SWGR +RP
1
2
Version
TB
Initiation For
Check Synch
S251
kV
P1
+S1
Core-1
200/1A
-ICT
Class: 5P20
A10CT2
TB
+RP
TB
7SJ61
S511
T1
R/P
7SJ61
87NL
F871
T1
R/P
7SJ61
T1
R/P
7SJ61
T1
R/P
7PG15
86
K311
Master Trip Relay
S511
R/P
7PG17
74
K312
Trip Circuit Supervision Relay
S201
6MD664
A
VAr
TO 11kV SCS
Switch
TO BBP
PANEL
Sq.mm XLPE.,
CU Cable
T1
R/P
7PG15
63T
K342
Tx. Buchholz Trip
T1
R/P
7PG15
63P(T)
K332
Tx. Pressure Relief Trip
T1
R/P
7PG15
49OTT
K341
Tx. Oil Temperature Trip
7PG18 86BBP
K87Z1
X
X
S871
3Fs5
S871
7SJ61
3-Ph
LVAC Board
51 50BF
Note:-
* At Ambient Temperature From 40C
** At Ambient Temperature From 50C
Protection
-F871
Tx Fault Relays
63T
63P(T)
490TT
49WTT
87NL
Panel
%
Note:
Depicts shorting towards P2
Isolating link
Depicts shorting towards P1
Link.G
TS- Test Switch
TB
LV-REF
-F511
LVAC
Trip-LVAC
P2
1500/1A
-F671
Link.H
I/C -1
LV ACB
1600A
1500/1A
1-Ph
415V ACB Protection
86BBP
ONAN,Dyn11,50Hz
TB
Note:-
Oil Temp Trip-LVAC
TB- Terminal Block
For RHS T2+/- will be used for trip supply instead of T1+/-
Link.F
For A20 Bus-2 VT Shall be Connected
Link B WDG. TEMP TRIP
Wdg. Temp Trip-LVAC
400V AC Bus-1
DEVICE TYPE
% Link C OIL TEMP TRIP
DEVICE NO.
ANSI NO.
1600A, (@ 50C),3ph+Neu+PE,50Hz,50kA/1Sec,Cu. Busbar
Date 27.03.14
DTA/14/0207 04.06.14 VJS Drawn SRG
DTA/14/0508 16.12.14 SDG Appr. VJS
Remarks
Date
Name Norm
1
2
Al-Mashaaf, Khore South East, Rayyan South S/S
Orig./Repl.f./Repl.by
3
A12.RP
7SJ62
7PG18 -K87Z1
+RP
LVAC P
Tx. winding Temperature Trip
Link.E BF Initiation isolating Link (A12)
11kV Busbar
DATA COMMUNICATION
TB
7PG15 49WTT K331
7PG17 -K312
CONDUCTOR
+CC
R/P
From Busbar Panel
Link.D BF Initiation isolating Link (A18)
TO 11kV SCS
WTI CT2
T1
11kV Bus Bar Protn/BFP Trip
7PG15 -K311
86
steps of 2.5%
1500/2A,10VA
BBP2 R/P
67 67N 51 50BF
from PB
Protection Panel
P1
BBP1/ BBP
A18 RP
STRANDED CU
1500/1A
P2
+5% to -5%
7SJ62
SHEATHED
Z=5.45%
74
A10NCT1
S511
400 Sq.mm LEAD
1000kVA
110% O/C Alarm
Manual -PB
Reset
Bus-1 VT
*(Remot
synch.)
11kV 1x1Cx500
A106VT
630A
F511
BCU
Reset from BCU
DATA COMMUNICATION
CVD
Feeder O/C, E/F protection
SYNCH CHK. OK
25
MONITORING,INTERLOCK,Tx. ALARMS
A101
F511
Class: PX
CT2
OPEN/CLOSE, CONTROL,STATUS
A10CT3
CT1 Metering
50/51/
50N/51N
LV REF PROTECTION
SYNCH CHK. INITIATION
-A201
FR
S19
Synch. Sel.
1Cx500 Sq.mm
50/51/
50N/51N
DESCRIPTION
50/51 50N 51N
Core-2
2500/1A
Release Close Command
-F511
25
TO 11kV SCS
200/1A
Class: 5P20/1
Core-3
-A251
DATA COMMUNICATION
Bus Voltage
A10CT1
0.11
A166VT
7SJ64
DEVICE NO.
Line Voltage Bus
FUNCTION
CVD
A12.RP
Bus -1 Voltage Bus
TYPE
A1241
Eqpt Location
Local Synch Check
11
DC GROUP
=A16
BF Initiation in A12
BF Initiation in A18
Isolating link
CB - Q10 TRIP COIL
Link.A- CB trip
A100
LVAC CB TC
BBM1
LOCKOUT RELAY 86
ANNUNCIATION SCS/DCC
BUSBAR 1
630A
**
630A
This sheet is applicable only for Al-Mashaaf, Khore South East
11kV, 2500A, 2500A,31.5kA/3 Sec., 50Hz Busbar
P1
CopyRight (C) Siemens AG 2004 All Rights Reserved
**
STN.T1
11/0.415kV
CB CLOSE BLOCK
3/110V: 3
11kV:
P2
Symbol
Symbol
Symbol
Symbol
Project: //inggnh002ea/PTD/ANL/QAT/Ph-11/ETA_S4_DRW/Base Design/11kV Base Design_Without Hood/A10_BaseELCAD-Version
design.pro
7.7.1 SP2
library 1:
Translate file A:
Last used: 23.12.14
library 2:
Translate file B:
library 3:
Translate file C: C_FB_EN.etr, 04-04-26
library 4:
Translate file D:
Archive: = / B / AA / 5
11/0.415kV Aux. Transformer Feeder
Protection SLD & Tripping Diagram
Revision-A
Overview diagram
PH11-8A-10-35-1010
GTC/488A/2012
=A10
AA5
Sheet 5+
7 Sh.
(3)G719EA-EG9047-U5110-2
7