Air Cooled Packaged Inverter Floor Standing Type - Heat Pump 50Hz - APCVDT1512

This document provides product information for Daikin floor standing air conditioners with duct connection. It includes: - An overview of the duct connection type units and their benefits like flexible installation and high maintainability. - Product lineups for heat pump models ranging from 5 to 60HP with cooling and heating capacity details. - Specification tables listing features of select indoor units models like dimensions, fan motor output, and piping connections. - Information on installation flexibility options like outdoor unit connections and refrigerant piping lengths. - Descriptions of functions supporting efficient operation and maintenance like i-Demand power saving control.

Uploaded by

Phanhai Kaka
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
653 views54 pages

Air Cooled Packaged Inverter Floor Standing Type - Heat Pump 50Hz - APCVDT1512

This document provides product information for Daikin floor standing air conditioners with duct connection. It includes: - An overview of the duct connection type units and their benefits like flexible installation and high maintainability. - Product lineups for heat pump models ranging from 5 to 60HP with cooling and heating capacity details. - Specification tables listing features of select indoor units models like dimensions, fan motor output, and piping connections. - Information on installation flexibility options like outdoor unit connections and refrigerant piping lengths. - Descriptions of functions supporting efficient operation and maintenance like i-Demand power saving control.

Uploaded by

Phanhai Kaka
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 54

APCVDT1512

AIR COOLED PACKAGED


AIR CONDITIONERS
FLOOR STANDING TYPE

FLOOR STANDING TYPE


DUCT CONNECTION TYPE

HEAT PUMP 50Hz

HFC R-410A Line Up


for Offices
We have entered into an era where environmental responsibility has become
the utmost important factor to every company.
Daikin introduced a new model featuring HFC R-410A refrigerant that could be
the perfect step in promoting your corporate image.

Product Line Up

Heat pump

5
16.0 / 18.0

8
22.4 / 25.0

10
28.0 / 31.5

16
45.0 / 50.0

20
56.0 / 63.0

54,600 / 61,400
13,800 / 15,500

76,400 / 85,300
19,300 / 21,500

95,500 / 107,000
24,100 / 27,100

154,000 / 171,000
38,700 / 43,000

191,000 / 215,000
48,200 / 54,200

FXVQ125NY1

FXVQ200NY1

FXVQ250NY1

FXVQ400NY1

FXVQ500NY1(6)

RXYQ6TY1(E)

RXYQ8TY1(E)

RXYQ10TY1(E)

RXYQ16TY1(E)

RXYQ20TY1(E)

REFNET (JOINT+REDUCER)

OUTDOOR UNIT MULTI CONNECTION PIPING KIT 2

HP
kW
Btu/h
kcal/h

Capacity
(Cooling / Heating)

DUCT CONNECTION
TYPE
Specifications Page 5
Dimensions Page 8

Indoor unit

Dimensions

Page 10

Outdoor unit

PAIR

OUTDOOR UNIT

24
67.0 / 75.0

30
83.5 / 93.5

48
134 / 150

60
168 / 189

154,000 / 171,000
38,700 / 43,000

229,000 / 256,000
57,600 / 64,500

285,000 / 319,000
71,800 / 80,400

457,000 / 512,000
115,000 / 129,000

573,000 / 645,000
144,000 / 163,000

FXVQ125NY1 3

FXVQ200NY1 3

FXVQ250NY1 3

FXVQ400NY1 3

FXVQ500NY1(6) 3

RXYQ16TY1(E)

RXYQ24TSY1(E)

RXYQ30TSY1(E)

RXYQ48TSY1(E)

RXYQ60TNY1(E)

KHRP26A33T,
KHRP26A72T

KHRP26A72T,
KHRP26A73T
+KHRP26M73TP

KHRP26A72T,
KHRP26A73T
+KHRP26M73TP

(KHRP26A73T
+KHRP26M73TP) x 2

(KHRP26A73T
+KHRP26M73TP) x 2

BHFP22P100

BHFP22P100

BHFP22P151

BHFP22P151

TRIPLE

16
45.0 / 50.0

Note : 1 Combinations of outdoor units for High-COP, Standard, Space saving series can be selected. For details, please refer to VRV IV Catalog and Engineering data.
2
For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.

Large airflow type for large spaces.


Flexible interior design for each tenant.
l The

high static pressure type driven by the belt drive


system allows the use of air discharge outlets in
various shapes as well as long ducts. Highly flexible
installation is possible.
l Design with high maintainability that allows major
services and maintenance services to be performed
at the front.
l A long-life filter (maintenance free up to one year*)
is equipped as a standard accessory.
* 8 hr/day, 26 day/month. For dust concentration of
0.15 mg/m3
l A

wide range of optional accessories are available


such as high-efficiency filters.

l Large

airflow type that fits for spacious areas such as


factories and large stores.
l Various installations can be supported from full-scale
duct connection airflow to direct airflow that allows for
easy installation.
l Full-scale duct connection airflow allows even
air conditioning for spacious areas.

Duct connection type

l Adding

the plenum chamber (option)


allows for simple operation with direct airflow.
* Note that the operation sound increases by
approximately 5 dB(A).

Direct air blow type

50Hz
16
45.0 / 50.0

20
56.0 / 63.0

32
89.5 / 101

40
112 / 126

95,500 / 107,000
24,100 / 27,100

154,000 / 171,000
38,700 / 43,000

191,000 / 215,000
48,200 / 54,200

305,000 / 345,000
77,000 / 86,900

382,000 / 430,000
96,300 / 108,000

FXVQ125NY1 2

FXVQ200NY1 2

FXVQ250NY1 2

FXVQ400NY1 2 FXVQ500NY1(6) 2

RXYQ10TY1(E)

RXYQ16TY1(E)

RXYQ20TY1(E)

RXYQ32TSY1(E)

RXYQ40TSY1(E)

KHRP26A33T

KHRP26A72T

KHRP26A72T

KHRP26A73T
+KHRP26M73TP

KHRP26A73T
+KHRP26M73TP

BHFP22P100

BHFP22P100

Nice,
cool air in the office
or in the cafeteria

TWIN

10
28.0 / 31.5

FOUR CONNECT

50Hz
20
56.0 / 63.0

32
89.5 / 101

40
112 / 126

191,000 / 215,000
48,200 / 54,200

305,000 / 345,000
77,000 / 86,900

382,000 / 430,000
96,300 / 108,000

FXVQ125NY1 4

FXVQ200NY1 4

FXVQ250NY1 4

RXYQ20TY1(E)

RXYQ32TSY1(E)

RXYQ40TSY1(E)

KHRP26A33T,
KHRP26A72T x 2

KHRP26A72T 2,
KHRP26A73T
+KHRP26M73TP

KHRP26A72T,
(KHRP26A73T
+KHRP26M73TP) x 2

BHFP22P100

BHFP22P100

AIR COOLED PACKAGED AIR CONDITIONERS

Flexible design
FLOOR STANDING TYPE

Enhanced varieties of factory


modification and optional
accessories

DUCT CONNECTION TYPE

Rear suction

Option

Plenum chamber

Option

Standard model
Factory modification

Note 1

Static pressure up

Output

ON / OFF
Compressor ON

Option

Fan ON
Error
Cool / Heat / Ventilate operation mode

Option

Input

ON / OFF
Cool / Heat / Ventilate changeover

Option

Temperature set
DIII-NET centralized control
Note:
1
Operation sound will increase 5 dB when installed with plenum chamber,
not suitable for restricted areas.
In the case of sound restricted areas, the Duct connection type is recommended.

FXVQ500NY1(6)

Wide Operation Range


Covers a wide range of replacement and
reconstruction needs.
Operation limits
Cooling

Heating

RXYQ20TY1(E)

Indoor temperature

14~25 CWB

Outdoor temperature

5~43 CDB

Indoor temperature

15~27 CDB

Outdoor temperature

20~15.5 CWB

Outdoor Air Processing Mode


Outdoor air processing mode is useable as an outdoor-air processing air conditioner, only for pair connection.
*When using the unit as an outdoor-air processing unit, there are some restrictions.
Strictly follow the restrictions specified in the Engineering Data Book.

All-fresh (using outdoor air only) system

Outdoor air
introduction

Air
conditioning

Outside

Circulated air

Outside

Return + Outdoor air mixed system


Air
conditioning

Outdoor air
introduction
* Air introduced from the outside and circulated air must be mixed in the
air conditioner primary side before introduction into the air conditioner.

Improper to use in temperature near outdoor temperature (Condensation may occur).

and high energy saving


Great installation flexibility

Nighttime quiet operation function

A variety of refrigerant pipe length and level difference to cover a wide


range of building scales

Upper outdoor unit


Lower outdoor unit

outdoor temperature appears.


It will enable quiet operation mode after 8 h*1, and
return to normal mode after it keeps for 9 h*2.

165m
90m
90m

*1 8 h is the initial setting with 6 h or 10 h also available.


*2 9 h is the initial setting with 8 h or 10 h also available.

Capacity
(%)

Max. length
Max. level
difference

Outdoor PC board automatically memorises the time when the peak

Operating
sound (dB)

Load
(%)

Max. level difference refer to


VRV IV Engineering data.

Max. level
difference

90m

Max.length

165

Peak in outdoor temperature

Night mode

100

50

8 hrs

0
60

9 hrs

57

VRV IV

50

Enable night mode

40
8:00

12:00

16:00

min. 40

20:00

0:00

dB(A)
4:00

8:00

Notes: This function is available in setting at site.


The operating sound in quiet operation mode is the actual value
measured by our company.
The relationship of outdoor temperature (load) and time shown
above is just an example.

Consideration for power saving [i-Demand function]


Power consumption control can be finely set on 13 steps.
High static pressure outdoor unit increases installation flexibility.

78.4Pa

In case of 70% demand setting


High

Easy installation
in each floor of
the building

100

70

50
40

Low
Time

Backup function increasing reliability (for model 24HP or above)


Avoid air conditioning system
breakdowns due to the equipment
error stop.

Just press
the button twice
Emergency operating period is 8 hrs.
Applicable for multiple outdoor units system only.
Otherwise, the emergency stop switch is available.
(Except models 8HP and 10HP)

13 steps

5% of fine
setting

Power consumption

Easy to connect
with exhaust hood
when installed at
static pressure

Power consumption peak is cut down to meet the usage circumstance.


Notes:  Settings on circuit board of outdoor unit is applicable.
Option adaptor (DTA104A62) is necessary for each system.
Group controller and DTA104A62 cannot be mounted to the
same indoor unit at the same time.
In case of using i-Demand function, group controller function
is not available.

Centralized management system extension


Centralized management can integrate with D-BACS system with high
speed data transfer.

Centralized control is now available when using with SkyAir Inv. model
or VRV.

Display of air filter cleaning times and self-inspection function for


simple maintenance.
High efficiency integrated control

Intelligent Touch Manager


Lighting and ventilation control, energy use can be
monitored and managed by one controller.

th
ch wid
10.4 in reen
touch sc

INDOOR UNIT
Model Name

FXVQ125NY1

FXVQ200NY1

FXVQ250NY1

3 phase, 380-415V, 50Hz

3 phase, 380-415V, 50Hz

3 phase, 380-415V, 50Hz

kcal/h

12,000

19,300

24,100

Btu/h

47,800

76,400

95,500

kW

14.0

22.4

28.0

kcal/h

13,800

21,500

27,100

Btu/h

54,600

85,300

107,000

kW

16.0

25.0

31.5

Ivory white (5Y7.5/1)

Ivory white (5Y7.5/1)

Ivory white (5Y7.5/1)

Power supply
Cooling capacity 1, 3

Heating capacity 2,3


Casing / Colour
Dimensions: (HWD)
Coil (Cross fin
coil)

mm

1,670750510

1,670950510

1,6701,170510

RowsStagesFin pitch

mm

3322.0

3322.0

3322.0

Face area

0.419

0.560

0.715

D13/4G2BH5Y1

D13/4G3AD5Y1

2D13/4G2BX5Y1

Model
Type
Motor output
Number of units
Fan
Airflow rate
External static pressure 3

Sirocco fan

Sirocco fan

Sirocco fan

7501

1,5001

1,5001

m/min

43

69

86

cfm

1,518

2,436

3,036

Pa

Drive
Temperature control
Air filter
Piping
connections 4

Type

152

217

281

Belt drive

Belt drive

Belt drive

Microprocessor thermostat for cooling and


heating

Microprocessor thermostat for cooling and


heating

Microprocessor thermostat for cooling and


heating
Long-life filter (anti-mould resin net)

Long-life filter (anti-mould resin net)

Long-life filter (anti-mould resin net)

Liquid pipes

mm

9.5 (Brazing connection)

9.5 (Brazing connection)

9.5 (Brazing connection)

Gas pipes

mm

15.9 (Brazing connection)

19.1 (Brazing connection)

22.2 (Brazing connection)

Drain pipe

Mass
Sound pressure level 5

Rp1 (PS1B internal thread)

Rp1 (PS1B internal thread)

Rp1 (PS1B internal thread)

kg

118

144

169

dB(A)

52

56

60

Fuse, Overcurrent relay

Fuse, Overcurrent relay

Fuse, Overcurrent relay

Electronic expansion valve

Electronic expansion valve

Electronic expansion valve

R410A VRV Series

R410A VRV Series

Safety devices
Refrigerant control
Connectable outdoor unit

Connection pipe. Drain plug cap. Insulation


for drain plug. Clamp. Bolt. Nut. Operation
manual. Installation manual.

Standard accessories

Connection pipe. Drain plug cap. Insulation


for drain plug. Clamp. Bolt. Nut. Operation
manual. Installation manual.

Drawing No.

C: 3D095077A

Model Name
Power supply
Cooling capacity 1, 3

Heating capacity 2,3

Dimensions: (HWD)

38,700

48,200

48,200

191,000

191,000

kW

45.0

56.0

56.0

kcal/h

43,000

54,200

54,200

Btu/h

171,000

215,000

215,000

kW

50.0

63.0

63.0

Ivory white (5Y7.5/1)

Ivory white (5Y7.5/1)

Ivory white (5Y7.5/1)

mm

1,9001,170720

1,9001,470720

1,9001,470720

RowsStagesFin pitch

mm

3442.0

3442.0

3442.0

Face area

0.945

1.237

1.237

D2E1AG7Y1

2D2E1BB7Y1

2D2E1BB5

Sirocco fan

Sirocco fan

Sirocco fan

3,7001

3,7001

5,5001

Motor output
Number of units
Airflow rate
External static pressure 3

W
m/min

134

165

172

cfm

4,730

5,825

6,072

Pa

Drive
Temperature control

Piping
connections 4

Type

420

142

469

Belt drive

Belt drive

Belt drive

Microprocessor thermostat for cooling and


heating

Microprocessor thermostat for cooling and


heating

Microprocessor thermostat for cooling and


heating

Long-life filter (anti-mould resin net)

Long-life filter (anti-mould resin net)

Long-life filter (anti-mould resin net)

Liquid pipes

mm

12.7 (Brazing connection)

15.9 (Brazing connection)

15.9 (Brazing connection)

Gas pipes

mm

28.6 (Brazing connection)

28.6 (Brazing connection)

28.6 (Brazing connection)

Rp1 (PS1B internal thread)

Rp1 (PS1B internal thread)

Rp1 (PS1B internal thread)

kg

236

281

306

dB(A)

65

62

67

Fuse, Overcurrent relay

Fuse, Overcurrent relay

Fuse, Overcurrent relay

Electronic expansion valve

Electronic expansion valve

Electronic expansion valve

R410A VRV Series

R410A VRV Series

Drain pipe

Mass
Sound pressure level 5
Safety devices
Refrigerant control
Connectable outdoor unit
Standard accessories
Drawing No.

FXVQ500NY16
3 phase, 380-415V, 50Hz

154,000

Type

Air filter

FXVQ500NY1
3 phase, 380-415V, 50Hz

Btu/h

Model

Fan

FXVQ400NY1
3 phase, 380-415V, 50Hz
kcal/h

Casing / Colour

Coil (Cross fin


coil)

Connection pipe. Drain plug cap. Insulation


for drain plug. Clamp. Bolt. Nut. Operation
manual. Installation manual.

Connection pipe. Drain plug cap. Insulation


for drain plug. Clamp. Bolt. Nut. Operation
manual. Installation manual.

C: 3D095077A

Note : 1Indoor temp.: 27CDB, 19CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2
Indoor temp.: 20CDB / outdoor temp.: 7CDB, 6CWB / Standard external static pressure / Equivalent piping length: 7.5 m, level difference: 0 m.
3
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4
The value is the external static pressure with standard pulley.
5
Both liquid pipe and gas pipe need insulation work.
6
Sound level : measured when the air discharge outlet duct (2 m) is attached (anechoic chamber conversion value).
It increases by approximately 5 dB(A) when the plenum chamber is installed to deliver direct airflow.
7
Refer to Electric Characteristics for the power input.

R410A VRV Series


Connection pipe. Drain plug cap. Insulation
for drain plug. Clamp. Bolt. Nut. Operation
manual. Installation manual.

R410A VRV Series


Connection pipe. Drain plug cap. Insulation
for drain plug. Clamp. Bolt. Nut. Operation
manual. Installation manual.
C: 3D085648

OUTDOOR UNIT
Model Name

RXYQ6TY1(E)

RXYQ8TY1(E)

RXYQ10TY1(E)

3 phase, 380-415V, 50Hz

3 phase, 380-415V, 50Hz

3 phase, 380-415V, 50Hz

kcal/h

13,800

19,300

24,100

Btu/h

54,600

76,400

95,500

kW

16.0

22.4

28.0

kcal/h

15,500

21,500

27,100

Btu/h

61,400

85,300

107,000

kW

18.0

25.0

31.5

Ivory white (5Y7.5/1)

Ivory white (5Y7.5/1)

Ivory white (5Y7.5/1)

1,657930765

1,657930765

1,657930765

Cross fin coil

Cross fin coil

Cross fin coil

Hermetically sealed scroll type

Hermetically sealed scroll type

Hermetically sealed scroll type


24.37

Power Supply
Cooling Capacity 1

Heating Capacity 2
Casing Color
Dimensions: (HWD)

mm

Heat Exchanger
Type

Comp.

Displacement

m/h

16.24

16.24

Number of Revolutions

r/min

7,668

7,668

7,650

kW

2.41

3.41

4.11

Motor Output
Number of Units
Starting Method
Type

Fan

0.551

0.551

119

157

165

Direct drive

Direct drive

Direct drive

Liquid Pipe

mm

9.5 C1220T (Brazing connection)

9.5 C1220T (Brazing connection)

9.5 C1220T (Brazing connection)

Gas Pipe

mm

19.1 C1220T (Brazing connection)

19.1 C1220T (Brazing connection)

22.2 C1220T (Brazing connection)

kg

185

185

195

dB(A)

55

56

57

High pressure switch, Fan driver overload protector,


Over current relay, Inverter overload protector

High pressure switch, Fan driver overload protector,


Over current relay, Inverter overload protector

High pressure switch, Fan driver overload protector,


Over current relay, Inverter overload protector

20-100

20-100

16-100

R410A

R410A

R410A

5.9

5.9

6.0

Electronic expansion valve

Electronic expansion valve

Electronic expansion valve

Safety Devices
Capacity Control

%
Refrigerant Name
Charge

kg

Control
Refrigerator Oil

Refer to the nameplate of compressor


Installation manual, Operation manual,
Connection pipes, Clamps

Standard Accessories
Drawing No.

Model Name

Cooling Capacity 1

Heating Capacity 2

Dimensions: (HWD)

C: 4D085851

RXYQ16TY1(E)

RXYQ20TY1(E)

3 phase, 380-415V, 50Hz

3 phase, 380-415V, 50Hz

38,700

48,200

154,000

191,000

kW

45.0

56.0

kcal/h

43,000

54,200

Btu/h

171,000

215,000

kW

50.0

63.0

Ivory white (5Y7.5/1)

Ivory white (5Y7.5/1)

1,6571,240765

1,6571,240765

mm

Type

Cross fin coil

Cross fin coil

Hermetically sealed scroll type

Hermetically sealed scroll type


16.90+26.28

Displacement

m/h

16.27+17.54

Number of Revolutions

r/min

7,680+8,280

7,980+8,250

kW

(3.61)+(3.71)

(4.61)+(5.51)

Motor Output
Number of Units
Starting Method
Type

Soft start

Soft start

Propeller fan

Propeller fan
0.752

Motor Output

kW

0.752

Airflow Rate

m/min

233

268

Direct drive

Direct drive

Drive
Liquid Pipe

mm

12.7 C1220T (Brazing connection)

15.9 C1220T (Brazing connection)

Gas Pipe

mm

28.6 C1220T (Brazing connection)

28.6 C1220T (Brazing connection)

kg

285

320

dB(A)

61

Mass
Sound pressure level 2

High pressure switch, Fan driver overload protector,


Over current relay, Inverter overload protector

Safety Devices
Capacity Control

%
Refrigerant Name
Charge
Control

Refrigerator Oil
Standard Accessories
Drawing No.

C: 4D085850

Btu/h

Heat Exchanger

Refrigerant

Refer to the nameplate of compressor


Installation manual, Operation manual,
Connection pipes, Clamps

kcal/h

Casing Color

Connecting
Pipes

Refer to the nameplate of compressor


Installation manual, Operation manual,
Connection pipes, Clamps

C: 4D085850

Power Supply

Fan

0.551

kW
m/min

Sound pressure level 2

Comp.

Soft start
Propeller fan

Motor Output

Mass

Refrigerant

Soft start
Propeller fan

Airflow Rate
Drive

Connecting
Pipes

Soft start
Propeller fan

kg

65
High pressure switch, Fan driver overload protector,
Over current relay, Inverter overload protector

10-100

8-100

R410A

R410A

10.4

11.8

Electronic expansion valve

Electronic expansion valve

Refer to the nameplate of compressor


Installation manual, Operation manual, Connection pipes, Clamps

Refer to the nameplate of compressor


Installation manual, Operation manual, Connection pipes, Clamps

C: 4D085852A

C: 4D085853

Note : 1Indoor temp.: 27CDB, 19CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2
Indoor temp.: 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference: 0m.
3
Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4

Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5
Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric

component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to

salt damage and atmospheric pollution. Please contact Daikin for more information.

OUTDOOR UNIT
Model Name (Combination Unit)

RXYQ24TSY1(E)

RXYQ30TSY1(E)

RXYQ32TSY1(E)

Model Name (Independent Unit)

RXYQ12TY1(E)+RXYQ12TY1(E)

RXYQ12TY1(E)+RXYQ18TY1(E)

RXYQ12TY1(E)+RXYQ20TY1(E)
3 phase, 380-415V, 50Hz

Power Supply
Cooling Capacity 1

Heating Capacity 2

3 phase, 380-415V, 50Hz

3 phase, 380-415V, 50Hz

kcal/h

57,600

71,800

77,000

Btu/h

229,000

285,000

305,000

kW

67.0

83.5

89.5

kcal/h

64,500

80,400

86,900

Btu/h

256,000

319,000

345,000

kW

75.0

93.5

101

Ivory white (5Y7.5/1)

Ivory white (5Y7.5/1)

Ivory white (5Y7.5/1)

(1,657930765)+(1,657930765)

(1,657930765)+(1,6571,240765)

(1,657930765)+(1,6571,240765)

Cross fin coil

Cross fin coil

Cross fin coil

Hermetically sealed scroll type

Hermetically sealed scroll type

Hermetically sealed scroll type


(24.68)+(16.90+26.28)

Casing Color
Dimensions: (HWD)

mm

Heat Exchanger
Type

Comp.

Displacement

m/h

(24.68)+(24.68)

(24.68)+(16.27+17.54)

Number of Revolutions

r/min

(7,746)+(7,746)

(7,746)+(7,680+8,280)

(7,746)+(7,980+8,250)

kW

(5.21)+(5.21)

(5.21)+(4.41)+(4.01)

(5.21)+(4.61)+(5.51)

Motor Output
Number of Units
Starting Method
Type

Fan

Soft start
Propeller fan
(0.551)+(0.752)

kW

(0.551)+(0.551)

(0.551)+(0.752)

Airflow Rate

m/min

178+178

178+233

178+268

Direct drive

Direct drive

Direct drive

Liquid Pipe

mm

15.9 C1220T (Brazing connection)

19.1 C1220T (Brazing connection)

19.1 C1220T (Brazing connection)

Gas Pipe

mm

34.9 C1220T (Brazing connection)

34.9 C1220T (Brazing connection)

34.9 C1220T (Brazing connection)

kg

195+195

195+285

195+320

dB(A)

62

64

66

High pressure switch, Fan driver overload protector,


Over current relay, Inverter overload protector

High pressure switch, Fan driver overload protector,


Over current relay, Inverter overload protector

High pressure switch, Fan driver overload protector,


Over current relay, Inverter overload protector

Mass
Sound pressure level 2
Safety Devices
Capacity Control

%
Refrigerant Name
Charge

Refrigerant

Soft start
Propeller fan

Motor Output
Drive

Connecting
Pipes

Soft start
Propeller fan

kg

Control
Refrigerator Oil

8-100

6-100

5-100

R410A

R410A

R410A

6.3+6.3

6.3+10.5

6.3+11.8

Electronic expansion valve

Electronic expansion valve

Electronic expansion valve

Refer to the nameplate of compressor


Installation manual, Operation manual,
Connection pipes, Clamps

Standard Accessories

Refer to the nameplate of compressor


Installation manual, Operation manual,
Connection pipes, Clamps

Refer to the nameplate of compressor


Installation manual, Operation manual,
Connection pipes, Clamps

Drawing No.

Model Name (Combination Unit)

RXYQ40TSY1(E)

Model Name (Independent Unit)

RXYQ20TY1(E)+RXYQ20TY1(E)

Power Supply
Cooling Capacity 1

Heating Capacity 2

3 phase, 380-415V, 50Hz

3 phase, 380-415V, 50Hz

3 phase, 380-415V, 50Hz

96,300

115,000

144,000

Btu/h

382,000

457,000

573,000

kW

112

134

168

kcal/h

108,000

129,000

163,000

Btu/h

430,000

512,000

645,000

kW

126

150

189

Ivory white (5Y7.5/1)

Ivory white (5Y7.5/1)

Ivory white (5Y7.5/1)

(1,6571,240765)+(1,6571,240765)

(1,657930765)+(1,6571,240765)+(1,65
71,240765)

(1,6571,240765)+(1,6571,240765)
+(1,6571,240765)

mm

Heat Exchanger
Type

Comp.

Cross fin coil


Hermetically sealed scroll type

m/h

(16.90+26.28)+(16.90+26.28)

(24.68)+(16.27+17.54)+(16.27+17.54)

(16.90+26.28)+(16.90+26.28)+(16.90+26.28)

r/min

(7,980+8,250)+(7,980+8,250)

(7,746)+(7,680+8,280)+(7,680+8,280)

(7,980+8,250)+(7,980+8,250)+(7,980+8,250)

kW

(4.61)+(5.51)+(4.61)+(5.51)

(5.21)+(4.41)+(4.01)+(4.41)
+(4.01)

(4.61)+(5.51)+(4.61)+(5.51)
+(4.61)+(5.51)

Motor Output
Number of Units

Soft start

Soft start

Soft start

Propeller fan

Propeller fan

Propeller fan

Motor Output

kW

(0.752)+(0.752)

(0.551)+(0.752)+(0.752)

(0.752)+(0.752)+(0.752)

Airflow Rate

m/min

268+268

178+233+233

268+268+268

Direct drive

Direct drive

Direct drive

Drive
Liquid Pipe

mm

19.1 C1220T (Brazing connection)

19.1 C1220T (Brazing connection)

19.1 C1220T (Brazing connection)

Gas Pipe

mm

41.3 C1220T (Brazing connection)

41.3 C1220T (Brazing connection)

41.3 C1220T (Brazing connection)

kg

320+320

195+285+285

320+320+320

dB(A)

68

66

70

High pressure switch, Fan driver overload protector,


Over current relay, Inverter overload protector

High pressure switch, Fan driver overload protector,


Over current relay, Inverter overload protector

High pressure switch, Fan driver overload protector,


Over current relay, Inverter overload protector

Mass
Sound pressure level 2
Safety Devices
Capacity Control

%
Refrigerant Name

Refrigerant

Cross fin coil


Hermetically sealed scroll type

Displacement

Type

Connecting
Pipes

Cross fin coil


Hermetically sealed scroll type

Number of Revolutions

Starting Method

Fan

Charge
Control

Refrigerator Oil
Standard Accessories

kg

4-100

4-100

3-100

R410A

R410A

R410A

11.8+11.8

6.3+10.5+10.5

11.8+11.8+11.8

Electronic expansion valve

Electronic expansion valve

Electronic expansion valve

Refer to the nameplate of compressor


Installation manual, Operation manual,
Connection pipes, Clamps

Refer to the nameplate of compressor


Installation manual, Operation manual,
Connection pipes, Clamps

Drawing No.
Note : 1Indoor temp.: 27CDB, 19CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2
Indoor temp.: 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference: 0m.
3
Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4

Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5
Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric

component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to

salt damage and atmospheric pollution. Please contact Daikin for more information.

RXYQ60TNY1(E)

kcal/h

Casing Color
Dimensions: (HWD)

RXYQ48TSY1(E)

RXYQ12TY1(E)+RXYQ18TY1(E)+RXYQ18TY1(E) RXYQ20TY1(E)+RXYQ20TY1(E)+RXYQ20TY1(E)

Refer to the nameplate of compressor


Installation manual, Operation manual,
Connection pipes, Clamps

DIMENSIONS

(Unit: mm)

INDOOR UNIT
FXVQ125NY1

3D081764B

3D081764C

FXVQ200NY1

3D081765C

DIMENSIONS

(Unit: mm)

INDOOR UNIT
FXVQ250NY1

3D081766A

3D081766C

FXVQ400NY1

3D081767A

3D081767C

INDOOR UNIT / OUTDOOR UNIT


FXVQ500NY1(6)

3D085649

3D085649B

RXYQ6TY1
RXYQ8TY1
RXYQ10TY1

C: 3D084511D

10

DIMENSIONS

(Unit: mm)

OUTDOOR UNIT
RXYQ16TY1
RXYQ20TY1

C: 3D084507D

RXYQ24TSY1

C: 3D084457B

11

OUTDOOR UNIT
RXYQ30TSY1
RXYQ32TSY1

C: 3D084458B

RXYQ40TSY1

C: 3D084462B

12

DIMENSIONS

(Unit: mm)

OUTDOOR UNIT
RXYQ48TSY1

C: 3D084464B

RXYQ60TNY1

C: 3D084465B

13

WIRING DIAGRAMS
INDOOR UNIT
FXVQ125NY1
FXVQ200NY1
FXVQ250NY1

3D093434A

FXVQ400NY1
FXVQ500NY1

3D093435A

14

WIRING DIAGRAMS
INDOOR UNIT
FXVQ500NY16

3D101521

15

Electric Wiring Work and initial Setting for A2P


1. Wiring

2. Depending on whether [voltage input] or [non voltage input], connect the wiring as shown below.
Input/Output for External Control
3. Depending on whether [voltage input] or [non voltage input], connect the wiring as shown below.
Input with Voltage.
Set the Voltage/Non voltage changeover switch (SS1) to VOLT.

Input with No Voltage.


Set the Voltage/Non voltage changeover switch (SS1) to NON VOLT.

4. Display Signal Retrieval (Output)


The normal operation output terminals (W1, W2) and error output terminals (W3, W4)
are non-voltage output contacts. (Permissive current is 10mA~3A per contact.)

Output is as given below.


Output
System
Group control

Both Ry1 and Ry2 is OFF.

Only Ry1 is ON.

Only Ry2 is ON.

OFF

All normal operation

At least one unit is stopped due to


error or transmission error between
the adaptor and the indoor unit.
C: 1PA59890F

16

WIRING DIAGRAMS
5. Temperature setting input

KRP4A54
C: 1PA59890F

Temperature setting corresponds to resistance values in the range of 0 to 135.


Their relationship is as shown below.
Relation between the setting temperature and the resistance are as follows.
Setting
temperature (C)

16

Resistance ()

0.0 5.0 13.8 22.4 31.0 39.4 48.2 56.6 65.2 73.8 82.4 91.0 99.4 108.6 117.2 125.8 134.2
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
3.4 11.6 20.0 28.4 36.4 44.8 52.8 61.2 69.4 77.8 85.8 94.0 102.2 110.4 119.2 127.4 140.0

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

Note:
The value of resistance includes the resistance of wiring.
The setting temperature is limited within the setting range of indoor unit.
If you set the temperature outside of the range by the adaptor, it controls at
the nearest setting range.
6. Setting of control mode selector switch (RS1)
CONTROL
MODE
Position
RS1

Input A close
Function

Input Ignored

Remote Control Rejection

ON

Rejection

Central Priority

ON

Acceptable

ON

Only Stop
acceptable

Permit

Acceptable

3
4

OFF

Input A close/open
(pulse input)
Position

17

Function

Remote Control Rejection

Last command Priority

Input B close
(Input A is ignored)

Operation
Operation
Operation
From
or not of From Remote or not of From Remote or not of Remote
indoor
controller
indoor
controller
indoor controller
unit
unit
unit

Remote Controller
Acceptable/Rejection
Remote Controller
acceptable/rejection, OFF

Input A open

Rejection

Forced
OFF

Rejection

Constant Input B close


(Constant input) (Input A is ignored)

Operation
or not of From Remote controller Operation or not of From Remote
indoor
indoor unit
controller
unit
ON/
OFF
ON/
OFF

Rejection
Acceptable

Forced OFF at
close

Rejection

ELECTRIC CHARACTERISTICS
INDOOR UNIT / OUTDOOR UNIT

C: 4D095121A
C: 4D085660

C: 3D085335B
C: 3D085348B
C: 3D085349B
C: 3D085338B

18

CAPACITY TABLES / FAN PERFORMANCE


INDOOR UNIT
CAPACITY TABLES

Indoor air temp.


Capacity
indication

Model

FXVQ-NY1
FXVQ-NY1(6)

TC:
SHC:
Notes:

125
200
250
400
500

14.0CWB
20.0CDB
TC
9.4
15.1
18.9
30.4
37.8

SHC
8.8
13.8
17.0
27.4
35.2

16.0CWB
23.0CDB
TC
11.3
18.0
22.5
36.2
45.1

SHC
9.8
15.2
18.9
30.5
39.5

18.0CWB
26.0CDB
TC
13.1
20.9
26.2
42.1
52.4

SHC
10.8
16.7
20.8
33.5
43.4

19.0CWB
27.0CDB
TC
14.0
22.4
28.0
45.0
56.0

SHC
10.9
16.9
21.2
34.1
44.2

20.0CWB
28.0CDB
TC
14.2
22.7
28.3
45.5
56.7

SHC
10.5
16.4
20.4
33.0
42.7

22.0CWB
30.0CDB
TC
14.5
23.2
29.0
46.6
58.0

SHC
9.8
15.3
19.1
30.9
39.9

24.0CWB
32.0CDB
TC
14.9
23.8
29.7
47.7
59.4

SHC
9.1
14.1
17.6
28.7
37.3

Total capacity: kW
Sensible heat capacity: kW
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system
depends on factors such as the selected model of outdoor units, outdoor air temperature and piping length.
Please confirm that the corrected capacity of the VRV system satisfies the required heat load.
2. shows rated condition.

CA13A279A

FAN PERFORMANCE
FXVQ125NY1

4D095089A

19

FAN PERFORMANCE
INDOOR UNIT
FXVQ200NY1

4D095090A

FXVQ250NY1

4D095091A

20

FAN PERFORMANCE
INDOOR UNIT
FXVQ400NY1

4D095093A

FXVQ500NY1

4D095102A

21

INDOOR UNIT
FXVQ500NY16

C: 4D084927A

22

SOUND LEVELS
INDOOR UNIT
Overall
Location of microphone (for sound pressure level)

Notes:
1. The operating conditions are assumed to be standard
(JIS conditions).
2. These operating values were obtained in anechoic
chamber (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption coefficient)
of the particular room in which the equipment installed.

dB(A)
Sound pressure level

Model

380-415V, 50Hz

FXVQ125NY1

52

FXVQ200NY1

56

FXVQ250NY1

60

FXVQ400NY1

65

FXVQ500NY1

62

FXVQ500NY16

66

Octave Band Level


380-415V, 50Hz

FXVQ200NY1

FXVQ125NY1

FXVQ250NY1

4D095080A

FXVQ400NY1

4D095081A

4D095082A

FXVQ500NY16

FXVQ500NY1

4D095083A

23

4D095088A

4D085656

ACCESSORIES
OPTIONAL ACCESSORIES
Model
FXVQ125NY1

FXVQ200NY1

FXVQ250NY1

FXVQ400NY1

FXVQ500NY1(6)

KAFJ261L140

KAFJ261L224

KAFJ261L280

KAFJ261M450

KAFJ261M560

KAFSJ9A400

KAFSJ9A560

Item
Replacement long life filter
Ultra long-life filter

Front suction base flange

KD-9A140

KD-9A200

KD-9A280

KD-9A400

KD-9A560

KDGF-9A140

KDGF-9A200

KDGF-9A280

KDGF-9A400

KDGF-9A560

Replacement long-life filter 4, 5, 6

KAF-91A140

KAF-91A200

KAF-91A280

KAF-91A400

KAF-91A560

Colorimetric
method 65% 4, 6

KAF-92A140

KAF-92A200

KAF-92A280

KAF-92A400

KAF-92A560

Suction grille

Option for
discharge
and
suction

Front suction
filter chamber
for highefficiency filter

Filter
chamber
for highefficiency
fillter 4, 5

Replacement
highefficiency
filter

Colorimetric
method90% 5, 6

Filter chamber 4, 5
Plenum chamber
Pully for plenum chamber

KAF-93A200

KAF-93A280

KAF-93A400

KAF-93A560

KDDF-9A200

KDDF-9A280

KDDF-9A400

KDDF-9A560

KPCJ400A

KPCJ140A

KPC5J

KPC8J

KPP8JA

KPP9JA

KPP10JA

KPC15JA
7

Discharge grille for plenum side

KD101A10

KD101A20

Fresh air intake kit

KD106D10

KDFJ906A560

Rear suction kit


Wood base
Vibration isolating frame

Controller

KAF-93A140
KDDF-9A140

KDFJ905A140

KDFJ905A200

KDFJ905A280

KDFJ905A400

KKWJ9A140

KWF1G5P

KWF1G8P

KKWJ9A400

KWF1G15

K-ABSG1406A

K-ABSG1407A

K-ABSG1408A

K-ABSG1409A

K-ABSG1410A

Remote controller

BRC1C622/BRC1E623

Intelligent touch controller

DCS601C51

Intelligent touch manager

DCM601A51

Central remote controller

DCS302CA61

Unified ON/OFF Controller

DCS301BA61

Schedule timer

DST301BA61

Adaptor for wiring

KRP1C67

Wiring adaptor for electrical appendices (1)

KRP2A62

External control adaptor for cooling/heating1

KRP6A1

External control adaptor for outdoor unit1

DTA104A62

Remote sensor

KRCS01-1B

Remote controller box with key

KRCB37-1

KDFJ905A560

Note : 1Remove the group control adaptor which is a standard equipment before mounting KRP6A1 and DTA104A62.

KRP6A1 and DTA104A62 cannot be mounted to the same indoor unit at the same time.

2
Since the control panel is equipped as standard, use the option for 2 remote control system.

3
When using BRC1E62, be sure to remove the control panel and since BRC1E62 cannot be stored inside the indoor unit,

please place it separately.
4
When ordering a filter chamber for high-efficiency filter (colorimetric method 65%), please order with all the respective parts.
5

When ordering a filter chamber for high-efficiency filter (colorimetric method 90%), please order with all the respective parts.
6

When replacing with a new filter, please order the replacement filters with the corresponding filter model name.
7

The pulley and V-belt are fileld supply.

C: 3D085669F

Specification
Pulley

V-belt

FXVQ400NY1

B151

B40

FXVQ500NY1

B143

B39

FXVQ500NY16

B143

B40

24

ACCESSORIES
KAFJ261L140 224 280 / KAFJ261M450 560 Replacement Long-life Filter
KAFJ261L140
Model

AXBXC

KAFJ261L140

700 198 15
700 403 15

Unit (mm)

Dimensions

KAFJ261L224 700 403 15


KAFJ261L280

700 198 15
700 403 15

KAFJ261M450 483 315 20

Can be water-washed. Can be reused.

KAFJ261M560 483 315 20


Materials Filter frame
J: D3K2979

Model
Item
Average Efficiency (%)
Initial Pressure Loss (Pa)
Final Pressure Loss (Pa)
Life (h)
Materials
Number of Sheets Included

KAFJ261L140

KAFJ261L224

KAFJ261L280

KAFJ261M450

KAFJ261M560

40 (Gravity method)

2 (each 1)

50 (Gravity method)
9.0
49.0
2,500 hours (dust concentration 0.15 mg/m)
Mildew proof resin net
6
8
2
3 (Large:2, Small:1)

KAFSJ9A400 560 Ultra Long-life Filter Unit


Unit (mm)

Dimensions

Model

KAFSJ9A400560

478

317

Mounting diagram

Used after replacing with a standard


filter. (No main body remodeling)
Dust collection efficiency (45% gravity
method) equivalent to that of long-life
filter.
The interval between cleaning cycles is
extended by four times or more.
If installed in a pachinko parlour,
maintenance is required only once a
year. (Long-life filter: 3 months)
Can be synchronized with coil cleaning
(Approximately once a year in pachinko
parlours) to realize economy of
maintenance.
Caution
1. The filter should be cleaned (with water)
regularly according to the table to the
right.
2. The filter unit collects dirt and dust, but,
since it collects cigarette smoke
insufficiently, use in combination with an
air purifier will improve effectiveness.

25

KAFS1A

In case of KAFSJ9A
JC: D3K2359

Model
Item

KAFSJ9A400

Precipitation Efficiency (%)

45 or more (Gravity method)

Initial Pressure Loss (Pa)

25

Final Pressure Loss (Pa)


Life (h)

KAFSJ9A560

49
5,000 hours (dust concentration 0.35 mg/m)
10,000 hours (dust concentration 0.17 mg/m)

Materials

Mildew proof resin net

Number of Sheets Included

Component Parts

Reinforcing plate/frame/filter material

Mass (kg)

3.5

4.5

Both life shows a case that "the air purifier" is installed.

Mounting Locations
Locations with Much Dust (e.g. Pachinko parlours,
etc.)
Locations with Little Dust (e.g. offices)

Approximately Every 10,000 Hours


Approximately every 5,000 hours
Approximately every 10,000 hours

KDDF-92A140~560 / KDDF-93A140~560 High Efficiency Filter Chamber


Unit (mm)

Dimensions

High
efficiency
filter

Long-life filter

Model
Item
Inserted
Filter

Filter Chamber
High Efficiency Filter (65%
Colorimetric Method)
Long-life Filter

Mass (kg)
Model
Item
Inserted
Filter

Filter Chamber
High Efficiency Filter (65%
Colorimetric Method)
Long-life Filter

Mass (kg)

Dimensions

Model

KDDF-92A140
KDDF-92A200
KDDF-92A280
KDDF-92A400
KDDF-92A560
KDDF-93A140
KDDF-93A200
KDDF-93A280
KDDF-93A400
KDDF-93A560

640
840
1,060
1,050
1,350
640
840
1,060
1,050
1,350

680
880
1,100
1,090
1,390
680
880
1,100
1,090
915

685
865
685
865

735
915
735
915

KDDF-92A140

KDDF-92A200

KDDF-92A280

KDDF-92A400

KDDF-92A560

KDDF-9A140

KDDF-9A200

KDDF-9A280

KDDF-9A400

KDDF-9A560

KAF-92A140

KAF-92A200

KAF-92A280

KAF-92A400

KAF-92A560

KAF-91A140
16.1

KAF-91A200
18.5

KAF-91A280
22.3

KAF-91A400
26.0

KAF-91A560
32.0

KDDF-93A140

KDDF-93A200

KDDF-93A280

KDDF-93A400

KDDF-93A560

KDDF-9A140

KDDF-9A200

KDDF-9A280

KDDF-9A400

KDDF-9A560

KAF-93A140

KAF-93A200

KAF-93A280

KAF-93A400

KAF-93A560

KAF-91A140
16.1

KAF-91A200
18.5

KAF-91A280
22.3

KAF-91A400
26.0

KAF-91A560
32.0

KD-9A140~560 Front Suction Base Flange


Dimensions

Unit (mm)

Model

KD-9A140 682
KD-9A200

882

KD-9A560 1,392

654

2 300=600

690

854

800

250

1,074

1,020

2 250=500

1,064

1,010

2 250=500

1,364

1,310

3 250=750

632
740

KD-9A280 1,102
KD-9A400 1,092

832
40 1,052

920

1,042
1,342

870

712

280

16

14

18
892

2 250=500

20
22

J: D3K2903

Model
Item

KD-9A140

KD-9A200

Material
Mass (kg)

KD-9A280

KD-9A400

KD-9A560

5.1

5.9

Steel plate (painting)


3.5

4.2

4.8

26

ACCESSORIES
KDGF-9A140~560 Suction Grille
Unit (mm)

Dimensions
KDGF-9A140 . 200 . 280

KDGF-9A400
Model

KDGF-9A140

630

KDGF-9A200

830

KDGF-9A280

1,050

KDGF-9A560

JC: D3K2905

Item

Model

KDGF-9A140

KDGF-9A200

Material

KDGF-9A280

KDGF-9A400

KDGF-9A560

7.7

10

Steel plate (painting)

Mass (kg)

3.8

4.9

6.4

KAF-91A140~560 Long-life Filter

Additional required optional items

Dimensions

Unit (mm)

High efficiency filter chamber is


necessary.

KAF-91A140

Can be water-washed. Can be reused.

C
(Airflow Rate
Passing
Through Filter)

D
(Number of
Sheets)

210

670

16

Model

KAF-91A200
KAF-91A280

410

670

32

410

670

32

210

670

16

410

670

32

KAF-91A400

340

850

40

KAF-91A560

330

850

40

J: D3K2818

Model
Item

KAF-91A140

KAF-91A200

Average Efficiency (%)

49.0 or less

Life (h)

2,500 hours or more (dust concentration 0.15 mg/m)

Airflow Rate Passing Through Filter

C m/min

Materials

27

KAF-91A560

9.8 or less

Final Pressure Loss (Pa)

Number of Sheets Included (D)

KAF-91A400

50 (Gravity method)

Initial Pressure Loss (Pa)

Mass (kg)

KAF-91A280

Mildew proof resin net


2

3 (1+2)

2.0 (1+1)

2.4

3.2

4.5

6.0

KAF-92A140~560 / KAF-93A140~560 High Efficiency Filter


Dimensions

Model

Unit (mm)

Additional required optional items


High efficiency filter chamber is necessary.

KAF-92A140
KAF-92A200
KAF-92A280
KAF-92A400
KAF-92A560
KAF-93A140
KAF-93A200
KAF-93A280
KAF-93A400
KAF-93A560

Model
Item
Average Efficiency
(Colorimetric Method) (%)
Initial Pressure Loss (Pa)
Final Pressure Loss (Pa)
Life (h)
Materials
Number of Sheets Included
(C)
Mass (kg)

KAF92A140

KAF92A200

KAF92A280

KAF92A400

KAF92A560

KAF93A140

210
410
410
210
410
340
330
210
410
410
210
410
340
330

KAF93A200

C
(Number of sheets)
1
1
2
1
2
3
4
1
1
2
1
2
3
4

670

850

670

850

KAF93A280

65

KAF93A400

KAF93A560

90

60

70
75
95
150
200
2,200 hours or more (dust concentration 0.15 mg/m)
1,800 hours or more (dust concentration 0.15 mg/m)
Non-woven fabric of synthetic fiber
2 (1+1)

3 (1+2)

2 (1+1)

3 (1+2)

3.0

3.6

4.8

5.7

7.6

3.0

3.6

4.8

5.7

7.6

KPC(J) Plenum Chamber


Plenum Chamber
Kit Name

Unit (mm)

KPCJ140A

750

KPC5J

950

KPC8J

1,170

KPCJ400A

1,170

KPC15JA

1,470

Mass (kg)
14

510

720

230

15
16
23

320

27

28

ACCESSORIES
KPP5-10JA Pulley for Plenum Chamber

Pulley Kit Manual

This pulley kit comprises a replacement pulley and V-belt kit


for direct blowout in combination with the plenum chamber.
Components in this kit
(Variable motor pulley x 1, V-belt x 1, Manual)
Cautions regarding Usage
1. This kit should be used with no external static pressure
applied.
2. This pulley in this kit is designed for 60 Hz regions. In 50 Hz
regions, the pulley should be adjusted in accordance with
the following guidelines.
The variable side pulley is provided with two set screws.
Use one of the two screws for securing to the main body
pulley shaft.
Use the remaining screw to secure the variable side pulley
so that the clearance is AB mm as shown in the table
below.
60Hz (AA)mm

Kit Name

(Clearance)

Main body
side pulley

50Hz

(AB)mm
(Clearance)

Main body
side pulley

Variable
side pulley

Set screws
Tight after
adjustment

Variable
side pulley

Pulley Kit Manual


This pulley kit comprises a replacement pulley and V-belt kit
for direct blowout in combination with the plenum chamber.
Components in this kit
(Variable motor pulley x 1, V-belt x 1, Manual)
Cautions for Usage
1. This kit should be used with no external static pressure
applied.
2. This pulley in this kit is designed for 60 Hz regions. In 50 Hz
regions, the pulley should be adjusted in accordance with
the following guidelines.
The variable side pulley is provided with two set screws.
Use one of the two screws for securing to the main body
pulley shaft.
Use the remaining screw to secure the variable side pulley.

AA AB

BPPJ190A

7.5 1.5

BPPJ262A

7.5 3.0

KPP5JA
KPP8JA
KPP9JA
KPP10JA
6.0
RBP-KPP5JA
RBP-KPP8JA
RBP-KPP10JA

60Hz

3. After replacing the pulley, adjust the belt tension and


parallelism with the fan pulley.

3P255225-1D

50Hz

7.5
(Clearance)

Main body
side pulley

3.0
(Clearance)

Set screws
Tight after
adjustment

Variable
side pulley

Variable
Main body
side pulley side pulley

3. After replacing the pulley, adjust the belt tension and


parallelism with the fan pulley.

3P265225-2B

KD106D10 / KDFJ906A560 Fresh Air Intake Kit


KD106D10

Dimensions

Unit (mm)

Example

8-f8 hole
Flange mounting

Caution
A fabric duct (field supply) should
always be used for the connection
point between the air conditioner
and duct and vibration isolation
of the ducting system and air
conditioner should be implemented.

Fresh air intake port


companion flange
Fresh air intake
port base flange
The above diagram shows companion flanges only.
JC: D3K0677

Model

KD106D10

KDFJ906A560

260

350

260

Item

Dimensions (mm)

Inner Diameter of Connection Duct (mm)


Component Parts

29

E
F

350
40

25
210

300

210

300

Base flange, Companion flange, Cover plate, Bolts, Nuts, Installation manual

KDFJ905A140 200 280 400 560 Rear Suction Kit

Caution
A fabric duct (field supply) should
always be used for the connection
point between the air conditioner
and duct and vibration isolation
of the ducting system and air
conditioner should be implemented.

Dimensions

Unit (mm)

Example
Rear suction base flange
Rear suction port
companion flange

The above diagram shows companion flanges only.


JC: D3K2355B

Model
Item

Dimensions (mm)

Inner Diameter of Connection Duct (mm)

KDFJ905A140

KDFJ905A200

KDFJ905A280

KDFJ905A400

KDFJ905A560

740

940

1,160

1,160

1,460

514

514

514

484

484

40

40

40

40

40

25

25

25

25

25

640

840

1,060

1,050

1,350

260

260

260

300

300

Component Parts

Base flange, Companion flange, Front shield plate, Bolts, Nuts, Installation manual

Mass (kg)

12

17

19

21

24

KD101A10 20 Discharge Grille for Plenum Side


KD101A10

Dimensions

The airflow direction can be set to the left and right


of the air conditioner to match the room condition.
The vertical blade direction can be adjusted to the
left or right.
The airflow direction can be adjusted as required.
Model

6-7f hole

Colour
Component Parts

J: 2PA23790A

KD101A20

330

444

190

Mass (kg)

Bolt Pitch

Discharge grille for


side face of plenum

J: D3K0668

C
Diameter of Connection Duct (mm)

Example of grille mounting

KD101A10

Item
Dimensions (mm)

Unit (mm)

255
35

0.5

0.7

290

404

150

215

Width

2 155

2 213

Length

170

235

Ivory (Munsellvalue: Approximately 5Y7.5/1)


Discharge grille, Screws and washers, Installation manual

30

ACCESSORIES

(Unit: mm)

KWF1G5P 8P / KKWJ9A140 400 / KWF1G15 Wood Base

KWF1G5P

Dimensions

Model

Unit (mm)

A
730
1,150
930
1,150
1,450

KKWJ9A140
KKWJ9A400
KWF1G5P
KWF1G8P
KWF1G15

The air conditioner should be installed so that its


weight is distributed evenly on the floor.
(KWF1G5P 8P 15) with shock absorbing rubber.
Easy drain piping.
Drain piping is sloped downward to facilitate
drain discharge.
Model
Item
Materials
Shape
Colour
Accessories
Mass (kg)

Dimensions
B
480
685
480
480
685

C
85
85
85
85
85

J: D3K0968A

KKWJ9A140

KKWJ9A400

Western hemlock (Depending on the materials market status, Douglas fir may also be used.)
Onsite assembly
DK Black (Munsellvalue: Approximately N-1.2)
Shock absorbing rubber (t=2mm)
5.0
10.0
Model

Item
Materials
Shape
Colour
Accessories
Mass (kg)

KWF1G5P

KWF1G8P

KWF1G15

Western hemlock (Depending on the materials market status, Douglas fir may also be used.)
Onsite assembly
DK Black (Munsellvalue: Approximately N-1.2)
Shock absorbing rubber (t=2mm)
5.0
6.0
11.5

K-ABSG1406A-1410A Vibration Isolating Frame


Vibration Isolating Frame Installation manual Accessories
Please be sure to read the following before
installation and follow the instructions carefully
when performing installation work.

Before Installation
Please check that the product number on the product
nameplate matches the product order.
Please check the accessories (nuts and bolts).

Fig. 1 <Shape>
In case of K-KSV**, K-ABSG**, K-ABSZ**,
K-CBSG**, K-CBSZ**

<Device mounting bolt>


Nut and bolt joint shapes
There are two types of hole for
device mounting bolts and anchor
bolts: Through-frame and bracket
types.

Nut and
bolt joint
shapes

Accessories

In case of K-ABS**, K-ABSV**, K-CBS**, K-CBSV**


Anti-vibration stopper

For anchors

Product nameplate

Anti-vibration stopper

Base (Lower frame)

*1: "
", "
" or "
" is stamped
on the upper frame corresponding to the machine
nameplate or the piping side of mounted units.
*2: The vibration isolation material differs in arrangements
and numbers depending on the type of the model.

For device mounting

Product nameplate
Vibration isolating material
Anti-vibration stopper

Upper frame
Secure accessories
to the base.

Upper frame

Upper frame

Device
mounting
bolt hole

<Anchor bolt>

Bracket type

Through type

Base
(Lower
Anchor frame)
bolt hole

Device Base
(Lower frame)
mounting
bolt hole

Anchor
bolt hole

In case of K-KSV**, K-ABSG**, K-ABSZ**,


K-CBSG**, K-CBSZ**

In case of K-ABS**, K-ABSV**, K-CBS**, KCBSV**

Device mounting bolt


hole

Through
type

Through
type

Bracket
type

Bracket
type

Through
type

Through
type

Bracket
type

Bracket
type

Anchor bolt hole

Through
type

Bracket
type

Through
type

Bracket
type

Through
type

Bracket
type

Through
type

Bracket
type

Hexagon
head bolt

Upper frame
Secure the accessories
to the base.

Base (Lower frame)

Bracket type

Through type

Hexagon
head nut
Spring
washer
Plain
washer
Plain
washer
(Large)
Square
washer
Plain
washer
(Large)
Square
washer

For M12 O.D. f32

For M12 O.D. 42


For M16 O.D. 52

mark: Number equivalent to the number of bolt setting points provided as accessories.

<For connection types> The connection nuts and bolts are provided as accessories as shown in the figures below for connection installation of two or more vibration isolation frames.
Accessories

Spacer (Round washer, T: 8 mm)


Square or flat washer
Spring washer
Hexagon nut

Square or plan washer


Hexagon nut (Jam nut)
Hexagon nut
Long-thread bolt (M16)

Accessories

Accessories

No spacers are provided as accessory for


K-CBSV0134D. Please connect this unit as it is.
Frame 1

31

Frame 2

Plain washer
Spring washer
Hexagon nut

Hexagon head bolt


(M16 x 40)

Frame 1

Frame 2

Accessories

Dimensions of Optional Accessories


FXVQ125NY1

3D083638C

FXVQ200NY1

3D083639C

32

ACCESSORIES

(Unit: mm)

Dimensions of Optional Accessories


FXVQ250NY1

3D083640C

FXVQ400NY1

3D083641C

33

Dimensions of Optional Accessories


FXVQ500NY1(6)

3D085670B

34

FAN CHARACTERISTICS (FOR PULLEY SELECTION)


Fan Motor Specifications
Rated motor output

Items
Q

Motor
S

0.75

1.5

2.2

3.7

5.5
38

1. Shaft outer diameter

fS

19

24

28

28

2. Shaft length

40

50

60

60

80

3. Keyway width

10

4. Keyway depth

3.5

5. Insulation class
Type A and
type B

V Pulley

1. Shaft hole diameter

fd

19

24

28

28

38

2. Keyway

10

3. Keyway height

21.5

27

31

31

41

How to Select Motor Pulley


1. Select the fan revolution speed by air flow rate and external static pressure.
2. Select Motor Pulley by Fan revolution speed.
D1: Pitch Diameter of Motor Pulley (mm)
D2 x N2
D
: Pitch Diameter of Fan Pulley (mm)
2
D1 =

N
: Revolution Speed of Fan Motor (rpm)
N1
1

N2: Fan Revolution Speed
Relation between outer diameter and pitch diameter of each Pulley are as follows:
A type (Pitch Diameter) = Outer Diameter of Pulley - 9mm
B type (Pitch Diameter) = Outer Diameter of Pulley - 11mm
Please use the value given for the fan motor revolution speed (4 pole).
50Hz1450 rpm
How to Select V belt
When changing the motor pulley, the standard V belt may not be used.
In that case, select V belt in accordance with the following formula:
V-belt Size (Length)
(D2 - D1)2
4C

Lp : Effective Center Periphery Length (mm)
D1 : Pitch Diameter of Motor Pulley (mm)
D2 : Pitch Diameter of Fan Pulley (mm)

C : Distance between the shafts of the pulleys
(mm)

Lp = 2C + 1.57 (D1 + D2) +

Note: The unit of V belt length (Nominal number) is usually shown in "inch".
Distance between the shafts of the pulleys (C)
Unit: mm
50Hz
FXVQ125NY1
FXVQ200NY1
FXVQ250NY1
FXVQ400NY1
FXVQ500NY1(6)

326
325
330
245
232

Refer to each Fan Characteristics drawing for the latest value.


Pulley Specification
3B

29142
Boss inner diameter
(motor shaft diameter: mm)
Pulley outer diameter
B type pulley

The pulley makers give the pulley


size using the pitch diameter, while
Daikin uses the pulley outer
diameter.

Takes 3 belts

Pulley outer diameter


At Daikin, the outer diameter is used in pulley sizes.

Pitch Diameter (the actual diameter of the parts in contact with the belt)
The pulley makers often use the pitch diameter in pulley sizes.
When using air conditioners in duct connection, external static pressure and airflow rate will increase, exceeding the
range of use for standard motors and pulleys. Therefore, it is necessary to change the motor or pulley to deal with this.

35

Pulley and Fan Belt Adjustment


Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling

work.

In case of FXVQ125 / 200 / 250N


Operating procedures

Following the installation manual, remove the front panel and others.
Adjustment nut (C)
Fan pulley

Motor pulley
Motor pulley

Fixing nut
(B)

Parallelism criteria (K)


Less than 10 arc-minutes
(discrepancies of 3mm per 1m)

Fixing nut
(A)

Tension of V belt

Tension of a V belt must meet the deflection load (W) as shown.
Calculate the required deflection length (L) by the equation (1), its tolerance must be within the range as below.

W
L

Deflection load

L= 0.016 C (mm)
(1)
C: Distance between the shafts of the pulleys (mm)

Model

FXVQ125-250

V belt Number of belts

Type A

Motor output
(kW)

Motor pulley diameter (mm)

Deflection load W (N) per


single V belt

0.75

~99

9.0~9.9

0.75

104~

12.0~13.2

1.5

~115

14.8~16.3

1.5, 2.2

121~

12.0~13.2

Note:
When the new belt is used, adjust the tension to about 1.15 times the deflection load (W) shown above.
When the belt has adopted to the pulley (after operating about 50 hours), adjust the tension to the load shown
above.
(Even if the adjustments are made on a new belt, check the load again as shown on the above table after the belt
has adopted.)
With or without replacing the pulley, check the deflection load when about 50 hours passed after the test
operation.
After replacing belt or pulley, conduct the test operation and check if there is no abnormal noise or vibration.
Refer to the JIS B 1854 (Pulley) and JIS K 6323 (V belt) for details. (JIS: Japanese Industrial Standards)
1. Take measurements
1) Measure the parallelism of the fan pulley and motor pulley.
2) Measure the tension of the fan belt.
2. Make adjustments
1) Secure the pulley parallelism by adjustment of the motor pulley position and adjustment of fixing nuts (A) (B).
2) Adjust the fan belt tension with adjustment nut (C).
3. Perform checks
1) Check that the pulley parallelism and the fan belt tension are within the criteria.

36

FAN CHARACTERISTICS (FOR PULLEY SELECTION)


In case of FXVQ400 / 500N
Operating procedures

Following the installation manual, remove the front panel and others.
Fan pulley

Motor pulley

Parallelism criteria (K)


Less than 10"
(discrepancies of 3mm per 1m)
Tension of V belt

Tension of a V belt must meet the deflection load (W) as shown.
Calculate the required deflection length (L) by the equation (1), its tolerance must be within the range as below.

W
L

Deflection load

L= 0.016 C (mm)
(1)
C: Distance between the shafts of the pulleys (mm)

Model

FXVQ400 / 500

Motor output
(kW)

Motor pulley diameter (mm)

2.2

Any size

19.0~20.9

3.7

~136

30.0~33.0

3.7

143~161

25.4~27.9

V belt Number of belts

Type B

Deflection load W (N) per


single V belt

3.7

171~

21.1~23.2

3.7, 5.5

Any size

19.0~20.9

Note:
When the new belt is used, adjust the tension to about 1.15 times the deflection load (W) shown above.
When the belt has adopted to the pulley (after operating about 50 hours), adjust the tension to the load shown
above.
(Even if the adjustments are made on a new belt, check the load again as shown on the above table after the belt
has adopted.)
With or without replacing the pulley, check the deflection load when about 50 hours passed after the test
operation.
After replacing belt or pulley, conduct the test operation and check if there is no abnormal noise or vibration.
Refer to the JIS B 1854 (Pulley) and JIS K 6323 (V belt) for details. (JIS: Japanese Industrial Standards)
1. Take measurements
1) Measure the parallelism of the fan pulley and motor pulley.
2) Measure the tension of the fan belt.

37

2. Make adjustments
1) Secure the pulley parallelism by adjustment of the motor pulley position and adjustment of fixing bolt (A).
2) Adjust the fan belt tension by loosening fixing bolt (A) and using adjustment nut (B), (C).
Adjustment
nut (B)

Adjustment
nut (C)

Fixing bolt (A)

3. Perform checks
1) Check that the pulley parallelism and the fan belt tension are within the criteria.

V Belt Size Table


Refer to the JIS K 6323 (V belt) for details. (JIS: Japanese Industrial Standards)
(Unit: mm)
Nominal
number

Type A

Type B

Nominal
number

Type A

Type B

Nominal
number

Type A

Type B

Nominal
number

Type A

Type B

20

508

49

1245

1245

78

1981

1981

118

2997

2997

21

533

50

1270

1270

79

2007

2007

120

3048

3048

22

559

51

1295

1295

80

2032

2032

122

3099

3099

23

584

52

1321

1321

81

2057

2057

125

3175

3175

24

610

53

1346

1346

82

2083

2083

128

3251

3251

25

635

635

54

1372

1372

83

2108

2108

130

3302

3302

26

660

660

55

1397

1397

84

2134

2134

132

3353

27

686

686

56

1422

1422

85

2159

2159

135

3429

3429

28

711

711

57

1448

1448

86

2184

2184

138

3505

29

737

737

58

1473

1473

87

2210

2210

140

3556

3556

30

762

762

59

1499

1499

88

2235

2235

142

31

787

787

60

1524

1524

89

2261

2261

145

3683

3683

32

813

813

61

1549

1549

90

2286

2286

148

33

838

838

62

1575

1575

91

2311

2311

150

3810

3810

34

864

864

63

1600

1600

92

2337

2337

155

3937

3937

35

889

889

64

1626

1626

93

2362

2362

160

4064

4064

36

914

914

65

1651

1651

94

2388

2388

165

4191

4191

37

940

940

66

1676

1676

95

2413

2413

170

4318

4318

38

965

965

67

1702

1702

96

2438

2438

175

4445

39

991

991

68

1727

1727

97

2464

2464

180

4572

4572

40

1016

1016

69

1753

1753

98

2489

2489

185

4699

41

1041

1041

70

1778

1778

99

2515

2515

190

4826

42

1067

1067

71

1803

1803

100

2540

2540

195

4953

43

1092

1092

72

1829

1829

102

2591

2591

200

5080

210

5334

44

1118

1118

73

1854

1854

105

2667

2667

45

1143

1143

74

1880

1880

108

2743

2743

46

1168

1168

75

1905

1905

110

2794

2794

47

1194

1194

76

1930

1930

112

2845

2845

48

1219

1219

77

1956

1956

115

2921

2921

38

AIR TREATMENT EQUIPMENT


Air Treatment Equipment

Data and Notice in Using the Outdoor-Air Processing Mode


The FXVQ-series can be modified to the following operation mode.
- Outdoor air processing mode
It supports cooling and heating operations by introducing outdoor air.
In this outdoor-air processing mode, you cannot control the room temperature.
If you need to do so, please use this mode with another air conditioning unit for room temperature control.

- The combination with an outdoor unit is limited to one indoor unit and one set of outdoor unit (including multiple
connection of outdoor units). The connection of multiple floor standing duct units is prohibited. Connection of floor
standing duct units and other type of indoor units mixed together is prohibited.

When the outdoor-air processing mode is selected, the airflow range is limited. If the airflow exceeds the specified range,
the product may stop abnormally. On the other hand, if the airflow falls below the specified range, the equipment
reliability may decrease. For details, please see the " Airflow range" section.

When the outdoor-air processing mode is selected, the machine controls the operation so that the temperature of the
discharge air becomes closer to the preset temperature of the control panel. However, if the air-conditioning load is too
large or too small, the discharge air temperature may not become closer to the preset temperature.
Airflow range
Please set the airflow according to each operation mode. When selecting a pulley, please see "Fan characteristics (For Pully
Selection)".
Airflow range (m3/min); The value in (

Operation mode

FXVQ125NY1

FXVQ200NY1

) is the rated airflow.

FXVQ250NY1

FXVQ400NY1

FXVQ500NY1

FXVQ500NY1(6)

Standard operation mode

28 - 50 (43)

42 - 76 (69)

63 - 96 (86)

80 - 144 (134)

120 - 200 (165)

120 - 200 (172)

Outdoor-air processing mode

25 - 29 (27)

38 - 44 (41)

48 - 56 (52)

72 - 85 (78)

99 - 116 (107)

99 - 116 (107)

Option models of the rear side air inlet


When outdoor air is taken in from the rear side of the indoor unit in the outdoor-air processing mode, please prepare the following
option (Rear Suction Kit). For the shape and external dimension for the main unit attachment of this kit, please see "Detail of Optional
Accessories". Please remove the air inlet protection gauze of the main unit when attaching a front shield plate.
Option model name

FXVQ125NY1

FXVQ200NY1

FXVQ250NY1

FXVQ400NY1

FXVQ500NY1(6)

KDFJ905A140

KDFJ905A200

KDFJ905A280

KDFJ905A400

KDFJ905A560

Temperature setting range


The temperature you can set varies in each operation mode.
Operation mode

Cooling

Heating

Standard operation mode

15 - 32C

15 - 32C

Outdoor-air processing mode

15 - 27C(controlled by the discharge air


temperature)

18 - 35C(controlled by the discharge air


temperature)

Note : The setting is not available in the fan operation mode.

CJ: CA13A209

RH

air

te

0%

or

o
utd

90

10

B)

CW

. (
mp

RH

Operation limits

Operation limit
(cooling)
%

30

Operation limit
(heating)

20%

Fan only
operation

Outdoor air temp. (C DB)

39

RH
RH

Note : 1. This diagram shows operation limits under the following


conditions:
Indoor/Outdoor units - Equivalent piping length: 7.5 m
Level difference
:0m

2. Field settings and airflow rate should be changed from the
control panel.
(The airflow rate range is limited.)

3. Use the unit at indoor and outdoor air temperatures within the
operation limits.
(Using the unit at temperatures outside the operation limit may
cause it to malfunction or abnormal stop.)

4. Discharge air temperature can be set from the control panel,
but may not reach the set temperature depending on outdoor
air conditions or equipment protection control. (Particularly in
heating operation, discharge air temperature may come close
to room temperature and make you feel cold.)

5. Room temperature cannot be controlled while in outdoor-air
processing mode. If room temperature needs to be controlled,
use other room temperature control air conditioner in
combination.

Field settings
[In case of VRV IV]
Be sure to set from both (a) Field settings from the indoor unit and (b) Field settings from the outdoor unit.
(a) Field settings from the indoor unit
You need to configure the settings by the control panel of the indoor unit to change the operation mode.
Please configure the settings as shown below after completing test run.
Please also see the installation manual of the indoor unit for the setting method.
Operation mode

Mode No.

First code No.

14

Standard operation mode


Outdoor-air processing mode

Second code No.


01
03

(b) Field settings from the outdoor unit


Perform field settings with push button switch (BS1-3) on the Printed Circuit Board in the Electric Component Box.
After finishing check operation, set up according to following procedure.
As to setting method, refer to the paragraph of Field Setting in the installation manual of the outdoor unit as well.
Procedure of outdoor-air processing mode setting

7 Segment display

Details of setting

SEG1

SEG2

SEG3

1. Push the new page button (BS1) for 5 seconds in normal


mode. Confirm that 7 segment display is same as the figure Switched to Setting mode.
shown in the right.
2. Push the operation button (BS2) and adjust the 7 segment
"Outdoor-air processing mode"
display to the figure shown in the right.

The present settings of [4.] will be


indicated.
light off
light off
0

3. Push the confirmation button (BS3).


4. Push the operation button (BS2) and adjust the 7 segment
display to the figure shown in the right.

"Invalid" (factory set)

5. Push the confirmation button (BS3).

The setting in [4.] is defined.

6. Push the confirmation button (BS3) again.

The system starts the operation


according to the setting.

7. Push the new page button (BS1).

Returned to Normal mode.

"Valid"

light off

light off

It will turn to light ON.


2

light off

light off

light off

[In case of VRV III]


Set from (a) Field settings from the indoor unit only.
(a) Field settings from the indoor unit
You need to configure the settings by the control panel of the indoor unit to change the operation mode.
Please configure the settings as shown below after completing test run.
Please also see the installation manual of the indoor unit for the setting method.
Operation mode

Mode No.

First code No.

14

Standard operation mode


Outdoor-air processing mode

Second code No.


01
03

Specification table (outdoor-air processing mode)


Model name
Cooling capacity 1
Heating capacity 2
Fan

Note :

Airflow rate

FXVQ125NY1 FXVQ200NY1 FXVQ250NY1 FXVQ400NY1 FXVQ500NY1 FXVQ500NY16


kW

14.0

22.4

28.0

45.0

56.0

56.0

kW

16.0

25.0

31.5

50.0

63.0

63.0

m /min

27

41

52

78

107

172

External static pressure 4

Pa

120

150

120

261

175

469

Indoor temperature: 33CDB, 28CWB / outdoor temperature: 33CDB / Equivalent piping length: 7.5 m, level
difference: 0 m.
2

Indoor temperature: 7CDB / outdoor temperature: 7CDB, 3CWB / Equivalent piping length: 7.5 m, level
difference: 0 m.
3
This product is shipped with the airflow set to the standard mode. When introducing outdoor air (outdoor-air
processing mode), please make sure to adjust the air flow by conducting field settings from the control panel,
changing the pulley, or installing dampers. If not adjusting the airflow, the airflow would still be set to the standard
mode and therefore you might feel cold when heating or feel hot when cooling.
4

The value is the external static pressure with standard pulley.
1

40

AIR TREATMENT EQUIPMENT


Capacity characteristics

Capacity characteristics (outdoor-air processing mode)


Heating

Capacity

Capacity

Cooling

Outdoor temperature (DB)

Outdoor temperature (DB)


Note) 1. The characteristics in this chart indicates values under the
following conditions.
Equivalent piping length
: 7.5 m
Level difference
: 0.0 m
Airflow rate
: Rated
Static pressure
: Rated
Gas pipe
: Below table

Gas pipe diameter


15.9
19.1
22.2
28.6
3D057397D

Model name
125 Type
200 Type
250 Type
400 500 Type

2.

mark represents a rated point. Please read the value


multiplied by the capacity in the specification.
3. The capacity characteristics at heating does not include
capacity changes at frost accumulation (including
defrosting operation).
4. The blowing air temperature may not become the preset
temperature of the control panel due to capacity shortage,
compressor control range or protection control for
excessive capacity.
(Especially in the heating operation, you might feel cold as
the discharge air temperature becomes closer to the room
temperature.)
5. Since you cannot control the room temperature in the
outdoor-air processing mode, please use another airconditioning unit for room temperature control together if
you need to adjust the room temperature.

JC: CA13A209

41

INSTALLATION MANUAL

FXVQ125NY1 FXVQ200NY1 FXVQ250NY1 FXVQ400NY1 FXVQ500NY1

CONTENTS
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

SAFETY PRECAUTIONS ................................................. 1


BEFORE INSTALLATION................................................. 2
CARRY-IN METHOD ........................................................ 3
INSTALLATION SITE ....................................................... 3
CAUTION AT INSTALLATION .......................................... 4
REFRIGERANT PIPING ................................................... 4
DRAIN PIPING ................................................................. 6
ELECTRIC WIRING.......................................................... 6
FIELD SETTING AND CONTROL WIRING ......................... 9
TRIAL OPERATION .............................................................10

r

r

r

1. SAFETY PRECAUTIONS
Be sure to follow this SAFETY PRECAUTIONS.
This product comes under the term appliances not
accessible to the general public.
This is a class A product. In a domestic environment this
product may cause radio interference in which case the user
may be required to take adequate measures.
6JKUOCPWCNENCUUKGUVJGRTGECWVKQPUKPVQ9#40+0)5CPF
CAUTIONS.
Be sure to follow all the precautions below: They are all
important for ensuring safety.
WARNING......... Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
CAUTION .......... Indicates a potentially hazardous
situation which, if not avoided, may
result in minor or moderate injury.
It may also be used to alert against
unsafe practices.
r After the installation is completed, test the air conditioner
and check if the air conditioner operates properly. Give
the user adequate instructions concerning the use and
cleaning of the indoor unit according to the Operation
Manual. Ask the user to keep this manual and the
Operation Manual together in a handy place for future
reference.

r

r
r

r

r

r

WARNING
r #UM[QWTNQECNFGCNGTQTSWCNKGFRGTUQPPGNVQECTT[QWV
installation work.
Improper installation may result in water leakage, electric
UJQEMUQTCTG
r Perform installation work in accordance with this installation
manual.
Improper installation may result in water leakage, electric
UJQEMUQTCTG
r Consult your local dealer regarding what to do in case of
refrigerant leakage.
When the air conditioner is installed in a small room, it is
necessary to take proper measures so that the amount of
any leaked refrigerant does not exceed the concentration
limit in the event of a leakage.
Otherwise, this may lead to an accident due to oxygen
FGEKGPE[
r $GUWTGVQWUGQPN[VJGURGEKGFRCTVUCPFCEEGUUQTKGUHQT
installation work.

r

r

VRV System
air conditioner

Installation
manual

(CKNWTGVQWUGVJGURGEKGFRCTVUOC[TGUWNVKPVJGCKT
conditioner falling down, water leakage, electric shocks, a
TGGVE
Install the air conditioner on a foundation that can
withstand its mass.
It may lead to vibration of indoor units and cause
unpleasant chattering noise.
%CTT[QWVVJGURGEKGFKPUVCNNCVKQPYQTMKPEQPUKFGTCVKQPQH
strong winds, typhoons, or earthquakes.
Improper installation may result in an accident such as air
conditioner falling.
Make certain that all electrical work is carried out by
SWCNKGFRGTUQPPGNCEEQTFKPIVQVJGCRRNKECDNGNGIKUNCVKQP
(note 1) and this installation manual, using a separate
circuit.
In addition, even if the wiring is short, make sure to use
CYKTKPIVJCVJCUUWHEKGPVNGPIVJCPFPGXGTEQPPGEV
CFFKVKQPCNYKTKPIVQOCMGVJGNGPIVJUWHEKGPV
+PUWHEKGPVECRCEKV[QHVJGRQYGTUWRRN[EKTEWKVQTKORTQRGT
GNGEVTKECNEQPUVTWEVKQPOC[NGCFVQGNGEVTKEUJQEMUQTCTG
(note 1) applicable legislation means All international,
national and local directives, laws, regulations and/
or codes which are relevant and applicable for a
certain product or domain.
Earth the air conditioner.
Do not connect the earth wiring to gas or water piping,
lightning conductor or telephone earth wiring.
+PEQORNGVGGCTVJKPIOC[ECWUGGNGEVTKEUJQEMUQTCTG
Be sure to install an earth leakage circuit breaker.
(CKNWTGVQFQUQOC[ECWUGGNGEVTKEUJQEMUCPFCTG
Disconnect the power supply before touching the electric
components.
If you touch the live part, you may get an electric shocks.
/CMGUWTGVJCVCNNYKTKPIKUUGEWTGWUKPIVJGURGEKGF
wiring and ensuring that external forces do not act on the
terminal connections or wiring.
+PEQORNGVGEQPPGEVKQPQTZKPIOC[ECWUGCPQXGTJGCVQT
CTG
When wiring between the indoor and outdoor units, and
wiring the power supply, form the wiring orderly so that the
control box lid can be securely fastened.
If the control box lid is not in place, overheat of the
VGTOKPCNUGNGEVTKEUJQEMUQTCTGOC[DGECWUGF
If refrigerant gas leaks during installation work, ventilate
the area immediately.
Toxic gas may be produced if refrigerant gas comes into
EQPVCEVYKVJCTG
After completing the installation work, check to make sure
that there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the
TQQOCPFEQOGUKPVQEQPVCEVYKVJCUQWTEGQHCTGUWEJ
as a fan heater, stove or cooker.
Never directly touch any accidental leaking refrigerant.
This could result in severe wounds caused by frostbite.
CAUTION

r Install drain piping according to this installation manual to


ensure good drainage, and insulate the piping to prevent
condensation.
Improper drain piping may cause water leakage, make the
furniture get wet.

English
3P345056-6E

42

INSTALLATION MANUAL
r Install the air conditioner, power supply wiring, remote
controller wiring and transmission wiring at least 1
meter away from televisions or radios to prevent image
interference or noise.
(Depending on the radio waves, a distance of 1 meter may
PQVDGUWHEKGPVVQGNKOKPCVGVJGPQKUG
r Do not install the air conditioner in places such as the
following:
1. Where there is mist of oil, oil spray or vapour for
example a kitchen.
Resin parts may deteriorate, and cause them to fall out
or water to leak.
2. Where corrosive gas, such as sulfurous acid gas, is
produced.
Corrosion of copper pipings or brazed parts may cause
the refrigerant to leak.
3. Where there is machinery which emits electromagnetic
waves.
Electromagnetic waves may disturb the control system,
and cause malfunction of the equipment.
9JGTGCOOCDNGICUGUOC[NGCMYJGTGECTDQPDTG
or ignitable dust is suspended in the air or where volatile
COOCDNGUUWEJCUVJKPPGTQTICUQNKPGCTGJCPFNGF
If the gas should leak and remained around the air
conditioner, it may cause ignition.

r Make sure to use the R410A refrigerant before the


installation work.
(Otherwise, the unit cannot operate normally.)
r For installation of outdoor unit, refer to the installation
manual attached to the outdoor unit.
r Do not throw away the accessories required for installation
WPVKNVJGKPUVCNNCVKQPKUPKUJGF

PRECAUTION

r Be sure to instruct the customer how to properly operate


VJGU[UVGO
RCTVKEWNCTN[VJGENGCPKPIQHCKTNVGTQRGTCVKQP
method, temperature adjusting method) showing the
attached operation manual to the person.
r Do not install the unit where the atmosphere is salty
such as near the seaside, where the voltage frequently
WEVWCVGUQTKPCXGJKENGQTCDQCV

2-2

ACCESSORIES

Check if the following accessories are included in the indoor


unit.
Name

Quantity

Connection pipings
1 pc.
For each 1 pc.
(125-250 type) (400 500 type)

Drain
plug cap
1 pc.

(Liquid
piping)
Shape

(Gas piping)
(Gas piping)

Location

14 pcs.
Quantity
(125 200 type)

30 pcs.
(250 type)

Shape

Location

18 pcs.
(400 type)

36 pcs.
(500 type)

M820
Partition plate (However, 2 bolts and 2 nuts are used for
CPIGVGORQTCT[ZKPI

0WVU
HQTCPIGU
14 pcs.
30 pcs.
18 pcs.
36 pcs. [Others]
Quantity
(125 200 type) (250 type) (400 type) (500 type) rOperation
manual
rInstallation
Shape
manual
M8
Name

Location

2-3

Partition plate (However, 2 bolts and 2 nuts Stay for


CTGWUGFHQTCPIGVGORQTCT[ZKPI
control panel

CARRY OUT THE WORK GIVING


CAUTION TO THE FOLLOWING ITEMS
AND AFTER THE WORK IS COMPLETED
CHECK THESE AGAIN.

1. Items to be checked after the installation work is


completed

2. BEFORE INSTALLATION

2-1

$QNVU
HQTCPIGU

Name

Insulation
for Drain
plug

Clamp

1 pc.

3 pcs.

Items to be checked

In case of defective

Are the air conditioner rigidly


ZGF!

Drop vibration noise

Check
column

Are the installation work of the Does not operate burnout


CKTEQPFKVKQPGTEQORNGVG!
Have you carried out a
leakage test with the test
RTGUUWTGURGEKGFKPVJG
outdoor unit installation
OCPWCN!

Does not cool / Does not


heat

Is the insulation of refrigerant


piping and drain piping
EQORNGVGN[ECTTKGFQWV!

Water leakage

&QGUVJGFTCKPQYQWV
UOQQVJN[!

Water leakage

Is the power supply voltage


identical to that stated in the
manufacturers label on the air
EQPFKVKQPGT!

Does not operate burnout

Are you sure that there is no


wrong wiring nor piping or no
NQQUGYKTKPI!

Does not operate burnout

+UGCTVJKPIEQORNGVGF!

Danger in case of leakage

Are the sizes of electric wiring


Does not operate burnout
CEEQTFKPIVQVJGURGEKECVKQP!
Is any of air outlets or inlets of
the air conditioner blocked with
QDUVCENGU!
(It may lead to capacity drop
due to fan speed drop or
malfunction of equipment.)

Does not cool / Does not


heat

Have you recorded the


refrigerant piping length and
VJGTGHTKIGTCPVEJCTIGCFFGF!

Refrigerant charge amount


is not clear

Is the external static pressure


UGVRTQRGTN[!

Error A6 / Does not


operate

Partition plate

Make sure to recheck the items of SAFETY PRECAUTIONS.

English

2
3P345056-6E

43

2. Items to be checked at delivery


Check
column

Items to be checked
*CXG[QWECTTKGFQWVGNFUGVVKPI!
KHPGEGUUCT[
#TGVJGEQPVTQNDQZNKFVJGCKTNVGTCPFVJGUWEVKQPITKNNG
CVVCEJGF!
Does the cool air discharge during the cooling
operation and the warm air discharge during heating
QRGTCVKQP!
Have you explained how to operate the air conditioner
UJQYKPIVJGQRGTCVKQPOCPWCNVQVJGEWUVQOGT!
Have you explained the description of cooling and
JGCVKPIIKXGPKPVJGQRGTCVKQPOCPWCNVQVJGEWUVQOGT!
Have you handed the operation manual and the
KPUVCNNCVKQPOCPWCNVQVJGEWUVQOGT!

Points of the operation explanation


In addition to the general usage, since the items in the
operation manual with the WARNING and CAUTION
marks are likely to result in human bodily injuries and
property damages, it is necessary not only to explain
these items to the customer but also to have the
customer read them.
It is also necessary to explain the items of NOT
MALFUNCTION OF THE AIR CONDITIONER to the
customer and have the customer read them carefully.

3. CARRY-IN METHOD
Note
Do not throw away the accessories required for installation
WPVKNVJGKPUVCNNCVKQPKUPKUJGF
r Choose the carry-in route of the indoor unit.
r When lifting the unit with a crane, use belt sling and
RGTHQTONKHVKPIVJGWPKVCUUJQYPKPVJGIWTGDGNQY
Belt sling

4. INSTALLATION SITE

Put a rag or a corrugated


DGTDQCTFVQRTGXGPVFCOCIGQH
the suction grille and the control
RCPGNRCTV

Note
Do not apply force on the resin parts in case of carrying the
indoor unit when and after unpacking.
(1) Select an installation site where the following conditions
CTGUCVKUGFCPFQDVCKPVJGEWUVQOGToUCRRTQXCNDGHQTG
installation.
r The foundation is strong enough to support the weight
QHVJGWPKVCPFVJGQQTKUCVVQRTGXGPVXKDTCVKQPCPF
noise generation.
r The place where the cold (warm) air is spread all over
the room.
(In case of free blow by the plenum chamber)
r The place where the condensate can be properly
drained.
r 6JGRNCEGYJGTGVJGTGKUPQRQUUKDKNKV[QHCOOCDNG
gas leak.
r The place where is not heat affected by other heating
equipment.
r The space around the unit is adequate for servicing
and the minimum space for air inlet and air outlet is
available.
r The place where the piping length between indoor unit
and outdoor unit is within the allowable limit.
(Refer to the installation manual attached to the
outdoor unit.)
(2) After installation, remove the shipping brackets attached
to the bottom frame.
(3) Secure the unit to its base using foundation bolts.

4-1

EXAMPLE OF REQUIRED SPACE

r 5GNGEVCUWKVCDNGRCVVGTPHTQOVJGIWTGDGNQYCEEQTFKPI
to local space in view of walkway and ventilation when
installing.

+HVJGIKXGPGNFURCEGHCKNUVQOGGVVJGEQPFKVKQPUQHYQTM
KPVJKUIWTGEQPVCEVVJGFGCNGT
Piping connection

Left side

500 mm

100 mm

Right side

100 mm

500 mm

(QWPFCVKQPDQNVUZKPIRNCVG
(4 Portions)

/CMGUWTGVQUNKPIQXGTVJGJCPIGT

100 mm
or more

IJQNG(125-V[RG)
IJQNG(V[RG)

Indoor
unit
A or more

<Front

side>

B or more

900 mm or more

English
3P345056-6E

44

INSTALLATION MANUAL
5. CAUTION AT INSTALLATION
5-1

(Type 125-250)

HOW TO REPLACE PULLEY

<125-250 type>
(1) Remove the suction grille.
(2) Remove the protection net. Then remove the cushioning
material on the protection net.
(3) Remove the front panel (upper).
(4) Remove the front panel (lower).
(5) Put the iron plate, which must be wider than the fan
motor, under the fan motor, and on the heat exchanger
HQTRTQVGEVKQPHQTKVUP
+TQPRNCVGOWUVDGUWRRNKGFKPVJG
GNF
(6) Remove the terminal for the fan motor lead wire from the
magnet switch.
(7) Pull out the fan motor lead wire to the fan housing parts,
and let it out of the unit from the opening part on the front
plate (upper).
(8) Remove the nuts of the motor base.
(9) 4GOQXGVJGDGNV*QNFVJGHCPOQVQTDCUGTON[YJGP
working so that it may not move suddenly.
(10) Slide the fan housing assembly on the iron plate on which
the fan motor is put (the above procedure (5)) frontward
slowly. Work must be conducted by more than 3 persons.
One of them must hold the motor base, and two or more
of them must hold the fan housing.
(11) Move the fan housing assembly to the location where can
be worked and replace the pulley.
(12) After replacing, follow the above procedure in the reverse
order.

Parallelism
measurement tool*

Parallelism
measurement tool*

r Adopt the surface of the fan pulley side as a reference


surface.
r Consider the difference of the thickness of a pulley at the
shift amount measurement when using a pulley having
different thicknesses like variable pulley.
Fan pulley surface
(Reference surface)

Motor pulley surface

Shift amount (measurement position)

<400 500 type>


Follow the above procedure (1)-(4), (6), (7), (10), (11), (12) in
the order.
(3) Front panel
(upper)

(2) Protection net


(5) Iron plate
(Field supply)

(1) Suction
grille

Shift amount of pulleys inter-shaft distance

(8)
(9)
Fan
motor
(7)

Heat
exchanger

(4)
Front panel
(lower)

Ruler

Inter-shaft distance (mm)

(10)

Shift amount (mm)

200 - 350

1.0 or less

350 - 450

1.5 or less

Note
Use a metal ruler, L shape ruler or the like which is
measureable the straight line as a parallelism measurement
tool.

5-3 TENSION OF V BELT


Fan motor lead wire

5-2

(Type 400 or 500)

(6)

PARALLELISM OF PULLEY

r Adjust the parallelism between fan pulley and motor pulley


by measuring the upper and lower points of the V belt
CUVJGHQNNQYKPIIWTGUUQCUVQUCVKUH[VJGXCNWGKPVJG
following table.

Note
Be sure to conduct a trial operation after replacing the belt
and pulley to check the sound and vibration.
r Be sure to adjust the tension of the V belt when replacing
the belt and pulley.
r Be sure to re-adjust the tension of the V belt when roughly
JQWTUCHVGTVJGTUVVTKCNQRGTCVKQPQTCHVGTTGRNCEKPIVJG
DGNVCPFRWNNG[
CHVGTVJGDGNVIGVUVQV 
<How to adjust the tension>
(1) %CNEWNCVGCRTQRGTFGGEVKQPNGPIVJ
. D[HQTOWNC=?
(2) /GCUWTGPGEGUUCT[FGGEVKQPNQCFYJGPVJGNGPIVJ
. 
of the above (1) is given to the V belt. (See the following
IWTGU
(3) Adjust the inter-shaft distance of the pulley so that the
FGGEVKQPNQCFQHVJGCDQXG
 DGEQOGUYKVJKPVJG
following table range.
(4) 4GRGCVVJGCDQXGUVGR
 CPF
 WPVKNVJGFGGEVKQPNQCF
becomes within the table range.

English

4
3P345056-6E

45

Tension meter

CAUTION

(Type 400 or 500)

(Type 125-250)

This unit is for using R410A only.


Make sure to follow the items as shown in below when
working.
r 7UGVJGRKRGEWVVGTCPFVJGCTKPIVQQNVJCVCTG
exclusively used for R410A.
r #VCTGEQPPGEVKQPCRRN['6*'4QKNQT'56'4QKNVQ
VJGCTGUGEVKQP
r Protect the piping by a pinch or taping to prevent invasion
of contamination, moisture and dusts into the piping.

Tension meter

6-1

/GCUWTGVJGFGGEVKQPNQCF
9 YJKNGRTGUUKPIFQYPVJG
tension meter vertically to the midpoint of the belt until it
KPFKECVGUYKVJVJGRTQRGTFGGEVKQPNGPIVJ
. 

Qty

Piping on gas side

Piping on liquid side

125 type

I15.9 t1.0 mm

I9.5 t0.8 mm

200 type

I19.1 t1.0 mm

I9.5 t0.8 mm

250 type

I22.2 t1.0 mm

I9.5 t0.8 mm

400 type

I28.6 t1.0 mm

I12.7 t0.8 mm

500 type

I28.6 t1.0 mm

I15.9 t1.0 mm

6-2

Motor output
(kW)

Motor pulley
diameter (mm)

&GGEVKQPNQCF
W (N) per belt

0.75

- 99

9.0 9.9

0.75

104 -

12.0 13.2

1.5

- 115

14.8 16.3

1.5, 2.2

121 -

12.0 13.2

2.2

Any

19.0 20.9

3.7

- 136

30.0 33.0

3.7

143 - 161

25.4 27.9

3.7

171 -

21.1 23.2

3.7, 5.5

Any

19.0 20.9

6. REFRIGERANT PIPING
r For the refrigerant piping of the outdoor unit, refer to the
installation manual attached to the outdoor unit.
r Make sure to use R410A as refrigerant before the
installation work. (Otherwise, the unit cannot operate
normally)
r Make sure to insulate the piping on both the liquid side and
the gas side. Otherwise, water leakage may be caused.
7UGCJGCVKPUWNCVKPIOCVGTKCNUWHEKGPVN[TGUKUVCPVVQ
120 C. Reinforce the refrigerant piping according to the
installation environment. Otherwise, condensation may
form on the surface of the insulation.

#KTNVGTOWUV
DGTGOQXGF

Do not directly
COGVJGRKRG
ZKPIRNCVG

Do not directly
COGVJG
UQNGPQKFXCNXGCPF
OQVQTQRGTCVGFXCNXG

Connection pipings
4GOQXGVJGRKPEJGFRKRKPIU
&QPQVFKTGEVN[COGVJG
FTCKPRCPCPFVJGTOKUVQT

6-3

PIPING CONNECTION
CAUTION

Do not use anti-oxidants when brazing the piping joints.


Residue can clog pipings and break equipment.
r Be sure to perform a nitrogen blow when brazing
Brazing without performing nitrogen replacement or
releasing nitrogen into the piping will create large
SWCPVKVKGUQHQZKFK\GFNOQPVJGKPUKFGQHVJGRKRKPIU
adversely affecting valves and compressors in the
refrigerating system and preventing normal operation.

Note
r For nitrogen replacement, refer to the installation work
manual. (Contact the dealer.)
r 9JGPDTC\KPIRKRGUYJKNGQYKPIPKVTQIGPUGVVJGPKVTQIGP
pressure to 0.02 MPa or less using a pressure reducing
valve (to the extent that your cheeks feel breeze).
r &QPQVWUGCWZYJGPDTC\KPIVJGTGHTKIGTCPVU[UVGO7UG
phosphor copper brazing (BCup-2: JIS Z 3264/B-Cu93P-710
/795: ISO 3677 YJKEJFQGUPQVTGSWKTGWZ
7UKPICEJQTKPGWZOC[ECWUGVJGRKRGUVQEQTTQFG
CPFKHKVEQPVCKPUWQTKFGKVOC[ECWUGVJGTGHTKIGTCPV
lubricant to deteriorate, adversely affecting the
refrigerant piping system.

HOW TO WORK THE REFRIGERANT


PIPING

Remove the pinched pipings brazed to the end of the internal


piping.
Braze and connect the standard accessory piping.

Note
+PETGCUGVKOGUQHVJGHQNNQYKPIFGGEVKQPNQCF
9 CVVJG
initial tensioning when the belt is renewed.
Belt type

Piping size

Indoor unit
capacity

&GGEVKQPNQCF
9
0

L=0.016C
[1]
.&GGEVKQPNGPIVJ
OO
%+PVGTUJCHVFKUVCPEGQHRWNNG[
OO

CEVWCNOGCUWTGOGPV

MATERIAL OF PIPING

r Use the copper tube according to the following table.

English
3P345056-6E

46

INSTALLATION MANUAL
Note
$TC\GD[UQEMGVKHUNGGXGCTGRTQEGUUECPPQVDGEQPFWEVGF

Pressure reducing valve


Location to be brazed

CAUTION
6JGTOCNKPUWNCVKQPQHVJGGNFRKRKPIOWUVDGECTTKGFQWV
including the piping connection parts. Otherwise, it may
cause heat injury by condensation or connecting to the
exposed piping.

Nitrogen

Nitrogen
Taping
Refrigerant piping

Manual valve

CAUTION
Do not let any refrigerant other than R410A enter the
refrigerant system.
Ventilate if the refrigerant gas leaks during work.

r Secure the piping so that it does not touch the wiring.


r Insulation of pipes must be perfectly carried out without
leaving any clearance to avoid condensation.
r When connecting liquid and gas connection pipings,
KPUWNCVGCNNVJGKPVGTPCNRKRKPIUYKVJGNFUWRRNKGFKPUWNCVKQP
material for refrigerant pipings. (See following sketch.)
<125-250 type>

6-4

PROCESSING METHOD OF CONNECTION


PIPING

r See the following table for the Processing connection


piping.
r (QTTKIJVUKFGRKRKPITGRNCEGVJGRCTVKVKQPDWUJZGFQPVJG
TKIJVUKFGRCPGNYKVJVJGDWUJHQTJQNGZGFQPVJGNGHVUKFG
panel.

More than 40 mm

More than 40 mm

Left side piping connection Right side piping connection

Piping
on liquid
side
(125-250
type)

r Pass the piping from


r Pass the piping from
the hole on the right
the hole on the left side
side into the unit,
into the unit, conduct
EQPFWEVUNGGXGCTG
UNGGXGCTGRTQEGUU
process and brazed
and brazed connection.
connection.

Connection piping
(Accessory)

Gas piping

Liquid piping
Refrigerant piping
(Field supply)

<400 500 type>


Note)

More than 40 mm

Note)

Inside dia. of Flare


(See the table for
CTGRCTVFKOGPUKQPU)

Inside dia. of Flare


(5GGVJGVCDNGHQTCTG
part dimensions)

Gas piping
Connection piping
(Accessory)

Modify the accessory left


side piping and use it for
the right side.

Piping on
liquid side
(400 500
type)

Cut the
piping

Flare the pipe end or


WUGVJGVVKPICPFEQPPGEV
the piping by brazing.

THE TABLE FOR FLARE PART


DIMENSIONS

4GHGTVQVJGDGNQYVCDNGHQTCTGRCTVFKOGPUKQPU
(Unit: mm)
Indoor Piping Inside dia. of
size
CTG
unit
capacity
d0
d1 Tolerance

Allowance of
inserting part
L

Tolerance

+1.5
0

Bend
Flare shape
radius

125 type
R18

Id1

C1220T
+0.1
0

Id0

I9.5
200 type t0.8 or 9.64
more
250 type

English

More than 40 mm

7. DRAIN PIPING

side
( Connection
inside the unit )

Piping on
gas side
(125-500
type)

Refrigerant
piping insulation
(Field supply)

Liquid piping

For left side For right side


Connect the accessory
pipes and bring them
outside of the unit.

6-5

Refrigerant
piping insulation
(Field supply)

7-1

INSTALL DRAIN PIPING

r Install drain piping is order to ensure proper drainage and


insulate piping in order to prevent condensation.
r Keep the piping length as short as possible and slope the
pipe with a gradient of 1/100 or more. Do not create any air
accumulated pocket in the piping.
r Use the pipe size equivalent or larger to the pipe
connection size of the unit.
r The drain connection is available from both (left and right)
sides.
r For the right side connection, change the drain plug from
right to left.
r For piping goes through the indoor, make sure to insulate
the indoor drain socket to the end of socket.
r When connecting the drain piping, insulate the drain plug
on the opposite side of drain piping connection completely
with the attached insulation.
r Always make a drain trap at the drain outlet.

6
3P345056-6E

47

Check
r #HVGTEQORNGVKQPQHFTCKPRKRKPINGVYCVGTQYKPVQVJG
drain pan and check for drain and water leakage from the
piping connection area.
Downward inclination
1/100 or more

Drain plug cap


(accessories)
Insulation for
drain plug
(accessories)

Drain plug

100 mm 50 mm
or more or more

Unit bottom line

Indoor
unit

Drain trap
make a
drain trap

Remove the released


paper, and make sure
to label on the unit.

The end of the drain port


must be always kept in the
YCVGTVQRTGXGPVDCEMQYQH
odor from the sewage.

Drain trap
Drain piping
(for Left side connection)

CAUTION
r The connection of the drain piping
Do not directly connect the drain piping to sewerage, which
odor may smell like ammonia.
Sewerage may contain it, which may pass through the
drain piping, and result in corrosion of the indoor unit heat
exchanger.

r Do not close the branch switch and overcurrent circuit


breaker until all the works are completed.
<Method of wiring for the wiring between indoor unit
and outdoor unit, the earth wiring and the power supply
wiring>
(1) Remove the front panel (lower).
(2) Fix the each wire on the control box with the attached
clamp.
(3) (QTYKTKPIURGEKECVKQPUTGHGTVQVJG=&'6#+.51(
STANDARD DEVICES].
CAUTION
Apply putty or insulation material (Field supply) without
any clearance on the wiring intake section to prevent small
animals from entering the unit.
(If small animals such as insects enter the inside of the unit, it
may cause short circuit in the control box.)
%QPPGEVVJGYKTGUGEWTGN[WUKPIFGUKIPCVGFYKTGCPFZKV
with attached clamp without applying external pressure on
the terminal parts.
Make sure the wiring and the control box lid do not stick up
CDQXGVJGUVTWEVWTGCPFENQUGVJGEQPVTQNDQZNKFTON[

8-1

REMOVE THE FRONT PANEL (LOWER)

When removing the front panel (lower), there is the control


box.

Front panel (lower)

8. ELECTRIC WIRING
CAUTION

Screw

r Install earth leakage circuit breaker.


It is our obligation to mount earth leakage circuit
breaker in order to prevent accidents such as electric
UJQEMUCPFQTTG
r #NNGNFYKTKPICPFEQORQPGPVUOWUVDGKPUVCNNGFD[C
licensed electrician and must comply with relevant local
and national regulations.
r Use copper conductors only.
r Be sure to install an earth leakage breaker.
(Failure to install an earth leakage breaker may result in
GNGEVTKEUJQEMUQTTG
r Always earth wires. (In accordance with national
regulations of the pertinent country.)
r Do not connect the earth wire to gas pipe, sewage pipe,
lightning rods, or telephone earth wires.
r )CURKRGECPGZRNQFGQTECVEJTGKHVJGTGKUCICU
leak.
r Sewage pipes: no earth effect is possible if hard plastic
piping is used.
r Telephone earth wires and lightning rods: dangerous
when struck by lightning due to abnormal rise in
electrical potential in the earth.
r 6JGGNFYKTKPIOWUVDGECTTKGFQWVKPCEEQTFCPEGYKVJVJG
wiring diagrams and the instructions given below.
r If the fan rotates reversely, change the connection of two
power supply wires out of three.
r For connection to the terminal block, use ring type crimp
style terminal suitable for the wire size.

Front panel
(lower)
Remove the screw attached
front panel (lower).

8-2

EXTERNAL WIRING METHOD

<125-250 type>
Wiring from right side
Terminal block
for power
supply wiring

Terminal block for the


wiring between indoor
unit and outdoor unit

Control box

Pass the attached clamp through


the resin clamp, and bundle each
YKTKPIKPQPGCPFZVJGO
Earth terminal

Earth terminal for shield wire

Wiring from left side


Terminal block
for power
supply wiring
Pass the attached clamp through
the resin clamp, and bundle each
YKTKPIKPQPGCPFZVJGO

Terminal block for the


wiring between indoor
unit and outdoor unit
Control box
Earth terminal for
shield wire
Earth terminal

English
3P345056-6E

48

INSTALLATION MANUAL
<400 500 type>
Wiring from right side

Ex3. For group control

Terminal block for the


wiring between indoor
unit and outdoor unit
Control box

Outdoor unit

Power
supply

Earth terminal for


shield wire
Terminal block for
power supply wiring

Control box
IN-OUT

F1

Earth terminal

Terminal block for the


wiring between indoor
unit and outdoor unit

Earth terminal
Terminal block for
for shield wire power supply wiring

L1 L2 L3 N

Control box

Pass the attached clamp through


the resin clamp, and bundle each
YKTKPIKPQPGCPFZVJGO

Never to connect
high-voltage electricity
such as power supply cables.

Prohibited

The wiring between indoor unit and indoor unit

P1 P2
or or F F
P N 1 2

T T
1 2

Indoor unit A

L1 L2 L3 N

P1 P2
or or F F
P N 1 2

T T
1 2

L1 L2 L3 N

Indoor unit B

Earth

Earth

P1 P2
or or F F
P N 1 2

T T
1 2

Final indoor unit

Earth

Note
1. It is not necessary to set the indoor unit address for group
control.
(The setting is made automatically when the power supply
is turned on.)
2. Make sure to disconnect the control panel wiring of the
units over the second one.
3. In this case, all indoor units within the group are controlled
by the control panel for the group control.

Earth terminal

EXAMPLE OF WIRING

r The control panel is the standard built-in.


Ex1. When using in pairs
Outdoor unit
Power
supply

F2

The wiring between indoor unit and outdoor unit

Branch switch
Overcurrent
circuit breaker

Wiring from left side

8-3

F1

Control panel

Pass the attached clamp through


the resin clamp, and bundle each
YKTKPIKPQPGCPFZVJGO

OUT-OUT

F2

Control box
IN-OUT OUT-OUT
F1 F2 F1 F2

Ex4. When including BS unit


Prohibited

Never to
connect
high-voltage
electricity
such as power
supply cables.

Outdoor unit
Power
supply

Branch switch
Overcurrent
circuit breaker

F1

OUT-OUT

F2

F1

F2

The wiring between


outdoor unit and BS unit

Branch switch
Overcurrent
circuit breaker

Never to connect
high-voltage electricity such
Prohibited as power supply cables.

BS unit
Control box

*Control panel

Control panel
L1 L2L3 N

Control box
IN-OUT

The wiring between indoor


unit and outdoor unit

Outdoor

Indoor

F1

F1

L1 L2 L3 N

P1 P2
or or F F
P N 1 2

T T
1 2

Indoor unit A
Prohibited

Earth

Earth

Ex2. For multiple indoor units

8-4

Outdoor unit
Control box
F1

Control panel

Branch switch
Overcurrent
circuit breaker

L1 L2 L3 N

Power
supply

F2

The wiring between indoor


unit and outdoor unit

Prohibited

Never to connect
high-voltage
electricity such as
power supply cables.

P1 P2
or or F F T T
P N 1 2 1 2

Branch switch
Overcurrent
circuit breaker

Branch switch
Overcurrent
circuit breaker

The wiring between indoor


unit and indoor unit

L1 L2 L3 N

Indoor unit A
Earth

Power
supply

P1 P2
or or F F
P N 1 2

Control panel

OUT-OUT

F2

Control panel

IN-OUT

F1

F2

The wiring between


indoor unit and BS unit

P1 P2
or or F1F2 T1T2
P N

Indoor unit A

Power
supply

F2

T T
1 2

L1 L2 L3 N

Indoor unit B
Earth

P1 P2
or or F F
P N 1 2

T T
1 2

Final indoor unit


Earth

CAUTION
Do not have low-voltage wires (wiring between units) and other
high-voltage run through the same locations, and there must
be min. 50 mm distance between wires outside of the unit.
Or it may cause a malfunction or a breakdown of the unit by
receiving electrical noise (external noise).

Never to connect
high-voltage electricity
such as power supply cables.

PRECAUTIONS WHEN LAYING POWER


WIRING

Note
Use ring type crimp style terminals for connections to the
power terminal block.
Install the insulating sleeve for insulation of crimp part.
When none are available, follow the instructions below.
r If stranded wires are used, do not solder the front end of
the wires.
r Do not connect wiring of different size to the power
terminal block. (Slack in the power wiring may cause
abnormal heat.)
r When transmission wiring which is the same thickness, do
CUUJQYPKPVJGIWTGDGNQY
r For wiring, use the designated power wire and connect
TON[VJGPUGEWTGVQRTGXGPVQWVUKFGRTGUUWTGDGKPI
exerted on the terminal board.
Insulating sleeve

Power wire

Ring type crimp


style terminal

English

8
3P345056-6E

49

Connect same
size wiring to
both sides.

It is forbidden
to connect two
to one side.

r Use an appropriate screwdriver for tightening the terminal


screws.
A screwdriver with a small head will strip the head and
make proper tightening impossible.
r Over-tightening the terminal screws may break them.
r See the table below for tightening torque for the terminal
screws.
Tightening torque (Nm)
Terminal block for remote controller
and transmission wiring (6 poles)

0.79-0.97

Terminal block for power supply (4


poles)

1.33-1.61

Earth Terminal

3.02-4.08

8-5

Note
1. Shows only in case of protected piping. Use H07RN-F in
case of no protection.
2. Use the shield wire. Or it may cause a malfunction or
breakdown of the unit by receiving electrical noise (external
noise)

It is forbidden to
connect wiring of
different size.

9. FIELD SETTING AND CONTROL WIRING


9-1

FIELD SETTING

r Field setting of the following items is required depending


on the installation conditions.
r If optional accessories are mounted on the indoor unit, the
indoor unit setting may have to be changed. Refer to the
installation manual for each optional accessory.
2TQEGFWTGQHGNFUGVVKPI
(1) When in the normal mode, press the
button (i) for
4 seconds or more, and the FIELD SETTING MODE is
entered.
(2) Select the desired MODE NO. with the button (d).
(3) During group control, when setting by each indoor unit
(mode No. 20, 22 and 23 have been selected), press the

button (e) and select the INDOOR UNIT NO to


be set. (This operation is unnecessary when setting by
group.)
(4) Press the
upper button (f) and select FIRST
CODE NO.
(5) Press the
lower button (g) and select the
SECOND CODE NO.
TEST

DETAILS OF STANDARD DEVICES

r Refer to the installation manual attached to the outdoor


unit for the details of the wire gauge of the power supply
to the outdoor unit, the earth leakage breaker, the circuit
breaker capacity and wiring.
r 7UGQPN[VJGYKTKPIFGXKEGUURGEKGFKPVJGHQNNQYKPIVCDNG
for the wiring between indoor unit and outdoor unit.
r Branch off the exclusive lines for power supply to the
KPFQQTWPKVCEEQTFKPIVQVJGHQNNQYKPIURGEKECVKQP
1. Electrical characteristics

button (h) once and the present

(6) Press the

settings are SET.


button (i) to return to the NORMAL
(7) Press the
MODE.
TEST

Indoor units
Model

Hz

Volts

Power supply Fan motor


Voltage
range

MCA TOCA MFA kW FLA

FXVQ125NY1

2.5

2.0

16 0.75 2.0

FXVQ200NY1

4.4

3.6

16

3.6

FXVQ400NY1

380- Max. 456V 4.4


50 Hz 415V
Min. 342V
9.9

8.0

FXVQ500NY1

9.9

8.0

25

FXVQ250NY1

MCA: Min. Circuit Amps (A)


TOCA: Total Over Current Amp (A)
kW: Fan Motor Rated Output (kW)

1.5

3.5

16

1.5

3.5

25

3.7

7.9

3.7

7.9

FXVQ125NY1
FXVQ200NY1
FXVQ250NY1
FXVQ400NY1
FXVQ500NY1

16A

Wiring

FIRST
CODE NO.

SETTING

1 7

Size

TEST

Transmission wiring
Wiring

Wiring size
Balanced
and length
type shield
H05VV
must comply
wire
(Note 1)
with local
(Note 2)
codes.

Size


mm2

The lengths of remote controller wiring and transmission


wiring are as follows:
Transmission wiring ...................... Total wiring length 2000 m
r Outdoor unit - Indoor unit .... Max. 1000 m
r Outdoor unit - BS unit .......... Max. 1000 m
r BS unit - Indoor unit ............. Max. 1000 m
r Indoor unit - Indoor unit ....... Max. 1000 m

UNIT NO.

FLA: Full Load Amps (A)

Power supply wiring


Field fuses

MODE NO.
FIELD
SET
MODE

MFA: Max. Fuse Amps (A)

5RGEKECVKQPHQTGNFUWRRNKGFHWUGUCPFYKTKPI
Model

UNIT NO.
SECOND
CODE NO.

Note
1. Setting is carried out in the group mode, however, set the
mode number inside the ( ) for individual setting of the
GCEJKPFQQTWPKVQTEQPTOCVKQPCHVGTUGVVKPI
2. The SECOND CODE NO. is set to in
number when
shipped from the factory.
3. Do not make any settings not given in the table on the
below.
4. Not displayed if the indoor unit is not equipped with that
function.
5. When returning to the normal mode, 88 may be displayed
in the LCD in order for the remote.

English
3P345056-6E

50

INSTALLATION MANUAL
<Filter sign setting>
r Settings must be made when changing display interval of
NVGTUKIPCEEQTFKPIVQGPXKTQPOGPVCPFNVGTV[RG
SECOND CODE NO.
(Note.2)

Description of setting

01

02

Approx.
2500
Hrs.

Approx.
1250
Hrs.

Remote thermo-controller
(Setup is made when using a
remote thermo-controller.)

Use

Spacing time of display time to


ENGCPCKTNVGTEQWPV

5GVVKPIHQTYJGPVJGNVGTUKIP
is not to be used)

Display

10
(20)

Light

Filter Contamination-Heavy/
Light
(Setting for spacing time of
Long
FKURNC[VKOGVQENGCPCKTNVGT
life

5GVVKPIHQTYJGPNVGT
type
contamination is heavy, and
spacing time of display time to
ENGCPCKTNVGTKUVQDGJCNXGF

Heavy

Mode FIRST
NO. CODE
(Note.1) NO.

FIRST CODE
NO.

12(22)

9-2

Do not
display

01

02

None

Provided

<When operating forced OFF or ON/OFF control from the


terminal block (X3M)>
 /GVJQFQHYKTKPICPFURGEKECVKQPU
r Remote control can be carried out by connecting input
from outside to terminals T1 and T2 of the terminal block.
Class of wire

Vinyl cord with sheath or 2-wire cable

Wire gauge

0.75-1.25 mm2

Wire length

MAX 100 m

Outside contact
URGEKECVKQPU

Contact that guarantees minimum applicable


load DC15V 1 mA

T1

<Operation by centralized control>


r When using with the centralized control, remove the
jumper of the group remote control printed circuit board
mounted in the control box.
r If controlled by the centralized control equipment (the
central control panel (optional accessory)), the group NO.
must be set by the control panel.
For details, refer to the instruction of each centralized
control equipment.

SECOND CODE NO.

REMOTE CONTROLLER AND


CENTRALIZED CONTROL

F2

<When operating forced OFF, ON/OFF control, operation


display, and malfunction display from the wiring adaptor
for electrical appendices (A2P).>
Refer to For remote control in the VRV Engineering Data.

Nonuse

<Automatic reset of power failure>


r For automatic reset of power fault, settings must be made
as shown.
Mode NO.

3. For selecting Forced OFF and ON/OFF control


r Select input by control panel after turning on the power
supply.
r 5GVVQVJGGNFUGVOQFGD[EQPVTQNRCPGN

(QTGNFUGVVKPITGHGTVQVJGRTQEGFWTGUJQYPQP
previous page.)
r #HVGTGPVGTKPIVJGGNFUGVOQFGUGNGEVOQFG0QUGV
VJGTUVEQFG0QCPFUGVVJGUGEQPFEQFG0QVQpq
for forced OFF, or to 02 for ON/OFF control.
(Factory setting is set to forced OFF)

10. TRIAL OPERATION


(1) %QPTOVJCVVJGEQPVTQNDQZNKFQHVJGKPFQQTWPKVUCPFVJG
outdoor unit are closed.
(2) Perform the test run according to the installation manual
attached to the outdoor unit.
r +HVJGQRGTCVKQPNCORQPVJGEQPVTQNRCPGNKUCUJKPIKV
indicates malfunction.
Check the error code of the liquid crystal display and
the malfunction source.
For the error code and the details, refer to the
operation manual attached to the indoor unit.
In particular, if an error in the table 1 is displayed, it
may be the error of wiring work or the power supply
may not be turned ON.
(3) Carry out test run according to installation manual
attached to the outdoor unit.

T2

FORCED
OFF

Input A

2. Operation procedures
r Operation is as given in the table below for input A of
forced OFF, and ON/OFF control.
For forced OFF

For ON/OFF control

Forced OFF (control panel


rejection) by input A ON

Operate by switching input A


from OFF to ON

Control panel acceptance by


input A OFF

Stop by switching input A from


ON to OFF

English

10
3P345056-6E

51

(Table 1)
Control panel
(remote
controller)
display

Content

Under
rTerminal for forced OFF
centralized
(T1T2) may be short
control
circuiting.
CUJKPI

Solution

rFix not to short


circuit.

U4
CUJKPI
UH
CUJKPI

rThe power supply of the


outdoor unit may not turned
ON.
rThe power supply of the
outdoor unit may not be
installed yet.
rMisconnection between the
transmission wiring, and the
control panel wiring or the
forced OFF wiring.
rDisconnection of the
transmission wiring.

rTurn on the power


of outdoor unit.
rProceed installation
work for power
supply.
rFix the wiring.

NOT
display

rThe power supply of the


indoor unit is not turned ON.
rThe power supply of the
indoor unit may not be
installed yet.
rMisconnection between the
transmission wiring, and the
control panel wiring or the
forced OFF wiring.
rDisconnection of the control
panel wiring.

rTurn on the power


of indoor unit.
rProceed installation
work for power
supply.
rFix the wiring.

E4
CUJKPI

rA test run is carried out from


outdoor unit in a wrong mode
(other than standard mode).

rSelect the
standard mode,
then test run again
from outdoor unit.

A6
CUJKPI

r#KTQYTCVGKUJKIJGTVJCP
expected (overcurrent).

rAdjust the external


static pressure.

WARNING
'XGPVJQWIJVJGVGUVTWPKUPKUJGFKHVJGKPVGTKQTPKUJYQTM
is not completed, instruct the user not to operate until the
work is completed for protecting the indoor unit.
2CKPVQTCFJGUKXGWUGFHQTKPVGTKQTPKUJYQTMOC[UVCKPVJG
indoor unit, which may result in water splash or leak.

11

English
3P345056-6E