CASE - 4.1 (Star TCC)

The document shows the protection settings and curves for various circuit breakers in a power system. It includes the manufacturer and model of the circuit breakers, their current transformer ratios, protection characteristics like inverse time overcurrent, and pickup and time dial settings. The time dial settings determine the time multiplier for tripping at 3x, 5x and 8x of pickup current.

Uploaded by

josh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
59 views1 page

CASE - 4.1 (Star TCC)

The document shows the protection settings and curves for various circuit breakers in a power system. It includes the manufacturer and model of the circuit breakers, their current transformer ratios, protection characteristics like inverse time overcurrent, and pickup and time dial settings. The time dial settings determine the time multiplier for tripping at 3x, 5x and 8x of pickup current.

Uploaded by

josh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Amps X 1000 LVAC-AADC-BUS_A (Nom. kV=0.415, Plot Ref. kV=0.

415)
.5

10

30

50

100

300

500

1K

3K

5K

1K

10K
1K

500

500

RP-AADC-LVAC_I/C-1 - P
OC1

300

300

ABB
REF630
CT Ratio 2700:1
IEC - Normal Inverse
Pickup = 0.95 (0.3 - 5 xCT Sec)
Time Dial = 0.2
3x = 1.26 s, 5x = 0.856 s, 8x = 0.659 s

100

100

50

50

RP-AADC-LVAC-BS - P
OC1

30

10

10

RP-TRANSCO-LVAC_I/C-1 - P
OC1

ABB
REF630
CT Ratio 2000:1
IEC - Normal Inverse
Pickup = 0.65 (0.3 - 5 xCT Sec)
Time Dial = 0.14
3x = 0.882 s, 5x = 0.599 s, 8x = 0.462 s

.5

.5

.3

.3

RP-TRANSCO-LVAC_BS - P
OC1

.1

.1

ABB
REF630
CT Ratio 2000:1
IEC - Normal Inverse
Pickup = 0.65 (0.3 - 5 xCT Sec)
Time Dial = 0.07
3x = 0.441 s, 5x = 0.3 s, 8x = 0.231 s

.05

.03

RP-AADC-LVAC-O/G-1 - P
OC1
ABB
REF630
CT Ratio 2000:1
IEC - Normal Inverse
Pickup = 0.65 (0.3 - 5 xCT Sec)
Time Dial = 0.13
3x = 0.819 s, 5x = 0.556 s, 8x = 0.429 s

.01
.5

10

30

50

100

300

500

1K

Amps X 1000 LVAC-AADC-BUS_A (Nom. kV=0.415, Plot Ref. kV=0.415)


N7733-ZAKHER
Project:
Location:
Contract:
Engineer:
Filename:

220/33/11kV Zakher Grid


Zakher Area of Al Ain
N7733
JM
C:\ETAP 1250\N7733\N7733.OTI

.05

CASE:4.1
Date:
SN:
Rev:
Fault:
Circuit:

20-01-2016
LARSENTRN2
Base
Phase
LVAC

3K

.03

5K

.01
10K

ETAP Star 12.5.0C

Seconds

Seconds

30

ABB
REF630
CT Ratio 2700:1
IEC - Normal Inverse
Pickup = 0.95 (0.3 - 5 xCT Sec)
Time Dial = 0.15
3x = 0.945 s, 5x = 0.642 s, 8x = 0.495 s