0% found this document useful (0 votes)
514 views12 pages

Voltage Regulator Leroy Somer r250 Avr

Uploaded by

Phanendra Cotton
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
514 views12 pages

Voltage Regulator Leroy Somer r250 Avr

Uploaded by

Phanendra Cotton
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

4067 en - 11.

2006 / a

75 mm
110 0V E+ E-

R 250
140 mm

STAB VOLT

give o be l is t ser ua m a n e e nd u This th

n to

F1 P1 P2 ST4

Slow fuse 250V 8 A

FREQ. & L.A.M. CONFIG.

Voltage

47.5Hz
LAM OFF

KNEE

50Hz
9
78

LAM OFF 13%

SPECIAL

8 7 6

901

1 2 3 4

25% OFF 13% 25% LAM

Stability

65Hz
LAM OFF
KNEE

57Hz
LAM OFF

Option

External potentiometrer for voltage adjusting

R250
A.V.R.
Installation and maintenance

456

KNEE

60Hz

Freq / 60 and

23

LEROY-SOMER

Installation and maintenance

4067 en - 11.2006 / a

R250
A.V.R.
This manual concerns the alternator A.V.R. which you have just purchased. We wish to draw your attention to the contents of this maintenance manual. By following certain important points during installation, use and servicing of your A.V.R., you can look forward to many years of trouble-free operation.

SAFETY MEASURES Before using your machine for the first time, it is important to read the whole of this installation and maintenance manual. All necessary operations and interventions on this machine must be performed by a qualified technician. Our technical support service will be pleased to provide any additional information you may require. The various operations described in this manual are accompanied by recommendations or symbols to alert the user to potential risks of accidents. It is vital that you understand and take notice of the following warning symbols. Warning symbol for general danger to personnel.

WARNING
Warning symbol for an operation capable of damaging or destroying the machine or surrounding equipment.

Warning symbol for electrical danger to personnel.

Note : LEROY-SOMER reserves the right to modify the characteristics of its products at any time in order to incorporate the latest technological developments. The information contained in this document may therefore be changed without notice.

LEROY-SOMER

Installation and maintenance

4067 en - 11.2006 / a

R250
A.V.R.
SUMMARY 1 - SUPPLY .............................................................................................................................4 1.1 - SHUNT excitation system............................................................................................4 2 - R250 A.V.R. .......................................................................................................................5 2.1 - Characteristics .............................................................................................................5 2.2 - U/F fonction and LAM ..................................................................................................5 2.3 - R250 A.V.R. option ......................................................................................................5 2.4 - LAM Characteristics ....................................................................................................6 2.5 - Typical effects of the LAM ...........................................................................................7 3 - INSTALLATION - COMMISIONING ..................................................................................8 3.1 - Electrical checks on the AVR.......................................................................................8 3.2 - Settings........................................................................................................................8 3.3 - Electrical faults.............................................................................................................9 4 - SPARE PARTS ................................................................................................................10 4.1 - Designation................................................................................................................10 4.2 - Technical support service. .........................................................................................10

Any maintenance or breakdown operations on the A.V.R. are to be done by personnel trained on commisioning, servicing and maintenance for the electrical and mechanical elements.

Copyright 2005: MOTEURS LEROY-SOMER This document is the property of: MOTEURS LEROY SOMER. It may not be reproduced in any form without prior authorization All brands and models have been registered and patents applied for. 3

LEROY-SOMER

Installation and maintenance

4067 en - 11.2006 / a

R250
A.V.R.
1 - SUPPLY 1.1 - SHUNT excitation system
The SHUNT excitation alternator is autoexcited with a R 250 voltage regulator. The regulator controls the excitation current according to the alternators output voltage. With a very simple conception, the SHUNT excitation alternator does not have a short circuit capacity.

SHUNT SYSTEM

MAIN FIELD

STATOR : 12 wires (marking T1 to T12)

T1
Varistor

T7

T2

T8

T3

T9

5+

Induced
6-

Field

T4

T10

T5

T11

T6

T12

75 mm
110 0V E+ E-

R 250
140 mm

4 x holes 5.8 x 50 x 115 mm

F1 P1 P2 ST4

Slow fuse 250V 8 A

FREQ. & L.A.M. CONFIG.

STAB VOLT

Voltage

47.5Hz
LAM OFF

KNEE

50Hz
9

LAM OFF 13%

SPECIAL

Stability

65Hz
LAM OFF
KNEE

7 6

57Hz
LAM OFF

Option

External potentiometrer for voltage adjusting

456
5

KNEE

78

901

1 2 3 4

25% OFF 13% 25% LAM

60Hz

Frequency selector 50 Hz / 60 Hz for U/F fonction and LAM adjustement

23

LEROY-SOMER

Installation and maintenance

4067 en - 11.2006 / a

R250
A.V.R.
2 - R250 A.V.R. 2.1 - Characteristics
- Voltage regulation: around 0,5 %. - Supply range/voltage detection 85 to 139 V (50/60Hz). - Rapid response time (500 ms) for a transient voltage variation amplitude of 20 %. - Voltage setting P1. - Stability setting P2. - Supply protected with an 8 A fuse, slow action (supports 10 A for 10 s). Operating at 50 Hz: (U/F gradient) 0: threshold at 48 Hz without LAM for impacts between 30 and 40% of the rated load. 1: threshold at 48 Hz with LAM 13% for impacts between 40 and 70% of the rated load. 2: threshold at 48 Hz with LAM 25% for impacts > 70% of the rated load. Operating at 60 Hz: (U/F gradient) 3: threshold at 58 Hz without LAM for impacts between 30 and 40% of the rated load. 4: threshold at 58Hz with LAM 13% for impacts 40 and 70% of the rated load. 5: threshold at 58Hz with LAM 25% for impacts > 70% of the rated load. Specific operating 6: threshold at 57Hz without LAM for speed variations at a steady state > 2 Hz 7: threshold at 65Hz without LAM for variable speed and tractelec / gearlec (U/F gradient). 8: special: the factory setting 48Hz 2U/F gradient ; a special programme is possible on request. This programme must be specified before ordering, during the project study. 9: threshold at 47.5 Hz without LAM for speed variations at a steady state > 2 Hz

2.2 - U/F Fonction and LAM


The threshold position (50 Hz - 60 Hz) to action the U/F fonction as well as the LAM setting type is selected using the potentionmeter.
KNEE

47.5Hz
LAM OFF

50Hz
9
78

LAM OFF 13%

SPECIAL

8 7 6

901

1 2 3 4

25% OFF 13% 25% LAM

23

65Hz
LAM OFF
KNEE

57Hz
LAM OFF

WARNING: The jumper settings must correspond to the rated operating frequency (see the nameplate on the alternator). Risk of destruction for the alternator. The threshhold position and LAM fonction settings are done with the jumper.

456

KNEE

60Hz

2.3 - R250 A.V.R. option


Potentiometer for voltage setting, 1000 / 0,5 W min: setting range 5 %. - Remove the ST4 jumper.

LEROY-SOMER

Installation and maintenance

4067 en - 11.2006 / a

R250
A.V.R.
2.4 - LAM characteristics (Load Acceptance Module)
2.4.1 - Voltage drop The LAM system is integrated in the A.V.R. It is active as standard. It can be adjusted to 13% or 25%. - Role of the LAM (Load Adjustment Module): On application of a load, the rotation speed of the generator set decreases. When it passes below the preset frequency threshold, the LAM causes the voltage to drop by approximately 13% or 25% and consequently the amount of active load applied is reduced by approximately 25% to 50%, until the speed reaches its rated value again. Hence the "LAM" can be used either to reduce the speed variation (frequency) and its duration for a given applied load, or to increase the applied load possible for one speed variation (turbo-charged engines). To avoid voltage oscillations, the trip threshold for the "LAM" function should be set approximately 2 Hz below the lowest frequency in steady state. It is advised to use the "LAM" at 25% for load impacts > at 70% of the genset rated power.
Voltage UN U/f 0,85 U N LAM Voltage

2.4.2 - Gradual voltage return function During load impacts, the function helps the genset to return to its rated speed faster thanks to a gradual increase in voltage according to the following principles: - if the speed drops between 46 Hz and 50 Hz, the rated voltage follows a fast gradient as it is restored. - if the speed drops below 46 Hz, since the engine needs more help, the voltage follows a slow gradient as it returns to the reference value.

U Drop N < 46 Hz Drop N > 46 Hz

Time

48 or 58 Hz

0
ST3

50 or 60 Hz

fC

fN

LEROY-SOMER

Installation and maintenance

4067 en - 11.2006 / a

R250
A.V.R.
2.5 - Typical effects of the LAM with a diesel engine or without a LAM (U/ F only)
2.5.1 - Voltage
UN
0,9 with LAM 0 1s 2s
(U/f) without LAM

Transient voltage drop

0,8

Time 3s

2.5.2 - Frequency
Max speed drop

fN
0,9 0,8 0 1s 2s

with LAM

without LAM

Time 3s

2.5.3 - Power
LAM
Load on shaft (kW)

Load variation

Shedding due to "LAM"


Time 3s

1s

2s

LEROY-SOMER

Installation and maintenance

4067 en - 11.2006 / a

R250
A.V.R.
3 - INSTALLATION COMMISSIONING 3.1 - Electrical checks on the AVR
- Check that all connections have been made properly as shown in the attached wiring diagram. - Check that the position of the jumper corresponds to the operating frequency. - Check whether the ST4 jumper or the remote adjustment potentiometer have been connected. 3.2.2 - Special type of use

WARNING
Excitation circuit E+, E- must not be left open when the machine is running: A.V.R. damage will occur. 3.2.2.1 - R250 field weakening (SHUNT)

3.2 - Settings
110 0V E+ E-

The different settings made during the trial are to be done by qualified personnel. Respecting the load speed specified on the nameplate is vital in order to start a settings procedure. After operational testing, replace all access panels or covers. The only possible settings on the machine are to be done with the A.V.R. 3.2.1 - R250 settings (SHUNT system) Initial potentiometer positions - voltage setting potentiometer P1 for the A.V.R.: full left - remote voltage setting potentiometer: in the middle. Operate the alternator at its rated speed: if the voltage does not rise it is necessary to re-magnatise the magnetic circuit. - slowly adjust the voltage potentiometer of the A.V.R. P1 until the output voltage reaches its rated value. - Stability setting with P2.

The exciter is switched off by disconnecting the A.V.R. power supply (1 wire - 0 or 110V). Contact rating: 16A - 250V AC 3.2.2.2 - R250 field forcing
(400V - 10A)

Diode

Battery (B Volt)

The battery must be isolated from the mass.

Exciter field may be at line potential.

110 0V E+ E-

Excitation Inducer

LEROY-SOMER

Installation and maintenance

4067 en - 11.2006 / a

R250
A.V.R.
3.3 - Electrical faults
Fault Action Effect The alternator starts up and its voltage is still correct when the battery is removed. No voltage at Connect a new battery no load on of 4 to 12 volts to start-up terminals E- and E+ respecting the polarity for 2 to 3 seconds The alternator starts up but its voltage does not reach the rated value when the battery is removed. The alternator starts up but its voltage disappears when the battery is removed Check/cause - Lack of residual magnetism

- Check the connection of the voltage reference to the A.V.R. - Faulty diodes - Induced short circuit - Faulty A.V.R. - Exciter field short-circuited - Short-circuit in the main field. Check the resistance Check the A.V.R. connections (A.V.R. may be faulty) - Field windings short-circuited - Rotating diodes burnt out - Main field winding short-circuited - Check the resistance Increase the drive speed (Do not touch the A.V.R. pot (P1) before returning to the correct speed.) - Faulty A.V.R. - 1 faulty diode - Check the speed: possibility of cyclic irregularity - Loose terminals - Faulty A.V.R. - Speed too low on load (or U/F gradient set too high) - Check the speed (or U/F gradient set too high) - Faulty rotating diodes - Short-circuit in the main field. Check the resistance - Faulty induced excitaion

Correct speed Voltage too low Check the drive speed

Speed too low Voltage too high Voltage oscillations Adjust A.V.R. potentiometer Adjust A.V.R. stability potentiometer Adjustment ineffective

Voltage correct at no load and too low when on load (*)

Run at no load and check the voltage between E+ and E- on the A.V.R.

(*) Warning: For single-phase operation, check that the sensing wires coming from the A.V.R. are correctly connected to the operating terminals (see the alternator manual). Voltage disappears during operation Check the A.V.R., the surge suppressor, the rotating diodes and replace any defective components The voltage does not return to the - Exciter winding open circuit rated value. - Faulty induced excitation - Faulty A.V.R. - Main field open circuit or short-circuited

Warning: after setting-up or troubleshooting, replace all access panels or covers.

LEROY-SOMER

Installation and maintenance

4067 en - 11.2006 / a

R250
A.V.R.
4 - SPARE PARTS 4.1 - Designation
Description A.V.R. Type R 250 Code AEM 110 RE 019

4.2 - Technical support service


Our technical support service will be pleased to help you with any information needed. For replacement part orders, it is necessary to indicate the type and the code number of the A.V.R. Please contact your usual correspondant. An extensive network of service centres is available to rapidly supply any necessary parts. In order to ensure the correct operation and safety of our machines, we strongly recommend that original manufacturers spare parts are used. Failure to do so, will discharge the manufacturer from liabilty in the case of damage.

10

LEROY-SOMER

Installation and maintenance

4067 en - 11.2006 / a

R250
A.V.R.

11