Case - 2.2 Ef (Star TCC)

This document provides relay settings for three circuits: a 33kV bus section (BS), a 33kV outgoing feeder (O/G-SWGR-A), and a 120MVA transformer incoming feeder (I/C). It lists the device manufacturer and model, current transformer ratios, protection characteristics like inverse time overcurrent settings, and trip times for different fault currents. The document appears to be relay coordination study results for a substation.

Uploaded by

jm.mankavil6230
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
42 views1 page

Case - 2.2 Ef (Star TCC)

This document provides relay settings for three circuits: a 33kV bus section (BS), a 33kV outgoing feeder (O/G-SWGR-A), and a 120MVA transformer incoming feeder (I/C). It lists the device manufacturer and model, current transformer ratios, protection characteristics like inverse time overcurrent settings, and trip times for different fault currents. The document appears to be relay coordination study results for a substation.

Uploaded by

jm.mankavil6230
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Amps X 100 33kV(BB-2) SWGR-A (Nom. kV=33, Plot Ref.

kV=33)
.5

10

30

50

100

300

500

1K

3K

5K

1K

500

500

300

300

H17-RP - G
OC1

100

100

33kV B/S
ABB
REF615
CT Ratio 2500:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.39
3x = 2.46 s, 5x = 1.67 s, 8x = 1.29 s

50

30

Seconds

10K
1K

50

30

10

10

22015 A, 1.16 s

0.272 s

0.204 s
.5

.5

.3

H03-RP - G
OC1
33kV O/G-SWGR-A
ABB
REF615
CT Ratio 600:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.3
3x = 1.89 s, 5x = 1.28 s, 8x = 0.989 s

.1

.05

.03

H08-RP - G
OC1

.3

120MVA I/C
ABB
REF615
CT Ratio 2500:1
IEC - Normal Inverse
Pickup = 20 (1 - 100 xCT Sec)
Time Dial = 0.51
3x = 3.21 s, 5x = 2.18 s, 8x = 1.68 s

.1

.05

.03

.01
.5

10

30

50

100

300

500

1K

Amps X 100 33kV(BB-2) SWGR-A (Nom. kV=33, Plot Ref. kV=33)


N7733-ZAKHER
Project:
Location:
Contract:
Engineer:
Filename:

3K

5K

ETAP Star 12.5.0C

CASE:2.2 EF

220/33/11kV Zakher Grid


Zakher Area of Al Ain
N7733
JM
C:\Users\joshi\Desktop\LATEST RELAY SETTING\DUBAI\TRANSCO-Supercede 01.03.1

Date:
SN:
Rev:
Fault:
Circuit:

.01
10K

21-01-2016
LARSENTRN2
Base
Ground
120MVAMVSBEF,33kVI/C,BS,OG