Trafo Feeder RP - Base Design - Pages From 1473 11-0.415kV Auxiliary Transformer Feeder Bse Design For Comm SS

The document appears to be a single line diagram and tripping diagram for an 11kV/0.415kV auxiliary transformer. It shows the transformer, associated protection devices, wiring, and connections to other equipment.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
461 views1 page

Trafo Feeder RP - Base Design - Pages From 1473 11-0.415kV Auxiliary Transformer Feeder Bse Design For Comm SS

The document appears to be a single line diagram and tripping diagram for an 11kV/0.415kV auxiliary transformer. It shows the transformer, associated protection devices, wiring, and connections to other equipment.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SWGR +RP

1
2
Version

TB

Initiation For
Check Synch

S251

kV

P1

+S1

Core-1

200/1A
-ICT

Class: 5P20
A10CT2

TB

+RP

TB

7SJ61

S511

T1

R/P

7SJ61

87NL

F871

T1

R/P

7SJ61

T1

R/P

7SJ61

T1

R/P

7PG15

86

K311

Master Trip Relay

S511

R/P

7PG17

74

K312

Trip Circuit Supervision Relay

S201

6MD664
A

VAr

TO 11kV SCS

Switch
TO BBP
PANEL

Sq.mm XLPE.,
CU Cable

T1

R/P

7PG15

63T

K342

Tx. Buchholz Trip

T1

R/P

7PG15

63P(T)

K332

Tx. Pressure Relief Trip

T1

R/P

7PG15

49OTT

K341

Tx. Oil Temperature Trip

7PG18 86BBP

K87Z1

X
X

S871

3Fs5

S871

7SJ61

3-Ph

LVAC Board

51 50BF

Note:-

* At Ambient Temperature From 40C


** At Ambient Temperature From 50C

Protection

-F871

Tx Fault Relays
63T
63P(T)
490TT
49WTT

87NL

Panel
%

Note:

Depicts shorting towards P2

Isolating link

Depicts shorting towards P1


Link.G

TS- Test Switch


TB

LV-REF

-F511

LVAC

Trip-LVAC

P2

1500/1A

-F671

Link.H

I/C -1
LV ACB
1600A

1500/1A

1-Ph

415V ACB Protection

86BBP

ONAN,Dyn11,50Hz
TB

Note:-

Oil Temp Trip-LVAC

TB- Terminal Block

For RHS T2+/- will be used for trip supply instead of T1+/-

Link.F
For A20 Bus-2 VT Shall be Connected

Link B WDG. TEMP TRIP


Wdg. Temp Trip-LVAC

400V AC Bus-1

DEVICE TYPE

% Link C OIL TEMP TRIP

DEVICE NO.

ANSI NO.

1600A, (@ 50C),3ph+Neu+PE,50Hz,50kA/1Sec,Cu. Busbar

Date 27.03.14
DTA/14/0207 04.06.14 VJS Drawn SRG
DTA/14/0508 16.12.14 SDG Appr. VJS
Remarks
Date
Name Norm
1
2

Al-Mashaaf, Khore South East, Rayyan South S/S

Orig./Repl.f./Repl.by
3

A12.RP
7SJ62

7PG18 -K87Z1

+RP

LVAC P

Tx. winding Temperature Trip

Link.E BF Initiation isolating Link (A12)

11kV Busbar

DATA COMMUNICATION

TB

7PG15 49WTT K331

7PG17 -K312

CONDUCTOR

+CC

R/P

From Busbar Panel

Link.D BF Initiation isolating Link (A18)

TO 11kV SCS

WTI CT2

T1

11kV Bus Bar Protn/BFP Trip

7PG15 -K311
86

steps of 2.5%

1500/2A,10VA

BBP2 R/P

67 67N 51 50BF

from PB

Protection Panel

P1

BBP1/ BBP

A18 RP

STRANDED CU

1500/1A
P2

+5% to -5%

7SJ62

SHEATHED

Z=5.45%

74

A10NCT1

S511

400 Sq.mm LEAD

1000kVA

110% O/C Alarm

Manual -PB
Reset

Bus-1 VT
*(Remot
synch.)

11kV 1x1Cx500

A106VT

630A

F511

BCU

Reset from BCU

DATA COMMUNICATION

CVD

Feeder O/C, E/F protection

SYNCH CHK. OK

25

MONITORING,INTERLOCK,Tx. ALARMS

A101

F511

Class: PX

CT2

OPEN/CLOSE, CONTROL,STATUS

A10CT3

CT1 Metering

50/51/
50N/51N

LV REF PROTECTION

SYNCH CHK. INITIATION

-A201

FR

S19
Synch. Sel.

1Cx500 Sq.mm

50/51/
50N/51N

DESCRIPTION

50/51 50N 51N

Core-2

2500/1A

Release Close Command

-F511

25

TO 11kV SCS

200/1A
Class: 5P20/1

Core-3

-A251

DATA COMMUNICATION

Bus Voltage

A10CT1

0.11

A166VT

7SJ64

DEVICE NO.

Line Voltage Bus

FUNCTION

CVD

A12.RP

Bus -1 Voltage Bus

TYPE

A1241

Eqpt Location

Local Synch Check

11

DC GROUP

=A16

BF Initiation in A12

BF Initiation in A18

Isolating link

CB - Q10 TRIP COIL

Link.A- CB trip
A100

LVAC CB TC

BBM1

LOCKOUT RELAY 86

ANNUNCIATION SCS/DCC

BUSBAR 1

630A
**
630A

This sheet is applicable only for Al-Mashaaf, Khore South East

11kV, 2500A, 2500A,31.5kA/3 Sec., 50Hz Busbar

P1

CopyRight (C) Siemens AG 2004 All Rights Reserved

**

STN.T1
11/0.415kV

CB CLOSE BLOCK

3/110V: 3

11kV:

P2

Symbol
Symbol
Symbol
Symbol

Project: //inggnh002ea/PTD/ANL/QAT/Ph-11/ETA_S4_DRW/Base Design/11kV Base Design_Without Hood/A10_BaseELCAD-Version


design.pro
7.7.1 SP2
library 1:
Translate file A:
Last used: 23.12.14
library 2:
Translate file B:
library 3:
Translate file C: C_FB_EN.etr, 04-04-26
library 4:
Translate file D:
Archive: = / B / AA / 5

11/0.415kV Aux. Transformer Feeder


Protection SLD & Tripping Diagram

Revision-A

Overview diagram

PH11-8A-10-35-1010
GTC/488A/2012

=A10

AA5
Sheet 5+
7 Sh.

(3)G719EA-EG9047-U5110-2
7