MV SBEF
ABB
REF615
CT Ratio 2500:1
IEC - Normal Inverse
Pickup = 36 (1 - 100 xCT Sec)
Time Dial = 0.46
3x = 2.9 s, 5x = 1.97 s, 8x = 1.52 s

.05

.03

.01
.5

10

30

50

100

300

500

1K

Amps X 100 33kV(BB-2) SWGR-A (Nom. kV=33, Plot Ref. kV=33)


N7733-ZAKHER
Project:
Location:
Contract:
Engineer:
Filename:

220/33/11kV Zakher Grid


Zakher Area of Al Ain
N7733
JM
C:\ETAP 1250\N7733\N7733.OTI

3K

5K

ETAP Star 12.5.0C

CASE:2.2 EF
Date:
SN:
Rev:
Fault:
Circuit:

.01
10K

21-01-2016
LARSENTRN2
Base
Ground
120MVAMVSBEF,33kVI/C,BS,OG