Output Ratings
Generating Set Model P1000P1 P1100E1
380-415V,50Hz 1000.0 kVA 1100.0 kVA
800.0 kW 880.0 kW
220/127V, 60 Hz - -
- -
Ratings Definitions
Ratings at 0.8 power factor. www.FGWilson.com
Prime Power - Model P1000P1
These ratings are applicable for supplying continuous electrical
power (at variable load) in lieu of commercially purchased power.
There is no limitation to the annual hours of operation and this
model can supply 10% overload power for 1 hour in 12 hours.
Standby Power - Model P1100E1
These ratings are applicable for supplying continuous electrical
power (at variable load) in the event of a utility power failure. No
overload is permitted on these ratings. The alternator on this model
is peak continuous rated (as defined in ISO 8528-3).
Technical Data
Engine Make & Model: Perkins 4008TAG2A
Alternator Model: LL8124B
No. of Cylinders/Alignment: 8 / In Line
Displacement: litres (cu.in) 30.6 (1864.9)
Bore/Stroke: mm (in) 160.0 (6.3)/190.0 (7.5)
Compression Ratio: 13.6:1
Induction: Turbocharged Air To Air Charge Cooled
Frequency: 50 Hz 60 Hz
Engine Speed: 1500 RPM -
Gross Engine Power: kW (hp) 969.0 (1299.0) -
BMEP: kPa (psi) 2537.0 (367.9) -
Piston Speed: m/sec (ft/sec) 9.5 (31.2) -
Fuel Tank Capacity: litres (US gal) - -
Fuel Consump, P1000P1 l/hr (USg/hr) 215.4 (56.9) -
Fuel Consump, P1100E1 l/hr (USg/hr) 241.5 (63.8) -
Heat Rejected to
Exhaust System: kW (Btu/min) 807.0 (45893) -
Heat Rejected to
Water & Lube Oil: kW (Btu/min) 349.0 (19847) -
Heat Radiation to Room: kW (Btu/min) 151.0 (8587) -
Exhaust Gas Temperature: °C (°F) 465 (869) -
Radiator Cooling
Air Flow: m³/min (cfm) 1152.0 (40683) -
Combustion Air Flow: m³/min (cfm) 80.5 (2843) -
Exhaust Gas Flow: m³/min (cfm) 200.0 (7063) -
* Contact your local FG Wilson dealer for power ratings at specific site conditions.
Dimensions and Weights
Length: mm (in) Width: mm (in) Height: mm (in) Dry: kg (lb) Wet: kg (lb)
4790 (188.6) 2036 (80.2) 2235 (88.0) 7334 (16169) 7568 (16685)
Dry = With Lube Oil Wet = With Lube Oil and coolant
Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1/22.
P1000P1 / P1100E1
Generating set pictured may include optional accessories.
FG Wilson has manufacturing facilities in the following
locations:
Northern Ireland · Brazil · China · India · USA
With headquarters in Northern Ireland, FG Wilson operates through a Global
Dealer Network. To contact your local Sales Office please visit the FG Wilson
website at www.FGWilson.com
In line with our policy of continuous product development, we reserve the right to change specification without notice
P1000P1 / P1100E1/1PP/1207/GB