SINEAX M561 / M562 / M563 with 1, 2 resp.
3 analog outputs Programmable Multi-Transducer for Industry
for the measurement of electrical variables in heavycurrent power system Application
SINEAX M 561/M 562/M 563 (Fig.1) is a programmable transducer with a RS 232 C interface. M 561 supervises 1 variable (input) which is available on an analog output signal. Input and output are electrically isolated. M 562 resp. M 563 measure 2 resp. 3 variables simultaneously and generate 2 resp. 3 electrically isolated analog output signals. The transducers are also equipped with an RS 232 serial interface to which a PC with the corresponding software can be connected for programming or accessing and executing useful ancillary functions. The usual methods of connection, the types of measured variables, their ratings, the transfer characteristic for each output etc. are the main parameters that can be programmed. The ancillary functions include displaying, recording and evaluation of measurements on a PC, the simulation of the outputs for test purposes and a facility for printing nameplates. The transducer fulls all the essential requirements and regulations concerning electromagnetic compatibility (EMC) and safety (IEC 1010 resp. EN 61 010). It was developed and is manufactured and tested in strict accordance with the quality assurance standard ISO 9001.
Fig. 1. SINEAX M 563 transducer in housing P20/105 clipped onto a top-hat rail.
Features / Benets
Simultaneous measurement of several variables of a heavy-current power system Measured variables Nominal input current Nominal input voltage
Fig. 2. Screen print-out from the conguration software (M563).
1 2 3 4 5 6 7 8
Current, voltage (rms), active/reactive/apparent power cos, sin, power factor RMS value of the current with wire setting range (bimetal measuring function) 1 to 6 A Slave pointer function for the measurement of the RMS value IB Frequency Average value of the currents with sign of the active power (power system only)
57.7 to 400 V (phase-to-neutral) resp. 100 to 693 V (phase-to-phase)
I1 I2 I3 A/D L1 L2 L3 N UH 1 1 2 3 4 = = = = = SCI D/A C RS 232 P D/A B
D/A
For all heavy-current power system variables Universal analog outputs (programmable) Input voltage up to 693 V (phase-to-phase) High accuracy: Class 0.2 (U, I) resp. 0.5 (all other quantities) Windows software with password protection for programming, data analysis, power system status simulation DC-, AC-power pack with wide power supply tolerance / Universal
Camille Bauer
9 5 6 7 8 9 = = = = = Microcontroller Electrical insulation D/A converter Output stage DC, AC power pack
Input transformer (I1, I2, I3) Voltage divider (L1, L2, L3) Multiplexer Latching stage A/D converter
Fig. 3. Block diagram (M563).
Data Sheet Data Sheet M561 / M562 / M563 Le 01.10
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Symbols
Symbols X X0 X1 X2 Y Y0 Y1 Y2 Y2 SW U Ur U 12 U 23 U 31 U1N U2N U3N I I1 I2 I3 Ir IM IMS IB IBT BS BST F Fn P P1 Meaning Measured variable Lower limit of the measured variable Break point of the measured variable Upper limit of the measured variable Q1 Output variable Lower limit of the output variable Break point of the output variable Upper limit of the output variable Programmed upper limit of the output variable Input voltage Rated value of the input voltage Phase-to-phase voltage L1 L2 Phase-to-phase voltage L2 L3 Phase-to-phase voltage L3 L1 Phase-to-neutral voltage L1 N Phase-to-neutral voltage L2 N Phase-to-neutral voltage L3 N Input current AC current L1 AC current L2 AC current L3 Rated value of the input current Average value of the currents (I1 + I2 + I3) / 3 Average value of the currents and sign of the active power (P) RMS value of the current with wire setting range (bimetal measuring function) Response time for IB Slave pointer function for the measurement of the RMS value IB Response time for BS Phase-shift between current and voltage Frequency of the input variable Rated frequency Active power of the system P = P1 + P2 + P3 Active power phase 1 (phase-to-neutral L1 N) LF1 LF2 LF3 c R Rn H Hn CT VT S S1 S2 S3 Sr PF PF1 PF2 PF3 QF QF1 QF2 QF3 LF Q3 Q2 Q P3 Symbols P2 Meaning Active power phase 2 (phase-to-neutral L2 N) Active power phase 3 (phase-to-neutral L3 N) Reactive power of the system Q = Q1 + Q2 + Q3 Reactive power phase 1 (phase-to-neutral L1 N) Reactive power phase 2 (phase-to-neutral L2 N) Reactive power phase 3 (phase-to-neutral L3 N) Apparent power of the system Apparent power phase 1 (phase-to-neutral L1 N) Apparent power phase 2 (phase-to-neutral L2 N) Apparent power phase 3 (phase-to-neutral L3 N) Rated value of the apparent power of the system Active power factor cos = P/S Active power factor phase 1 Active power factor phase 2 Active power factor phase 3 P1/S1 P2/S2 P3/S3
Reactive power factor sin = Q/S Reactive power factor phase 1 Reactive power factor phase 2 Reactive power factor phase 3 Power factor of the system LF = sgnQ (1 PF) Power factor phase 1 sgnQ1 (1 PF1) Power factor phase 2 sgnQ2 (1 PF2) Power factor phase 3 sgnQ3 (1 PF3) Factor for the intrinsic error Output load Rated burden Power supply Rated value of the power supply c.t. ratio v.t. ratio Q1/S1 Q2/S2 Q3/S3
Data Sheet M561 / M562 / M563 Le 01.10
Camille Bauer
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Applicable standards and regulations
IEC 688 or EN 60 688 Electrical measuring transducers for converting AC electrical variables into analog and digital signals Safety regulations for electrical measuring, control and laboratory equipment Protection types by case (code IP) Electromagnetic compatibility for industrial-process measurement and control equipment Electromagnetic compatibility of data processing and telecommunication equipment Limits and measuring principles for radio interference and information equipment Thermal rating of inputs Input variable Number of inputs Duration of overload Interval between two overloads
Current circuit 400 V single-phase AC system 693 V three-phase system 12 A 120 A 120 A 250 A Voltage circuit 480 V/831 V1 600 V/1040 V
1
IEC 1010 or EN 61 010
10 5 1 10 10
continuous 1s 3s 1s continuous 10 s 1s
100 s 5 min. 1 hour 10 s 10 s
iEC 529 or EN 60 529 IEC 1000-4-2/-3/-4/-5/-6
EN 55 011
800 V/1386 V1
1
Maximum 264 V across the power supply when it is obtained from the measured variable with a power supply unit for 85230 V DC/AC and maximum 69 V with a power supply unit for 2460 V DC/AC.
IEC 68-2-1/-2/-3/-6/-27 or EN 60 068-2-1/-2/-3/-6/-27 Ambient tests -1 Cold, -2 Dry heat, -3 Damp heat, -6 Vibration, -27 Shock DIN 40 110 DIN 43 807 UL 94 AC quantities Terminal markings Tests for flammability of plastic materials for parts in devices and appliances
Analog outputs
For the outputs A, B and C:
Technical data
Measuring input
Nominal input voltage: 57.7 to 400 V (phase-to-neutral) resp. 100 to 693 V (phase-to-phase) 1 to 6 A See page 4 under System response, column Condition, and pages 9 and 10 under Description 13 and 14 Sinusoidal 50 or 60 Hz Voltage circuit: U2 / 400 k with external power supply Current circuit: I2 0.01
Output variable Y Full scale Y2 Limits of output signal for input overload and/or R=0 R
Impressed DC current 1 Y2 20 mA
Impressed DC voltage 5 Y2 10 V
1.2 Y2 30 V
40 mA 1.2 Y2 Y2 Y2 2 mA 1 mA 0.02 Y2
Nominal input current: Admissible measuring range end values:
Rated useful range 7.5 V 15 V 0 of output load Y2 Y2 AC component of output signal (peak-to-peak) 0.02 Y2
Waveform: Rated frequency: Consumption [VA]:
The outputs A, B and C may be either short or open-circuited. They are electrically insulated from each other and from all other circuits (oating). All the full-scale output values can be reduced subsequently using the programming software, but a supplementary error results.
3
Camille Bauer
Data Sheet M561 / M562 / M563 Le 01.10
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Reference conditions
Ambient temperature: Pre-conditioning: Input variable: Power supply: Active/reactive factor: Frequency: Waveform: Output load: 15 30 C 30 min. acc. to EN 60 688 Rated useful range H = Hn 1% cos = 1 resp. sin = 1 50 or 60 Hz Sinusoidal, form factor 1.1107 DC current output: Rn = 7.5 V Y2 1% Bent characteristic: X0 X X1 Response time: Duration of the measurement cycle: Approx. 0.6 to 1.6 s at 50 Hz, depending on measured variable and programming 1 2 times the measurement cycle
Factor c (the highest value applies): Linear characteristic: Y0 Y2 c= or c = 1 X0 1X2 1c= Y1 - Y0 X2 or c = 1 X1 - X0 Y2 1-
DC voltage output: Rn = Miscellaneous: Y2 1 mA 1%
X1 < X X2
Y1 Y2 c= or c = 1 X1 1X2
Y X0/Y0 X1/Y1 X2/Y2 X X
EN 60 688
X0/Y0 X2/Y2
System response
Accuracy class: (the reference value is the full-scale value Y2) Condition 0.5 X2/Sr 1.5 0.3 X2/Sr < 0.5 Accuracy class1) 0.5 c 1.0 c
Measured variable X System: Active, reactive and apparent power Phase: Active, reactive and apparent power
Limit of the output range
Fig. 4. Examples of settings with linear characteristic.
Limit of the output range
Fig. 5. Examples of settings with bent characteristic.
0.167 X2/Sr 0.5 0.5 c 0.1 X2/Sr < 0.167 1.0 c 0.5Sr S 1.5 Sr, (X2 - X0) = 2 0.5Sr S 1.5 Sr, 1 (X2 - X0) < 2 0.5 c 1.0 c 2.0 c 1.0 c 2.0 c 4.0 c
(System response inversely congurable)
Inuencing quantities and permissible variations
Acc. to EN 60 688
Safety
Protection class: Enclosure protection: II (protection isolated, EN 61 010-1) IP 40, housing (test wire, EN 60 529) IP 20, terminals (test nger, EN 60 529) 2 III (with 300 V versus earth) II (with > 300 V versus earth) 300 V 2) 600 V 3) 230 V 40 V
Power factor, active power and reactive power
0.5Sr S 1.5 Sr, 0.5 (X2 - X0) < 1 0.1Sr S < 0.5Sr, (X2 - X0) = 2 0.1Sr S < 0.5Sr, 1 (X2 - X0) < 2 0.1Sr S < 0.5Sr, 0.5 (X2 - X0) < 1
Pollution degree: Installation category:
AC voltage
0.1 Ur U 1.2 Ur 0.2 c 0.2 c
AC current/ 0.1 Ir I 1.2 Ir current averages System frequency
1)
Insulation test (versus earth): Inputs: Power supply: Outputs:
2)
0.1 Ur U 1.2 Ur resp. 0.15 + 0.03 c 0.1 Ir I 1.2 Ir
3)
Basic accuracy 1,0 c for applications with phase-shift
Overvoltage category III Overvoltage category II Camille Bauer
Data Sheet M561 / M562 / M563 Le 01.10
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Surge test: Test voltage: 5 kV; 1.2/50 s; 0.5 Ws 50 Hz, 1 min. acc. to EN 61 010-1 3700 V, inputs versus all other circuits as well as outer surface 2200 V, input circuits versus each other 3700 V, power supply versus outputs and outer surface 490 V, outputs versus each other and versus outer surface Orientation: Weight: Any Approx. 0.35 kg
Terminals
Type: Max. wire gauge: Screw terminals with wire guards 4.0 mm2 single wire or 2 2.5 mm2 ne wire
Ambient tests
EN 60 068-2-6: Acceleration: Frequency range: Number of cycles: EN 60 068-2-27: Acceleration: EN 60 068-2-1/-2/-3: Vibration 2g 10 150 10 Hz, rate of frequency sweep: 1 octave/minute 10, in each of the three axes Shock 3 50 g 3 shocks each in 6 directions Cold, dry heat, damp heat
Power supply
DC, AC power pack (DC or 50 60 Hz) Table 1: Rated voltages and tolerances Rated voltage UN 24 60 V DC/AC 85 230 V DC/AC Consumption: Tolerance DC 15 + 33% AC 15% 5 W resp. 7 VA
Programming connector on transducer
The programming connector on the transducer is connected by the programming cable PRKAB 560 to the RS-232 interface on the PC. The electrical insulation between the two is provided by the programming cable.
Ambient conditions
Variations due to ambient temperature: Nominal range of use for temperature: Operating temperature: Storage temperature: Annual mean relative humidity: Altitude: Indoor use statement 0.2% / 10 K 0153045 C (usage group II) 10 to + 55 C 40 to + 85 C 75% 2000 m max.
Installation data
Housing: Housing P20/105 See Section Dimensioned drawings Lexan 940 (polycarbonate), ammability class V-0 acc. to UL 94, self-extinguishing, non-dripping, free of halogen For snapping onto top-hat rail (35 15 mm or 35 7.5 mm) acc. to EN 50 022
Housing material:
Mounting:
Dimensioned drawings
112.5
15 16 17 18 19 20
1 2 3 4
5 6 7 8 9 10 11 12 13 14
114.1
105
Fig. 6. SINEAX M 563 in housing P20/105 clipped onto a top-hat rail (35 15 mm or 3575 mm, acc. to EN 50 022). Camille Bauer Data Sheet M561 / M562 / M563 Le 01.10 5
69.1
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Table 2: SINEAX M 561 (1 analogue output) SINEAX M 562 (2 analogue outputs) SINEAX M 563 (3 analogue outputs) available as standard versions
The versions of the transducer below programmed with the basic conguration are available ex stock. It is only necessary to quote the Order No.: Description / Basic programming 1. Mechanical design: Housing P20/105 for rail mounting Housing P20/105 for rail mounting Housing P20/105 for rail mounting 2. Rated input frequency: 50 Hz 3. Power supply / external connection 24 60 V DC/AC (standard): 85230 V DC/AC 4. Full-scale output signal, output A: 5. Full-scale output signal, output B: 6. Full-scale output signal, output C: 7. Test certicate: 8. Conguration: See Table 3 Ordering Information Y2 = 20 mA Y2 = 20 mA Y2 = 20 mA None supplied Basic conguration Marking 561 - 4 562 - 4 563 - 4 1 1 2 1 1 1 0 0 158 411 158 429 158 437 158 445 146 458 146 440 Order No. M 561 M 562 M 563
Basic conguration
Input data 9. Application: 10. Nominal input voltage: 11. Nominal input current: 12. Primary rating: Output A 13. Meas. variable/meas. range (part 1): 14. Meas. variable/meas. range (part 2): 15. Signal range/system response: 16. Characteristic: 17. Limits: Output B 18. Meas. variable/meas. range (part 1): 19. Meas. variable/meas. range (part 2): 20. Signal range/system response: 21. Characteristic: 22. Limits: Output C 23. Meas. variable/meas. range (part 1): 24. Meas. variable/meas. range (part 2): 25. Signal range/system response: 26. Characteristic: 27. Limits: P3; X0 = 115.47 W; X2 = 115.47 W Not used Y0 = 20 mA; Y2 = 20 mA Linear Standard 2 0 1 1 1 P2; X0 = 115.47 W; X2 = 115.47 W Not used Y0 = 20 mA; Y2 = 20 mA Linear Standard 2 0 1 1 1 P1; X0 = 115.47 W; X2 = 115.47 W Not used Y0 = 20 mA; Y2 = 20 mA Linear Standard 2 0 1 1 1 4-wire, 3-phase system asymmetric load (NPS) Rated value Ur = 100 V Rated value Ir = 2 A Without specication of primary rating H A 9 0
The complete Order Code according to Table 3: Ordering information should be stated for other versions..
6 Data Sheet M561 / M562 / M563 Le 01.10 Camille Bauer
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Table 3: Ordering information
DESCRIPTION 1. Mechanical design Housing P20/105 for rail mounting Housing P20/105 for rail mounting Housing P20/105 for rail mounting 2. Nominal input frequency 50 Hz 60 Hz 3. Power supply / Connection 24 60 V DC/AC, external connection (standard) 85 230 V DC/AC, external connection (standard) 24 60 V AC, internal connection from measuring input 85 230 V AC, internal connection from measuring input Lines 3 and 4: Line 3: Line 4: 4. Not allowed with application E, F and J in feature 9 Not allowed with nominal input voltage > 60 VL-L (lines A and Z in feature 10) Not allowed with nominal input voltage 57.74 V L-N (line 1 in feature 10) 1 2 3 4 1 2 561 - 4 562 - 4 563 - 4 MARKING
Please refer to remark under feature 10 Output signal nal value, output A Output A, Y2 = 20 mA (standard) Output A, Y2 [mA] Output A, Y2 [V] 5. Output signal nal value, output B Output B not used (at M561) Output B, Y2 = 20 mA (standard) Output B, Y2 [mA] Output B, Y2 [V] 6. Output signal nal value, output C Output C not used (at M561 and M562) Output C, Y2 = 20 mA (standard) Output C, Y2 [mA] Output C, Y2 [V] 7. Test records Without test records With test records in German With test records in English 8. Conguration Basic conguration programmed (see table 2) Programmed to order Line 0: No further details are necessary when specifying the basic conguration. Not allowed with internal power supply from measuring input. 0 9 0 D E (1 Y2 < 20 mA) (5 Y2 10 V) 0 1 9 Z (1 Y2 < 20 mA) (5 Y2 10 V) 0 1 9 Z (1 Y2 < 20 mA) (5 Y2 10 V) 1 9 Z
Line 9: The order must include a full specication of the following features 9 to 27 by means of a completely lled in form W 2407e (see appendix) with the conguration information.
Table 3 continued on next page!
Camille Bauer Data Sheet M561 / M562 / M563 Le 01.10 7
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Continuation Table 3: Ordering Information DESCRIPTION 9. Application (system) Single-phase AC 4-wire, 3-phase symmetric load 3-wire, 3-phase symmetric load 3-wire, 3-phase symmetric load, phase-shift UL1-L2 / IL1* 3-wire, 3-phase symmetric load, phase-shift UL3-L1 / IL1* 3-wire, 3-phase symmetric load, phase-shift UL2-L3 / IL1* 3-wire, 3-phase asymmetric load 4-wire, 3-phase asymmetric load 4-wire, 3-phase asymmetric load, open-Y Lines E, F, J: Not possible with power supply from measuring input! 10. Nominal input voltage Rated value Ur = 57.74 V Rated value Ur [VL-N]: Rated value Ur = 100 V Rated value Ur [VL-L]:
1
MARKING A B C D E F G H J
phase-to-neutral (57.74 VL-N < Ur 400 VL-N)1 phase-to-phase (100 VL-L < Ur 693 VL-L)
1
1 9 A Z
Max. 230 V with power supply from measuring input (feature 3, line 4)!
The transducer is only valid for the rated power supply range when the power supply is being taken from the measuring input (symmetrically loaded single-phase and four-wire three-phase supply: L1-N; otherwise L1-L2). Lines 1 and 9: Only for application A and B Lines A and Z: Only for application C to J 11. Nominal input current Rated value Ir = 1 A Rated value Ir = 5 A Rated value Ir [A] 12. Primary rating (voltage and current transformer) Without specication of primary rating VT, U prim = CT, I prim = kV A 0 9 (1 A < Ir 6 A) 1 2 9
Line 9: Specify transformer ratio primary, e.g. 33 kV, 1000 A The secondary ratings must correspond to the rated input voltage and current specied for feature 10, respectively 11.
* Basic accuracy 1.0 c
Table 3 continued on next page!
8 Data Sheet M561 / M562 / M563 Le 01.10 Camille Bauer
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Continuation Table 3: Ordering information Application AF G H/J
DESCRIPTION 13. Output A, measured variable, range Part 1 (power, power factor, frequency) Part 1 not used P P1 P2 P3 Q Q1 Q2 Q3 S S1 S2 S3 PF PF1 PF2 PF3 QF QF1 QF2 QF3 LF LF1 LF2 LF3 F System L1 L2 L3 System L1 L2 L3 System L1 L2 L3 System L1 L2 L3 System L1 L2 L3 System L1 L2 L3 Frequency Initial range X0 X2 X2 0 0 1 45 Hz X0 0.8 X2 X0 0.8 X2 X0 0.8 X2 X0 0.8 X2 X0 (X2 0.5) X0 (X2 1) Hz X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: X0: Final range X2 0.3 0.1 0.3 0.1 0 (X0 + 1) Hz X2/Sr 1.5 X2/Sr 0.5 X2/Sr 1.5 X2/Sr 0.5 X2 1 X2 65 Hz X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2: X2:
Marking
0 1 2 3 4 5 6 7 8 A B C D E F G H J K L M N P Q R S
Meas. variable: P, Q System P, Q L1/L2/L3 S System S L1/L2/L3 PF, QF, LF F
Table 3 continued on next page!
Camille Bauer Data Sheet M561 / M562 / M563 Le 01.10 9
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Continuation Table 3: Ordering information DESCRIPTION 14. Application AF G H/J Marking
15.
Output A, measured variable, range Part 2 (current, voltage) Part 2 not used I System X0: X2: I1 L1 X0: X2: I2 L2 X0: X2: I3 L3 X0: X2: IB System (15 min) X0: X2: IB1 L1 (15 min) X0: X2: IB2 L2 (15 min) X0: X2: IB3 L3 (15 min) X0: X2: BS System (15 min) X0: X2: BS1 L1 (15 min) X0: X2: BS2 L2 (15 min) X0: X2: BS3 L3 (15 min) X0: X2: IM System X0: X2: IMS System X0: X2: U System X0: X2: U1N L1-N X0: X2: U2N L2-N X0: X2: U3N L3-N X0: X2: U12 L1-L2 X0: X2: U23 L2-L3 X0: X2: U31 L3-L1 X0: X2: Meas. variable: Initial range X0 Final range X2 I, I1, I2, I3 0 X0 0.8 X2 0.5 Ir X2 1.2 Ir IB, IBS X0 = 0 0.5 Ir X2 1.2 Ir IM 0 X0 0.8 X2 0.5 Ir X2 1.2 Ir IMS X2 X0 0.8 X2 0.5 Ir X2 1.2 Ir U System 0 X0 0.9 X2 0.8 Ur X2 1.2 Ur U L1-L2 0 X0 0.9 X2 0.8 Ur X2 1.2 Ur U L2-L3 0 X0 0.9 X2 0.8 Ur X2 1.2 Ur U L3-L1 0 X0 0.9 X2 0.8 Ur X2 1.2 Ur U L1-N 0 X0 0.9 X2 0.8 Ur/ 3 X2 1.2 Ur/ 3 U L2-N 0 X0 0.9 X2 0.8 Ur/ 3 X2 1.2 Ur/ 3 U L3-N 0 X0 0.9 X2 0.8 Ur/ 3 X2 1.2 Ur/ 3 Output A, signal range, system response Not used Signal (Y0 Y2SW): Y2 Y2 Signal (Y0 Y2SW): 0 Y2 Signal (Y0 Y2SW): 0.2 Y2 Y2 Signal Y0 Y2SW: Signal inversely (Y2SW Y0): Y2 Y2 Signal inversely (Y2SW Y0): Y2 0 Signal inversely (Y2SW Y0): Y2 0.2 Y2 Signal inversely Y2SW Y0: Lines 9 and Z: Y2 = selected nal value in feature 4. Specify Y0 and Y2SW in mA or V, within the limits 1 Y2SW Y2 (additional error!); Y2SW Y0 0.2 Y2SW
0 1 2 3 4 5 6 7 8 A B C D E F G H J K L M N
0 1 2 3 9 A B C Z
Table 3 continued on next page!
10 Data Sheet M561 / M562 / M563 Le 01.10 Camille Bauer
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Continuation Table 3: Ordering information DESCRIPTION 16. Output A, characteristic Not used Characteristic linear Characteristic kinked Marking 0 1 9
X1:
Y1:
17.
18.
Line 9: Specify kink point, X1 (input) as value of the measured quantity, Y1 (output) in mA or V, within the limits (X0 + 0.015 X2) X1 0.985 X2; Y0 Y1 Y2SW Output A, limitation Not used Limitation Standard (Ymin = Y0 0.2 Y2SW; Ymax = 1.2 Y2SW) Limitation Ymin: Ymax.: (Y0 0.2 Y2SW) Ymin Y0; Y2SW Ymax 1.2 Y2SW In case of SINEAX M561 the coding is completed up to here! Output B, measured variable, range Application Part 1 (power, power factor, frequency) AF G H/J Part 1 not used P Netz X0: X2: P1 L1 etc. see output A, feature 13 X0: X2:
0 1 9
0 1 2 3
19.
Output B, measured variable, range Part 2 (current, voltage) Part 2 not used I System I1 L1 etc. see output A, feature 14
X0: X0:
X2: X2:
0 1 2 3 0 1 2 3 9 A B C Z
20.
21.
Output B, signal range, system response Not used Signal (Y0 Y2SW): Y2 Y2 Signal (Y0 Y2SW): 0 Y2 Signal (Y0 Y2SW): 0.2 Y2 Y2 Signal Y0 Y2SW: Signal inversely (Y2SW Y0): Y2 Y2 Signal inversely (Y2SW Y0): Y2 0 Signal inversely (Y2SW Y0): Y2 0.2 Y2 Signal inversely Y2SW Y0: Lines 9 and Z: Y2 = selected nal value in feature 4. Specify Y0 and Y2SW in mA or V, within the limits 1 Y2SW Y2 (additional error!)); Y2SW Y0 0.2 Y2SW Output B, characteristic Not used Characteristic linear Characteristic kinked X1: Y1: Line 9: Specify kink point, X1 (input) as value of the measured quantity, Y1 (output) in mA or V, within the limits (X0 + 0.015 X2) X1 0.985 X2; Y0 Y1 Y2SW Output B, limitation Not used Limitation Standard (Ymin = Y0 0.2 Y2SW; Ymax = 1.2 Y2SW) Limitation Ymin: Ymax: (Y0 0.2 Y2SW) Ymin Y0; Y2SW Ymax 1.2 Y2SW In case of SINEAX M562 the coding is completed up to here!
0 1 9
22.
0 1 9
Table 3 continued on next page!
Camille Bauer Data Sheet M561 / M562 / M563 Le 01.10 11
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Continuation Table 3: Ordering Information DESCRIPTION 23. Output C, measured variable, range Part 1 (power, power factor, frequency) Part 1 not used P System X0: X0: X2: X2: Application AF G H/J 0 1 2 3 Marking
P1 L1 etc. see output A, feature 13 24. Output C, measured variable, range Part 2 (current, voltage) Part 2 not used I I1 System L1
0 X0: X0: X2: X2: 1 2 3
etc. see output A, feature 14 25. Output C, signal range, system response Not used Signal (Y0 Y2SW): Y2 Y2 Signal (Y0 Y2SW): 0 Y2 Signal (Y0 Y2SW): 0.2 Y2 Y2 Signal Y0 Y2SW: Signal inversely (Y2SW Y0): Y2 Y2 Signal inversely (Y2SW Y0): Y2 0 Signal inversely (Y2SW Y0): Y2 0.2 Y2 Signal inversely Y2SW Y0:
0 1 2 3 9 A B C Z
Lines 9 and Z: Y2 = selected nal value in feature 4. Specify Y0 and Y2SW in mA or V, within the limits 1 Y2SW Y2 (additional error!); Y2SW Y0 0.2 Y2SW 26. Output C, characteristic Not used Characteristic linear Characteristic kinked X1: Y1: 0 1 9
Line 9: Specify kink point, X1 (input) as value of the measured quantity, Y1 (output) in mA or V, within the limits (X0 + 0.015 X2) X1 0.985 X2; Y0 Y1 Y2SW 27. Output C, limitation Not used Limitation Standard (Ymin = Y0 0.2 Y2SW; Ymax = 1.2 Y2SW) Limitation Ymin: Ymax: (Y0 0.2 Y2SW) Ymin Y0; Y2SW Ymax 1.2 Y2SW 0 1 9
12
Data Sheet M561 / M562 / M563 Le 01.10
Camille Bauer
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Electrical connections
Function Measuring input AC current IL1 IL2 IL3 UL1 UL2 UL3 N Connection 1/3 4/6 7/9 2 5 8 11 If power supply is taken from the measured voltage internal connections are as follow: Application (system) Single-phase AC current 4-wire 3-phase symmetric load All other (apart from feature 9, lines E and F) Internal connection Terminal / System 2 / 11 (L1 N) 2 / 11 (L1 N) 2/5 (L1 L2)
AC voltage
M561: Output A M562: Output A + B M563: Output A + B + C Analog A + B + C + ~ Power supply AC ~ DC + RS 232 C interface Outputs
C RS 232
+ + +
15 16 17 18 19 20 13 14 13 14
15 16 17 18 19 20
1 2 3 4
5 6 7 8 9 10 11 12 13 14
IL1 UL1
IL1 IL2 UL2 IL2
IL3 UL3
IL3 N
Measuring inputs, acc. to measuring mode
Measuring inputs System / Application
2 11 1 3 2 11
Terminals
1 3 2 11 1 3
Single-phase AC system
L1 N L1 N
K
u k l U L
v k V K L l
L1 N
11
11
11
v k l L V K
4-wire 3-phase symmetric load I: L-1
l U L
L1 L2 L3 N
L1 L2 L3 N
L1 L2 L3 N
Connect the voltage according to the following table for current measurement in L2 or L3:
Current transformer L2 L3
Terminals 1 1 3 3
2 L2 L3
11 N N
Camille Bauer
Data Sheet M561 / M562 / M563 Le 01.10
13
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Measuring inputs System / Application Terminals
u k l U K L
v k l L
3-wire 3-phase symmetric load I: L1
L1 L2 L3
L1 L2 L3
V K
L1 L2 L3
Connect the voltage according to the following table for current measurement in L2 or L3: Current transformer L2 L3 Terminals 1 1 3 3 2 L2 L3 5 L3 L1 8 L1 L2
v k l L V K
3-wire 3-phase symmetric load Phase-shift U: L1 L2 I: L1
l U L
L1 L2 L3
L1 L2 L3
L1 L2 L3
Connect the voltage according to the following table for current measurement in L2 or L3: Current transformer L2 L3 Terminals 1 1 3 3 2 L2 L3 5 L3 L1
v k l V K L
3-wire 3-phase symmetric load Phase-shift U: L3 L1 I: L1
l U
L1 L2 L3
L1 L2 L3
L1 L2 L3
Connect the voltage according to the following table for current measurement in L2 or L3: Current transformer L2 L3 Terminals 1 1 3 3 8 L1 L2 2 L2 L3
14
Data Sheet M561 / M562 / M563 Le 01.10
Camille Bauer
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Measuring inputs System / Application
5 8 1 3 5 8
Terminals
1 3 5 8 1 3
v k l V K L
3-wire 3-phase symmetric load Phase-shift U: L2 L3 I: L1
l U
L1 L2 L3
L1 L2 L3
L1 L2 L3
Connect the voltage according to the following table for current measurement in L2 or L3: Current transformer L2 L3 Terminals 1 1 3 3 5 L3 L1 8 L1 L2
u k l U K L k l
v k l L k l
L1 L2
L1 L2 L3 2
u x X
V K
L1 L2 L3
3-wire 3-phase asymmetric load
L3 5
u x X U
8
u x X U K
l L k l
L1 L2 L3
11
11
l k l k K L K L l L
L1 L2
L1 L2 L3 N 2
u x X
4-wire 3-phase asymmetric load
L3 N 5
u x X U
8
u x X U
11
k K
l k L K L K L l k l
L1 L2 L3 N
3 single-pole insulated voltage transformers in high-voltage system
Camille Bauer
Data Sheet M561 / M562 / M563 Le 01.10
15
SINEAX M561 / M562 / M563 with 1, 2 resp. 3 analog outputs Programmable Multi-Transducer for Industry
Measuring input System / Application Terminals
1 2 8 11 1 3 4 6 7 9
u u x x k l k l k K L K L l L X X k
9 11
4-wire 3-phase asymmetric load, Open Y connection
L1 L2 L3 N
L1 L2 L3 N
UU K L K L L K L
Low-voltage system
2 single-pole insulated voltage transformers in high-voltage system
Relationship between PF, QF and LF
Output
ind. cap. ind. cap.
Table 4: Accessories and spare parts
Description Programming cable PRKAB 560 Ancillary cable Conguration software M 560 Windows 3.1 or higher on CD in German, English, French, Italian and Dutch (Download free of charge under: http://www.camillebauer.com) In addition, the CD contains all conguration programmes presently available for Camille Bauer products. Order No. 147 779 143 587 146 557
PF
QF
180
90
90
180
LF
outgoing
incoming
outgoing
Fig. 7. Active power PF , reactive power QF ------, power factor LF - - .
Operating Instructions M 561/M 562-4 B d-f-e in three languages: German, French, English Operating Instructions M 563-4 B d-f-e in three languages: German, French, English
156 316 143 579
Standard accessories
1 Operating Instructions for SINEAX M561/M562 resp. M563, in three languages: German, French, English 1 blank type label, for recording programmed settings
Rely on us.
Camille Bauer Ltd Aargauerstrasse 7 CH-5610 Wohlen / Switzerland Phone: +41 56 618 21 11 Fax: +41 56 618 35 35 [email protected] www.camillebauer.com
Subject to change without notice Edition 01.10 Data Sheet M561 / M562 / M563 Le
Appendix: CONFIGURATION FOR SINEAX M561 / M562 / M563
with 1, 2 resp. 3 analogue outputs and RS 232 interface
(see data sheet M561/M562/M563 Le, Table 3: Ordering information)
Customer / Agent: Order No. / Item: No of instruments: Type of instrument (marking): 9. Application System 10. Nominal input voltage, rated value Ur = 11. Nominal input current, rated value Ir = 12. Primary transformer VT = kV CT =
Date: Delivery date:
Specify transformer ratio primary, e.g. 33 kV, 1000 A The secondary ratings must correspond to the rated input voltage and current specied for feature 10, respectively 11. Output A Part 1 (power, power factor, frequency) 13. Measured variable Part 2 (current, voltage) 14. Measured variable 15. Output signal 16. Characteristic linear / bent 17. Limits Output B (not used with type M561) Part 1 (power, power factor, frequency) 18. Measured variable Part 2 (current, voltage) 19. Measured variable 20. Output signal 21. Characteristic linear / bent 22. Limite Output C (not used with type type M561 and M562) Part 1 (power, power factor, frequency) 23. Measured variable Part 2 (current, voltage) 24. Measured variable 25. Output signal 26. Characteristic linear / bent 27. Limits Order example see on next page1! W 2407 e Type: X0 = Y0 = X1 = Standard / Ymin = X2 = Y2 = Y1 = Ymax = Type: X0 = X2 = Type: X0 = Y0 = X1 = Standard / Ymin = X2 = Y2 = Y1 = Ymax = Type: X0 = X2 = Type: X0 = Y0 = X1 = Standard / Ymin = X2 = Y2 = Y1 = Ymax = Type: X0 = X2 =
Order example type SINEAX M563:
Codes for features 1 to 8: ITEM 1. 2. 3. 4. 5. 6. 7. 8. Description Mechanical design Housing P20/105 for rail mounting Nominal input frequency 50 Hz Power supply / Connection 85230 V DC/AC Output signal nal value, output A Output signal nal value, output B Output signal nal value, output C Without test records Conguration, programmed to order Y2 = 20 mA Y2 = 20 mA Y2 = 20 mA MARKING 563 4 1 2 1 1 1 0 9
Codes for features 9 to 27: Features 9 to 27 concern data for conguring the software. ITEM 9. 10. 11. 12. Description Application System 4-wire, 3-phase asymmetric load Nominal input voltage, rated value Ur = 400 V Nominal input current, rated value Ir = 2 A Primary rating VT = 4 kV, CT = 200 A 9 Specify transformer ratio primary, e.g. 4 kV, 200 A The secondary ratings must correspond to the rated input voltage and current specied for feature 10, respectively 11. Output A Part 1 (power, power factor, frequency) 13. 14. 15. 16. 17. Measured value Part 2 (current, voltage) Measured variable, meas. range Signal range, system response Characteristic linear / kinked Limitation Output B Part 1 (power, power factor, frequency) 18. 19. 20. 21. 22. Measured variable Part 2 (current, voltage) Measured variable, meas. range Signal range, system response Characteristic linear / kinked Limitation Output C Part 1 (power, power factor, frequency) 23. 24. 25. 26. 27. Measured variable Part 2 (current, voltage) Measured variable, meas. range Signal range, system response Characteristic linear / kinked Limitation Type: / X0 = / Y0 = 0 X1 = 400 kVA Standard / Ymin = / X2 = / Y2 = 20 mA Y1 = 4 mA Ymax = / 0 2 9 1 Type: S1 X0 = 0 X2 = 600 kVA B Type: IB1 (15 min) X0 = 0 Y0 = 0 X1 = / Standard / Ymin = / X2 = 200 A Y2 = 20 mA Y1 = / Ymax = / 6 2 1 1 Type: / X0 = / X2 = / 0 Type: / X0 = / Y0 = 20 X1 = / Standard / Ymin = / X2 = / Y2 = 20 mA Y1 = / Ymax = / 0 1 1 1 Type: P1 X0 = 500 X2 = 500 kW 2 MARKING H Z 9