22-8301-25 1q PC 01012013

4TCY4 - XL14c - Convertible Packaged Cooling - R-410A Cooling Model Capacity Shipping Number (Btuh) SEER / EER Weight MCA Max Fuse Sound Rating Packaged Cooling Convertible 1 1 / 2 -5 tons table.

Uploaded by

Gerardo Zamorano
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views26 pages

22-8301-25 1q PC 01012013

4TCY4 - XL14c - Convertible Packaged Cooling - R-410A Cooling Model Capacity Shipping Number (Btuh) SEER / EER Weight MCA Max Fuse Sound Rating Packaged Cooling Convertible 1 1 / 2 -5 tons table.

Uploaded by

Gerardo Zamorano
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 26

Packaged Cooling

Convertible 1-5 Tons


Table PC-1-A 4TCY4 - XL14c - Convertible Packaged Cooling - R-410A
Cooling
Model
Capacity
Shipping
Number
(Btuh)
SEER/EER Weight
MCA

4TCY4

Max
Fuse

Sound
Rating

Cabinet
Dimensions (in.)
H x D xW

4TCY4 208-230/1/60
4TCY4024A1000A
23,400 14.00/12.00
444
16.5
25
68
36 x 43 x 51
4TCY4030A1000A
30,000 14.00/12.00
444
19.1
30
71
36 x 43 x 51
4TCY4036B1000A
38,000 14.20/12.00
450
24.6
40
69
36 x 43 x 51
4TCY4042B1000A
42,000 14.25/12.00
607
31.6
50
74
38 x 46 x 61
4TCY4048B1000A
48,000 14.20/12.00
607
35.4
50
72
38 x 46 x 61
4TCY4060A1000A
60,000 14.00/12.00
612
42.3
60
76
42 x 46 x 61
4TCY4 208-230/3/60
4TCY4036A3000A
36,000 14.20/11.60
450
19.8
30
69
36 x 43 x 51
4TCY4048A3000A
48,500 14.20/11.90
607
26.4
40
72
38 x 46 x 61
4TCY4060A3000A
60,000 14.00/12.00
612
30.6
45
76
42 x 46 x 61

Table PC-1-B 4TCX3 - XL13c - Convertible Packaged Cooling - R-410A


Cooling
Model
Capacity
Shipping
Number
(Btuh)
SEER/EER Weight
MCA

4TCX3

Max
Fuse

Sound
Rating

Cabinet
Dimensions (in.)
H x D xW

4TCX3 208-230/1/60
4TCX3018A1000A
18,000 13.00/11.00
444
10.1
15
69
36 x 43 x 51
4TCX3024A1000A
24,000 13.00/11.20
444
13.6
20
70
36 x 43 x 51
4TCX3030A1000A
29,600 13.00/11.00
445
21.7
35
72
36 x 43 x 51
4TCX3036A1000B
36,000 13.00/11.00
450
23.2
35
72
36 x 43 x 51
4TCX3042B1000A
42,000 13.00/11.00
523
27.9
45
72
38 x 46 x 61
4TCX3048A1000B
46,500 13.00/11.00
607
31.1
50
72
38 x 46 x 61
4TCX3060A1000B
60,000 13.00/11.00
610
43.5
60
72
40 x 46 x 61
4TCX3 208-230/3/60
4TCX3036A3000B
36,000 13.00/11.00
450
18.2
30
72
36 x 43 x 51
4TCX3048A3000A
46,500 13.00/11.00
607
23.6
35
72
38 x 46 x 61
4TCX3060A3000B
60,000 13.00/11.00
610
31.7
50
72
40 x 46 x 61
4TCX3 460/3/60
4TCX3036A4000B
36,000 13.00/11.00
450
8.7
15
72
36 x 43 x 51
4TCX3048A4000A
46,500 13.00/11.00
607
11.7
15
72
38 x 46 x 61
4TCX3060A4000B
60,000 13.00/11.00
610
19.5
25
72
40 x 46 x 61

Table PC-1-C 4TCC3 - XB13c - Convertible Packaged Cooling - R-410A


Cooling
Model
Capacity
Shipping
Number
(Btuh)
SEER/EER Weight
MCA

4TCC3

Max
Fuse

Sound
Rating

Cabinet
Dimensions (in.)
H x D xW

Packaged Cooling

4TCC3 208-230/1/60
4TCC3018A1000A
18,000 13.00/11.00
444
10.1
15
74
36 x 42 x 49
4TCC3024A1000A
23,000 13.00/11.00
444
13.6
20
76
36 x 42 x 49
4TCC3030A1000A
28,000 13.00/10.40
445
21.7
35
75
36 x 42 x 49
4TCC3036A1000B
35,000 13.00/11.00
450
23.2
35
76
36 x 42 x 49
4TCC3042B1000A
40,000 13.00/11.00
523
27.9
45
78
38 x 45 x 59
4TCC3048A1000B
46,500 13.00/11.00
607
31.1
50
80
38 x 45 x 59
4TCC3060A1000B
58,000 13.00/11.00
610
43.5
60
79
40 x 45 x 59
4TCC3 208-230/3/60
4TCC3036A3000B
35,000 13.00/11.00
450
18.2
30
76
36 x 42 x 49
4TCC3048A3000B
46,500 13.00/11.00
607
23.6
35
80
38 x 45 x 59
4TCC3060A3000B
58,000 13.00/11.00
610
31.7
50
79
40 x 45 x 59
4TCC3 460/3/60
4TCC3036A4000B
35,000 13.00/11.00
450
8.7
15
76
36 x 42 x 49
4TCC3048A4000A
46,500 13.00/11.00
607
11.7
15
80
38 x 45 x 59
4TCC3060A4000B
58,000 13.00/11.00
610
19.5
25
79
40 x 45 x 59

For dimensional/outline drawings, please refer to Product Data.


For information on Roof Curbs, please refer to the Accessories/Information Tab.
For complete equipment / combination selections,
installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-1

Effective 1/1/13
22-8301-25

Packaged Cooling
Convertible 1-5 Tons
XL14c
XL13c
XB13c
(4TCY4) (4TCX3) (4TCC3)
Table PC-2-A Features 2-5
1-5
1-5



























SEER up to........................................................................................................................................... 14.25


13.20
13.00
Exclusive Climatuff high efficiency compressor with internal overload protection...........................


Factory supplied charge........................................................................................................................ R-410A R-410A R-410A

Composite Vortica indoor blower........................................................................................................


High efficiency ECM indoor blower motor with Comfort-R airflow system.......................................

Direct drive multi-speed indoor blower motors......................................................................................

All aluminum Spine Fin outdoor coil.................................................................................................



Swept-blade outdoor fan for quiet operation.........................................................................................




Architecturally integrated louvers and corner guards...........................................................................


All steel louvers.....................................................................................................................................

Polyslate gray cabinet...........................................................................................................................



Single stage cool...................................................................................................................................



Start kit - factory installed (single phase only)......................................................................................


3
1 & 2
1 & 2
High pressure cutout.............................................................................................................................

Low pressure cutout.............................................................................................................................. 3-Phase Only 3-Phase Only 3-Phase Only


Liquid line drier - factory installed.........................................................................................................

Non-bleed expansion valves on indoor coil...........................................................................................



Pressure taps, including liquid line taps, easily accessed and protected inside
compressor compartment...................................................................................................................

Right side electrical service access for high and low voltage connections...........................................

Rugged steel basepan features deep drawn duct connections............................................................



Steeply sloped composite drainpan......................................................................................................



Ships in horizontal configuration and converts quickly for downflow....................................................



Copper tube, aluminum fin indoor coil..................................................................................................



All models are certified to UL 1995.......................................................................................................



10-year compressor, 10-year outdoor coil & all other functional parts

registered limited warranty (Residential Use)1 ...........................................................................


Extended warranties available ..........................................................................................................

Packaged Cooling

1 Registered Limited Warranty terms are available when you register within 60 days of installation. You can register online at trane.com or by phone at 800-554-6413;
otherwise Trane Base Limited Warranty terms will apply. Base Limited Warranty information on specific products can be found on Comfortsite.com.

For dimensional/outline drawings, please refer to Product Data.


For information on Roof Curbs, please refer to the Accessories/Information Tab.
For complete equipment / combination selections,
installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-2

Effective 1/1/13
22-8301-25

Packaged Cooling
Convertible 1-5 Tons

XL14c XL13c XB13c

(4TCY4) (4TCX3) (4TCC3)
Table PC-3-A Accessories
2-5 1-5 1-5
Model Number

Description

Shipping Weight

BAYACCDOR1A...................Hinged Filter Access Doorq ................................................................................. 2-3 1-3 1-3


BAYACCDOR2A...................Hinged Filter Access Doorq ................................................................................. 3-5 3-5 3-5
BAYADAP050A.....................Adapter Curb (Cabinet A/B)................................................................................... 2-3 1-3 1-3
BAYADAP051A.....................Adapter Curb (Cabinet C)...................................................................................... 2-3 1-3 1-3
BAYADAP052A.....................Adapter Curb (Cabinet A/B)................................................................................... 3-5 3-5 3-5
BAYADAP053A.....................Adapter Curb (Cabinet C)...................................................................................... 3-5 3-5 3-5
BAYADAP054A.....................Adapter Curb (Cabinet D)...................................................................................... 3-5 3-5 3-5
BAYASCT001.......................Anti-Short Cycle Timer4........................................................................................

BAYCCHT101A....................Crankcase Heater (230V)(Reciprocating).............................................................


2
1-2
1-2
BAYCCHT102A....................Crankcase Heater (230V)(Scroll).......................................................................... 2-5 2-5 2-5
BAYCCHT404B....................Crankcase Heater (460V)(Scroll)......................................................................... 3,4,5 3,4,5 3,4,5
BAYCOVR112A....................12" Duct Shourd (Covers Horizontal Ducts)5....................................................... 2-5 1-5 1-5
BAYCOVR118A....................18" Duct Shourd (Covers Horizontal Ducts)5....................................................... 2-5 1-5 1-5
BAYCURB050A....................Flat Roof Full Perimeter Curb (Insulated) ...................................74...................... 2-3 1-3 1-3
BAYCURB051A....................Flat Roof Full Perimeter Curb (Insulated) ...................................74...................... 3-5 3-5 3-5
BAYDMPR101A...................2-Position Motorized Fresh Air Damper16789 ............................................... 2-3 1-3 1-3
BAYDMPR102A...................2-Position Motorized Fresh Air Damper16789 ............................................... 3-5 3-5 3-5
BAYECON101A....................Economizer with Barometric Relief (Downflow)12390 ........50...................... 2-3 1-3 1-3
BAYECON102A....................Economizer with Barometric Relief (Downflow)12390 ........65...................... 3-5 3-5 3-5
BAYECON200A....................Economizer (Horizontal)1236 ................................................85...................... 2-3 1-3 1-3
BAYECON201A....................Economizer (Horizontal)1236.................................................85...................... 3-5 3-5 3-5
BAYECON204A....................Economizer (Horizontal)1236.................................................85...................... 2-5 1-5 1-5
BAYECONCOMB101B.........BAYECON101A, door, and filter kit........................................................................
2-3
1-3
1-3
BAYECONCOMB102B.........BAYECON102A, door, and filter kit........................................................................ 3-5 3-5 3-5
BAYENTH001A....................Enthalpy Control Kit2 ..................................................................2.......................

BAYEXMK001A....................Extreme Conditions Mounting Kit




(Used on BAYCURB & BAYADAP).........................................................................

BAYEXMK002B....................Extreme Conditions Mounting Kit (Used on BAYUTIL)..........................................



BAYEXMK003A....................Extreme Conditions Mounting Kit (Used on Slab Mounts).....................................



BAYFLTR101C.....................1-2" Filter Frame (requires one 20x25 filter which is




not included)1 .............................................................................6....................... 2-3 1-3 1-3
BAYFLTR201C.....................1-2" Filter Frame (requires one 20x20 and one 20x18


filter which are not included)1 .....................................................6....................... 3-5 3-5 3-5
BAYLIFT002B.......................Lifting Lug Kit................................................................................5.......................

BAYLOAM011A....................Evaporator Defrost Control Kit...............................................................................



BAYLOAM105A....................Low Ambient Control Kit................................................................5.......................



BAYOSAH001A....................Manual Fresh Air Damper1 .........................................................6....................... 2-3 1-3 1-3


BAYOSAH002A....................Manual Fresh Air Damper1 .........................................................8....................... 3-5 3-5 3-5
BAYQSTK300A....................Start Kit ................................................................................................................. 1 Phase Only 1 Phase Only 1 Phase Only
BAYSQRD001A....................16" Round Duct Adapter0............................................................5....................... 2-3 1-3 1-3
BAYSQRD002A....................18" Round Duct Adapter0............................................................3....................... 2-5 1-5 1-5
BAYUTIL101B......................Roof Curb Utility Extension Kit............................................................................... 2-3 1-3 1-3
BAYUTIL102B......................Roof Curb Utility Extension Kit............................................................................... 3-5 3-5 3-5
BAYUV101A.........................21" Retrofit UVC Lamp Kit.............................................................5....................... 1-3 1-3 1-3
BAYUV102A.........................33" Retrofit UVC Lamp Kit.............................................................5....................... 3-5 3-5 3-5

For dimensional/outline drawings, please refer to Product Data.


For information on Roof Curbs, please refer to the Accessories/Information Tab.
For complete equipment / combination selections,
installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-3

Effective 1/1/13
22-8301-25

Packaged Cooling

1 Must use filter frame when economizer/fresh air kit is used.


2 Dry bulb control standard with economizer.
EXISTING
NEW UNIT
USE
3 2-Stage cooling control required when using economizer.
CURB
4TC/WC/YC****A
BAYADAP0**A
4 Do not use with electronic thermostats.
BAYCURB030,38A
018-036
50
5 BAYCOVR112,118A will not cover BAYSQRD002A applications.
BAYCURB030,38A
042-060
52
6 Does not contain barometric relief.
7 Max fresh air - 25%.
BAYCURB033A
018-036
51
8 For non-continuous fan gas-heating applications, the damper opens only when the OD
BAYCURB033A
018-060
53
ambient is above 50 F.
BAYCURB034A
042-060
54
9 It is the designer/engineer's responsibility to review product specifications prior to
equipment selection to insure optimal performance and compliance to codes.
0 Temperature of mixed air entering the heat exchanger is monitored and fresh air intake may be reduced under certain conditions.
q BAYACCDOR1A requires BAYFLTR101B & BAYACCDOR2A requires BAYFLTR201B. They are not backward compatible to BAYFLTR101/201A.

Packaged Cooling
Convertible 1-5 Tons
Table PC-4-A Supplementary Heaters Separate power source/power entry required
Model
Number
Description
Used With

BAYHTRV105E
BAYHTRV108E
BAYHTRV110E
BAYHTRV115E
BAYHTRV120E
BAYHTRV125E
BAYHTRV305E
BAYHTRV308E
BAYHTRV310E
BAYHTRV315E
BAYHTRV320E
BAYHTRV325E
BAYHTRV405E
BAYHTRV408E
BAYHTRV410E
BAYHTRV415E
BAYHTRV420E
BAYHTRV425E

3.76/5.0 kW Heater (208/240V 1PH)


6.0/8.0 kW Heater (208/240V 1PH)
7.50/10.0 kW Heater (208/240V 1PH)
11.27/15.00 kW Heater (208/240V 1PH)
15.00/20.0 kW Heater (208/240V 1PH)
18.78/25.0 kW Heater (208/240V 1PH)
3.76/5.0 kW Heater (208/240V 3PH)
6.0/8.0 kW Heater (208/240V 3PH)
7.50/10.0 kW Heater (208/240V 3PH)
11.27/15.00 kW Heater (208/240V 3PH)
15.0/20.0 kW Heater (208/240V 3PH)
18.78/25.0 kW Heater (208/240V 3PH)
5.0 kW Heater (480V 3PH)
8.0 kW Heater (480V 3PH)
10.0 kW Heater (480V 3PH)
15.00 kW Heater (480V 3PH)
20.0 kW Heater (480V 3PH)
25.0 kW Heater (480V 3PH)

Shipping
Weight

4TC*3018-060A1,4024-060A1
4TC*3018-060A1,4024-060A1
4TC*3024-060A1,4024-060A1
4TC*3030-060A1,4036-060A1
4TC*3048-060A1,4048-060A1
4TC*3060A1,4048-060A1
4TC*3018-060A3,4036-060A3
4TC*3018-060A3,4036-060A3
4TC*3024-060A3,4036-060A3
4TC*3030-060A3,4036-060A3
4TC*3048-060A3,4048-060A3
4TC*3060A3,4048-060A3
4TC*3018-060A4
4TC*3018-060A4
4TC*3024-060A4
4TC*3030-060A4
4TC*3048-060A4
4TC*3060A4

9
10
10
14
14
21
9
10
10
14
14
20
9
10
10
14
14
16

Table PC-4-B Single Power Entry Kit/Heater Matrix:


Single Power
Heater
Entry Kit1 Model

Unit
Model

Shipping
Weight

BAYSPEK060F


BAYSPEK061E








BAYSPEK062F


BAYSPEK063F

BAYHTRV105E
BAYHTRV108E
BAYHTRV110E
BAYHTRV305E
BAYHTRV308E
BAYHTRV310E
BAYHTRV315E
BAYHTRV405E
BAYHTRV408E
BAYHTRV410E
BAYHTRV415E
BAYHTRV420E
BAYHTRV105E
BAYHTRV108E
BAYHTRV110E
BAYHTRV115E
BAYHTRV120E

4TC*3018-048A1,4TCY4024-048A1
4TC*3018-048A1,4TCY4024-060A1
4TC*3024-036A1,4TCY4024-036A1
4TC*3036-060A3,4TCY4036-060A3
4TC*3036-060A3,4TCY4036-060A3
4TC*3036-048A3,4TCY4036-048A3
4TC*3036-060A3,4TCY4036-048A3
4TC*3036-060A4
4TC*3036-060A4
4TC*3036-060A4
4TC*3036-060A4
4TC*3048-060A4
4TC*3060A1
4TC*3060A1
4TC*3060A1,4TCY4036-060A1
4TC*3030-060A1,4TCY4036-060A1
4TC*3048-060A1,4TCY4048-060A1

BAYSPEK064E

BAYHTRV320E

4TC*3048-060A3,4TCY4048-060A3

Packaged Cooling

1 All necessary fuses are included in kit; however, not all kits require fuses. Please refer to BAYSPEK Installers Guide.
Note: Replace "*" with "C" or "X" as appropriate.

For dimensional/outline drawings, please refer to Product Data.


For information on Roof Curbs, please refer to the Accessories/Information Tab.
For complete equipment / combination selections,
installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-4

Effective 1/1/13
22-8301-25

Precedent Packaged Cooling


Convertible 3-10 Tons
Standard Features:

Beveled Top
Smoother Design
Small compact cabinet
Recessed access handles

Trane scroll compressors on all 3-10 ton units


Colored and numbered wiring
Phase Monitor, R-410A, 3 Phase Units
Provisions for through the Base Condensate Drain Connections
2" throwaway filters provided on all units
Liquid Line Refrigerant Drier
Operating Charge of R-410A
IAQ Sloped Drain Pans
Single point power for Electric Heat
Low Ambient to 40F on Electromechanical models
Low Ambient to 0F on ReliaTel models
5 - year Limited Compressor Warranty
1 - year Limited Parts Warranty

Added Flexibility

Electromechanical or ReliaTel controls (See page PC-17 for ReliaTel Control


Information)
Standard or high efficiency cooling models available. 17+ available in 3T to 5T. For
reference to 17+ please refer to publications RT-PRC048-EN and RT-SLB020-EN.
Convertible airflow (ships in downflow application)
Fork lift openings on three sides of unit
Direct or belt drive - standard or oversized motors (Direct for 3-5 ton only)
We dont prepackage options
Choose options tailored to suit each job pay only for what is needed
Units ship with options installed and within our standard ship cycle time

Factory Installed Options

Through-the-Base Electrical
Convenience Outlet Powered or unpowered
Unit Disconnect Switch
Smoke Detectors Supply, return, or both
Condenser Coil Coating
Hinged Access Service Panels
Discharge Air Sensor
Fan Fail and Clogged Filter Switches
Condenser Coil Guard Hail Protection Quality
Dehumidification Hot Gas Reheat Coil
Frostat
Novar Controls
TCI (Trane Communications Interface)
LonTalk (Communications Interface)
2" Pleated Media filters
2" MERV 8 filters or 2" MERV 13 filters
Multi-Speed & Single Zone VAV ID Airflow
Demand Control Ventilation
Stainless Steel Drainpan
Condensate Drainpan Overflow Switch

Packaged Cooling

The same Trane Quality and Reliability with added Flexibility!


For complete equipment / combination selections,
installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-5

Effective 1/1/13
22-8301-25

Precedent Packaged Cooling


Convertible 3-5 Tons, R-410A
Table PC-6-A Precedent 17 Plus - R-410A - ReliaTel Controls Only


Unit
Performance
Tons
Ordering No.
SEER/EER

Cooling Cabinet Shipping


Capacity
Dimensions (in.)
Downflow
Downflow
Weight
(Btuh)
H x W x L
Supply
Return
(Ibs.)
MCA**

Max
Fuse**

THC - 208-230/3/60 - Three Phase - No Heat


3
THC037E3R0A0000
17.5
36,500
36 x 44 x 69
18 x 15.5
24 x 14
614
23.3
30
4
THC047E3R0A0000
17.5
50,500
41 x 53 x 88
33 x 17.5
33 x 17.5
787
29.4
40
5
THC067E3R0A0000
17.2
60,000
41 x 53 x 88
33 x 17.5
33 x 17.5
841
32.2
45
THC - 460/3/60 - Three Phase - No Heat
3
THC037E4R0A0000
17.5
36,500
36 x 44 x 69
18 x 15.5
24 x 14
614
11.4
15
4
THC047E4R0A0000
17.5
50,500
41 x 53 x 88
33 x 17.5
33 x 17.5
787
13.7
20
5
THC067E4R0A0000
17.2
60,000
41 x 53 x 88
33 x 17.5
33 x 17.5
841
15.2
20

Table PC-6-B Base Unit 15 SEER High Efficiency R-410A Electromechanical or ReliaTel

Unit
Performance2
Tons
Ordering No.
SEER/EER

Cooling Cabinet Shipping


Capacity
Dimensions (in.)
Downflow
Downflow
Weight
(Btuh)
H x W x L
Supply
Return
(Ibs.)
MCA**

THC 208-230/1/60 Single Phase No Heat


3
THC036E1*0A0000
15.2
38,490
4
THC048E1*0A0000
15.0
48,930
5
THC060E1*0A0000
15.0
62,480
THC 208/3/60 Three Phase No Heat
3
THC036E3*0A0000
15.0
38,490
4
THC048E3*0A0000
15.0
49,930
5
THC060E3*0A0000
15.0
63,490
THC 460/3/60 Three Phase No Heat
3
THC036E4*0A0000
15.0
38,490
4
THC048E4*0A0000
15.0
49,830
5
THC060E4*0A0000
15.0
63,480

Max1
Fuse**

36 x 44 x 69
41 x 53 x 88
41 x 53 x 88

16 x 15.5
33 x 17.5
33 x 17.5

24 x 14 555 26.7 40
32.2 x 17.5 798 35.7 50
32.2 x 17.5 823 43.8 70

36 x 44 x 69
41 x 53 x 88
41 x 53 x 88

16 x 15.5
33 x 17.5
33 x 17.5

24 x 14 555 21.9 30
32.2 x 17.5 637 28.3 40
32.2 x 17.5 869 32.1 45

36 x 44 x 69
41 x 53 x 88
41 x 53 x 88

16 x 15.5
33 x 17.5
33 x 17.5

24 x 14 555 10.2 15
32.2 x 17.5 637 13.8 20
32.2 x 17.5 869 17.0 25

Table PC-6-C Base Unit Standard Efficiency R-410A Electromechanical or ReliaTel




Unit
Performance
Tons
Ordering No.
SEER/EER

Cooling Cabinet Shipping


Capacity
Dimensions (in.)
Downflow
Downflow
Weight
(Btuh)
H x W x L
Supply
Return
(Ibs.)
MCA**

Max
Fuse**

Packaged Cooling

TSC 208-230/1/60 Single Phase No Heat


3
TSC036E1*0A0000
13.0
35,620
36 x 43 x 69
16 x 15.5
24 x 14
555
27.2
40
4
TSC048E1*0A0000
13.0
49,210
36 x 43 x 69
16 x 15.5
24 x 14
586
35.2
50
5
TSC060E1*0A0000
13.0
59,900
36 x 43 x 69
16 x 15.5
24 x 14
636
43.8
70
TSC 208-230/3/60 Three Phase No Heat
3
TSC036E3*0A0000
13.0
37,150
36 x 43 x 69
16 x 15.5
24 x 14
555
23.0
35
4
TSC048E3*0A0000
13.0
49,450
36 x 43 x 69
16 x 15.5
24 x 14
586
25.2
35
5
TSC060E3*0A0000
13.0
62,270
36 x 43 x 69
16 x 15.5
24 x 14
636
29.5
45
TSC 460/3/60 Three Phase No Heat
3
TSC036E4*0A0000
13.0
37,150
36 x 43 x 69
16 x 15.5
24 x 14
555
11.7
15
4
TSC048E4*0A0000
13.0
49,450
36 x 43 x 69
16 x 15.5
24 x 14
586
12.5
15
5
TSC060E4*0A0000
13.0
62,270
36 x 43 x 69
16 x 15.5
24 x 14
636
15.5
25
TSC 575/3/60 Three Phase No Heat
3
TSC036EW*0A0000
13.0
37,150
36 x 43 x 69
16 x 15.5
24 x 14
555
9.4
15
4
TSC048EW*0A0000
13.0
49,450
36 x 43 x 69
16 x 15.5
24 x 14
586
9.0
15
5
TSC060EW*0A0000
13.0
62,270
36 x 43 x 69
16 x 15.5
24 x 14
636
10.1
15
1 HACR breaker per NEC.
2 SEER applies, 3-5 tons; EER applies 6-10 tons.
* Digit 9 - E = Electromechanical or R = ReliaTel.
** Information subject to change. Please confirm with current Product Data/Service Facts for current factory production.

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-6

Effective 1/1/13
22-8301-25

Precedent Packaged Cooling


Convertible 6 - 10 Tons, R-410A
Table PC-7-A Base Unit High Efficiency R-410A Electromechanical or ReliaTel


Unit
Performance
Tons
Ordering No.
EER

Cooling Cabinet
Capacity
Dimensions (in.)
Downflow
Downflow
(Btuh)
H x W x L
Supply
Return

THC 208-230/3/60 Three Phase High Efficiency


6
THC072E3*0A0000
12.6
72,000
7
THC092F3*0A0000
12.6
92,000
8
THC102E3*0A0000
13.0
103,000
10
THC120E3*0A0000
12.5
119,000
THC 460/3/60 Three Phase
6
THC072E4*0A0000
12.6
72,000
7
THC092F4*0A0000
12.6
92,000
8
THC102E4*0A0000
13.0
103,000
10
THC120E4*0A0000
12.5
119,000

Shipping
Weight
Max1
(Ibs.)
MCA** Fuse**

47 x 53 x 88
47 x 53 x 88
51 x 63 x 100
51 x 63 x 100

33 x 17.5
33 x 17.5
32.25 x 19.25
32.25 x 19.25

32.13 x 17.5
997
32.13 x 17.5 1026
32.25 x 16.75 1553
32.25 x 16.75 1563

33.9
41.9
44.7
50.3

50
50
60
60

47 x 53 x 88
47 x 53 x 88
51 x 63 x 100
51 x 63 x 100

33 x 17.5
33 x 17.5
32.25 x 19.25
32.25 x 19.25

32.13 x 17.5
997
32.13 x 17.5 1026
32.25 x 16.75 1553
32.25 x 16.75 1563

16.3
19.9
22.9
24.9

25
25
30
30

Table PC-7-B Base Unit Standard Efficiency R-410A Electromechanical or ReliaTel




Unit
Performance
Tons
Ordering No.
SEER/EER

Cooling Cabinet Shipping


Capacity
Dimensions (in.)
Downflow
Downflow
Weight
(Btuh)
H x W x L
Supply
Return
(Ibs.)
MCA**

Max
Fuse**

TSC 208-230/3/60 Three Phase No Heat


6
TSC072E3*0A0000
11.2
75,000
42 x 53 x 88
33 x 17.5
32.13 x 17.5 898
36.5
50
71/2
TSC090E3*0A0000
11.2
89,000
42 x 53 x 88
33 x 17.5
32.13 x 17.5 815
38.2
60
71/2
TSC092E3*0A0000
11.2
94,000
46 x 53 x 88
33 x 17.5
32.13 x 17.5 1009
41.2
50
81/2
TSC102E3*0A0000
11.2
102,000 46 x 53 x 88
33 x 17.5
32.13 x 17.5 1048
46.3
60
10
TSC120F3*0A0000
11.3
119,000 46 x 53 x 88
33 x 17.5
32.13 x 17.5 1058
49.6
60
TSC 460/3/60 Three Phase No Heat
6
TSC072E4*0A0000
11.2
75,000
42 x 53 x 88
33 x 17.5
32.13 x 17.5 898
18.2
25
71/2
TSC090E4*0A0000
11.2
89,000
42 x 53 x 88
33 x 17.5
32.13 x 17.5 815
19.5
30
71/2
TSC092E4*0A0000
11.2
94,000
46 x 53 x 88
33 x 17.5
32.13 x 17.5 1009
21.5
25
81/2
TSC102E4*0A0000
11.2
102,000 46 x 53 x 88
33 x 17.5
32.13 x 17.5 1048
21.9
25
10
TSC120F4*0A0000
11.3
119,000 46 x 53 x 88
33 x 17.5
32.13 x 17.5 1058
22.7
35
TSC 575/3/60 Three Phase No Heat
6
TSC072EW*0A0000
11.2
75,000
42 x 53 x 88
33 x 17.5
32.13 x 17.5 898
12.7
20
71/2
TSC090EW*0A0000
11.2
89,000
42 x 53 x 88
33 x 17.5
32.13 x 17.5 815
14.7
20
71/2
TSC092EW*0A0000
11.2
94,000
46 x 53 x 88
33 x 17.5
32.13 x 17.5 1009
15.0
20
81/2
TSC102EW*0A0000
11.2
102,000 46 x 53 x 88
33 x 17.5
32.13 x 17.5 1048
17.5
20
10
TSC120FW*0A0000
11.3
119,000 46 x 53 x 88
33 x 17.5
32.13 x 17.5 1058
18.9
25
1 HACR breaker per NEC.
* Digit 9-E=Electromechanical or R=ReliaTel.
** Information subject to change. Please confirm with current Product Data/Service Facts for current factory production.

Packaged Cooling

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-7

Effective 1/1/13
22-8301-25

Precedent Packaged Cooling


Convertible 3-10 Tons
(Model Digit Numbers)
Digit

Description

Digit

Order Number

Packaged Cooling

1 Enthalpy control not available factory installed with electro-mechanical controls.


2 Economizer with Barometric Relief is for downfllow configured units only. Order
Economizer without Barometric Relief for horizontal configuration. Barometric
relief for horizontal configured units must be ordered as field installed accessory
BAYBARM010A.
3 Requires use of Disconnect or Circuit Breaker.
4 Frostat cannot be field installed in electro-mechanical units.
5 Not available with BAYFRST001A High Temperature Stat accessory.
6 The return air smoke detector may not fit up or work properly on the Convertible units
when used in conjunction with 3rd party accessories such as bolt on heat wheels,
economizers and power exhaust. Do not order the return air smoke detectors when
using this type of accessory.
7 Return Air Smoke Detector cannot be ordered with Novar Controls.
8 These options are standard when ordering Novar Controls.
9 This options for use when ordering Novar Control only.
0 The manual outside air damper will ship factory supplied within the unit, but must be
field installed.
q Through the base electric required when ordering disconnect/circuit breaker options.
w Not available with electro-mechanical unit controls.
e Novar Sensor utilized with digit 21 = (4) Novar 3051 Controls without Zone Sensor.
r Available for T/Y 10 ton standard efficiency models only.

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

Description

Order Number

21
Communications Optionsw

No Communications Interface....................................... 0

Trane Communications Interface (TCI).......................... 1
LonTalk Communications Interface (LCI)..................... 2

Novar 2024 Controls..................................................... 3

Novar 3051 Controls..................................................... 4
22
Refrigeration System Option

Standard Refrigeration System..................................... 0

Dehumidification (Hot Gas Reheat Coil)........................ B
23
Refrigeration Controls

No Refrigeration Control .............................................. 0
Frostat4........................................................................ 2
24
Smoke Detector5w

No Smoke Detector....................................................... 0

Return Air Smoke Detector67.................................... A

Supply Air Smoke Detector........................................... B

Supply and Return Air Smoke Detectors67................ C
25
Monitoring Controlsw

No Monitoring Control8 ............................................... 0

Clogged Filter Switch8 ................................................ 1

Fan Failure Switch8..................................................... 2

Discharge Air Sensing Tube8....................................... 3

Clogged Filter Switch and Fan Fail Switch8................. 4

Clogged Filter Switch and Discharge

Air Sensing Tube8..................................................... 5

Fan Fail Switch and Discharge Air Sensing Tube8....... 6

Clogged Filter and Fan Fail Switches

and Discharge Air Sensing Tube8............................. 7

Novar Return Air Sensor9............................................ 8

Novar 3051 Zone Sensore........................................... 9

Condensate Drain Pan Overflow Switch........................ A

Clogged Filter Switch8 and

Condensate Drain Pan Overflow Switch...................... B

Fan Failure Switch8 and Condensate

Drain Pan Overflow Switch.......................................... C

Discharge Air Sensing8 and

Condensate Drain Pan Overflow Switch...................... D

Clogged Filter Switch8, Fan Failure Switch8

and Condensate Drain Pan Overflow Switch................E

Clogged Filter Switch8, Discharge Air

Sensing Tube8 and Condensate Drain Pan

Overflow Switch........................................................... F

Fan Failure Switch, Discharge Air SensingTube8

and Condensate Drain Pan Overflow Switch............... G

Clogged Filter Switch8, Fan Failure Switch8,

Discharge Air Sensing8 and Condensate Drain

Pan Overflow Switch................................................... H
26
System Monitoring Controls

No Monitoring Controls................................................. 0

Demand Control Ventilation (CO2)rt...........................A
27
Unit Hardware Enhancements

No Enhancements......................................................... 0

Stainless Steel Drain Pan.............................................. 1

1-8
Main Assembly (see previous page)
9
Unit Controls

Electro-Mechanical ....................................................... E

ReliaTel Micro-processor........................................... R
10
(See Heater Table below)
11
Minor Design Sequence

First Sequence............................................................. A
12-13
Service Sequence

First Sequence (Factory Supplied).............................. ,
14
Fresh Air Selection

No Fresh Air.................................................................. 0

0-50% Manual Outside Air Damper0........................... A

0-50% Motorized Outside Air Damper........................... B

0-100% Economizer, Dry Bulb without
Barometric Relief 2 .................................................. C

0-100% Economizer, Dry Bulb with
Barometric Relief2 ................................................. D

0-100% Economizer, Reference Enthalpy
without Barometric Relief12 ................................... E

0-100%Economizer, Reference Enthalpy
with Barometric Relief12 ....................................... F

0-100%Economizer, Comparative Enthalpy
without Barometric Relief 12
............................ G

0-100%Economizer, Comparative Enthalpy
with Barometric Relief 12 ...................................... H
15
Supply Fan/Drive Type/Motor

Standard Drive.............................................................. 0

Oversized Motor............................................................ 1

Optional Belt Drive Motor (3 phase only)...................... 2
16
Hinged Service Access & Filters

Standard Panels & Filters.............................................. 0

Hinged Access Panels & Standard Filters..................... A

Standard Panels & 2" Pleated Filters MERV 8.............. B

Hinged Access Panels & 2" Pleated Filters MERV 8..... C

Standard Panels/2" MERV 13 Filters............................. D

High Access Panels/2" MERV 13 Filters....................... E
17
Condenser Coil Protection

Standard Coil ............................................................... 0

Standard Coil with Hail Guard....................................... 1
Black Epoxy Pre-Coated Condenser Coil...................... 2
Black Epoxy Pre-Coated Condenser Coil
with Hail Guard.......................................................... 3

Complete Coat Condenser Coil................................. 4

Complete Coat Condenser Coil with Hail Guard........ 5
18
Through the Base Provisions

No Through the Base Provisions................................... 0
Through the Base Electricq......................................... A
19
Disconnect/Circuit Breaker /Phase Monitor (3 phase only)

No Disconnect/ Circuit Breaker..................................... 0

Unit Mounted Non-Fused Disconnectq........................ 1

Unit Mounted Circuit Breakerq..................................... 2
20
Convenience Outlet

No Convenience Outlet................................................. 0

Unpowered Convenience Outlet.................................... A

Powered Convenience Outlet (3 phase only)3 ............ B

t Available for T/Y 3, 4, 5, 6, 7, 8 ton standard/high efficiency models only.


y Requires selection of 2" Pleated Filters (option B or C) for Digit 16.
u Not available on 6 ton units and all single phase or standard efficiency.
i Standard on T/YSC 6, 7 (single and dual systems), 8, 10 ton standard
efficiency models and T/YHC 4, 5, 6, 7 ton high efficiency models (except for
dehumidification models).
o Epoxy coil and epoxy with hailguard options are not available for units with
microchannel condenser coil.
p Single ZoneVAV is only available on 7.5-10 ton high efficiency and 10 ton standard
efficiency products with ReliaTel controls.
a Multi-speed indoor fan available only on 7.5 & 8.5 ton high efficiency, and 10 ton
products with ReliaTel controls.
s Motorized Outside Air Damper is not available on Multi-Speed or SZVAV (Single
Zone Variable Air Volume) products.
d Frostat standard on Multi-Speed and SZVAV (Single Zone Variable Air Volume)
products.
f Novar is not available with SZVAV products.
g Demand Control Ventilation not available with electromechanical controls.
h Demand Control Ventilation Option includes wiring only. The C02 sensor is a fieldinstalled only option.

PC-8

Effective 1/1/13
22-8301-25

Precedent Packaged Cooling


Convertible 3-10 Tons
(Model Digit Numbers)
Heaters (Digit 10)
kW Nominal No.

Rating
Digit
BTUH
Stages
Used With
208/240/1/60

3.7/5.0

7.5/10.0
10.3/13.8
13.2/17.6
208/240/3/60

4.5/6.0

9.0/12.0
13.2/17.6
17.2/23.0

6.75/9.0
13.5/18.0
20.3/27.0
27.0/36.0
40.5/54.0

(A)
(D)
(F)
(G)

12,800/17,100
25,600/34,100
35,300/47,100
45,100/60,100

1
2
2
2

T*C036-060*1
T*C036-060*1
T*C036-060*1
T*C048-060*1

(B)
(E)
(G)
(J)
(C)
(G)
(K)
(N)
(P)

13,400/20,500
30,800/59,400
44,600/59,400
58,900/78,500
23,000/30,700
46,100/61,400
69,000/92,100
92,200/122,900
138,200/184,300

1
2
2
2
1
1
2
2
2

T*C036-060*3
T*C036-060*3
T*C036-060*3
T*C060*3
T*C072-102*3
T*C072-120*3
T*C072-120*3
T*C072-120*3
T*C120*3

kW Nominal No.

Rating
Digit
BTUH
Stages
Used With
460/3/60

6.0

12.0

17.6

23.0

9.0

18.0

27.0

36.0

54.0
575/3/60

6.0

12.0

17.6

23.0

9.0

18.0

27.0

36.0

54.0

(B)
(E)
(G)
(J)
(C)
(G)
(K)
(N)
(P)

20,500
41,000
59,400
78,500
30,700
61,400
92,100
122,900
184,300

1
2
2
2
1
1
2
2
2

T*C036-060*4
T*C036-060*4
T*C036-060*4
T*C060*4
T*C072-102,*4
T*C072-120*4
T*C072-120*4
T*C072-120*4
T*C120*4

(B)
(E)
(G)
(J)
(C)
(G)
(K)
(N)
(P)

20,500
41,000
59,400
78,500
30,700
61,400
92,100
122,900
184,300

1
2
2
2
1
1
2
2
2

T*C036-060*W
T*C036-060*W
T*C036-060*W
T*C060*W
T*C072-102*W
T*C072-120*W
T*C072-120*W
T*C072-120*W
T*C120*W

Packaged Cooling

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-9

Effective 1/1/13
22-8301-25

Precedent Packaged Cooling


Convertible 3-5 Tons, R-410A
Electric Heaters
Table PC-10-A Accessory Electric Heaters Unit with heater is single circuit / single point power entry
Model
Number

Power
Supply

kW
Rating

Nominal
BTUH

No.
Stages

BAYHTRE105A
BAYHTRE110A
BAYHTRE114A
BAYHTRE118A

208-230/1/60
208-230/1/60
208-230/1/60
208-230/1/60

3.8/5.0
7.5/10.0
10.4/13.8
13.2/17.6

12,900/13,400
25,600/34,000
35,000/47,100
45,100/60,100

1
2
2
2

Used With
T*C036E1,TSC048-060E1
T*C036E1,TSC048-060E1
T*C036E1,TSC048-060E1
TSC048-060E1

BAYHTRE306B
BAYHTRE312B
BAYHTRE318B
BAYHTRE323B

208-230/3/60
208-230/3/60
208-230/3/60
208-230/3/60

4.5/6.0
9.0/12.0
13.0/17.4
17.3/23.0

13,400/20,500
30,800/41,000
44,600/59,400
44,600/59,400

1
2
2
2

T*C036E3,TSC048-060E3, THC037E3
T*C036E3,TSC048-060E3, THC037E3
T*C036E3,TSC048-060E3, THC037E3
TSC060E3

BAYHTRE406B
460/3/60
6.0
20,500
1
T*C036E4,TSC048-060E4, THC037E4
BAYHTRE412B
460/3/60
12.0
41,000
2
T*C036E4,TSC048-060E4, THC037E4
BAYHTRE418B
460/3/60
17.4
59,400
2
T*C036E4,TSC048-060E4, THC037E4
BAYHTRE423B
460/3/60
17.3/23.0
59,400
2
TSC060E4

BAYHTREW06B
575/3/60
6.0
20,500
1
T*C036EW,TSC048-060EW
BAYHTREW12B
575/3/60
12.0
41,000
2
T*C036EW,TSC048-060EW
BAYHTREW18B
575/3/60
17.4
59,400
2
T*C036EW,TSC048-060EW
BAYHTREW23B
575/3/60
17.3/23.0
59,400
2
TSC060EW
208-230/1/60
208-230/1/60
208-230/1/60
208-230/1/60

3.8/5.0
7.5/10.0
10.4/13.8
13.2/17.6

12,900/13,400
25,600/34,000
35,000/47,100
45,100/60,100

1
2
2
2

THC048-060E1
THC048-060E1
THC048-060E1
THC048-060E1

BAYHTRX306B
BAYHTRX312B
BAYHTRX318B
BAYHTRX323B

208-230/1/60
208-230/3/60
208-230/3/60
208-230/3/60

4.5/6.0
9.0/12.0
13.0/17.4
17.3/23.0

13,400/20,500
30,800/41,000
44,600/59,400
59,000/78,500

1
2
2
2

THC048-060E3, THC047E3, THC067E3


THC048-060E3, THC047E3, THC067E3
THC048-060E3, THC047E3, THC067E3
THC060E3

BAYHTRX406B
BAYHTRX412B
BAYHTRX418B
BAYHTRX423B

460/3/60
460/3/60
460/3/60
460/3/60

6.0
12.0
18.0
23.0

20,500
41,000
59,400
78,500

1
2
2
2

THC048-060E4, THC047E4, THC067E4


THC048-060E4, THC047E4, THC067E4
THC048-060E4, THC047E4, THC067E4
THC060E4, THC067E4

Packaged Cooling

BAYHTRX105A
BAYHTRX110A
BAYHTRX114A
BAYHTRX118A

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-10

Effective 1/1/13
22-8301-25

Precedent Packaged Cooling


Convertible 6-10 Tons, R-410A
Electric Heaters
Table PC-11-A Accessory Electric Heaters Unit with heater is single circuit / single point power entry
Model
Number

Power
Supply

kW
Rating

Nominal
BTUH

No.
Stages

Used With

BAYHTRS309B
BAYHTRS318B
BAYHTRS327B
BAYHTRS336B

208-230/3/60
208-230/3/60
208-230/3/60
208-230/3/60

6.75/9.0
13.5/18.0
20.3/27.0
27.0/36.0

23,000/30,700
46,100/61,400
69,000/92,100
92,200/122,900

1
2
2
2

TSC072E3
TSC072E3
TSC072E3
TSC072E3

BAYHTRW309A
BAYHTRW318A
BAYHTRW327A
BAYHTRW336A

208-230/3/60
208-230/3/60
208-230/3/60
208-230/3/60

6.75/9.0
13.5/18.0
20.3/27.0
27.0/36.0

23,000/30,700
46,100/61,400
69,000/92,100
92,200/122,900

1
1
2
2

TSC090E3
TSC090E3
TSC090E3
TSC090E3

BAYHTRT309B
BAYHTRT318B
BAYHTRT327B
BAYHTRT336B

208-230/3/60
208-230/3/60
208-230/3/60
208-230/3/60

6.75/9.0
13.5/18.0
20.3/27.0
27.0/36.0

23,000/30,700
46,100/61,400
69,000/92,100
92,200/122,900

1
2
2
2

TSC092E3, TSC102E3
TSC092E3, TSC102E3
TSC092E3, TSC102E3
TSC092E3, TSC102E3

BAYHTRA318A
BAYHTRA327A
BAYHTRA336A
BAYHTRA354A

208-230/3/60
208-230/3/60
208-230/3/60
208-230/3/60

13.5/18
20.3/27
27/36
40.5/54

46,100/61,400
69,000/92,100
92,200/122,900
138,200/184,300

1
2
2
2

TSC120F3
TSC120F3
TSC120F3
TSC120F3

BAYHTRS409B
BAYHTRS418B
BAYHTRS427B
BAYHTRS436B

460/3/60
460/3/60
460/3/60
460/3/60

9.0
18.0
27.0
36.0

30,700
61,400
92,100
122,900

1
2
2
2

TSC072E4
TSC072E4
TSC072E4
TSC072E4

BAYHTRW409A
460/3/60
9
30,700
BAYHTRW418A
460/3/60
18
61,400
BAYHTRW427A
460/3/60
27
92,100
BAYHTRW436A
460/3/60
36
122,900

BAYHTRT409B
460/3/60
9.0
30,700
BAYHTRT418B
460/3/60
18.0
61,400
BAYHTRT427B
460/3/60
27.0
92,100
BAYHTRT436B
460/3/60
36.0
122,900

1
1
2
2

TSC090E4
TSC090E4
TSC090E4
TSC090E4

1
2
2
2

TSC092E4, TSC102E4
TSC092E4, TSC102E4
TSC092E4, TSC102E4
TSC092E4, TSC102E4

BAYHTRA418A
BAYHTRA427A
BAYHTRA436A
BAYHTRA454A

1
2
2
2

TSC120F4**B
TSC120F4**B
TSC120F4**B
TSC120F4**B

460/3/60
460/3/60
460/3/60
460/3/60

18
27
36
54

61,400
92,100
122,900
184,300

Packaged Cooling

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-11

Effective 1/1/13
22-8301-25

Precedent Packaged Cooling


Convertible 6-10 Tons, R-410A
Electric Heaters
Table PC-12-A Accessory Electric Heaters Unit with heater is single circuit / single point power entry
Model
Number

575/3/60
575/3/60
575/3/60
575/3/60

kW
Rating

9.0
18.0
27.0
36.0

Nominal
BTUH

30,700
61,400
92,100
122,900

No.
Stages

Used With

1
2
2
2

TSC072EW
TSC072EW
TSC072EW
TSC072EW

BAYHTRWW18A
575/3/60
18
61,400
BAYHTRWW27A
575/3/60
27
92,100
BAYHTRWW36A
575/3/60
36
122,900

BAYHTRTW18B
575/3/60
18.0
61,400
BAYHTRTW27B
575/3/60
27.0
92,100
BAYHTRTW36B
575/3/60
36.0
122,900

1
2
2

TSC090EW
TSC090EW
TSC090EW

2
2
2

TSC092EW, TSC102EW
TSC092EW, TSC102EW
TSC092EW, TSC102EW

BAYHTRAW18A
BAYHTRAW36A
BAYHTRAW54A

575/3/60
575/3/60
575/3/60

18
36
54

61,400
122,900
184,300

1
2
2

TSC120FW
TSC120FW
TSC120FW

BAYHTRU309A
BAYHTRU318A
BAYHTRU327A
BAYHTRU336A

208-230/3/60
208-230/3/60
208-230/3/60
208-230/3/60

6.8/9.0
13.5/18.0
20.3/27.0
27.0/36.0

23,000/30,700
46,100/61,400
69,000/92,100
92,100/122,900

1
1
2
2

THC072E3
THC072E3
THC072E3
THC072E3

Packaged Cooling

BAYHTRSW09B
BAYHTRSW18B
BAYHTRSW27B
BAYHTRSW36B

Power
Supply

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-12

Effective 1/1/13
22-8301-25

Precedent Packaged Cooling


Convertible 6-10 Tons, High Efficiency
R-410A Heaters
Table PC-13-A Accessory Electric Heaters Unit with heater is single circuit / single point power entry
Model
Number

Power
Supply

kW
Rating

Nominal
BTUH

BAYHTRA309A 208-230/3/60 9.0


30,700
BAYHTRA318A 208-230/3/60 18.0
61,400
BAYHTRA327A 208-230/3/60 27.0
92,100
BAYHTRA336A 208-230/3/60 36.0
122,900

BAYHTRA409A 460/3/60
9.0
30,700
BAYHTRA418A 460/3/60
18.0
61,400
BAYHTRA427A 460/3/60
27.0
92,100
BAYHTRA436A 460/3/60
36.0
122,900

No.
Stages

Used With

1 THC092F3
1 THC092F3
2 THC092F3
2 THC092F3
1 THC092F4
1 THC092F4
2 THC092F4
2 THC092F4

BAYHTRD309A 208-230/3/60 6.8/9.0 23,000/30,700 1 THC102E3


BAYHTRD318A 208-230/3/60 13.5/18.0 46,100/61,400 1 THC102E3,THC120E3
BAYHTRD327A 208-230/3/60 20.3/27.0 69,000/92,100 2 THC102E3,THC120E3
BAYHTRD336A 208-230/3/60 27.0/36.0 92,100/122,900 2 THC102E3,THC120E3
BAYHTRD354A 208-230/3/60 40.6/54.0 138,000/184,300 2 THC120E3

BAYHTRU409A
460/3/60
9.0
30,700
1
THC072E4

BAYHTRU418A
460/3/60
18.0
61,400
1
THC072E4

BAYHTRU427A
460/3/60
27.0
92,100
2
THC072E4

BAYHTRU436A
460/3/60
36.0
122,900
2
THC072E4

BAYHTRD409A
BAYHTRD418A
BAYHTRD427A
BAYHTRD436A
BAYHTRD454A

460/3/60
460/3/60
460/3/60
460/3/60
460/3/60

9.0
18.0
27.0
36.0
54.0

30,700
61,400
92,100
122,900
184,300

1 THC102E4
1 THC102E4,THC120E4
2 THC102E4,THC120E4
2 THC102E4,THC120E4
2 THC120E4

Packaged Cooling

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-13

Effective 1/1/13
22-8301-25

Precedent Packaged Cooling


Convertible 3-10 Tons Accessories
Table PC-14-A Accessories
Model Number

Description

Used With

BAYABRD001C........... ReliaTel Options Module................................................... All Precedents (ReliaTel) See Note5


BAYASCT00167* ...... Anti-Short-Cycle Timer......................................................... All Precedents (Electro Mechanical)
BAYBARM010A4 ....... Barometric Relief................................................................. THC036-060E, THC036E
BAYBARM011A4 ....... Barometric Relief................................................................. TSC072-102E, THC092F, TSC120F, THC048E-120E
BAYBCIR001A............. Bacnet Communication Interface..................................... ReliaTel Controller (BCI-R)
BAYCCHT010B........... Crankcase Heater................................................................ TSC036-048E1, 3
BAYCCHT011B........... Crankcase Heater................................................................ TSC036-048E4, W
BAYCCHT017A........... Crankcase Heater................................................................ TSC060E1, 3
BAYCCHT018A........... Crankcase Heater................................................................ TSC060E4, EW
BAYCO2K001B38 .... CO2 Sensor Kit, Wall Mounted............................................. All Precedents (ReliaTel)
BAYCO2K003B38 .... CO2 Sensor Kit, Duct Mounted............................................. All Precedents (ReliaTel)
BAYCURB042A2........ Roof Curb............................................................................. THC036E, TSC036E-060E
BAYCURB043A2........ Roof Curb............................................................................. THC048E-072E, TSC072-102E, THC092F, TSC120F
BAYCURB044A........... Roof Curb............................................................................. THC102E-120E
BAYDFPS003B35 ..... Clogged Filter Switch........................................................... All Precedents (ReliaTel)
BAYDFPS004A35 ..... Fan Failure Switch................................................................ All Precedents (ReliaTel)
BAYDFPS014A ........... Clogged Filter Switch (w/MERV 13 Filter)............................ All Precedents (ReliaTel)
BAYDMPR053B9 ....... 0-50% Manual Outside Air Damper..................................... THC036E, TSC036E-060E
BAYDMPR056B9 ....... 0-50% Manual Outside Air Damper..................................... THC048E-120E, TSC072-102E, TSC120F
BAYDMPR051A3 ....... 0-50% Motorized Outside Air Damper................................. THC036E_R, TSC036-060E_R (ReliaTel)
BAYDMPR052A6 ....... 0-50% Motorized Outside Air Damper................................. THC036E_E, TSC036E-060E_E (Electro Mechanical)
BAYDMPR054A3 ....... 0-50% Motorized Outside Air Damper................................. THC048-120E_R, TSC072-120F_R (ReliaTel)
BAYDMPR055A6 ...... 0-50% Motorized Outside Air Damper................................. THC048-120E_E, TSC072-120F_E



(Electro Mechanical)
BAYECON085A3 ....... 0-100% Dry Bulb Economizer without Barometric Relief .... THC036E_R, TSC036E-060E_R (ReliaTel)
BAYECON086A6 ....... 0-100% Dry Bulb Economizer without Barometric Relief .... THC036E_E, TSC036E-060E_E (Electro Mechanical)
BAYECON087A3 ....... 0-100% Dry Bulb Economizer without Barometric Relief .... THC048-120*_R, TSC072*-120_R (ReliaTel)
BAYECON088A6 ....... 0-100% Dry Bulb Economizer without Barometric Relief .... THC048-120*_E, TSC072*-120_E



(Electro Mechanical)
BAYENTH005A13 .... Reference Enthalpy Kit......................................................... BAYECON085A, 087A
BAYENTH006B13 .... Comparative Enthalpy Kit..................................................... BAYECON085A, 087A
BAYENTH001A........... Enthalpy Control (Solid State).............................................. BAYECON0086A, 088A

Packaged Cooling

BAYFRST003A36 ..... High Temperature Stat......................................................... All Precedents


1 Kits contain all necessary parts to achieve desired level of enthalpy control.
2 Lynn Haven Manufacturing has a No-Return policy for this roof curb.
3 For use with ReliaTel controlled units only.
4 Barometric Relief accessory installs in ductwork for horizontal configuration. For downflow configuration, installs in the unit's horizontal return duct. See Installer's
Guide for complete instructions.
5 BAYABRD001C is required when ordering field installed accessories Clogged Filter Switch (BAYDFPS003A), Fan Fail Switch (BAYDFPS004A), Discharge Air
Sensing Kit (BAYTUBE004A) or Evaporator Defrost Control (Frostat) (BAYLOAM020B) Ventilation Override Kit (BAYVNOR001B) unless the following options
are factory installed: Frostat, Smoke Detector, Clogged Filter Switch, Fan Failure Switch, Discharge Air Sensing Kit. These factory installed options include the
ReliaTel Options Module.
6 For use with electromechanical controlled units only.
7 Activated on Power On.
8 Field installed accessory requires economizer.
9 The manual outside air damper will ship factory supplied within the unit, but must be field installed.

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-14

Effective 1/1/13
22-8301-25

Precedent Packaged Cooling


Convertible 3-10 Tons Accessories
Table PC-15-A Accessories
Model Number

Description

Used With

BAYGARD037B..................Condenser Coil Hail Guard....................................................TSC036-060E, THC036E


BAYGARD040A..................Condenser Coil Hail Guard....................................................THC048-060E,TSC072E-090E
BAYGARD041A..................Condenser Coil Hail Guard....................................................TSC092E, TSC102E, THC072E
BAYGARD070A..................Condenser Coil Hail Guard....................................................THC102E, THC120E
BAYGARD141A..................Condenser Coil Hail Guard....................................................TSC120F, THC092F
BAYHSDR012A..................High Static Drive Kit...............................................................THC072E
BAYHSMT082A..................2 HP Oversized Motor Kit (208-230/460V).............................TSC072E3, 4
BAYHSMT083A..................2 HP Oversized Motor Kit (575V)...........................................TSC072EW
BAYHSMT086A..................3 HP Oversized Motor Kit (208-230/460V).............................TSC090E-102E3, 4
BAYHSMT087A..................3 HP Oversized Motor Kit (575V)...........................................TSC090E-102EW
BAYHSMT402A..................2 HP Oversized Motor Kit.......................................................THC072E3, 4
BAYICSI003A38..............Trane Communications Interface (TCI) ..................................All Precedents (ReliaTel)
BAYKSKT255B...................Start Kit..................................................................................TSC036E1-060E1
BAYLMSW001A0..............Power Exhaust Limit Switch...................................................All Precedents
BAYLOAM020B134........Evaporator Defrost Control (Frostat)......................................All Precedents (ReliaTel)
BAYLSDR006B...................Low Static Drive Kit: 3-5T High Efficiency..............................THC036E-060E
BAYLSDR009A...................Low Static Drive Kit................................................................TSC092-102E, THC072E
BAYLTCI002B3 ................LonTalk Communications Interface (LCI)..............................All Precedents (ReliaTel)
BAYPWRX026A6..............Power Exhaust (208-230/3 VAC)............................................TSC072-102E3, TSC120F3, THC072E3,

THC092F3, THC102E3, TCH120E3
BAYPWRX027A6..............Power Exhaust (460/3 VAC)...................................................TSC072-102E4, TSC120F4, THC072E4,

THC092F4, THC102E4, TCH120E4
BAYPWRX028A6..............Power Exhaust (575/3 VAC)...................................................TSC072-102EW, TSC120FW
BAYPWRX070A6..............Power Exhaust (208-230/3 VAC)............................................TSC036-060E3, TCH036-THC060E3, THC037E3,

THC047E3, THC067E3
BAYPWRX071A6..............Power Exhaust (460/3 VAC)...................................................TSC036-060E4, TCH036-THC060E4, THC037E4,

THC047E4, THC067E4
BAYPWRX072A6..............Power Exhaust (575/3 VAC)...................................................TSC036-060EW
BAYQACB009A25...........Quick Adapt Roof Curb..........................................................TSC036-060E, THC036E, THC037E
BAYQACB010A25...........Quick Adapt Roof Curb..........................................................TSC036-060E, THC036E, THC037E
BAYQACB011A27...........Quick Adapt Roof Curb..........................................................TSC072-102E, TSC120F, THC048-072E, THC047E, THC067E
BAYQACB012A27...........Quick Adapt Roof Curb..........................................................TSC072-102E, TSC120F, THC048-072E, THC047E, THC067E
BAYQACB013A27...........Quick Adapt Roof Curb..........................................................TSC072-102E, TSC120F, THC048-072E, THC047E, THC067E
BAYRTEM001Aq...............Fully Featured ReliaTel Economizer Logic Model...............All Precedents
BAYSTAT0233 ..................Remote Potentiometer............................................................All Precedents
BAYSERV001A3...............Selective Resistance Service Tester......................................All Precedents
BAYSENS016A3...............Temperature Sensor...............................................................All Precedents
BAYSENS250A3w............CO2 Duct Mounted, Sensor Only............................................All Precedents (ReliaTel)
BAYSENS251A 3w...........CO2 Wall Mounted, Sensor Only............................................All Precedents (ReliaTel)
BAYTUBE005A...................Discharge Air Sensing Kit.......................................................TSC036-060E*R, THC036-037E*R
BAYTUBE007A...................Discharge Air Sensing Kit.......................................................TSC072-102E*R, THC047E-072E*R
BAYTUBE401A...................Discharge Air Sensing Kit.......................................................TSC120F*R, THC092F*R
BAYTUBE403A...................Discharge Air Sensing Kit.......................................................TSC102-120E*R
BAYVNOR001B349 ......Ventilation Override Kit w/ReliaTel options module.............All Precedents

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-15

Effective 1/1/13
22-8301-25

Packaged Cooling

1 For ReliaTel microprocessor controlled units only. Must be factory installed for electromechanical controlled units.
2 Lynn Haven Manufacturing has a No-Return policy for this roof curb.
3 For use with ReliaTel controlled units only.
4 BAYABRD001C is required when ordering field installed accessories Clogged Filter Switch (BAYDFPS003A), Fan Fail Switch (BAYDFPS004A), Discharge Air Sensing Kit
(BAYTUBE004A) or Evaporator Defrost Control (Frostat) (BAYLOAM020B) Ventilation Override Kit (BAYVNOR001B) unless the following options are factory installed: Frostat,
Smoke Detector, Clogged Filter Switch, Fan Failure Switch, Discharge Air Sensing Kit. These factory installed options include the ReliaTel Options Module.
5 BAYQACB009A adapts Voyager BAYCURB021B to accept Precedent 3-5 ton unit. BAYQACB010A adapts Voyager BAYCURB022B to accept Precedent unit.
6 Cannot be used in conjunction with Barometric Relief. Order Economizer without Barometric Relief.
7 BAYQACB012A adapts Voyager BAYCURB025A to accept Precedent 6-10 ton unit. BAYQACB013A adapts Voyager BAYCURB026A to accept Precedent 6-10 ton unit.
8 Interface allows a unit with ReliaTel Controls to communicate with Tracer 100, Tracker, VariTrac II, and is the preferred method of communication to Tracer Summit.
9 Field installed accessory requires economizer.
0 When ordering a field installed power exhaust on a unit with electromechanical controls, BAYLMSW001A must be ordered.
q If any version of comparative or reference enthalpy is ordered, BAYRTEM001A does not need to be ordered.
w Order only when unit has factory installed Demand Control Ventilation option.

Precedent Packaged Cooling


Convertible 3-10 Tons, R-410A
Zone Sensors / Thermostats
Table PC-16-A Zone Sensors for ReliaTel Controlled Units
Model
Number
Description

BAYSENS036A2
BAYSENS037A2
BAYSENS073A1
BAYSENS074A1

BAYSENS077A
BAYSENS106A
BAYSENS108A
BAYSENS110A

BAYSENS119A
BAYSENS135A
BAYSENS050A3
BAYMTPL110A

Used With

Wall-Mounted Humidity Zone Sensor


Duct-Mounted Humidity Zone Sensor
Room Sensor w/ Override and Cancel Buttons
Room Sensor w/ Temp. Adjustment with Override and
Cancel Buttons

Remote Room Sensor

Single Setpoint Manual Changeover
Dual Setpoint Manual or Auto Changeover
Dual Setpoint Man. or Auto Changeover with System
Function Lights

Programmable Night Setback w/System Function Lights
Digital Display Zone Sensor T*C033-120_R
Wireless Zone Sensor T*C033-120_R
Retrofit Wall Cover from Horizontal to Vertical

All Precedents (with Reheat)


All Precedents (with Reheat)
T*036-120*R

T*036-120*R
BAYSENS106B,108B,110B, & 119A
T*C033-120_R
T*C033-120_R

T*C033-120_R
T*C033-120_R

T*C036-120A

1 Used with Integrated ComfortTM Systems, any unit type. These sensors do not work with TCM. Consult BASD Marketing for them.
2 For use with ReliaTel Controls only.
3 Kit comes with everything required for installing and operation.
*Either standard or high efficiency models.

Table PC-16-B Thermostats Electromechanical


Model
Number
Description

2H/2C Digital Display Programmable Thermostat


3H/2C Programmable Touchscreen Thermostat
3H/2C Digital Display Thermostat
Duct Mounted Return Air Sensor

Used With
All Precedents
All Precedents
All Precedents
BAYSTAT152A

Packaged Cooling

BAYSTAT150A
BAYSTAT152A
BAYSTAT155A
BAYSTAT170A

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-16

Effective 1/1/13
22-8301-25

ReliaTel Controls for


Precedent and Voyager

Packaged Unit Protection/Operation Timings and Features


Alternating Lead/Lag Dual Compressor Models Only
During periods of part load operation, each compressor cycles
alternately as circuit number one, equalizing compressor wear and run
time. Enabled by cutting the wire (BLUE) at (RTRM) junction number
J3-8. Standard
Anti Short Cycle Timer (ASCT) Function Provides a three (3)
minute minimum ON time and a three (3) minute minimum OFF time
for compressors, enhances compressor reliability by ensuring proper oil
return. Standard
Built In Evaporator Defrost Control (EDC) Function
Provides low ambient cooling down to 0F. Standard
Built In Fan Delay Relay (FDR) Function Provides custom indoor
fan timing sequences for the different types of equipment, enhancing
efficiency and reliability. Standard
Built In Night Set Back and Unoccupied Functions1 When using
a standard dual setpoint/auto change over Zone Sensor Module (ZSM),
this function is enabled by applying a short across terminal J6-11 and
J6-12. Sets cooling setpoint up a minimum of 7F, sets heating setpoint
back a minimum of 7F, forces outside air damper (if present) minimum
position to zero, and forces fan operation to automatic. Accessory
(requires time clock accessory or field supplied/installed switch or
contacts).
Built In TEST Mode Aids in quick verification of system
and control operation, exercises both hardware and software
(no special tools required). Standard
Built In Unoccupied Mode1 When using a standard single
setpoint/manual change over Zone Sensor Module (ZSM), this function
is enabled by applying a short across terminal J6-11 and J6-12. Forces
outside air damper (if present) minimum position to zero, forces fan
operation to automatic. Accessory (requires time clock accessory or
field supplied/installed switch or contacts).
Direct Digital Control (DDC)1 Proportional Integral (PI) control.
Proportional sets corrective action proportional to deviation from
setpoint. Integral fine tunes the rate of corrective action proportional
to the error (results in superior space temperature control). Standard
Economizer Preferred Cooling1 Provides fully integrated
operation if required. Will not turn on a compressor with the economizer,
if the space is recovering adequately with the economizer alone (0.2F/
minute). Allows the equipment to be utilized in more varied applications.
Standard with economizer accessory.
Emergency Stop Terminals On Low Voltage Terminal Board
(LTB-5 and LTB-6) Provides a convenient point to disable the
equipment completely, and immediately. Still provides communication to
BAS. Standard
Heat Pump Smart Recovery and Smart Staging1 Inhibits
auxiliary heat operation if the space is recovering adequately
(0.1F/minute) with the heat pump alone, providing considerable
savings in operating costs. Standard
Heat Pump Soft Start Provides a smooth transition into heating
after defrost, minimizing noise and compressor stress associated with
switch over. Standard

Increased Reliability Fewer components (moving electromechanical parts), less likelihood of equipment down time or
failure. Standard
Integral Electric Heat Staging1 Stages electric heaters OFF
and ON, eliminating the use of outdated sequencers. Standard
Intelligent Fallback1 A built in Default Control provides adaptive
operation, which allows the equipment to continue to operate,
providing comfort in the event of certain component failures. Also,
allows emergency operation without a Zone Sensor Module (ZSM).
Standard
Low Ambient Start Timer (LAST) Function Bypasses low
pressure control when a compressor starts, eliminating nuisance
compressor lock outs. Standard
Lower Installation Cost Using a standard Zone Sensor Module
(ZSM), control voltage wiring may be run up to five (5) times further
than any electromechanical system, with no increase in wire gauge.
Example: Electromechanical System 30 feet maximum using 22
gauge wire. Micro Control System 150 feet using 22 gauge wire.
Standard
On Board Diagnostics1 Assist with equipment troubleshooting, if
a problem occurrence should take place. Standard
Remote Sensing1 All standard Zone Sensor Modules
(ZSMs) have remote sensing capabilities, typically achieved by using
an expensive program-mable thermostat and remote sensor with
electromechanical equipment. Accessory (requires use of remote
sensor).
Selectable Economizer Dry Bulb Change Over Allows the
capability of selecting the following dry bulb change over points:
63, 67, 70 or 73F. Standard with economizer accessory.
Space Temperature Averaging1 All standard Zone Sensor
Modules (ZSMs) have space temperature averaging capabilities,
typically achieved by using an expensive programmable thermostat
and minimum of four (4) remote sensors with electromechanical
equipment. Averaging with ReliaTel can be achieved with two
(2) sensors.
Supply Air Tempering1 A built in feature, once enabled only
through an ICS device, may also be enabled using a digital or
programmable Zone Sensor Module. When in the HEAT mode
(and not actively heating), if supply air temperature drops 10F below
the heating setpoint, heat is turned on until supply air temperature
rises to a point 10F above the heating setpoint. Provides temperate
air during the OFF cycle, and eliminates cold air dumping from
supply ducts. Extremely effective when introducing any quantity of
fresh air. Standard when using a RTOM, ICS device, digital, or
programmable Zone Sensor Module.
Time Delay Relay (TDR) Function Provides an incremental
staging delay between compressors, minimizes equipment current
inrush and consumption by keeping compressors from starting
simultaneously. Standard
Low Pressure and High Pressure Compressor Lockout 3 trips
will lockout control.

Packaged Cooling

1 Denotes features lost from utilizing standard conventional stat.

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-17

Effective 1/1/13
22-8301-25

ReliaTel Controls for


Precedent and Voyager

Operation With An Electromechanical Thermostat


When the ReliaTel RTRM Thermostat Interface is used, equipment operation
differs significantly. The basic equipment protection features remain intact, and the
following features and benefits are lost:
Space Temperature Averaging
capabilities are lost, unless generic
control being applied can accomplish
this.
Supply Air Tempering feature is lost,
discharge air temperature may be cold
when not actively heating if outdoor
air is being introduced through the
equipment.
Built In Night Set Back and
Unoccupied functions are lost, unless
generic control being applied can
accomplish this.
Built In Unoccupied Mode is lost,
unless generic control being applied
can accomplish this.
Economizer Preferred Cooling
Feature is lost, all compressor
operation is locked out below 50F.

Packaged Cooling

Direct Digital Control (DDC)


Proportional Integral (PI) control
is lost, equipment is controlled by
a thermostat or generic building
automation system device.
Intelligent Fall back is lost, if a failure
occurs in the device controlling the
equipment, operation will cease.
Installation is more costly, with the
addition of a thermostat or generic
control, the control wiring size must be
increased.
Heat Pump Smart Recovery and
Smart Staging is lost, Heat Pump
operation becomes more costly unless
generic control being applied can
accomplish this.
Remote Sensing capabilities are lost,
unless generic control being applied
can accomplish this.
Low ambient disabled economizer
and second condensing fan cycling
capability.

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-18

Effective 1/1/13
22-8301-25

Voyager Packaged Cooling with ReliaTel


Controls 12-25 Tons, R-410A
12-25 Ton T*D-F Downflow
12-25 Ton T*H-F Horizontal
ReliaTel control features are listed on
page PC-17
Built-in anti-short cycle, time-delay relay
and minimum on time controls
2" throwaway filters
Liquid line drier
Built-in fork lift holes

Operating charge of R-410A


Quick-Access on 12 25
Sloped sheet metal drain pan
Dedicated horizontal and downflow units
Single point power for electric heat
Complete line of optional electric heaters
Internally enhanced coil tubing
Low ambient to 0F standard
Colored and numbered wiring

Phase monitor
Quick-adjust idler arm pulley. Adjust belt
tension, change belts, adjust airflow quickly
(12 25 tons), downflow only
UL listed and CSA certified
5-year limited compressor warranty
(12 17 tons)
1-year limited compressor warranty
(20 and 25 tons)

Table PC-19-A High Efficiency ReliaTel Units (R-410A)



Unit
Tons Model No.

Power Supply Performance


Cooling
Volts/Phase/Hz
EER
Capacity (Btuh)

Dimensions (in.)
H x W x L

Shipping
Max Fuse Size or
Downflow3
Weight (Ibs.) MCA2 Max Circuit Breaker1
Roofcurb

121/2 TH*150F3R0A000 208-230/3/60 12.1


140,000 54 x 855/16 x 1225/16 2373
65
80
15 TH*180F3R0A000 208-230/3/60 12.0
172,000 64 1/8 x 855/16 x 1225/16 2322
72
90
171/2 TH*210F3R0A0000 208-230/3/60 11.8
198,000 64 1/8 x 855/16 x 1225/16 2396
88
110
20 TH*240F3R0A0000 208-230/3/60 11.0
242000 64 1/8 x 855/16 x 1225/16 2399
104
125
25 TH*300F3R0A0000 208-230/3/60 10.6
272000 64 1/8 x 855/16 x 1225/16 2365
116
150

121/2 TH*150F4R0A0000 460/3/60
12.1
140,000 54 x 855/16 x 1225/16 2373
32
40
15 TH*180F4R0A0000 460/3/60
12.0
172,000 641/8 x 855/16 x 1225/16 2322
36
45
171/2 TH*210F4R0A0000 460/3/60
11.8
198,000 641/8 x 855/16 x 1225/16 2396
42
50
20 TH*240F4R0A0000 460/3/60
11.0
242000 641/8 x 855/16 x 1225/16 2399
50
60
25 TH*300F4R0A0000 460/3/60
10.6
272000 641/8 x 855/16 x 1225/16 2365
56
70

121/2 TH*150FWR0A0000 575/3/60
12.1
140,000 54 x 855/16 x 1225/16 2373
25
30
15 TH*180FWR0A0000 575/3/60
12.0
172,000 641/8 x 855/16 x 1225/16 2322
29
40
171/2 TH*210FWR0A0000 575/3/60
11.8
198,000 641/8 x 855/16 x 1225/16 2396
36
45
20 TH*240FWR0A0000 575/3/60
11.0
242000 641/8 x 855/16 x 1225/16 2399
42
50
25 TH*300FWR0A0000 575/3/60
10.6
272000 641/8 x 855/16 x 1225/16 2365
47
60

BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B

Table PC-19-B High Efficiency ReliaTel Units (R-410A) - Multi Speed Indoor Fan

Unit
Tons Model No.

Power Supply Performance


Cooling
Volts/Phase/Hz
EER
Capacity (Btuh)

Dimensions (in.)
H x W x L

Shipping
Max Fuse Size or1 Downflow
Weight (Ibs.) MCA2 Max Circuit Breaker*
Roofcurb

121/2 TH*150F3R0A1B8B 208-230/3/60 12.1


140,000 54 x 855/16 x 1225/16 2398
65
80
15 TH*180F3R0A1B8B 208-230/3/60 12.0
172,000 641/8 x 855/16 x 1225/16 2347
72
90
171/2 TH*210F3R0A1B8B 208-230/3/60 11.8
198,000 641/8 x 855/16 x 1225/16 2421
88
110
20 TH*240F3R0A1B8B 208-230/3/60 11.0
242000 641/8 x 855/16 x 1225/16 2424
104
125
25 TH*300F3R0A1B8B 208-230/3/60 10.6
272000 641/8 x 855/16 x 1225/16 2430
116
150

121/2 TH*150F4R0A1B8B 460/3/60
12.1
140,000 54 x 855/16 x 1225/16 2398
32
40
15 TH*180F4R0A1B8B 460/3/60
12.0
172,000 641/8 x 855/16 x 1225/16 2347
36
45
171/2 TH*210F4R0A1B8B 460/3/60
11.8
198,000 641/8 x 855/16 x 1225/16 2421
42
50
20 TH*240F4R0A1B8B 460/3/60
11.0
242000 641/8 x 855/16 x 1225/16 2424
50
60
25 TH*300F4R0A1B8B 460/3/60
10.6
272000 641/8 x 855/16 x 1225/16 2410
56
70

121/2 TH*150FWR0A1B8B 575/3/60
12.1
140,000 54 x 855/16 x 1225/16 2398
25
30
15 TH*180FWR0A1B8B 575/3/60
12.0
172,000 641/8 x 855/16 x 1225/16 2347
29
40
171/2 TH*210FWR0A1B8B 575/3/60
11.8
198,000 641/8 x 855/16 x 1225/16 2421
36
45
20 TH*240FWR0A1B8B 575/3/60
11.0
242000 641/8 x 855/16 x 1225/16 2424
42
50
25 TH*300FWR0A1B8B 575/3/60
10.6
272000 641/8 x 855/16 x 1225/16 2410
47
60

BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-19

Packaged Cooling

1 HACR type circuit breaker per NEC.


2 Information subject to change. Please confirm with current Product Data/Service Facts for current factory production.
3 Downflow only.
4 278,000 in the horizontal airflow configuration.
* Digit 3 - H = Horizontal or D = Downflow.

Effective 1/1/13
22-8301-25

Voyager Packaged Cooling with ReliaTel


Controls 12-25 Tons, R-410A
12-25 Ton T*D-F Downflow
12-25 Ton T*H-F Horizontal
ReliaTel control features are listed on
page PC-17
Built-in anti-short cycle, time-delay relay
and minimum on time controls
2" throwaway filters
Liquid line drier
Built-in fork lift holes

Operating charge of R-410A


Quick-Access on 12 25
Sloped sheet metal drain pan
Dedicated horizontal and downflow units
Single point power for electric heat
Complete line of optional electric heaters
Internally enhanced coil tubing
Low ambient to 0F standard
Colored and numbered wiring

Phase monitor
Quick-adjust idler arm pulley. Adjust belt
tension, change belts, adjust airflow quickly
(12 25 tons), downflow only
UL listed and CSA certified
5-year limited compressor warranty
(12 17 tons)
1-year limited compressor warranty
(20 and 25 tons)

Table PC-20-A ReliaTel Units (R-410A) - Standard Efficiency



Unit
Tons Model No.

Power Supply Performance


Cooling
Volts/Phase/Hz
EER) Capacity (Btuh)

Dimensions (in.)
H x W x L

Shipping
Max Fuse Size or
Downflow3
Weight (Ibs.) MCA2 Max Circuit Breaker1
Roofcurb

121/2 TS*150F3R0A0000 208-230/3/60 11.0


140,000 501/8 x 715/8 x 1075/16 1781
64
80
15 TS*180F3R0A0000 208-230/3/60 11.0
176,000 54 x 855/16 x 1225/16 2281
75
100
171/2 TS*210F3R0A0000 208-230/3/60 11.0
193,000 54 x 855/16 x 1225/16 2292
93
125
20 TS*240F3R0A0000 208-230/3/60 10.0
240,000 54 x 855/16 x 1225/16 2353
108
125
25 TS*300F3R0A0000 208-230/3/60 10.0
272,000 54 x 855/16 x 1225/16 2337
124
150

121/2 TS*150F4R0A0000 460/3/60 11.0 140,000 501/8 x 715/8 x 1075/16 1781
31
40
15 TS*180F4R0A0000 460/3/60
11.0
176,000 54 x 85 5/16 x 1225/16 2281
28
50
171/2 TS*210F4R0A0000 460/3/60
11.0
193,000 54 x 85 5/16 x 1225/16 2292
44
60
20 TS*240F4R0A0000 460/3/60
10.0
240,000 54 x 85 5/16 x 1225/16 2353
52
70
25 TS*300F4R0A0000 460/3/60
10.0
272,000 54 x 85 5/16 x 1225/16 2337
59
70

121/2 TS*150FWR0A0000 575/3/60 11.0 140,000 501/8 x 715/8 x 1075/16 1781
23
30
15 TS*180FWR0A0000 575/3/60
11.0
176,000 54 x 855/16 x 1225/16 2281
31
40
171/2 TS*210FWR0A0000 575/3/60
11.0
193,000 54 x 855/16 x 1225/16 2292
35
50
20 TS*240FWR0A0000 575/3/60
10.0
240,000 54 x 855/16 x 1225/16 2353
44
60
25 TS*300FWR0A0000 575/3/60
10.0
272,000 54 x 855/16 x 1225/16 2337
48
60

BAYCURB026B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB026B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB026B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B

Table PC-20-B ReliaTel Units (R-410A) - Standard Efficiency - Multi Speed Indoor Fan

Unit
Tons Model No.

Power Supply Performance


Cooling
Volts/Phase/Hz
EER
Capacity (Btuh)

Dimensions (in.)
H x W x L

Shipping
Max Fuse Size or1 Downflow
Weight (Ibs.) MCA2 Max Circuit Breaker*
Roofcurb

Packaged Cooling

121/2 TS*150F3R0A1B8B 208-230/3/60 11.0


140,000 501/8 x 715/8 x 1075/16 1806
64
80
15 TS*180F3R0A1B8B 208-230/3/60 11.0
176,000 54 x 855/16 x 1225/16 2306
75
100
171/2 TS*210F3R0A1B8B 208-230/3/60 11.0
193,000 54 x 855/16 x 1225/16 2317
93
125
20 TS*240F3R0A1B8B 208-230/3/60 10.0
240,000 54 x 855/16 x 1225/16 2378
108
125
25 TS*300F3R0A1B8B 208-230/3/60 10.0
272,000 54 x 855/16 x 1225/16 2402
124
150

121/2 TS*150F4R0A1B8B 460/3/60 11.0 140,000 501/8 x 715/8 x 1075/16 1806
31
40
15 TS*180F4R0A1B8B 460/3/60
11.0
176,000 54 x 855/16 x 1225/16 2306
28
50
171/2 TS*210F4R0A1B8B 460/3/60
11.0
193,000 54 x 855/16 x 1225/16 2317
44
60
20 TS*240F4R0A1B8B 460/3/60
10.0
240,000 54 x 855/16 x 1225/16 2378
52
70
25 TS*300F4R0A1B8B 460/3/60
10.0
272,000 54 x 855/16 x 1225/16 2382
59
70

121/2 TS*150FWR0A1B8B 575/3/60 11.0 140,000 501/8 x 715/8 x 1075/16 1806
23
30
15 TS*180FWR0A1B8B 575/3/60
11.0
176,000 54 x 855/16 x 1225/16 2306
31
40
171/2 TS*210FWR0A1B8B 575/3/60
11.0
193,000 54 x 855/16 x 1225/16 2317
35
50
20 TS*240FWR0A1B8B 575/3/60
10.0
240,000 54 x 855/16 x 1225/16 2378
44
60
25 TS*300FWR0A1B8B 575/3/60
10.0
272,000 54 x 855/16 x 1225/16 2382
48
60

BAYCURB026B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB026B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB026B
BAYCURB027B
BAYCURB027B
BAYCURB027B
BAYCURB027B

1 HACR type circuit breaker per NEC.


2 Information subject to change. Please confirm with current Product Data/Service Facts for current factory production.
3 Downflow only.
4 278,000 in the horizontal airflow configuration.
* Digit 3 - H = Horizontal or D = Downflow.

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-20

Effective 1/1/13
22-8301-25

Voyager Packaged Cooling with ReliaTel


Controls 12-25 Tons
(Model Digit Numbers)
Digit

Description

Order Number

1
Unit Type

Packaged Cooling, Electric Heat................................... T
Packaged Gas/Electric.................................................. Y
2
Efficiency

Standard Efficiency....................................................... S
High Efficiency.............................................................. H
3
Airflow Configuration
Downflow....................................................................... D

Horizontal...................................................................... H
4-6
Nominal Gross Cooling Capacity (MBh)
12 Tons..................................................................... 150
15 Tons........................................................................ 180
17 Tons..................................................................... 210
20 Tons........................................................................ 240
25 Tons........................................................................ 300
7
Major Design Sequence

Microchannel Type Condenser Coils............................. F
8
Voltage Selection
208-230/60/3................................................................. 3
460/60/3........................................................................ 4
575/60/3........................................................................W
380/60/3........................................................................ K
9
Unit Controls
ReliaTel....................................................................... R
10
Heating Capacity

No Heat2..................................................................... 0
18 kW Electric Heat2................................................... G
27 kW Electric Heat2................................................... K
36 kW Electric Heat2................................................... N
54 kW Electric Heat2................................................... P
72 kW Electric Heat2................................................... R
Gas Heat - High1......................................................... H
Gas Heat - Low1.......................................................... L

Gas Heat - SS Ht Ex - Modulating1............................. V

Gas Heat - SS Ht Ex - Low1........................................ X

Gas Heat - SS Ht Ex - High1....................................... Z
11
Minor Design Sequence
12-13
Service Sequence
14
Fresh Air Selection

No Fresh Air.................................................................. 0
Econ Dry Bulb w/ Barometric Relief.............................. D
Econ Reference Enthalpy w/Barometric Relief.............. F
Econ Comparative Enthalpy w/Barometric Relief.......... H
15
Supply Fan/Drive Type/Motor

Standard Motor............................................................. 0

Oversized Motor............................................................ 1

High Efficiency Motor.................................................... 3

Single Zone Variable Air Volume Standard Motor.......... 6

Multi-Speed Standard Motor......................................... 7

Single Zone Variable Air Volume Oversized Motor........ 8

Multi-Speed Oversized Motor........................................ 9

Single Zone Variable Air Volume Standard

Motor w/Shaft Ground Ring........................................ A

Multi-Speed Standard Motor w/Shaft Ground Ring....... B

Single Zone Variable Air Volume Oversized

Motor w/Shaft Ground Ring........................................ C

Multi-Speed Oversized Motor w/Shaft Ground Ring...... D
16
Hinged Service Access / Filters

Standard Panels/Standard Filters.................................. 0

Hinged Access/Standard Filters.................................... A

Standard Panels/MERV 8 Filters................................... B

Hinged Access/MERV 8 Filters..................................... C

Standard Panels/MERV 13 Filters................................. D

Hinged Access/MERV 13 Filters................................... E
17
Condenser Coil Protection

Standard Coil................................................................ 0

Standard Coil With Hail Guard...................................... 1

CompleteCoat Condenser Coil.................................. 4

CompleteCoat Condenser Coil with Hail Guard......... 5
18
Through The Base Provisions.

No Through The Base Provisions3.............................. 0
Through The Base Electric3........................................ A
Through The Base Gas1.............................................. B
Through The Base Electric/Gas1................................. C
Through The Base Access1......................................... D

Description

Order Number

Note: Most Factory Installed Options available for Downflow Air Discharge
units only. Please verify with ordering system for availability.

PC-21

5 TCI is for use with non-VariTrac systems and VariTrac systems.


6 Novar is not available with SZ VAV products.
7 Demand Control Ventilation Option includes wiring only. The C02 sensor is a fieldinstalled only option.

Effective 1/1/13
22-8301-25

Packaged Cooling

1 Applicable to Digit 1 Y models only.


2 Applicable to Digit 1 T models only.
3 Applicable to Digit 1, T or Y models.
4 Available factory installed on downflow AND horizontal units. Verify with ordering
system.

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

Digit

19
Disconnect Switch/Circuit Breaker

No Disconnect/circuit break........................................... 0

Unit Mounted Non-Fused Disconnect Switch................ 1

Unit Mounted Circuit Breaker........................................ 2
20
Convenience Outlet Option
Without Convenience Outlet.......................................... 0

Unpowered Convenience Outlet.................................... A
Powered Convenience Outlet........................................ B
21 Communications Options
Without Communications Options................................. 0
Trane Communications Interface45............................ 1
Lontalk Communications Interface4........................... 2

Novar 2024 Controls Interface6................................... 3

Novar 3051 Controls Interface6................................... 4

Novar 3051 Communications Interface with

Demand Control Ventilation6.................................... 5

Building Automation Control Network
Communications Interface.......................................... 6
22
Refrigeration System Option

Standard refrigeration system....................................... 0

Thermal Expansion Valve (TXV)................................... A

Dehumidification (Hot Gas Reheat)............................... B
23
Refrigeration Controls
Without Refrigeration Controls...................................... 0
Frostat........................................................................... 1
24
Smoke Detector

Without Smoke Detector............................................... 0

Return Air Smoke Detector........................................... A

Supply Air Smoke Detector........................................... B

Return/Supply Air Smoke Detector............................... C

Plenum Smoke Detector............................................... D
25
System Monitoring Controls

No Monitoring Controls................................................. 0

Clogged Filter Switch.................................................... 1

Fan Failure Switch......................................................... 2

Discharge Air Sensing................................................... 3

Clogged Filter Switch and Fan Failure switch................ 4

Clogged Filter Switch and Discharge Air Sensing......... 5

Fan Failure Switch and Discharge Air Sensing.............. 6

Clogged Filter Switch, Fan Failure Switch and

Discharge Air Sensing................................................ 7

NOVAR Return Air Sensor (Novar 2024)6................... 8

NOVAR Zone Temp Sensor(Novar 3051)6................... 9

Condensate Drain Pan Overflow Switch........................ A

Clogged Filter Switch and Condensate Drain

Pan Overflow Switch.................................................. B

Fan Failure Switch and Condensate Drain

Pan Overflow Switch.................................................. C

Discharge Air Sensing and Condensate

Drain Pan Overflow Switch......................................... D

Clogged Filter Switch, Fan Failure Switch and

Condensate Drain Pan Overflow Switch..................... E

Clogged Filter Switch, Discharge Air Sensing

Tube and Condensate Drain Pan Overflow Switch..... F

Fan Failure Switch, Discharge Air Sensing Tube and

Condensate Drain Pan Overflow Switch..................... G

Clogged Filter Switch, Fan Failure Switch, Discharge

Air Sensing and Condensate Drain Pan Overflow

Switch........................................................................ H
26
System Monitoring Controls

No Monitoring Controls................................................. 0

Demand Control Ventilation (CO2)7............................. A
27
Unit Hardware Enhancements

No Enhancements......................................................... 0

Stainless Steel Drain Pan.............................................. 1

Voyager Packaged Cooling with ReliaTel


Controls 12-25 Tons, R-410A
Zone Sensors / Thermostats
Table PC-22-A Zone Sensors for ReliaTel
Model Number

Description

Used With

BAYSENS036A
BAYSENS037A
baysens073A
BAYSENS074A
BAYSENS077A
BAYSENS106A
BAYSENS108A
BAYSENS110A


BAYSENS119A
BAYSENS135A
BAYSENS050A1
BAYMTPL110A

Wall-Mounted Humidity Sensor


Duct-Mounted Humidity Sensor
Room Sensor with Override Button
Room Sensor with Temperature Adjustment and Override
Remote Room Sensor
Single Setpoint Manual Changeover
Dual Setpoint Manual or Automatic Changeover
Dual Setpoint Manual or Automatic Changeover
with System Function Lights
Programmable Night Setback with System Function Lights
Digital Display Zone Sensor
Wireless Zone Sensor
Retrofit Wall Cover from Vertical to Horizontal

THD150-240 (with Reheat)


THD150-240 (with Reheat)
All Voyagers
All Voyagers
BAYSENS106A, 108A, 110A, 119A, BAYSTAT152
All Voyagers
All Voyagers
All Voyagers
All Voyagers
All Voyagers
All Voyagers
BAYSENS106,108,119

Table PC-22-B Thermostats Electromechanical


Model Number

Description

Used With

BAYSTAT150A
BAYSTAT152A
BAYSTAT155A
BAYSTAT170A

2H/2C Digital Display Programmable Thermostat


3H/2C Programmable Touchscreen Thermostat
3H/2C Digital Display Thermostat
Duct Mounted Return Air Sensor

All Voyagers
All Voyagers
All Voyagers
BAYSTAT152A

Packaged Cooling

1 Kit comes with everything required for installing and operation.

For additional Controls Information:


See ReliaTel and Micro Control features on PC-17 and PC-18.
For complete equipment / combination selections,
installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-22

Effective 1/1/13
22-8301-25

Voyager Packaged Cooling with ReliaTel


Controls 12-25 Tons Accessories
Table PC-23-A Field Installed Accessories
For complete list of of All Factory Installed Options refer to FIOPS section of this book.
Model Number
Description
Used With
BAYBCIR001A................ BACnet Communication Interface............................................... All Voyagers
BAYABRD0029.............. ReliaTel Options Module............................................................. All Voyagers
BAYCO2K002B0............ CO2 Sensor Wall Mounted............................................................. All Voyagers w/Economizers
BAYCO2K004B0............ CO2 Sensor Duct Mounted............................................................. All Voyagers w/Economizers
BAYCURB026B56........ Downflow Roof Curb (Can not be adapted for horizontal use)...... TSD150F
BAYCURB027B56........ Downflow Roof Curb (Can not be adapted for horizontal use)...... THD150F-300F, TSD180-300F
BAYDFPS005A89......... Clogged Filter Switch (MERV 7)..................................................... All Voyagers
BAYDFPS006A89......... Fan Failure Switch.......................................................................... All Voyagers
BAYDFPS013A............... Clogged Filter Switch (MERV 13)................................................... All Voyagers
BAYDMPR029C.............. 0-25% Manual Outside Air Damper................................................ All Voyagers
BAYDMPR057A.............. 0-50% Motorized Outside Air Damper............................................ TSD150F
BAYDMPR058A.............. 0-50% Motorized Outside Air Damper............................................ TSD151F-300F, TSD180F-300F
BAYECON089A9........... Downflow Economizer with Barometric Relief................................ TSD150F
BAYECON090A9........... Downflow Economizer with Barometric Relief................................ TSD151F-300F, TSD180F-300F
BAYECON091A.............. Horizontal Economizer .................................................................. TSH150F
BAYECON092A.............. Horizontal Economizer .................................................................. TSH151F-300F, TSF180F-300F
BAYENTH007A12 ........ Reference Enthalpy Kit................................................................... All BAYECON089-92A
BAYENTH008A13 ........ Comparative Enthalpy Kit............................................................... All BAYECON089-92A
BAYFRST003A7............ High Temperature Stat................................................................... All Voyagers
BAYGARD144A9........... Tool-less Hail Guard....................................................................... TS*150F
BAYGARD145A9........... Tool-less Hail Guard....................................................................... TH*150F, TS*210F, TS*240F, TS*300F
BAYGARD150A.............. Tool-less Hail Guard....................................................................... TH*180F, TH*210F, TH*240F, TH*300F
BAYHSDR005B4........... High Static Drive............................................................................ TS*150F, TH*150F, TH*180F
BAYHSDR010A4........... High Static Drive............................................................................ TH*210F, TH*240F, TS*300F
BAYHSDR011A4........... High Static Drive............................................................................ TS*210F, TS*240F, TH*300F
BAYHSDR016A.............. High Static Drive............................................................................ TS*180F
1 Kit contains all necessary parts to achieve desired level of Enthalpy Control.
2 Reference Enthalpy senses outside temperature/humidity and inside return/mixed air temperature/humidity.
3 Comparative Enthalpy senses outside temperature/humidity and inside return/mixed air temperature/humidity.
4 High static drive and oversized motors are mutually exclusive, Do Not Combine.
5 Clarksville manufacturing has a no return policy for this roof curb.
6 For downflow use only. Can not be adapted for horizontal units.
7 Must be used with either field or factory installed TCI (Trane Communications Interface).
8 BAYABRD002B is required when ordering field installed BAYDFPS005A or 006A, BAYTUBE008A or 009A and BAYLOAM023A or BAYVNOR002B.
9 Field or factory installed option.
0 Field installed accessory. Requires an economizer.

Packaged Cooling

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-23

Effective 1/1/13
22-8301-25

Voyager Packaged Cooling with ReliaTel


Controls 12-25 Tons Accessories
Table PC-24-A Field Installed Accessories
For complete list of of All Factory Installed Options refer to FIOPS section of this book.
Model Number
Description
Used With
BAYHSMT039B16........ 5HP Oversized Motor Kit (208-230/460V)..................................TS*150F
BAYHSMT040B16........ 5HP Oversized Motor Kit (575V)................................................TS*150F
BAYHSMT055B16........ 5HP Oversized Motor Kit (208-230/460V)..................................TS*180F
BAYHSMT042A16........ 7-1/2HP Oversized Motor Kit (575V)..........................................TS*210F, TH*210F, TS*240F, TH*240F
BAYHSMT072A16........ 7-1/2HP Oversized Motor Kit (575V)..........................................TS*180F, TH*180F
BAYHSMT098A16........ 7-1/2HP Oversized Motor Kit (208-230V)...................................TH*210F, TH*240F
BAYHSMT099A16........ 7-1/2HP Oversized Motor Kit (460V)..........................................TH*210F, TH*240F
BAYICSI004B78........... Trane Communications Interface (TCI).......................................All Voyagers
BAYLOAM023A6........... Evaporator Defrost Control Frostat.............................................TS*150F, TH*150F, TS*180F



TS*210F, TS*240F, TS*300F
BAYLOAM031A.............. Evaporator Defrost Control Frostat.............................................TH*180F, TH*210F, TH*240F, TH*300F
BAYLSDR004A2............ Low Static Drive.........................................................................TS*150F, TS*180F, TS*210F



TH*210F, TH*240F, TS*240F
BAYLSDR002A2............ Low Static Drive.........................................................................TH*150F, TH*180F, TH*300F
BAYLTCI003B8.............. LonTalk Communications Interface (LCI)..................................All Voyagers
BAYPWRX029A.............. Power Exhaust for all Voyagers 12-25 Ton 230V units.............BAYECON089-090A, TCD150-301
BAYPWRX030A.............. Power Exhaust for all Voyagers 12-25 Ton 460V units.............BAYECON089-090A, TCD150-301
BAYPWRX031A.............. Power Exhaust for all Voyagers 12-25 Ton 575V units.............BAYECON089-090A, TCD150-301
BAYSERV001A............... Selective Resistance Service Tester..........................................All Voyagers 12-25 Tons
BAYSTAT0233................ Remote Potentiometer...............................................................All Economizers and 0-50%



Motorized Air Dampers
BAYTUBE008A456...... Discharge Air Sensing Kit..........................................................All Voyagers 12-25 Ton Downflow
BAYTUBE009A456...... Discharge Air Sensing Kit..........................................................All Voyagers 12-25 Ton Horizontal
BAYQACB044A.............. Adapter Curb..............................................................................BAYCURB026A/B to BAYCURB027A/B
BAYVNOR002B5........... Ventilation Override Kit...............................................................Voyagers w/ReliaTel



Options Module

Packaged Cooling

1 High static drive and oversized motors are mutually exclusive, Do Not Combine.
2 Low static drive and oversized motors are mutually exclusive, Do Not Combine.
3 Cannot be used with Integrated Comfort Systems.
4 Used for true discharge air sensing in both heating and cooling models.
5 BAYABRD002B is required when ordering field installed BAYDFPS005A or 006A, BAYTUBE008A or 009A and BAYLOAM031A or BAYVNOR002B.
6 Field or factory installed option.
7 Interface allows a unit with ReliaTel Controls to communicate with Tracer 100, Tracker, VariTrac II, and is the preferred method of communication to Tracer
Summit.
8 With ReliaTel controlled units only.

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-24

Effective 1/1/13
22-8301-25

Voyager Packaged Cooling with ReliaTel


Controls 12-25 Tons Heaters
Table PC-25-A Downflow Supplementary Heaters:
Model Power
Number
Supply

AYDHTRK318A
AYDHTRK336A
AYDHTRK354A

208-230/3/60
208-230/3/60
208-230/3/60

kW Nominal
Rating
BTUH

13.5/18.0
27.0/36.0
40.5/54.0

AYDHTRL418A
460/3/60
AYDHTRK427A 460/3/60
AYDHTRK436A
460/3/60
AYDHTRK454A
460/3/60
AYDHTRL336A
AYDHTRL354A
AYDHTRK372A

208-230/3/60
208-230/3/60
208-230/3/60

AYDHTRL427A
AYDHTRL436A
AYDHTRL454A
AYDHTRK472A

460/3/60
460/3/60
460/3/60
460/3/60

18.0
27.0
36.0
54.0
27.0/36.0
40.5/54.0
54.0/72.0
27.0
36.0
54.0
72.0

No.
Stages
Used With

46,100/61,400
92,200/122,900
138,200/184,300

1
2
2

TSD150F-180F, THD150F-180F
TSD150F-180F, THD150F-180F
TSD150F-180F, THD150F-180F

61,400
92,150
122,900
184,300

1
2
2
2

TSD150F-180F, THD150F-180F
THD180F
TSD150F-180F, THD150F-180F
TSD150F-180F, THD150F-180F

92,200/122,900
138,200/184,300
184,300/245,700

2
2
2

TSD210F-300F, THD210-300F
TSD210F-300F, THD210-300F
TSD210F-300F, THD210-300F

92,150
122,900
184,300
245,700

2
2
2
2

THD210F, THD240-300F
TSD210F-300F, THD210-300F
TSD210F-300F, THD210-300F
TSD210F-300F, THD210-300F

Table PC-25-B Horizontal Supplementary Heaters:


Model Power
Number
Supply

AYHHTRN318A
AYHHTRP336A
AYHHTRP354A

208-230/3/60
208-230/3/60
208-230/3/60

AYHHTRN418A
AYHHTRP436A
AYHHTRP454A

460/3/60
460/3/60
460/3/60

AYHHTRN336A
AYHHTRN354A
AYHHTRN372A

AYHHTRN436A
AYHHTRN454A
AYHHTRN472A

208-230/3/60
208-230/3/60
208-230/3/60

AYHHTRM318A
AYHHTRM336A
AYHHTRM354A

208-230/3/60
208-230/3/60
208-230/3/60

AYHHTRM418A
AYHHTRM436A
AYHHTRM454A

460/3/60
460/3/60
460/3/60

kW Nominal
Rating
BTUH

13.5/18.0
27.0/36.0
40.5/54.0
18.0
36.0
54.0
27.0/36.0
40.5/54.0
54.0/72.0

460/3/60
460/3/60
460/3/60

36.0
54.0
72.0
13.5/18.0
27.0/36.0
40.5/54.0
18.0
36.0
54.0

No.
Stages
Used With

46,000/61,400
92,200/122,900
138,200/184,300

1
2
2

TSH150F, TSH180F
TSH150F, TSH180F
TSH150F, TSH180F

61,400
122,900
184,300

1
2
2

TSH150F, TSH180F
TSH150F, TSH180F
TSH150F, TSH180F

92,200/122,900
138,200/184,300
184,300/245,700

2
2
2

TSH210-300F, THH210-300F
TSH210-300F, THH210-300F
TSH210-300F, THH210-300F

122,900
184,300
245,700

2
2
2

TSH210-300F, THH210-300F
TSH210-300F, THH210-300F
TSH210-300F, THH210-300F

46,100/61,400
92,200/122,900
138,200/184,300

1
2
2

THH150F, THH180F
THH150F, THH180F
THH150F, THH180F

61,400
122,900
184,300

1
2
2

THH150F, THH180F
THH150F, THH180F
THH150F, THH180F

Note: Unit with heater is single circuit/single point.

Packaged Cooling

For complete equipment / combination selections,


installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-25

Effective 1/1/13
22-8301-25

Voyager Packaged Cooling with ReliaTel


Controls 12-25 Tons Heaters
Table PC-26-A Downflow Supplementary Heaters:
Model Power
Number
Supply

kW Nominal No.
Rating
BTUH
Stages
Used With

AYDHTRLW54A 575/3/60

54.0 184,300

TSD210-300F, THD210-300F

AYDHTRKW18A 575/3/60
AYDHTRKW54A 575/3/60
AYDHTRKW72A 575/3/60

18.0
54.0
72.0

61,400
184,300
245,700

1
2
2

TSD150-180F, THD150-180F
TSD150-180F, THD150-180F
TSD210-300F, THD210-300F

AYDHTRMW36A

36.0

122,900

TSD150-300F, THD150-300F

575/3/60

Table PC-26-B Horizontal Supplementary Heaters:


Model Power
Number
Supply

kW Nominal No.
Rating
BTUH
Stages
Used With

AYHHTRMW18A
AYHHTRMW36A
AYHHTRMW54A

575/3/60
575/3/60
575/3/60

18.0
36.0
54.0

61,400
122,900
184,300

1
2
2

THH150F, THH180F
TSH210F-300F, TSH150F-300F
THH150F, THH180F

AYHHTRNW18A
AYHHTRNW54A
AYHHTRNW72A
AYHHTRPW36A
AYHHTRPW54A

575/3/60
575/3/60
575/3/60
575/3/60
575/3/60

18.0
54.0
72.0
36.0
54.0

61,400
184,300
245,700
122,900
184,300

1
2
2
2
2

TSH150F, TSH180F
TSH210F-300F, THH210F-300F
TSH210F-300F, THH210F-300F
TSH150F, TSH180F
TSH150F, TSH180F

Packaged Cooling

Note: Unit with heater is single circuit/single point.

For additional Controls Information:


See ReliaTel and Micro Control features on PC-17 and PC-18.
For complete equipment / combination selections,
installation instructions and warranty information,
please refer to Product Data/Ratings and/or Installers
Guides and Limited Warranty Handbooks.

PC-26

Effective 1/1/13