Air Cooled Packaged Inverter Floor Standing Type - Heat Pump 50Hz - APCVDT1512
Air Cooled Packaged Inverter Floor Standing Type - Heat Pump 50Hz - APCVDT1512
Product Line Up
Heat pump
5
16.0 / 18.0
8
22.4 / 25.0
10
28.0 / 31.5
16
45.0 / 50.0
20
56.0 / 63.0
54,600 / 61,400
13,800 / 15,500
76,400 / 85,300
19,300 / 21,500
95,500 / 107,000
24,100 / 27,100
154,000 / 171,000
38,700 / 43,000
191,000 / 215,000
48,200 / 54,200
FXVQ125NY1
FXVQ200NY1
FXVQ250NY1
FXVQ400NY1
FXVQ500NY1(6)
RXYQ6TY1(E)
RXYQ8TY1(E)
RXYQ10TY1(E)
RXYQ16TY1(E)
RXYQ20TY1(E)
REFNET (JOINT+REDUCER)
HP
kW
Btu/h
kcal/h
Capacity
(Cooling / Heating)
DUCT CONNECTION
TYPE
Specifications Page 5
Dimensions Page 8
Indoor unit
Dimensions
Page 10
Outdoor unit
PAIR
OUTDOOR UNIT
24
67.0 / 75.0
30
83.5 / 93.5
48
134 / 150
60
168 / 189
154,000 / 171,000
38,700 / 43,000
229,000 / 256,000
57,600 / 64,500
285,000 / 319,000
71,800 / 80,400
457,000 / 512,000
115,000 / 129,000
573,000 / 645,000
144,000 / 163,000
FXVQ125NY1 3
FXVQ200NY1 3
FXVQ250NY1 3
FXVQ400NY1 3
FXVQ500NY1(6) 3
RXYQ16TY1(E)
RXYQ24TSY1(E)
RXYQ30TSY1(E)
RXYQ48TSY1(E)
RXYQ60TNY1(E)
KHRP26A33T,
KHRP26A72T
KHRP26A72T,
KHRP26A73T
+KHRP26M73TP
KHRP26A72T,
KHRP26A73T
+KHRP26M73TP
(KHRP26A73T
+KHRP26M73TP) x 2
(KHRP26A73T
+KHRP26M73TP) x 2
BHFP22P100
BHFP22P100
BHFP22P151
BHFP22P151
TRIPLE
16
45.0 / 50.0
Note : 1 Combinations of outdoor units for High-COP, Standard, Space saving series can be selected. For details, please refer to VRV IV Catalog and Engineering data.
2
For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
l Large
l Adding
50Hz
16
45.0 / 50.0
20
56.0 / 63.0
32
89.5 / 101
40
112 / 126
95,500 / 107,000
24,100 / 27,100
154,000 / 171,000
38,700 / 43,000
191,000 / 215,000
48,200 / 54,200
305,000 / 345,000
77,000 / 86,900
382,000 / 430,000
96,300 / 108,000
FXVQ125NY1 2
FXVQ200NY1 2
FXVQ250NY1 2
FXVQ400NY1 2 FXVQ500NY1(6) 2
RXYQ10TY1(E)
RXYQ16TY1(E)
RXYQ20TY1(E)
RXYQ32TSY1(E)
RXYQ40TSY1(E)
KHRP26A33T
KHRP26A72T
KHRP26A72T
KHRP26A73T
+KHRP26M73TP
KHRP26A73T
+KHRP26M73TP
BHFP22P100
BHFP22P100
Nice,
cool air in the office
or in the cafeteria
TWIN
10
28.0 / 31.5
FOUR CONNECT
50Hz
20
56.0 / 63.0
32
89.5 / 101
40
112 / 126
191,000 / 215,000
48,200 / 54,200
305,000 / 345,000
77,000 / 86,900
382,000 / 430,000
96,300 / 108,000
FXVQ125NY1 4
FXVQ200NY1 4
FXVQ250NY1 4
RXYQ20TY1(E)
RXYQ32TSY1(E)
RXYQ40TSY1(E)
KHRP26A33T,
KHRP26A72T x 2
KHRP26A72T 2,
KHRP26A73T
+KHRP26M73TP
KHRP26A72T,
(KHRP26A73T
+KHRP26M73TP) x 2
BHFP22P100
BHFP22P100
Flexible design
FLOOR STANDING TYPE
Rear suction
Option
Plenum chamber
Option
Standard model
Factory modification
Note 1
Static pressure up
Output
ON / OFF
Compressor ON
Option
Fan ON
Error
Cool / Heat / Ventilate operation mode
Option
Input
ON / OFF
Cool / Heat / Ventilate changeover
Option
Temperature set
DIII-NET centralized control
Note:
1
Operation sound will increase 5 dB when installed with plenum chamber,
not suitable for restricted areas.
In the case of sound restricted areas, the Duct connection type is recommended.
FXVQ500NY1(6)
Heating
RXYQ20TY1(E)
Indoor temperature
14~25 CWB
Outdoor temperature
5~43 CDB
Indoor temperature
15~27 CDB
Outdoor temperature
20~15.5 CWB
Outdoor air
introduction
Air
conditioning
Outside
Circulated air
Outside
Outdoor air
introduction
* Air introduced from the outside and circulated air must be mixed in the
air conditioner primary side before introduction into the air conditioner.
165m
90m
90m
Capacity
(%)
Max. length
Max. level
difference
Operating
sound (dB)
Load
(%)
Max. level
difference
90m
Max.length
165
Night mode
100
50
8 hrs
0
60
9 hrs
57
VRV IV
50
40
8:00
12:00
16:00
min. 40
20:00
0:00
dB(A)
4:00
8:00
78.4Pa
Easy installation
in each floor of
the building
100
70
50
40
Low
Time
Just press
the button twice
Emergency operating period is 8 hrs.
Applicable for multiple outdoor units system only.
Otherwise, the emergency stop switch is available.
(Except models 8HP and 10HP)
13 steps
5% of fine
setting
Power consumption
Easy to connect
with exhaust hood
when installed at
static pressure
Centralized control is now available when using with SkyAir Inv. model
or VRV.
th
ch wid
10.4 in reen
touch sc
INDOOR UNIT
Model Name
FXVQ125NY1
FXVQ200NY1
FXVQ250NY1
kcal/h
12,000
19,300
24,100
Btu/h
47,800
76,400
95,500
kW
14.0
22.4
28.0
kcal/h
13,800
21,500
27,100
Btu/h
54,600
85,300
107,000
kW
16.0
25.0
31.5
Power supply
Cooling capacity 1, 3
mm
1,670750510
1,670950510
1,6701,170510
RowsStagesFin pitch
mm
3322.0
3322.0
3322.0
Face area
0.419
0.560
0.715
D13/4G2BH5Y1
D13/4G3AD5Y1
2D13/4G2BX5Y1
Model
Type
Motor output
Number of units
Fan
Airflow rate
External static pressure 3
Sirocco fan
Sirocco fan
Sirocco fan
7501
1,5001
1,5001
m/min
43
69
86
cfm
1,518
2,436
3,036
Pa
Drive
Temperature control
Air filter
Piping
connections 4
Type
152
217
281
Belt drive
Belt drive
Belt drive
Liquid pipes
mm
Gas pipes
mm
Drain pipe
Mass
Sound pressure level 5
kg
118
144
169
dB(A)
52
56
60
Safety devices
Refrigerant control
Connectable outdoor unit
Standard accessories
Drawing No.
C: 3D095077A
Model Name
Power supply
Cooling capacity 1, 3
Dimensions: (HWD)
38,700
48,200
48,200
191,000
191,000
kW
45.0
56.0
56.0
kcal/h
43,000
54,200
54,200
Btu/h
171,000
215,000
215,000
kW
50.0
63.0
63.0
mm
1,9001,170720
1,9001,470720
1,9001,470720
RowsStagesFin pitch
mm
3442.0
3442.0
3442.0
Face area
0.945
1.237
1.237
D2E1AG7Y1
2D2E1BB7Y1
2D2E1BB5
Sirocco fan
Sirocco fan
Sirocco fan
3,7001
3,7001
5,5001
Motor output
Number of units
Airflow rate
External static pressure 3
W
m/min
134
165
172
cfm
4,730
5,825
6,072
Pa
Drive
Temperature control
Piping
connections 4
Type
420
142
469
Belt drive
Belt drive
Belt drive
Liquid pipes
mm
Gas pipes
mm
kg
236
281
306
dB(A)
65
62
67
Drain pipe
Mass
Sound pressure level 5
Safety devices
Refrigerant control
Connectable outdoor unit
Standard accessories
Drawing No.
FXVQ500NY16
3 phase, 380-415V, 50Hz
154,000
Type
Air filter
FXVQ500NY1
3 phase, 380-415V, 50Hz
Btu/h
Model
Fan
FXVQ400NY1
3 phase, 380-415V, 50Hz
kcal/h
Casing / Colour
C: 3D095077A
Note : 1Indoor temp.: 27CDB, 19CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2
Indoor temp.: 20CDB / outdoor temp.: 7CDB, 6CWB / Standard external static pressure / Equivalent piping length: 7.5 m, level difference: 0 m.
3
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4
The value is the external static pressure with standard pulley.
5
Both liquid pipe and gas pipe need insulation work.
6
Sound level : measured when the air discharge outlet duct (2 m) is attached (anechoic chamber conversion value).
It increases by approximately 5 dB(A) when the plenum chamber is installed to deliver direct airflow.
7
Refer to Electric Characteristics for the power input.
OUTDOOR UNIT
Model Name
RXYQ6TY1(E)
RXYQ8TY1(E)
RXYQ10TY1(E)
kcal/h
13,800
19,300
24,100
Btu/h
54,600
76,400
95,500
kW
16.0
22.4
28.0
kcal/h
15,500
21,500
27,100
Btu/h
61,400
85,300
107,000
kW
18.0
25.0
31.5
1,657930765
1,657930765
1,657930765
Power Supply
Cooling Capacity 1
Heating Capacity 2
Casing Color
Dimensions: (HWD)
mm
Heat Exchanger
Type
Comp.
Displacement
m/h
16.24
16.24
Number of Revolutions
r/min
7,668
7,668
7,650
kW
2.41
3.41
4.11
Motor Output
Number of Units
Starting Method
Type
Fan
0.551
0.551
119
157
165
Direct drive
Direct drive
Direct drive
Liquid Pipe
mm
Gas Pipe
mm
kg
185
185
195
dB(A)
55
56
57
20-100
20-100
16-100
R410A
R410A
R410A
5.9
5.9
6.0
Safety Devices
Capacity Control
%
Refrigerant Name
Charge
kg
Control
Refrigerator Oil
Standard Accessories
Drawing No.
Model Name
Cooling Capacity 1
Heating Capacity 2
Dimensions: (HWD)
C: 4D085851
RXYQ16TY1(E)
RXYQ20TY1(E)
38,700
48,200
154,000
191,000
kW
45.0
56.0
kcal/h
43,000
54,200
Btu/h
171,000
215,000
kW
50.0
63.0
1,6571,240765
1,6571,240765
mm
Type
Displacement
m/h
16.27+17.54
Number of Revolutions
r/min
7,680+8,280
7,980+8,250
kW
(3.61)+(3.71)
(4.61)+(5.51)
Motor Output
Number of Units
Starting Method
Type
Soft start
Soft start
Propeller fan
Propeller fan
0.752
Motor Output
kW
0.752
Airflow Rate
m/min
233
268
Direct drive
Direct drive
Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
285
320
dB(A)
61
Mass
Sound pressure level 2
Safety Devices
Capacity Control
%
Refrigerant Name
Charge
Control
Refrigerator Oil
Standard Accessories
Drawing No.
C: 4D085850
Btu/h
Heat Exchanger
Refrigerant
kcal/h
Casing Color
Connecting
Pipes
C: 4D085850
Power Supply
Fan
0.551
kW
m/min
Comp.
Soft start
Propeller fan
Motor Output
Mass
Refrigerant
Soft start
Propeller fan
Airflow Rate
Drive
Connecting
Pipes
Soft start
Propeller fan
kg
65
High pressure switch, Fan driver overload protector,
Over current relay, Inverter overload protector
10-100
8-100
R410A
R410A
10.4
11.8
C: 4D085852A
C: 4D085853
Note : 1Indoor temp.: 27CDB, 19CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2
Indoor temp.: 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference: 0m.
3
Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4
Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5
Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
OUTDOOR UNIT
Model Name (Combination Unit)
RXYQ24TSY1(E)
RXYQ30TSY1(E)
RXYQ32TSY1(E)
RXYQ12TY1(E)+RXYQ12TY1(E)
RXYQ12TY1(E)+RXYQ18TY1(E)
RXYQ12TY1(E)+RXYQ20TY1(E)
3 phase, 380-415V, 50Hz
Power Supply
Cooling Capacity 1
Heating Capacity 2
kcal/h
57,600
71,800
77,000
Btu/h
229,000
285,000
305,000
kW
67.0
83.5
89.5
kcal/h
64,500
80,400
86,900
Btu/h
256,000
319,000
345,000
kW
75.0
93.5
101
(1,657930765)+(1,657930765)
(1,657930765)+(1,6571,240765)
(1,657930765)+(1,6571,240765)
Casing Color
Dimensions: (HWD)
mm
Heat Exchanger
Type
Comp.
Displacement
m/h
(24.68)+(24.68)
(24.68)+(16.27+17.54)
Number of Revolutions
r/min
(7,746)+(7,746)
(7,746)+(7,680+8,280)
(7,746)+(7,980+8,250)
kW
(5.21)+(5.21)
(5.21)+(4.41)+(4.01)
(5.21)+(4.61)+(5.51)
Motor Output
Number of Units
Starting Method
Type
Fan
Soft start
Propeller fan
(0.551)+(0.752)
kW
(0.551)+(0.551)
(0.551)+(0.752)
Airflow Rate
m/min
178+178
178+233
178+268
Direct drive
Direct drive
Direct drive
Liquid Pipe
mm
Gas Pipe
mm
kg
195+195
195+285
195+320
dB(A)
62
64
66
Mass
Sound pressure level 2
Safety Devices
Capacity Control
%
Refrigerant Name
Charge
Refrigerant
Soft start
Propeller fan
Motor Output
Drive
Connecting
Pipes
Soft start
Propeller fan
kg
Control
Refrigerator Oil
8-100
6-100
5-100
R410A
R410A
R410A
6.3+6.3
6.3+10.5
6.3+11.8
Standard Accessories
Drawing No.
RXYQ40TSY1(E)
RXYQ20TY1(E)+RXYQ20TY1(E)
Power Supply
Cooling Capacity 1
Heating Capacity 2
96,300
115,000
144,000
Btu/h
382,000
457,000
573,000
kW
112
134
168
kcal/h
108,000
129,000
163,000
Btu/h
430,000
512,000
645,000
kW
126
150
189
(1,6571,240765)+(1,6571,240765)
(1,657930765)+(1,6571,240765)+(1,65
71,240765)
(1,6571,240765)+(1,6571,240765)
+(1,6571,240765)
mm
Heat Exchanger
Type
Comp.
m/h
(16.90+26.28)+(16.90+26.28)
(24.68)+(16.27+17.54)+(16.27+17.54)
(16.90+26.28)+(16.90+26.28)+(16.90+26.28)
r/min
(7,980+8,250)+(7,980+8,250)
(7,746)+(7,680+8,280)+(7,680+8,280)
(7,980+8,250)+(7,980+8,250)+(7,980+8,250)
kW
(4.61)+(5.51)+(4.61)+(5.51)
(5.21)+(4.41)+(4.01)+(4.41)
+(4.01)
(4.61)+(5.51)+(4.61)+(5.51)
+(4.61)+(5.51)
Motor Output
Number of Units
Soft start
Soft start
Soft start
Propeller fan
Propeller fan
Propeller fan
Motor Output
kW
(0.752)+(0.752)
(0.551)+(0.752)+(0.752)
(0.752)+(0.752)+(0.752)
Airflow Rate
m/min
268+268
178+233+233
268+268+268
Direct drive
Direct drive
Direct drive
Drive
Liquid Pipe
mm
Gas Pipe
mm
kg
320+320
195+285+285
320+320+320
dB(A)
68
66
70
Mass
Sound pressure level 2
Safety Devices
Capacity Control
%
Refrigerant Name
Refrigerant
Displacement
Type
Connecting
Pipes
Number of Revolutions
Starting Method
Fan
Charge
Control
Refrigerator Oil
Standard Accessories
kg
4-100
4-100
3-100
R410A
R410A
R410A
11.8+11.8
6.3+10.5+10.5
11.8+11.8+11.8
Drawing No.
Note : 1Indoor temp.: 27CDB, 19CWB / outdoor temp.: 35CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2
Indoor temp.: 20CDB / outdoor temp.: 7CDB, 6CWB / Equivalent piping length: 7.5m, level difference: 0m.
3
Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4
Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5
Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
RXYQ60TNY1(E)
kcal/h
Casing Color
Dimensions: (HWD)
RXYQ48TSY1(E)
RXYQ12TY1(E)+RXYQ18TY1(E)+RXYQ18TY1(E) RXYQ20TY1(E)+RXYQ20TY1(E)+RXYQ20TY1(E)
DIMENSIONS
(Unit: mm)
INDOOR UNIT
FXVQ125NY1
3D081764B
3D081764C
FXVQ200NY1
3D081765C
DIMENSIONS
(Unit: mm)
INDOOR UNIT
FXVQ250NY1
3D081766A
3D081766C
FXVQ400NY1
3D081767A
3D081767C
3D085649
3D085649B
RXYQ6TY1
RXYQ8TY1
RXYQ10TY1
C: 3D084511D
10
DIMENSIONS
(Unit: mm)
OUTDOOR UNIT
RXYQ16TY1
RXYQ20TY1
C: 3D084507D
RXYQ24TSY1
C: 3D084457B
11
OUTDOOR UNIT
RXYQ30TSY1
RXYQ32TSY1
C: 3D084458B
RXYQ40TSY1
C: 3D084462B
12
DIMENSIONS
(Unit: mm)
OUTDOOR UNIT
RXYQ48TSY1
C: 3D084464B
RXYQ60TNY1
C: 3D084465B
13
WIRING DIAGRAMS
INDOOR UNIT
FXVQ125NY1
FXVQ200NY1
FXVQ250NY1
3D093434A
FXVQ400NY1
FXVQ500NY1
3D093435A
14
WIRING DIAGRAMS
INDOOR UNIT
FXVQ500NY16
3D101521
15
2. Depending on whether [voltage input] or [non voltage input], connect the wiring as shown below.
Input/Output for External Control
3. Depending on whether [voltage input] or [non voltage input], connect the wiring as shown below.
Input with Voltage.
Set the Voltage/Non voltage changeover switch (SS1) to VOLT.
OFF
16
WIRING DIAGRAMS
5. Temperature setting input
KRP4A54
C: 1PA59890F
16
Resistance ()
0.0 5.0 13.8 22.4 31.0 39.4 48.2 56.6 65.2 73.8 82.4 91.0 99.4 108.6 117.2 125.8 134.2
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
3.4 11.6 20.0 28.4 36.4 44.8 52.8 61.2 69.4 77.8 85.8 94.0 102.2 110.4 119.2 127.4 140.0
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Note:
The value of resistance includes the resistance of wiring.
The setting temperature is limited within the setting range of indoor unit.
If you set the temperature outside of the range by the adaptor, it controls at
the nearest setting range.
6. Setting of control mode selector switch (RS1)
CONTROL
MODE
Position
RS1
Input A close
Function
Input Ignored
ON
Rejection
Central Priority
ON
Acceptable
ON
Only Stop
acceptable
Permit
Acceptable
3
4
OFF
Input A close/open
(pulse input)
Position
17
Function
Input B close
(Input A is ignored)
Operation
Operation
Operation
From
or not of From Remote or not of From Remote or not of Remote
indoor
controller
indoor
controller
indoor controller
unit
unit
unit
Remote Controller
Acceptable/Rejection
Remote Controller
acceptable/rejection, OFF
Input A open
Rejection
Forced
OFF
Rejection
Operation
or not of From Remote controller Operation or not of From Remote
indoor
indoor unit
controller
unit
ON/
OFF
ON/
OFF
Rejection
Acceptable
Forced OFF at
close
Rejection
ELECTRIC CHARACTERISTICS
INDOOR UNIT / OUTDOOR UNIT
C: 4D095121A
C: 4D085660
C: 3D085335B
C: 3D085348B
C: 3D085349B
C: 3D085338B
18
Model
FXVQ-NY1
FXVQ-NY1(6)
TC:
SHC:
Notes:
125
200
250
400
500
14.0CWB
20.0CDB
TC
9.4
15.1
18.9
30.4
37.8
SHC
8.8
13.8
17.0
27.4
35.2
16.0CWB
23.0CDB
TC
11.3
18.0
22.5
36.2
45.1
SHC
9.8
15.2
18.9
30.5
39.5
18.0CWB
26.0CDB
TC
13.1
20.9
26.2
42.1
52.4
SHC
10.8
16.7
20.8
33.5
43.4
19.0CWB
27.0CDB
TC
14.0
22.4
28.0
45.0
56.0
SHC
10.9
16.9
21.2
34.1
44.2
20.0CWB
28.0CDB
TC
14.2
22.7
28.3
45.5
56.7
SHC
10.5
16.4
20.4
33.0
42.7
22.0CWB
30.0CDB
TC
14.5
23.2
29.0
46.6
58.0
SHC
9.8
15.3
19.1
30.9
39.9
24.0CWB
32.0CDB
TC
14.9
23.8
29.7
47.7
59.4
SHC
9.1
14.1
17.6
28.7
37.3
Total capacity: kW
Sensible heat capacity: kW
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system
depends on factors such as the selected model of outdoor units, outdoor air temperature and piping length.
Please confirm that the corrected capacity of the VRV system satisfies the required heat load.
2. shows rated condition.
CA13A279A
FAN PERFORMANCE
FXVQ125NY1
4D095089A
19
FAN PERFORMANCE
INDOOR UNIT
FXVQ200NY1
4D095090A
FXVQ250NY1
4D095091A
20
FAN PERFORMANCE
INDOOR UNIT
FXVQ400NY1
4D095093A
FXVQ500NY1
4D095102A
21
INDOOR UNIT
FXVQ500NY16
C: 4D084927A
22
SOUND LEVELS
INDOOR UNIT
Overall
Location of microphone (for sound pressure level)
Notes:
1. The operating conditions are assumed to be standard
(JIS conditions).
2. These operating values were obtained in anechoic
chamber (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption coefficient)
of the particular room in which the equipment installed.
dB(A)
Sound pressure level
Model
380-415V, 50Hz
FXVQ125NY1
52
FXVQ200NY1
56
FXVQ250NY1
60
FXVQ400NY1
65
FXVQ500NY1
62
FXVQ500NY16
66
FXVQ200NY1
FXVQ125NY1
FXVQ250NY1
4D095080A
FXVQ400NY1
4D095081A
4D095082A
FXVQ500NY16
FXVQ500NY1
4D095083A
23
4D095088A
4D085656
ACCESSORIES
OPTIONAL ACCESSORIES
Model
FXVQ125NY1
FXVQ200NY1
FXVQ250NY1
FXVQ400NY1
FXVQ500NY1(6)
KAFJ261L140
KAFJ261L224
KAFJ261L280
KAFJ261M450
KAFJ261M560
KAFSJ9A400
KAFSJ9A560
Item
Replacement long life filter
Ultra long-life filter
KD-9A140
KD-9A200
KD-9A280
KD-9A400
KD-9A560
KDGF-9A140
KDGF-9A200
KDGF-9A280
KDGF-9A400
KDGF-9A560
KAF-91A140
KAF-91A200
KAF-91A280
KAF-91A400
KAF-91A560
Colorimetric
method 65% 4, 6
KAF-92A140
KAF-92A200
KAF-92A280
KAF-92A400
KAF-92A560
Suction grille
Option for
discharge
and
suction
Front suction
filter chamber
for highefficiency filter
Filter
chamber
for highefficiency
fillter 4, 5
Replacement
highefficiency
filter
Colorimetric
method90% 5, 6
Filter chamber 4, 5
Plenum chamber
Pully for plenum chamber
KAF-93A200
KAF-93A280
KAF-93A400
KAF-93A560
KDDF-9A200
KDDF-9A280
KDDF-9A400
KDDF-9A560
KPCJ400A
KPCJ140A
KPC5J
KPC8J
KPP8JA
KPP9JA
KPP10JA
KPC15JA
7
KD101A10
KD101A20
KD106D10
KDFJ906A560
Controller
KAF-93A140
KDDF-9A140
KDFJ905A140
KDFJ905A200
KDFJ905A280
KDFJ905A400
KKWJ9A140
KWF1G5P
KWF1G8P
KKWJ9A400
KWF1G15
K-ABSG1406A
K-ABSG1407A
K-ABSG1408A
K-ABSG1409A
K-ABSG1410A
Remote controller
BRC1C622/BRC1E623
DCS601C51
DCM601A51
DCS302CA61
DCS301BA61
Schedule timer
DST301BA61
KRP1C67
KRP2A62
KRP6A1
DTA104A62
Remote sensor
KRCS01-1B
KRCB37-1
KDFJ905A560
Note : 1Remove the group control adaptor which is a standard equipment before mounting KRP6A1 and DTA104A62.
KRP6A1 and DTA104A62 cannot be mounted to the same indoor unit at the same time.
2
Since the control panel is equipped as standard, use the option for 2 remote control system.
3
When using BRC1E62, be sure to remove the control panel and since BRC1E62 cannot be stored inside the indoor unit,
please place it separately.
4
When ordering a filter chamber for high-efficiency filter (colorimetric method 65%), please order with all the respective parts.
5
When ordering a filter chamber for high-efficiency filter (colorimetric method 90%), please order with all the respective parts.
6
When replacing with a new filter, please order the replacement filters with the corresponding filter model name.
7
The pulley and V-belt are fileld supply.
C: 3D085669F
Specification
Pulley
V-belt
FXVQ400NY1
B151
B40
FXVQ500NY1
B143
B39
FXVQ500NY16
B143
B40
24
ACCESSORIES
KAFJ261L140 224 280 / KAFJ261M450 560 Replacement Long-life Filter
KAFJ261L140
Model
AXBXC
KAFJ261L140
700 198 15
700 403 15
Unit (mm)
Dimensions
700 198 15
700 403 15
Model
Item
Average Efficiency (%)
Initial Pressure Loss (Pa)
Final Pressure Loss (Pa)
Life (h)
Materials
Number of Sheets Included
KAFJ261L140
KAFJ261L224
KAFJ261L280
KAFJ261M450
KAFJ261M560
40 (Gravity method)
2 (each 1)
50 (Gravity method)
9.0
49.0
2,500 hours (dust concentration 0.15 mg/m)
Mildew proof resin net
6
8
2
3 (Large:2, Small:1)
Dimensions
Model
KAFSJ9A400560
478
317
Mounting diagram
25
KAFS1A
In case of KAFSJ9A
JC: D3K2359
Model
Item
KAFSJ9A400
25
KAFSJ9A560
49
5,000 hours (dust concentration 0.35 mg/m)
10,000 hours (dust concentration 0.17 mg/m)
Materials
Component Parts
Mass (kg)
3.5
4.5
Mounting Locations
Locations with Much Dust (e.g. Pachinko parlours,
etc.)
Locations with Little Dust (e.g. offices)
Dimensions
High
efficiency
filter
Long-life filter
Model
Item
Inserted
Filter
Filter Chamber
High Efficiency Filter (65%
Colorimetric Method)
Long-life Filter
Mass (kg)
Model
Item
Inserted
Filter
Filter Chamber
High Efficiency Filter (65%
Colorimetric Method)
Long-life Filter
Mass (kg)
Dimensions
Model
KDDF-92A140
KDDF-92A200
KDDF-92A280
KDDF-92A400
KDDF-92A560
KDDF-93A140
KDDF-93A200
KDDF-93A280
KDDF-93A400
KDDF-93A560
640
840
1,060
1,050
1,350
640
840
1,060
1,050
1,350
680
880
1,100
1,090
1,390
680
880
1,100
1,090
915
685
865
685
865
735
915
735
915
KDDF-92A140
KDDF-92A200
KDDF-92A280
KDDF-92A400
KDDF-92A560
KDDF-9A140
KDDF-9A200
KDDF-9A280
KDDF-9A400
KDDF-9A560
KAF-92A140
KAF-92A200
KAF-92A280
KAF-92A400
KAF-92A560
KAF-91A140
16.1
KAF-91A200
18.5
KAF-91A280
22.3
KAF-91A400
26.0
KAF-91A560
32.0
KDDF-93A140
KDDF-93A200
KDDF-93A280
KDDF-93A400
KDDF-93A560
KDDF-9A140
KDDF-9A200
KDDF-9A280
KDDF-9A400
KDDF-9A560
KAF-93A140
KAF-93A200
KAF-93A280
KAF-93A400
KAF-93A560
KAF-91A140
16.1
KAF-91A200
18.5
KAF-91A280
22.3
KAF-91A400
26.0
KAF-91A560
32.0
Unit (mm)
Model
KD-9A140 682
KD-9A200
882
KD-9A560 1,392
654
2 300=600
690
854
800
250
1,074
1,020
2 250=500
1,064
1,010
2 250=500
1,364
1,310
3 250=750
632
740
KD-9A280 1,102
KD-9A400 1,092
832
40 1,052
920
1,042
1,342
870
712
280
16
14
18
892
2 250=500
20
22
J: D3K2903
Model
Item
KD-9A140
KD-9A200
Material
Mass (kg)
KD-9A280
KD-9A400
KD-9A560
5.1
5.9
4.2
4.8
26
ACCESSORIES
KDGF-9A140~560 Suction Grille
Unit (mm)
Dimensions
KDGF-9A140 . 200 . 280
KDGF-9A400
Model
KDGF-9A140
630
KDGF-9A200
830
KDGF-9A280
1,050
KDGF-9A560
JC: D3K2905
Item
Model
KDGF-9A140
KDGF-9A200
Material
KDGF-9A280
KDGF-9A400
KDGF-9A560
7.7
10
Mass (kg)
3.8
4.9
6.4
Dimensions
Unit (mm)
KAF-91A140
C
(Airflow Rate
Passing
Through Filter)
D
(Number of
Sheets)
210
670
16
Model
KAF-91A200
KAF-91A280
410
670
32
410
670
32
210
670
16
410
670
32
KAF-91A400
340
850
40
KAF-91A560
330
850
40
J: D3K2818
Model
Item
KAF-91A140
KAF-91A200
49.0 or less
Life (h)
C m/min
Materials
27
KAF-91A560
9.8 or less
KAF-91A400
50 (Gravity method)
Mass (kg)
KAF-91A280
3 (1+2)
2.0 (1+1)
2.4
3.2
4.5
6.0
Model
Unit (mm)
KAF-92A140
KAF-92A200
KAF-92A280
KAF-92A400
KAF-92A560
KAF-93A140
KAF-93A200
KAF-93A280
KAF-93A400
KAF-93A560
Model
Item
Average Efficiency
(Colorimetric Method) (%)
Initial Pressure Loss (Pa)
Final Pressure Loss (Pa)
Life (h)
Materials
Number of Sheets Included
(C)
Mass (kg)
KAF92A140
KAF92A200
KAF92A280
KAF92A400
KAF92A560
KAF93A140
210
410
410
210
410
340
330
210
410
410
210
410
340
330
KAF93A200
C
(Number of sheets)
1
1
2
1
2
3
4
1
1
2
1
2
3
4
670
850
670
850
KAF93A280
65
KAF93A400
KAF93A560
90
60
70
75
95
150
200
2,200 hours or more (dust concentration 0.15 mg/m)
1,800 hours or more (dust concentration 0.15 mg/m)
Non-woven fabric of synthetic fiber
2 (1+1)
3 (1+2)
2 (1+1)
3 (1+2)
3.0
3.6
4.8
5.7
7.6
3.0
3.6
4.8
5.7
7.6
Unit (mm)
KPCJ140A
750
KPC5J
950
KPC8J
1,170
KPCJ400A
1,170
KPC15JA
1,470
Mass (kg)
14
510
720
230
15
16
23
320
27
28
ACCESSORIES
KPP5-10JA Pulley for Plenum Chamber
Kit Name
(Clearance)
Main body
side pulley
50Hz
(AB)mm
(Clearance)
Main body
side pulley
Variable
side pulley
Set screws
Tight after
adjustment
Variable
side pulley
AA AB
BPPJ190A
7.5 1.5
BPPJ262A
7.5 3.0
KPP5JA
KPP8JA
KPP9JA
KPP10JA
6.0
RBP-KPP5JA
RBP-KPP8JA
RBP-KPP10JA
60Hz
3P255225-1D
50Hz
7.5
(Clearance)
Main body
side pulley
3.0
(Clearance)
Set screws
Tight after
adjustment
Variable
side pulley
Variable
Main body
side pulley side pulley
3P265225-2B
Dimensions
Unit (mm)
Example
8-f8 hole
Flange mounting
Caution
A fabric duct (field supply) should
always be used for the connection
point between the air conditioner
and duct and vibration isolation
of the ducting system and air
conditioner should be implemented.
Model
KD106D10
KDFJ906A560
260
350
260
Item
Dimensions (mm)
29
E
F
350
40
25
210
300
210
300
Base flange, Companion flange, Cover plate, Bolts, Nuts, Installation manual
Caution
A fabric duct (field supply) should
always be used for the connection
point between the air conditioner
and duct and vibration isolation
of the ducting system and air
conditioner should be implemented.
Dimensions
Unit (mm)
Example
Rear suction base flange
Rear suction port
companion flange
Model
Item
Dimensions (mm)
KDFJ905A140
KDFJ905A200
KDFJ905A280
KDFJ905A400
KDFJ905A560
740
940
1,160
1,160
1,460
514
514
514
484
484
40
40
40
40
40
25
25
25
25
25
640
840
1,060
1,050
1,350
260
260
260
300
300
Component Parts
Base flange, Companion flange, Front shield plate, Bolts, Nuts, Installation manual
Mass (kg)
12
17
19
21
24
Dimensions
6-7f hole
Colour
Component Parts
J: 2PA23790A
KD101A20
330
444
190
Mass (kg)
Bolt Pitch
J: D3K0668
C
Diameter of Connection Duct (mm)
KD101A10
Item
Dimensions (mm)
Unit (mm)
255
35
0.5
0.7
290
404
150
215
Width
2 155
2 213
Length
170
235
30
ACCESSORIES
(Unit: mm)
KWF1G5P
Dimensions
Model
Unit (mm)
A
730
1,150
930
1,150
1,450
KKWJ9A140
KKWJ9A400
KWF1G5P
KWF1G8P
KWF1G15
Dimensions
B
480
685
480
480
685
C
85
85
85
85
85
J: D3K0968A
KKWJ9A140
KKWJ9A400
Western hemlock (Depending on the materials market status, Douglas fir may also be used.)
Onsite assembly
DK Black (Munsellvalue: Approximately N-1.2)
Shock absorbing rubber (t=2mm)
5.0
10.0
Model
Item
Materials
Shape
Colour
Accessories
Mass (kg)
KWF1G5P
KWF1G8P
KWF1G15
Western hemlock (Depending on the materials market status, Douglas fir may also be used.)
Onsite assembly
DK Black (Munsellvalue: Approximately N-1.2)
Shock absorbing rubber (t=2mm)
5.0
6.0
11.5
Before Installation
Please check that the product number on the product
nameplate matches the product order.
Please check the accessories (nuts and bolts).
Fig. 1 <Shape>
In case of K-KSV**, K-ABSG**, K-ABSZ**,
K-CBSG**, K-CBSZ**
Nut and
bolt joint
shapes
Accessories
For anchors
Product nameplate
Anti-vibration stopper
*1: "
", "
" or "
" is stamped
on the upper frame corresponding to the machine
nameplate or the piping side of mounted units.
*2: The vibration isolation material differs in arrangements
and numbers depending on the type of the model.
Product nameplate
Vibration isolating material
Anti-vibration stopper
Upper frame
Secure accessories
to the base.
Upper frame
Upper frame
Device
mounting
bolt hole
<Anchor bolt>
Bracket type
Through type
Base
(Lower
Anchor frame)
bolt hole
Device Base
(Lower frame)
mounting
bolt hole
Anchor
bolt hole
Through
type
Through
type
Bracket
type
Bracket
type
Through
type
Through
type
Bracket
type
Bracket
type
Through
type
Bracket
type
Through
type
Bracket
type
Through
type
Bracket
type
Through
type
Bracket
type
Hexagon
head bolt
Upper frame
Secure the accessories
to the base.
Bracket type
Through type
Hexagon
head nut
Spring
washer
Plain
washer
Plain
washer
(Large)
Square
washer
Plain
washer
(Large)
Square
washer
mark: Number equivalent to the number of bolt setting points provided as accessories.
<For connection types> The connection nuts and bolts are provided as accessories as shown in the figures below for connection installation of two or more vibration isolation frames.
Accessories
Accessories
Accessories
31
Frame 2
Plain washer
Spring washer
Hexagon nut
Frame 1
Frame 2
Accessories
3D083638C
FXVQ200NY1
3D083639C
32
ACCESSORIES
(Unit: mm)
3D083640C
FXVQ400NY1
3D083641C
33
3D085670B
34
Items
Q
Motor
S
0.75
1.5
2.2
3.7
5.5
38
fS
19
24
28
28
2. Shaft length
40
50
60
60
80
3. Keyway width
10
4. Keyway depth
3.5
5. Insulation class
Type A and
type B
V Pulley
fd
19
24
28
28
38
2. Keyway
10
3. Keyway height
21.5
27
31
31
41
Note: The unit of V belt length (Nominal number) is usually shown in "inch".
Distance between the shafts of the pulleys (C)
Unit: mm
50Hz
FXVQ125NY1
FXVQ200NY1
FXVQ250NY1
FXVQ400NY1
FXVQ500NY1(6)
326
325
330
245
232
29142
Boss inner diameter
(motor shaft diameter: mm)
Pulley outer diameter
B type pulley
Takes 3 belts
Pitch Diameter (the actual diameter of the parts in contact with the belt)
The pulley makers often use the pitch diameter in pulley sizes.
When using air conditioners in duct connection, external static pressure and airflow rate will increase, exceeding the
range of use for standard motors and pulleys. Therefore, it is necessary to change the motor or pulley to deal with this.
35
Motor pulley
Motor pulley
Fixing nut
(B)
Fixing nut
(A)
Tension of V belt
Tension of a V belt must meet the deflection load (W) as shown.
Calculate the required deflection length (L) by the equation (1), its tolerance must be within the range as below.
W
L
Deflection load
L= 0.016 C (mm)
(1)
C: Distance between the shafts of the pulleys (mm)
Model
FXVQ125-250
Type A
Motor output
(kW)
0.75
~99
9.0~9.9
0.75
104~
12.0~13.2
1.5
~115
14.8~16.3
1.5, 2.2
121~
12.0~13.2
Note:
When the new belt is used, adjust the tension to about 1.15 times the deflection load (W) shown above.
When the belt has adopted to the pulley (after operating about 50 hours), adjust the tension to the load shown
above.
(Even if the adjustments are made on a new belt, check the load again as shown on the above table after the belt
has adopted.)
With or without replacing the pulley, check the deflection load when about 50 hours passed after the test
operation.
After replacing belt or pulley, conduct the test operation and check if there is no abnormal noise or vibration.
Refer to the JIS B 1854 (Pulley) and JIS K 6323 (V belt) for details. (JIS: Japanese Industrial Standards)
1. Take measurements
1) Measure the parallelism of the fan pulley and motor pulley.
2) Measure the tension of the fan belt.
2. Make adjustments
1) Secure the pulley parallelism by adjustment of the motor pulley position and adjustment of fixing nuts (A) (B).
2) Adjust the fan belt tension with adjustment nut (C).
3. Perform checks
1) Check that the pulley parallelism and the fan belt tension are within the criteria.
36
Following the installation manual, remove the front panel and others.
Fan pulley
Motor pulley
W
L
Deflection load
L= 0.016 C (mm)
(1)
C: Distance between the shafts of the pulleys (mm)
Model
FXVQ400 / 500
Motor output
(kW)
2.2
Any size
19.0~20.9
3.7
~136
30.0~33.0
3.7
143~161
25.4~27.9
Type B
3.7
171~
21.1~23.2
3.7, 5.5
Any size
19.0~20.9
Note:
When the new belt is used, adjust the tension to about 1.15 times the deflection load (W) shown above.
When the belt has adopted to the pulley (after operating about 50 hours), adjust the tension to the load shown
above.
(Even if the adjustments are made on a new belt, check the load again as shown on the above table after the belt
has adopted.)
With or without replacing the pulley, check the deflection load when about 50 hours passed after the test
operation.
After replacing belt or pulley, conduct the test operation and check if there is no abnormal noise or vibration.
Refer to the JIS B 1854 (Pulley) and JIS K 6323 (V belt) for details. (JIS: Japanese Industrial Standards)
1. Take measurements
1) Measure the parallelism of the fan pulley and motor pulley.
2) Measure the tension of the fan belt.
37
2. Make adjustments
1) Secure the pulley parallelism by adjustment of the motor pulley position and adjustment of fixing bolt (A).
2) Adjust the fan belt tension by loosening fixing bolt (A) and using adjustment nut (B), (C).
Adjustment
nut (B)
Adjustment
nut (C)
3. Perform checks
1) Check that the pulley parallelism and the fan belt tension are within the criteria.
Type A
Type B
Nominal
number
Type A
Type B
Nominal
number
Type A
Type B
Nominal
number
Type A
Type B
20
508
49
1245
1245
78
1981
1981
118
2997
2997
21
533
50
1270
1270
79
2007
2007
120
3048
3048
22
559
51
1295
1295
80
2032
2032
122
3099
3099
23
584
52
1321
1321
81
2057
2057
125
3175
3175
24
610
53
1346
1346
82
2083
2083
128
3251
3251
25
635
635
54
1372
1372
83
2108
2108
130
3302
3302
26
660
660
55
1397
1397
84
2134
2134
132
3353
27
686
686
56
1422
1422
85
2159
2159
135
3429
3429
28
711
711
57
1448
1448
86
2184
2184
138
3505
29
737
737
58
1473
1473
87
2210
2210
140
3556
3556
30
762
762
59
1499
1499
88
2235
2235
142
31
787
787
60
1524
1524
89
2261
2261
145
3683
3683
32
813
813
61
1549
1549
90
2286
2286
148
33
838
838
62
1575
1575
91
2311
2311
150
3810
3810
34
864
864
63
1600
1600
92
2337
2337
155
3937
3937
35
889
889
64
1626
1626
93
2362
2362
160
4064
4064
36
914
914
65
1651
1651
94
2388
2388
165
4191
4191
37
940
940
66
1676
1676
95
2413
2413
170
4318
4318
38
965
965
67
1702
1702
96
2438
2438
175
4445
39
991
991
68
1727
1727
97
2464
2464
180
4572
4572
40
1016
1016
69
1753
1753
98
2489
2489
185
4699
41
1041
1041
70
1778
1778
99
2515
2515
190
4826
42
1067
1067
71
1803
1803
100
2540
2540
195
4953
43
1092
1092
72
1829
1829
102
2591
2591
200
5080
210
5334
44
1118
1118
73
1854
1854
105
2667
2667
45
1143
1143
74
1880
1880
108
2743
2743
46
1168
1168
75
1905
1905
110
2794
2794
47
1194
1194
76
1930
1930
112
2845
2845
48
1219
1219
77
1956
1956
115
2921
2921
38
- The combination with an outdoor unit is limited to one indoor unit and one set of outdoor unit (including multiple
connection of outdoor units). The connection of multiple floor standing duct units is prohibited. Connection of floor
standing duct units and other type of indoor units mixed together is prohibited.
When the outdoor-air processing mode is selected, the airflow range is limited. If the airflow exceeds the specified range,
the product may stop abnormally. On the other hand, if the airflow falls below the specified range, the equipment
reliability may decrease. For details, please see the " Airflow range" section.
When the outdoor-air processing mode is selected, the machine controls the operation so that the temperature of the
discharge air becomes closer to the preset temperature of the control panel. However, if the air-conditioning load is too
large or too small, the discharge air temperature may not become closer to the preset temperature.
Airflow range
Please set the airflow according to each operation mode. When selecting a pulley, please see "Fan characteristics (For Pully
Selection)".
Airflow range (m3/min); The value in (
Operation mode
FXVQ125NY1
FXVQ200NY1
FXVQ250NY1
FXVQ400NY1
FXVQ500NY1
FXVQ500NY1(6)
28 - 50 (43)
42 - 76 (69)
63 - 96 (86)
80 - 144 (134)
25 - 29 (27)
38 - 44 (41)
48 - 56 (52)
72 - 85 (78)
99 - 116 (107)
99 - 116 (107)
FXVQ125NY1
FXVQ200NY1
FXVQ250NY1
FXVQ400NY1
FXVQ500NY1(6)
KDFJ905A140
KDFJ905A200
KDFJ905A280
KDFJ905A400
KDFJ905A560
Cooling
Heating
15 - 32C
15 - 32C
CJ: CA13A209
RH
air
te
0%
or
o
utd
90
10
B)
CW
. (
mp
RH
Operation limits
Operation limit
(cooling)
%
30
Operation limit
(heating)
20%
Fan only
operation
39
RH
RH
Field settings
[In case of VRV IV]
Be sure to set from both (a) Field settings from the indoor unit and (b) Field settings from the outdoor unit.
(a) Field settings from the indoor unit
You need to configure the settings by the control panel of the indoor unit to change the operation mode.
Please configure the settings as shown below after completing test run.
Please also see the installation manual of the indoor unit for the setting method.
Operation mode
Mode No.
14
7 Segment display
Details of setting
SEG1
SEG2
SEG3
"Valid"
light off
light off
light off
light off
light off
Mode No.
14
Note :
Airflow rate
14.0
22.4
28.0
45.0
56.0
56.0
kW
16.0
25.0
31.5
50.0
63.0
63.0
m /min
27
41
52
78
107
172
Pa
120
150
120
261
175
469
Indoor temperature: 33CDB, 28CWB / outdoor temperature: 33CDB / Equivalent piping length: 7.5 m, level
difference: 0 m.
2
Indoor temperature: 7CDB / outdoor temperature: 7CDB, 3CWB / Equivalent piping length: 7.5 m, level
difference: 0 m.
3
This product is shipped with the airflow set to the standard mode. When introducing outdoor air (outdoor-air
processing mode), please make sure to adjust the air flow by conducting field settings from the control panel,
changing the pulley, or installing dampers. If not adjusting the airflow, the airflow would still be set to the standard
mode and therefore you might feel cold when heating or feel hot when cooling.
4
The value is the external static pressure with standard pulley.
1
40
Capacity
Capacity
Cooling
Model name
125 Type
200 Type
250 Type
400 500 Type
2.
JC: CA13A209
41
INSTALLATION MANUAL
CONTENTS
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
r
r
r
1. SAFETY PRECAUTIONS
Be sure to follow this SAFETY PRECAUTIONS.
This product comes under the term appliances not
accessible to the general public.
This is a class A product. In a domestic environment this
product may cause radio interference in which case the user
may be required to take adequate measures.
6JKUOCPWCNENCUUKGUVJGRTGECWVKQPUKPVQ9#40+0)5CPF
CAUTIONS.
Be sure to follow all the precautions below: They are all
important for ensuring safety.
WARNING......... Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
CAUTION .......... Indicates a potentially hazardous
situation which, if not avoided, may
result in minor or moderate injury.
It may also be used to alert against
unsafe practices.
r After the installation is completed, test the air conditioner
and check if the air conditioner operates properly. Give
the user adequate instructions concerning the use and
cleaning of the indoor unit according to the Operation
Manual. Ask the user to keep this manual and the
Operation Manual together in a handy place for future
reference.
r
r
r
r
r
r
WARNING
r #UM[QWTNQECNFGCNGTQTSWCNKGFRGTUQPPGNVQECTT[QWV
installation work.
Improper installation may result in water leakage, electric
UJQEMUQTCTG
r Perform installation work in accordance with this installation
manual.
Improper installation may result in water leakage, electric
UJQEMUQTCTG
r Consult your local dealer regarding what to do in case of
refrigerant leakage.
When the air conditioner is installed in a small room, it is
necessary to take proper measures so that the amount of
any leaked refrigerant does not exceed the concentration
limit in the event of a leakage.
Otherwise, this may lead to an accident due to oxygen
FGEKGPE[
r $GUWTGVQWUGQPN[VJGURGEKGFRCTVUCPFCEEGUUQTKGUHQT
installation work.
r
r
VRV System
air conditioner
Installation
manual
(CKNWTGVQWUGVJGURGEKGFRCTVUOC[TGUWNVKPVJGCKT
conditioner falling down, water leakage, electric shocks, a
TGGVE
Install the air conditioner on a foundation that can
withstand its mass.
It may lead to vibration of indoor units and cause
unpleasant chattering noise.
%CTT[QWVVJGURGEKGFKPUVCNNCVKQPYQTMKPEQPUKFGTCVKQPQH
strong winds, typhoons, or earthquakes.
Improper installation may result in an accident such as air
conditioner falling.
Make certain that all electrical work is carried out by
SWCNKGFRGTUQPPGNCEEQTFKPIVQVJGCRRNKECDNGNGIKUNCVKQP
(note 1) and this installation manual, using a separate
circuit.
In addition, even if the wiring is short, make sure to use
CYKTKPIVJCVJCUUWHEKGPVNGPIVJCPFPGXGTEQPPGEV
CFFKVKQPCNYKTKPIVQOCMGVJGNGPIVJUWHEKGPV
+PUWHEKGPVECRCEKV[QHVJGRQYGTUWRRN[EKTEWKVQTKORTQRGT
GNGEVTKECNEQPUVTWEVKQPOC[NGCFVQGNGEVTKEUJQEMUQTCTG
(note 1) applicable legislation means All international,
national and local directives, laws, regulations and/
or codes which are relevant and applicable for a
certain product or domain.
Earth the air conditioner.
Do not connect the earth wiring to gas or water piping,
lightning conductor or telephone earth wiring.
+PEQORNGVGGCTVJKPIOC[ECWUGGNGEVTKEUJQEMUQTCTG
Be sure to install an earth leakage circuit breaker.
(CKNWTGVQFQUQOC[ECWUGGNGEVTKEUJQEMUCPFCTG
Disconnect the power supply before touching the electric
components.
If you touch the live part, you may get an electric shocks.
/CMGUWTGVJCVCNNYKTKPIKUUGEWTGWUKPIVJGURGEKGF
wiring and ensuring that external forces do not act on the
terminal connections or wiring.
+PEQORNGVGEQPPGEVKQPQTZKPIOC[ECWUGCPQXGTJGCVQT
CTG
When wiring between the indoor and outdoor units, and
wiring the power supply, form the wiring orderly so that the
control box lid can be securely fastened.
If the control box lid is not in place, overheat of the
VGTOKPCNUGNGEVTKEUJQEMUQTCTGOC[DGECWUGF
If refrigerant gas leaks during installation work, ventilate
the area immediately.
Toxic gas may be produced if refrigerant gas comes into
EQPVCEVYKVJCTG
After completing the installation work, check to make sure
that there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the
TQQOCPFEQOGUKPVQEQPVCEVYKVJCUQWTEGQHCTGUWEJ
as a fan heater, stove or cooker.
Never directly touch any accidental leaking refrigerant.
This could result in severe wounds caused by frostbite.
CAUTION
English
3P345056-6E
42
INSTALLATION MANUAL
r Install the air conditioner, power supply wiring, remote
controller wiring and transmission wiring at least 1
meter away from televisions or radios to prevent image
interference or noise.
(Depending on the radio waves, a distance of 1 meter may
PQVDGUWHEKGPVVQGNKOKPCVGVJGPQKUG
r Do not install the air conditioner in places such as the
following:
1. Where there is mist of oil, oil spray or vapour for
example a kitchen.
Resin parts may deteriorate, and cause them to fall out
or water to leak.
2. Where corrosive gas, such as sulfurous acid gas, is
produced.
Corrosion of copper pipings or brazed parts may cause
the refrigerant to leak.
3. Where there is machinery which emits electromagnetic
waves.
Electromagnetic waves may disturb the control system,
and cause malfunction of the equipment.
9JGTGCOOCDNGICUGUOC[NGCMYJGTGECTDQPDTG
or ignitable dust is suspended in the air or where volatile
COOCDNGUUWEJCUVJKPPGTQTICUQNKPGCTGJCPFNGF
If the gas should leak and remained around the air
conditioner, it may cause ignition.
PRECAUTION
2-2
ACCESSORIES
Quantity
Connection pipings
1 pc.
For each 1 pc.
(125-250 type) (400 500 type)
Drain
plug cap
1 pc.
(Liquid
piping)
Shape
(Gas piping)
(Gas piping)
Location
14 pcs.
Quantity
(125 200 type)
30 pcs.
(250 type)
Shape
Location
18 pcs.
(400 type)
36 pcs.
(500 type)
M820
Partition plate (However, 2 bolts and 2 nuts are used for
CPIGVGORQTCT[ZKPI
0WVU
HQTCPIGU
14 pcs.
30 pcs.
18 pcs.
36 pcs. [Others]
Quantity
(125 200 type) (250 type) (400 type) (500 type) rOperation
manual
rInstallation
Shape
manual
M8
Name
Location
2-3
2. BEFORE INSTALLATION
2-1
$QNVU
HQTCPIGU
Name
Insulation
for Drain
plug
Clamp
1 pc.
3 pcs.
Items to be checked
In case of defective
Check
column
Water leakage
&QGUVJGFTCKPQYQWV
UOQQVJN[!
Water leakage
+UGCTVJKPIEQORNGVGF!
Partition plate
English
2
3P345056-6E
43
Items to be checked
*CXG[QWECTTKGFQWVGNFUGVVKPI!
KHPGEGUUCT[
#TGVJGEQPVTQNDQZNKFVJGCKTNVGTCPFVJGUWEVKQPITKNNG
CVVCEJGF!
Does the cool air discharge during the cooling
operation and the warm air discharge during heating
QRGTCVKQP!
Have you explained how to operate the air conditioner
UJQYKPIVJGQRGTCVKQPOCPWCNVQVJGEWUVQOGT!
Have you explained the description of cooling and
JGCVKPIIKXGPKPVJGQRGTCVKQPOCPWCNVQVJGEWUVQOGT!
Have you handed the operation manual and the
KPUVCNNCVKQPOCPWCNVQVJGEWUVQOGT!
3. CARRY-IN METHOD
Note
Do not throw away the accessories required for installation
WPVKNVJGKPUVCNNCVKQPKUPKUJGF
r Choose the carry-in route of the indoor unit.
r When lifting the unit with a crane, use belt sling and
RGTHQTONKHVKPIVJGWPKVCUUJQYPKPVJGIWTGDGNQY
Belt sling
4. INSTALLATION SITE
Note
Do not apply force on the resin parts in case of carrying the
indoor unit when and after unpacking.
(1) Select an installation site where the following conditions
CTGUCVKUGFCPFQDVCKPVJGEWUVQOGToUCRRTQXCNDGHQTG
installation.
r The foundation is strong enough to support the weight
QHVJGWPKVCPFVJGQQTKUCVVQRTGXGPVXKDTCVKQPCPF
noise generation.
r The place where the cold (warm) air is spread all over
the room.
(In case of free blow by the plenum chamber)
r The place where the condensate can be properly
drained.
r 6JGRNCEGYJGTGVJGTGKUPQRQUUKDKNKV[QHCOOCDNG
gas leak.
r The place where is not heat affected by other heating
equipment.
r The space around the unit is adequate for servicing
and the minimum space for air inlet and air outlet is
available.
r The place where the piping length between indoor unit
and outdoor unit is within the allowable limit.
(Refer to the installation manual attached to the
outdoor unit.)
(2) After installation, remove the shipping brackets attached
to the bottom frame.
(3) Secure the unit to its base using foundation bolts.
4-1
r 5GNGEVCUWKVCDNGRCVVGTPHTQOVJGIWTGDGNQYCEEQTFKPI
to local space in view of walkway and ventilation when
installing.
+HVJGIKXGPGNFURCEGHCKNUVQOGGVVJGEQPFKVKQPUQHYQTM
KPVJKUIWTGEQPVCEVVJGFGCNGT
Piping connection
Left side
500 mm
100 mm
Right side
100 mm
500 mm
(QWPFCVKQPDQNVUZKPIRNCVG
(4 Portions)
/CMGUWTGVQUNKPIQXGTVJGJCPIGT
100 mm
or more
IJQNG(125-V[RG)
IJQNG(V[RG)
Indoor
unit
A or more
<Front
side>
B or more
900 mm or more
English
3P345056-6E
44
INSTALLATION MANUAL
5. CAUTION AT INSTALLATION
5-1
(Type 125-250)
<125-250 type>
(1) Remove the suction grille.
(2) Remove the protection net. Then remove the cushioning
material on the protection net.
(3) Remove the front panel (upper).
(4) Remove the front panel (lower).
(5) Put the iron plate, which must be wider than the fan
motor, under the fan motor, and on the heat exchanger
HQTRTQVGEVKQPHQTKVUP
+TQPRNCVGOWUVDGUWRRNKGFKPVJG
GNF
(6) Remove the terminal for the fan motor lead wire from the
magnet switch.
(7) Pull out the fan motor lead wire to the fan housing parts,
and let it out of the unit from the opening part on the front
plate (upper).
(8) Remove the nuts of the motor base.
(9) 4GOQXGVJGDGNV*QNFVJGHCPOQVQTDCUGTON[YJGP
working so that it may not move suddenly.
(10) Slide the fan housing assembly on the iron plate on which
the fan motor is put (the above procedure (5)) frontward
slowly. Work must be conducted by more than 3 persons.
One of them must hold the motor base, and two or more
of them must hold the fan housing.
(11) Move the fan housing assembly to the location where can
be worked and replace the pulley.
(12) After replacing, follow the above procedure in the reverse
order.
Parallelism
measurement tool*
Parallelism
measurement tool*
(1) Suction
grille
(8)
(9)
Fan
motor
(7)
Heat
exchanger
(4)
Front panel
(lower)
Ruler
(10)
200 - 350
1.0 or less
350 - 450
1.5 or less
Note
Use a metal ruler, L shape ruler or the like which is
measureable the straight line as a parallelism measurement
tool.
5-2
(6)
PARALLELISM OF PULLEY
Note
Be sure to conduct a trial operation after replacing the belt
and pulley to check the sound and vibration.
r Be sure to adjust the tension of the V belt when replacing
the belt and pulley.
r Be sure to re-adjust the tension of the V belt when roughly
JQWTUCHVGTVJGTUVVTKCNQRGTCVKQPQTCHVGTTGRNCEKPIVJG
DGNVCPFRWNNG[
CHVGTVJGDGNVIGVUVQV
<How to adjust the tension>
(1) %CNEWNCVGCRTQRGTFGGEVKQPNGPIVJ
.D[HQTOWNC=?
(2) /GCUWTGPGEGUUCT[FGGEVKQPNQCFYJGPVJGNGPIVJ
.
of the above (1) is given to the V belt. (See the following
IWTGU
(3) Adjust the inter-shaft distance of the pulley so that the
FGGEVKQPNQCFQHVJGCDQXG
DGEQOGUYKVJKPVJG
following table range.
(4) 4GRGCVVJGCDQXGUVGR
CPF
WPVKNVJGFGGEVKQPNQCF
becomes within the table range.
English
4
3P345056-6E
45
Tension meter
CAUTION
(Type 125-250)
Tension meter
6-1
/GCUWTGVJGFGGEVKQPNQCF
9YJKNGRTGUUKPIFQYPVJG
tension meter vertically to the midpoint of the belt until it
KPFKECVGUYKVJVJGRTQRGTFGGEVKQPNGPIVJ
.
Qty
125 type
I15.9 t1.0 mm
I9.5 t0.8 mm
200 type
I19.1 t1.0 mm
I9.5 t0.8 mm
250 type
I22.2 t1.0 mm
I9.5 t0.8 mm
400 type
I28.6 t1.0 mm
I12.7 t0.8 mm
500 type
I28.6 t1.0 mm
I15.9 t1.0 mm
6-2
Motor output
(kW)
Motor pulley
diameter (mm)
&GGEVKQPNQCF
W (N) per belt
0.75
- 99
9.0 9.9
0.75
104 -
12.0 13.2
1.5
- 115
14.8 16.3
1.5, 2.2
121 -
12.0 13.2
2.2
Any
19.0 20.9
3.7
- 136
30.0 33.0
3.7
143 - 161
25.4 27.9
3.7
171 -
21.1 23.2
3.7, 5.5
Any
19.0 20.9
6. REFRIGERANT PIPING
r For the refrigerant piping of the outdoor unit, refer to the
installation manual attached to the outdoor unit.
r Make sure to use R410A as refrigerant before the
installation work. (Otherwise, the unit cannot operate
normally)
r Make sure to insulate the piping on both the liquid side and
the gas side. Otherwise, water leakage may be caused.
7UGCJGCVKPUWNCVKPIOCVGTKCNUWHEKGPVN[TGUKUVCPVVQ
120 C. Reinforce the refrigerant piping according to the
installation environment. Otherwise, condensation may
form on the surface of the insulation.
#KTNVGTOWUV
DGTGOQXGF
Do not directly
COGVJGRKRG
ZKPIRNCVG
Do not directly
COGVJG
UQNGPQKFXCNXGCPF
OQVQTQRGTCVGFXCNXG
Connection pipings
4GOQXGVJGRKPEJGFRKRKPIU
&QPQVFKTGEVN[COGVJG
FTCKPRCPCPFVJGTOKUVQT
6-3
PIPING CONNECTION
CAUTION
Note
r For nitrogen replacement, refer to the installation work
manual. (Contact the dealer.)
r 9JGPDTC\KPIRKRGUYJKNGQYKPIPKVTQIGPUGVVJGPKVTQIGP
pressure to 0.02 MPa or less using a pressure reducing
valve (to the extent that your cheeks feel breeze).
r &QPQVWUGCWZYJGPDTC\KPIVJGTGHTKIGTCPVU[UVGO7UG
phosphor copper brazing (BCup-2: JIS Z 3264/B-Cu93P-710
/795: ISO 3677YJKEJFQGUPQVTGSWKTGWZ
7UKPICEJQTKPGWZOC[ECWUGVJGRKRGUVQEQTTQFG
CPFKHKVEQPVCKPUWQTKFGKVOC[ECWUGVJGTGHTKIGTCPV
lubricant to deteriorate, adversely affecting the
refrigerant piping system.
Note
+PETGCUGVKOGUQHVJGHQNNQYKPIFGGEVKQPNQCF
9CVVJG
initial tensioning when the belt is renewed.
Belt type
Piping size
Indoor unit
capacity
&GGEVKQPNQCF
9
0
L=0.016C
[1]
.&GGEVKQPNGPIVJ
OO
%+PVGTUJCHVFKUVCPEGQHRWNNG[
OO
CEVWCNOGCUWTGOGPV
MATERIAL OF PIPING
English
3P345056-6E
46
INSTALLATION MANUAL
Note
$TC\GD[UQEMGVKHUNGGXGCTGRTQEGUUECPPQVDGEQPFWEVGF
CAUTION
6JGTOCNKPUWNCVKQPQHVJGGNFRKRKPIOWUVDGECTTKGFQWV
including the piping connection parts. Otherwise, it may
cause heat injury by condensation or connecting to the
exposed piping.
Nitrogen
Nitrogen
Taping
Refrigerant piping
Manual valve
CAUTION
Do not let any refrigerant other than R410A enter the
refrigerant system.
Ventilate if the refrigerant gas leaks during work.
6-4
More than 40 mm
More than 40 mm
Piping
on liquid
side
(125-250
type)
Connection piping
(Accessory)
Gas piping
Liquid piping
Refrigerant piping
(Field supply)
More than 40 mm
Note)
Gas piping
Connection piping
(Accessory)
Piping on
liquid side
(400 500
type)
Cut the
piping
4GHGTVQVJGDGNQYVCDNGHQTCTGRCTVFKOGPUKQPU
(Unit: mm)
Indoor Piping Inside dia. of
size
CTG
unit
capacity
d0
d1 Tolerance
Allowance of
inserting part
L
Tolerance
+1.5
0
Bend
Flare shape
radius
125 type
R18
Id1
C1220T
+0.1
0
Id0
I9.5
200 type t0.8 or 9.64
more
250 type
English
More than 40 mm
7. DRAIN PIPING
side
( Connection
inside the unit )
Piping on
gas side
(125-500
type)
Refrigerant
piping insulation
(Field supply)
Liquid piping
6-5
Refrigerant
piping insulation
(Field supply)
7-1
6
3P345056-6E
47
Check
r #HVGTEQORNGVKQPQHFTCKPRKRKPINGVYCVGTQYKPVQVJG
drain pan and check for drain and water leakage from the
piping connection area.
Downward inclination
1/100 or more
Drain plug
100 mm 50 mm
or more or more
Indoor
unit
Drain trap
make a
drain trap
Drain trap
Drain piping
(for Left side connection)
CAUTION
r The connection of the drain piping
Do not directly connect the drain piping to sewerage, which
odor may smell like ammonia.
Sewerage may contain it, which may pass through the
drain piping, and result in corrosion of the indoor unit heat
exchanger.
8-1
8. ELECTRIC WIRING
CAUTION
Screw
Front panel
(lower)
Remove the screw attached
front panel (lower).
8-2
<125-250 type>
Wiring from right side
Terminal block
for power
supply wiring
Control box
English
3P345056-6E
48
INSTALLATION MANUAL
<400 500 type>
Wiring from right side
Outdoor unit
Power
supply
Control box
IN-OUT
F1
Earth terminal
Earth terminal
Terminal block for
for shield wire power supply wiring
L1 L2 L3 N
Control box
Never to connect
high-voltage electricity
such as power supply cables.
Prohibited
P1 P2
or or F F
P N 1 2
T T
1 2
Indoor unit A
L1 L2 L3 N
P1 P2
or or F F
P N 1 2
T T
1 2
L1 L2 L3 N
Indoor unit B
Earth
Earth
P1 P2
or or F F
P N 1 2
T T
1 2
Earth
Note
1. It is not necessary to set the indoor unit address for group
control.
(The setting is made automatically when the power supply
is turned on.)
2. Make sure to disconnect the control panel wiring of the
units over the second one.
3. In this case, all indoor units within the group are controlled
by the control panel for the group control.
Earth terminal
EXAMPLE OF WIRING
F2
Branch switch
Overcurrent
circuit breaker
8-3
F1
Control panel
OUT-OUT
F2
Control box
IN-OUT OUT-OUT
F1 F2 F1 F2
Never to
connect
high-voltage
electricity
such as power
supply cables.
Outdoor unit
Power
supply
Branch switch
Overcurrent
circuit breaker
F1
OUT-OUT
F2
F1
F2
Branch switch
Overcurrent
circuit breaker
Never to connect
high-voltage electricity such
Prohibited as power supply cables.
BS unit
Control box
*Control panel
Control panel
L1 L2L3 N
Control box
IN-OUT
Outdoor
Indoor
F1
F1
L1 L2 L3 N
P1 P2
or or F F
P N 1 2
T T
1 2
Indoor unit A
Prohibited
Earth
Earth
8-4
Outdoor unit
Control box
F1
Control panel
Branch switch
Overcurrent
circuit breaker
L1 L2 L3 N
Power
supply
F2
Prohibited
Never to connect
high-voltage
electricity such as
power supply cables.
P1 P2
or or F F T T
P N 1 2 1 2
Branch switch
Overcurrent
circuit breaker
Branch switch
Overcurrent
circuit breaker
L1 L2 L3 N
Indoor unit A
Earth
Power
supply
P1 P2
or or F F
P N 1 2
Control panel
OUT-OUT
F2
Control panel
IN-OUT
F1
F2
P1 P2
or or F1F2 T1T2
P N
Indoor unit A
Power
supply
F2
T T
1 2
L1 L2 L3 N
Indoor unit B
Earth
P1 P2
or or F F
P N 1 2
T T
1 2
CAUTION
Do not have low-voltage wires (wiring between units) and other
high-voltage run through the same locations, and there must
be min. 50 mm distance between wires outside of the unit.
Or it may cause a malfunction or a breakdown of the unit by
receiving electrical noise (external noise).
Never to connect
high-voltage electricity
such as power supply cables.
Note
Use ring type crimp style terminals for connections to the
power terminal block.
Install the insulating sleeve for insulation of crimp part.
When none are available, follow the instructions below.
r If stranded wires are used, do not solder the front end of
the wires.
r Do not connect wiring of different size to the power
terminal block. (Slack in the power wiring may cause
abnormal heat.)
r When transmission wiring which is the same thickness, do
CUUJQYPKPVJGIWTGDGNQY
r For wiring, use the designated power wire and connect
TON[VJGPUGEWTGVQRTGXGPVQWVUKFGRTGUUWTGDGKPI
exerted on the terminal board.
Insulating sleeve
Power wire
English
8
3P345056-6E
49
Connect same
size wiring to
both sides.
It is forbidden
to connect two
to one side.
0.79-0.97
1.33-1.61
Earth Terminal
3.02-4.08
8-5
Note
1. Shows only in case of protected piping. Use H07RN-F in
case of no protection.
2. Use the shield wire. Or it may cause a malfunction or
breakdown of the unit by receiving electrical noise (external
noise)
It is forbidden to
connect wiring of
different size.
FIELD SETTING
Indoor units
Model
Hz
Volts
FXVQ125NY1
2.5
2.0
16 0.75 2.0
FXVQ200NY1
4.4
3.6
16
3.6
FXVQ400NY1
8.0
FXVQ500NY1
9.9
8.0
25
FXVQ250NY1
1.5
3.5
16
1.5
3.5
25
3.7
7.9
3.7
7.9
FXVQ125NY1
FXVQ200NY1
FXVQ250NY1
FXVQ400NY1
FXVQ500NY1
16A
Wiring
FIRST
CODE NO.
SETTING
1 7
Size
TEST
Transmission wiring
Wiring
Wiring size
Balanced
and length
type shield
H05VV
must comply
wire
(Note 1)
with local
(Note 2)
codes.
Size
mm2
UNIT NO.
MODE NO.
FIELD
SET
MODE
5RGEKECVKQPHQTGNFUWRRNKGFHWUGUCPFYKTKPI
Model
UNIT NO.
SECOND
CODE NO.
Note
1. Setting is carried out in the group mode, however, set the
mode number inside the ( ) for individual setting of the
GCEJKPFQQTWPKVQTEQPTOCVKQPCHVGTUGVVKPI
2. The SECOND CODE NO. is set to in
number when
shipped from the factory.
3. Do not make any settings not given in the table on the
below.
4. Not displayed if the indoor unit is not equipped with that
function.
5. When returning to the normal mode, 88 may be displayed
in the LCD in order for the remote.
English
3P345056-6E
50
INSTALLATION MANUAL
<Filter sign setting>
r Settings must be made when changing display interval of
NVGTUKIPCEEQTFKPIVQGPXKTQPOGPVCPFNVGTV[RG
SECOND CODE NO.
(Note.2)
Description of setting
01
02
Approx.
2500
Hrs.
Approx.
1250
Hrs.
Remote thermo-controller
(Setup is made when using a
remote thermo-controller.)
Use
5GVVKPIHQTYJGPVJGNVGTUKIP
is not to be used)
Display
10
(20)
Light
Filter Contamination-Heavy/
Light
(Setting for spacing time of
Long
FKURNC[VKOGVQENGCPCKTNVGT
life
5GVVKPIHQTYJGPNVGT
type
contamination is heavy, and
spacing time of display time to
ENGCPCKTNVGTKUVQDGJCNXGF
Heavy
Mode FIRST
NO. CODE
(Note.1) NO.
FIRST CODE
NO.
12(22)
9-2
Do not
display
01
02
None
Provided
Wire gauge
0.75-1.25 mm2
Wire length
MAX 100 m
Outside contact
URGEKECVKQPU
T1
F2
Nonuse
(QTGNFUGVVKPITGHGTVQVJGRTQEGFWTGUJQYPQP
previous page.)
r #HVGTGPVGTKPIVJGGNFUGVOQFGUGNGEVOQFG0QUGV
VJGTUVEQFG0QCPFUGVVJGUGEQPFEQFG0QVQpq
for forced OFF, or to 02 for ON/OFF control.
(Factory setting is set to forced OFF)
T2
FORCED
OFF
Input A
2. Operation procedures
r Operation is as given in the table below for input A of
forced OFF, and ON/OFF control.
For forced OFF
English
10
3P345056-6E
51
(Table 1)
Control panel
(remote
controller)
display
Content
Under
rTerminal for forced OFF
centralized
(T1T2) may be short
control
circuiting.
CUJKPI
Solution
U4
CUJKPI
UH
CUJKPI
NOT
display
E4
CUJKPI
rSelect the
standard mode,
then test run again
from outdoor unit.
A6
CUJKPI
r#KTQYTCVGKUJKIJGTVJCP
expected (overcurrent).
WARNING
'XGPVJQWIJVJGVGUVTWPKUPKUJGFKHVJGKPVGTKQTPKUJYQTM
is not completed, instruct the user not to operate until the
work is completed for protecting the indoor unit.
2CKPVQTCFJGUKXGWUGFHQTKPVGTKQTPKUJYQTMOC[UVCKPVJG
indoor unit, which may result in water splash or leak.
11
English
3P345056-6E
52
Warning
Thailand 16/01/001 AK
Specifications, designs and other content appearing in this brochure are current as of January 2016 but subject to change without notice.