Cable Fault Current Calculation

The document contains calculations for determining the fault current capacity of copper tape used as insulation screening for various sized power cables. It describes using a formula to calculate the fault current based on parameters like the copper tape area, initial and final temperature, and provides sample calculations for copper tapes used in 3-core 300sqmm, 185sqmm, and 120sqmm cables showing the tape meets the requirement of carrying 200A for 1 second. A similar calculation is shown for a copper screen in a 1-core 240sqmm cable.

Uploaded by

skc1234
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
3K views

Cable Fault Current Calculation

The document contains calculations for determining the fault current capacity of copper tape used as insulation screening for various sized power cables. It describes using a formula to calculate the fault current based on parameters like the copper tape area, initial and final temperature, and provides sample calculations for copper tapes used in 3-core 300sqmm, 185sqmm, and 120sqmm cables showing the tape meets the requirement of carrying 200A for 1 second. A similar calculation is shown for a copper screen in a 1-core 240sqmm cable.

Uploaded by

skc1234
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

ANNEXURE I

Calculation for Fault current of Insulation screen i.e. Copper tape for Three core cable ( 6.35/11 kV ) 3C X 300 sqmm. Name of Customer : M/S. EIL INDIA LTD, BPCL.. P.O NO : 4145 Dt. 22/11/10.

The Formula used for Calculation of Short Ckt./ Fault Current :I 2 = K2 S2 log e Q1 + B T Q0 + B Where I = Fault current in Amps T = Duration of short circuit (fault current)in seconds K = Constant (226 for copper) S = Area of copper tape = 40 x 0.045= 1.8 sq.mm (Copper tapes of 40X0.045 ) Q1 = Final temperature of copper tape = 200 OC Q0 = Initial temperature of copper tape = 80 OC B = Reciprocal of the temperature co-efficient of resistance of the copper tape per OC at O 0C = 234.5 = Constant I2 = 2262 X 1.8 2 loge 200 + 234.5 1 80+234.5 I2 = 165486.24 X 0.323211868 I2 = 53487.11676 I = 53487.11676 I = 231.27 Amps for 1 seconds for each . Thus the requirement of CU tape to carry 200A for 1 Sec is met

ANNEXURE II

Calculation for Fault current of Insulation screen i.e. Copper tape for Three core cable ( 6.35/11 kV ) 3C X 185 sqmm. Name of Customer : M/S. EIL INDIA LTD, BPCL.. P.O NO : 4145 Dt. 22/11/10.

The Formula used for Calculation of Short Ckt./ Fault Current :I 2 = K2 S2 log e Q1 + B T Q0 + B Where I = Fault current in Amps T = Duration of short circuit (fault current)in seconds K = Constant (226 for copper) S = Area of copper tape = 40 x 0.045= 1.8 sq.mm (Copper tapes of 40X0.045 ) Q1 = Final temperature of copper tape = 200 OC Q0 = Initial temperature of copper tape = 80 OC B = Reciprocal of the temperature co-efficient of resistance of the copper tape per OC at O 0C = 234.5 = Constant I2 = 2262 X 1.8 2 loge 200 + 234.5 1 80+234.5 I2 = 165486.24 X 0.323211868 I2 = 53487.11676 I = 53487.11676 I = 231.27 Amps for 1 seconds for each core i.e 693.81 Amps / 1 Sec for 3 Core Thus the requirement of CU tape to carry 200A for 1 Sec all 3 cores together is met.

ANNEXURE III

Calculation for Fault current of Insulation screen i.e. Copper tape for Three core cable ( 6.35/11 kV ) 3C X 120 sqmm. Name of Customer : M/S. EIL INDIA LTD, BPCL.. P.O NO : 4145 Dt. 22/11/10.

The Formula used for Calculation of Short Ckt./ Fault Current :I 2 = K2 S2 log e Q1 + B T Q0 + B Where I = Fault current in Amps T = Duration of short circuit (fault current)in seconds K = Constant (226 for copper) S = Area of copper tape = 40 x 0.045= 1.8 sq.mm (Copper tapes of 40X0.045 ) Q1 = Final temperature of copper tape = 200 OC Q0 = Initial temperature of copper tape = 80 OC B = Reciprocal of the temperature co-efficient of resistance of the copper tape per OC at O 0C = 234.5 = Constant I2 = 2262 X 1.8 2 loge 200 + 234.5 1 80+234.5 I2 = 165486.24 X 0.323211868 I2 = 53487.11676 I = 53487.11676 I = 231.27 Amps for 1 seconds for each core i.e 693.81 Amps / 1 Sec for 3 Core Thus the requirement of CU tape to carry 200A for 1 Sec all 3 cores together is met.

ANNEXURE IV Calculation for earth fault current for screen for Size 19 / 33 KV 1 core X 240 sq.mm cable.
Name of Customer : M/S. EIL INDIA LTD, BPCL.. P.O NO : 4145 Dt. 22/11/10.

I ) The Formula used for Calculation of Short Ckt. / Fault Current for screen

1 + K S log I = + T e 0
2 2 2
Where I T K S = Fault current in Amps = Duration of short circuit (fault current)in seconds = 0.2 sec = Constant (226 for copper) = Area of copper screen = 109.64 sq.mm 1 = Final temperature of copper = 200 OC 0 = Initial temperature of copper = 80 OC = Reciprocal of the temperature co-efficient of resistance of the copper tape per OC at O 0C = 234.5 = Constant I2 = 2262 X 109.642 loge 200 + 234.5 0.2 80+234.5 I = 31499.67 Amps for 0.2 second and

= 31.5 kA for 0.2 second

Thus the requirement of CU tape to carry 31.5 kA for 0.2 Sec is met.

CALCULATION OF SCREEN AREA TO GET 40 kA FOR 0.5 Sec.

1 + I T S = log + K e 0
2 2
S2
(31499.67)2 x 0.2 = ------------------------------------------------2262 x loge((200+234.5)/(80+234.5))

198445842 =----------------------------------16508.3694

S2 = 12020.923 S = 109.64 sq.mm