1000A 3-Phase Power & Harmonics Analyzer

For Power Measurements and Analysis plus Datalogging


Of single and 3-phase/3-wire or 3-phase/4-wire systems plus datalogs to 52,428 single phase readings or 17,476 3-phase readings

Features:
• Large backlighting LCD displays up to 35 parameters Meter Displays
in one screen
• Clamp-on True RMS power measurements with
on-screen Harmonics display
• Simultaneous display of Harmonics and Waveform Harmonics Analysis Power Analysis
• Display of Waveform with Peak Values
(1024 samples/period)
• Analysis of Total Harmonic Distortion (THD-F)
• Maximum Demand (MDkW, MW, kVA, MVA) with Phase Analysis Internal Menu
programmable period
• Adjustable CT ratio (1 to 600) and VT ratio (1 to 3000) Software PC Displays
• Graphic Phase diagram with 3-Phase system parameters
• 3-phase Voltage or Current Unbalanced Ratio (VUR, VIR)
and Unbalanced Factor (d0%, d2%)
• Calculated Unbalanced Current through Neutral Line (In)
• Capture 28 Transient events (including Dip, Swell and Software Harmonics Software Harmonics
Phase Analysis Analysis
Outage) with programmable threshold (%)
• Optically isolated RS-232 interface with software to
download Waveforms, Power Parameters and Harmonics
• Complete with 4 voltage leads with alligator clips, 8 AA
batteries, AC adaptor, software, PC interface cable, and case

Specifications Range Basic Accuracy


ACV (True rms) 600V ±(0.5%rdg+5d) Optional Clamp Probes
ACA 1000A ±(0.5%rdg+5d)
Active Power (kW) 9.999MW ±(1%rdg+8d) Choose the best clamp probes to fit your application needs
Apparent Power (kVA) 9999kVA VA=Vrms x Arms ranging from 100A to 3000A and flexible vs traditional jaw type.
Reactive Power (kVAR) 9999kVAR VAR= sqr (VA2-W2)
Power Factor 0.0 to +1.00 ±(1.5%°rdg±8d)
Frequency 45-65Hz 0.1Hz
Phase -180.0°~ 0°~ +180.0° ±1°
Harmonics 1 to 99 ±2%
Crest Factor 1.00 to 99.99 ±(5%+30d)
Peak AC Voltage accuracy ±(5%rdg+30d)
Peak AC Current accuracy ±(5%rdg+30d)
Active Power Energy (kWh) 0mWh to 999,999kWh
Reactive Power Energy (kVARh) 0.0kVARh to 1000MWh
Datalogging 52428 records (single phase)/17476 records (3 phase)
Dimensions/Weight 10.1 x 6.1 x 2.3" (257 x 155 x 57mm)/ 2.5 lbs (1160g) Model 382098 Model 382097
3000A (24”/609mm) 100A Current Clamp
Flexible Current Clamp Probes with 1.2" (30mm)
Probes for wrapping jaw size
Ordering Information: around busbars
382095 ........1000A 3-Phase Power Harmonics Analyzer (120V)
382096 ........1000A 3-Phase Power Harmonics Analyzer (220V)
Accessories
382000 ........Voltage Test Leads with Alligator and Plunger Clips (4 leads)
382097 ........100A Current Clamp Probes (Set of 3)
382098 ........3000A, Flexible Current Probes (Set of 3)
USB100 ........RS-232 to USB Adaptor

www.extech.com Specifications subject to change without notice. 11/10/10 - R1


Copyright © 2007-2008 Extech Instruments Corporation. All rights reserved including the right of reproduction in whole or in part in any form.