VF-nC1 Is A Compact, User Friendly Inverter Drive Suitable For Low Power Applications
VF-nC1 Is A Compact, User Friendly Inverter Drive Suitable For Low Power Applications
VF-nC1 is a Compact, user friendly Inverter drive suitable for low power applications.
Main Power terminals use a screw clamp design, encapsulated within the compact body that enables simple installation. High torque at low speed with Toshiba's new motor control software makes it easy to apply to a wide range of applications. VF-nC1 also meets major Global Standards and accepts a wide input power supply range.
Easy selections
VF-nC1 meets major global standards: UL, CSA, CE and C-tick High carrier frequency capability reduces audible motor noise. VF-nC1 can detect analog input (4-20mA) failure. Built in cumulative operation timer for planed maintenance. Model with Built in Class B EMC noise filter available. Main power terminal is located on the top and bottom enabling quick installation. Screw clamp design of the power terminals allows easy and secure connection. Side by side installation minimises installation space. Control circuit I/O logic (Sink/Source) is parameter selectable. Optional DIN rail mounting kit, up to 0.75kW, allows fixing free installation. RUN/STOP keys and potentiometer on front panel allows simple operation. New motor control software provides high starting torque at low speeds. Wizard function simplifies parameter setting. All models have PI control function for pump and fan applications. VF-nC1 has a serial communication port for network connection as standard.
Global Standard
Complies with major world standards (CE marking, UL, CSA, C-tick)
C-tickUnder application
Input voltage class 1-phase 100V 1-phase 200V 3-phase 200V 1-phase 200V
(European model)
0.1kW
0.2kW
0.4kW
0.75kW
1.5kW
2.2kW
TM
Standard specifications
Item Input voltage Applicable motor (kW) Voltage Class 1-phase 100V 1-phase 200V 3-phase 200V 1-phase 200V (European model) Capacity(kVA) Note1) Model Rating Specification 1-phase 100V/1-phase 200V/3-phase 200V 0.1 0.2 0.4 0.75 1.5 2.2 VFNC1/VFNC1S 1007P 1004P 1002P 1001P 2022P 2015P 2007P 2004P 2002P 2022P 2015P 2007P 2004P 2002P 2001P 2022PL 2015PL 2007PL 2004PL 2002PL 3.9 (4.1) 2.9 1.6 1.0 (0.9) 0.6 (0.5) 0.3 4.0 2.4 1.4 0.7 10.0 7.5 4.0 2.4 1.4 10.0 7.5 4.0 2.4 1.4 0.7 10.7 7.5 4.0 2.3 1.2 100V class: 1-phase 100V-115V-50/60Hz, 200V class: 1-phase 200V-240V-50/60Hz, 3-phase 200V-240V-50/60Hz Voltage +10%, -15%, frequency 5% Sinusoidal PWM control Adjustable within a range of 100 to 120% of the corrected supply voltage(200V) (Unadjustable to any voltage higher than the input voltage). 0.5 to 200Hz, default setting: 0.5 to 80Hz, maximum frequency: 30 to 200Hz. 150%-60 seconds Forward/reverse run, jog run, standby signal, preset-speed operation, reset, etc. / Switching between sink/source. Indoor, altitude: 1000M(Max.), not exposed to direct sunlight, corrosive gas, explosive gas or vibration (less than 5.9m/s2) (10 to 55Hz). -10-50C (Above 40C: Remove the protective seal from the top of VF-nC1) / 20 to 93% (free from condensation and vapor). Enclosed type IP20 / Self cooling Enclosed type IP20 / Forced air-cooled Enclosed type IP20 / Self cooling Enclosed type IP20 / Forced air-cooled Enclosed type IP20 / Self cooling Enclosed type IP20 / Forced air-cooled Enclosed type IP20 / Self cooling Enclosed type IP20 / Forced air-cooled
Type-Form VFNC1SVFNC1SVFNC1VFNC1S1-phase 100V 1-phase 200V 3-phase 200V 1-phase 200V (European model)
Note1) Capacity is calculated at 220V. (European model) Note2) In case of PWM carrier frequency : 4kHz or less.
Voltage-frequency Allowable fluctuation Control system Rated output voltage Output frequency range Overload current rating Input terminal functions Use environments Ambient temperature / Relative humidity 1-phase 100V Protective method / cooling method 1-phase 200V 3-phase 200V 1-phase 200V (European model)
External dimensions/weights
Voltage class Applicable motor capacity(kW)
0.1 0.2 0.4 0.75 0.2 0.4 0.75 1.5 2.2 0.1 0.2 0.4 0.75 1.5 2.2 0.2 0.4 0.75 1.5 2.2
Inverter type
VFNC1S-1001P VFNC1S-1002P VFNC1S-1004P VFNC1S-1007P VFNC1S-2002P VFNC1S-2004P VFNC1S-2007P VFNC1S-2015P VFNC1S-2022P VFNC1-2001P VFNC1-2002P VFNC1-2004P VFNC1-2007P VFNC1-2015P VFNC1-2022P VFNC1S-2002PL VFNC1S-2004PL VFNC1S-2007PL VFNC1S-2015PL VFNC1S-2022PL
1-phase 100V
1
EMI Filter FLC FLB FLA Main circuit
IM
Forward Reverse Preset speed 1 Preset speed 2 Common
Control circuit
1-phase 200V
External potentiometer(3-10k) or input voltage signal across 0-10V Current signal 420mA
P5
VF-nC1
Connector for common serial communications
S2 CC
VI/S3 2 3 4 CC
3-phase 200V
FM/OUT2 CC
Meter Frequency meter(Ammeter)
P15
RY
1European model has an EMI Filter inside. 2FM/OUT and VI/S3 terminals are switched by the parameter. 3VI terminal is switched for input terminal by the parameter. 4To use VI/S3 terminal as an input terminal, P15 and VI/S3 must be short-circuited with a resistor (recommended:4.7k-1/4W)
To users of our inverters : Our inverters are designed to control the speeds of three-phase induction motors for general industry.
Precautions
* Read the instruction manual before installing or operating the inverter unit and store it in a safe place for reference. * When using our inverters for equipment such as nuclear power control equipment, aviation and space flight control equipment, traffic equipment, and safety equipment, and there is a risk that any failure or malfunction of the inverter could directly endanger human life or cause injury, please contact our headquarters, branch, or office printed on the front and back covers of this catalogue. Such applications must be studied carefully. * When using our inverters for critical equipment, even though the inverters are manufactured under strict quality control always fit your equipment with safety devices to prevent serious accident or loss should the inverter fail (such as failure to issue an inverter trouble signal). * Do not use our inverters for any load other than three-phase induction motors. * None of Toshiba, its subsidiaries, affiliates or agents, shall be liable for any physical damages, including, without limitation, malfunction, anomaly, breakdown or any other problem that may occur to any apparatus in which the Toshiba inverter is incorporated or to any equipment that is used in combination with the Toshiba inverter. Nor shall Toshiba, its subsidiaries, affiliates or agents be liable for any compensatory damages resulting from such utilization, including compensation for special, indirect, incidental, consequential, punitive or exemplary damages, or for loss of profit, income or data, even if the user has been advised or apprised of the likelihood of the occurrence of such loss or damages.
For further information, please contact your nearest Toshiba Representative or International Operations-Producer Goods. The information in this brochure is subject to change without notice.
Industrial Equipment Department 1-1,Shibaura 1-chome, Minato-ku, Tokyo 105-8001,Japan Tel.: (03)3457-4880 Fax.: (03)5444-9268
03-1 (AB)6495
AB
Printed in Japan