Siprotec: Communication Module Profibus-Dp Bus Mapping

Data in The PROFIBUS-DP messages of the SIPROTEC device 7UT612 is described in this manual. The information in this manual is checked periodically, and necessary corrections will be included in future editions. We reserve the right to make technical improvements without notice.

Uploaded by

Futuro Inocente
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
335 views

Siprotec: Communication Module Profibus-Dp Bus Mapping

Data in The PROFIBUS-DP messages of the SIPROTEC device 7UT612 is described in this manual. The information in this manual is checked periodically, and necessary corrections will be included in future editions. We reserve the right to make technical improvements without notice.

Uploaded by

Futuro Inocente
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 46

Preface Table of contents Data in the PROFIBUS-DP messages

SIPROTEC Transformer differential protection 7UT612


Communication module PROFIBUS-DP Bus mapping

Standard mapping 3-1 Standard mapping 3-2 Index

1 2 3

Revision 2.0 Edition: May 2004 C53000-L1840-B010-03

Liability statement We have checked the contents of this manual against the hardware and software described. Exclusions and deviations cannot be ruled out; we accept no liability for lack of total agreement. The information in this manual is checked periodically, and necessary corrections will be included in future editions. We appreciate any suggested improvements. We reserve the right to make technical improvements without notice.

Copyright Copyright Siemens AG 2004. All rights reserved. Dissemination or reproduction of this document, or evaluation and communication of its contents, is not authorized except where expressly permitted. Violations are liable for damages. All rights reserved, particularly for the purposes of patent application or trademark registration. Registered trademarks SIPROTEC, SIMATIC, SIMATIC NET , SINAUT , SICAM and DIGSI are registered trademarks of Siemens AG. Other designations in this manual may be trademarks that if used by third parties for their own purposes may violate the rights of the owner.

Siemens Aktiengesellschaft C53000-L1840-B010-03

Preface
Purpose of this manual This manual describes the data in the PROFIBUS-DP messages of the SIPROTEC device 7UT612 and is devided into the following topics: Data in the PROFIBUS-DP messages Chapter 1, Standard mapping 3-1 Chapter 2, Standard mapping 3-2 Chapter 3. General details about the function, operation, assembly and commissioning of the SIPROTEC devices you find in the SIPROTEC4 System Manual, order no. E50417H1176C151. PROFIBUS-DP communication profile documentation The following additional manual informs you about the data types, bus specific parameters and hardware inteface of the PROFIBUS-DP slave modul of the SIPROTEC devices:
Manual SIPROTEC Communication module, PROFIBUS-DP - Communication profile Order number C53000-L1840-B001-03

PROFIBUS-DP specification

The PROFIBUS-DP specification and the structure of the PROFIBUS-DP messages are defined in the European Standard EN 50170:
!

PROFIBUS Specification Normative Parts of PROFIBUS-FMS, -DP, -PA According to the European Standard EN 50170, Volume 2 PROFIBUS Nutzerorganisation e.V.

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Preview

Validity

This manual is valid for the SIPROTEC device: 7UT612 (firmware version 4.0 or higher) with PROFIBUS-DP communication module version 02.00.05 or higher, PROFIBUS-DP communication module version 03.00.03 or higher at use of standard mapping 3-2.

For device parameterization have to be used: DIGSI 4.3 or higher, DIGSI 4.21 considering the preconditions explained in the manual SIPROTEC Communication module, PROFIBUS-DP - Communication profile (ref. to page i), PROFIBUS-DP standard mappings 3-1 to 3-n (n = device type dependent number of standard mappings). Additional Support For questions regarding SIPROTEC4 devices, please contact your Siemens representative. Individual course offerings may be found in our Training Catalog and questions can be directed to our Training Centre. Please contact your Siemens representative. Protection engineers, commissioning engineers, personnel concerned with adjustment, checking and service of selective protective equipment, automatic and control facilities and personnel of electrical facilities and power plants.

Training courses

Target audience

ii

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Preview

Warning!
During operation of electrical equipment, certain parts of these devices are under high voltage. Severe personal injury or significant equipment damage could result from improper behaviour. Only qualified personnel should work on this equipment or in the vicinity of this equipment. These personnel must be familiar with all warnings and service procedures described in this manual, as well as with safety regulations. Prerequisites to proper and safe operation of this product are proper transport, proper storage, setup, installation, operation, and maintenance of the product, as well as careful operation and servicing of the device within the scope of the warnings and instructions of this manual. In particular, the general facility and safety regulations for work with high-voltage equipment (e.g. ANSI, IEC, EN, or other national or international regulations) must be observed. Noncompliance may result in death, injury or significant equipment damage. QUALIFIED PERSONNEL Within the meaning of safety precautions of this manual and the instructions, qualified personnel are those persons who are qualified to set up, install, place into service, and operate this device, and who possess the following qualifications: Training and instruction (or other qualification) for switching, grounding, and designating devices and systems. Training or instruction in accordance with safety standards for care and use of certain safety equipment. First aid training. Typographic and graphical conventions The following text formats are used to identify concepts giving device information described by the text flow: Parameter names, or identifiers for configuration or function parameters that appear in the device display or on the screen of a PC (with DIGSI) are shown in mono-script (same point size) bold text. This also applies to header bars for selection menus. Parameter conditions, or possible settings of parameters that appear in the device display or on the screen of a PC (with DIGSI), are additionally shown in italic style. This also applies to selection items for selection menus. Annunciations, or identifiers for information produced by the device or required by other devices or from the switchgear is shown in mono-script (same point size) and placed into quotation marks. For diagrams in which the identifier type results from the representation itself, text conventions may differ from the above-mentioned.

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

iii

Preview

iv

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Revision index
Listing of the changes between the editions of this manual:

Modified chapters / pages

Edition 1.0

Reasons of modification First edition, Doc.-No.: C53000-L1840-B010-03 Jan 14th, 2002 Specifications for measurement scaling values corrected New: Description of standard mapping 3-2 with event recorder May 7th, 2004

Chap. 1.3.2 Chap. 1.4, 6

2.0

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Revision index

vi

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Table of contents
Preface................................................................................................................................................... i

Revision index ..................................................................................................................................... v

Data in the PROFIBUS-DP messages ............................................................................................. 1-1 1.1 1.2 1.3 1.3.1 1.3.2 1.3.3 1.4 1.5 1.5.1 Explanations ........................................................................................................................ 1-2 Messages in output direction: PROFIBUS-DP master to the SIPROTEC device ............................................................... 1-4 Messages in input direction: SIPROTEC device to the PROFIBUS-DP master ............................................................... 1-5 Annunciations ...................................................................................................................... 1-5 Measured values ................................................................................................................. 1-5 Metered measurands........................................................................................................... 1-6 Configuration data of the standard mappings...................................................................... 1-7 Notes to SIPROTEC objects ............................................................................................... 1-9 Changing the setting group ................................................................................................. 1-9

Standard mapping 3-1 ...................................................................................................................... 2-1 2.1 2.1.1 2.1.2 2.1.3 2.2 2.2.1 2.2.1.1 2.2.1.2 2.2.1.3 2.2.1.4 2.2.1.5 2.2.1.6 2.2.1.7 2.2.1.8 2.2.1.9 2.2.1.10 2.2.1.11 2.2.1.12 Message in output direction................................................................................................. 2-2 User-defined double commands.......................................................................................... 2-2 User-defined single commands or taggings ........................................................................ 2-2 Internal commands .............................................................................................................. 2-2 Message in input direction................................................................................................... 2-3 Annunciations ...................................................................................................................... 2-3 User-defined double-point indications ................................................................................. 2-3 User-defined single-point indications or taggings................................................................ 2-3 Setting group ....................................................................................................................... 2-3 Diagnosis............................................................................................................................. 2-4 Differential protection........................................................................................................... 2-4 Restricted ground fault protection........................................................................................ 2-4 Time overcurrent protection (general) ................................................................................. 2-5 Time overcurrent protection (50/51) .................................................................................... 2-5 Time overcurrent protection (50N/51N) ............................................................................... 2-5 Time overcurrent protection (50G/51G)............................................................................... 2-6 Thermal overload protection................................................................................................ 2-6 Unbalanced load protection................................................................................................. 2-6

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

vii

Table of contents

2.2.1.13 2.2.1.14 2.2.1.15 2.2.1.16 2.2.1.17 2.2.2 2.2.2.1 2.2.2.2 2.2.2.3 2.2.3

Circuit breaker failure protection.......................................................................................... 2-6 Time overcurrent protection (50 1Ph) .................................................................................. 2-7 Thermobox (7XV566) .......................................................................................................... 2-7 External trip commands ....................................................................................................... 2-7 Trip coil monitor ................................................................................................................... 2-7 Measured values ................................................................................................................. 2-8 Operational values............................................................................................................... 2-8 Thermal measurement......................................................................................................... 2-8 Thermobox (7XV556) .......................................................................................................... 2-9 Metered measurands........................................................................................................... 2-9

Standard mapping 3-2 ...................................................................................................................... 3-1 3.1 3.1.1 3.1.2 3.1.3 3.1.4 3.2 3.2.1 3.2.1.1 3.2.1.2 3.2.1.3 3.2.1.4 3.2.1.5 3.2.1.6 3.2.1.7 3.2.2 3.2.2.1 3.2.2.2 3.2.2.3 3.2.3 3.2.4 Message in output direction................................................................................................. 3-2 Event list .............................................................................................................................. 3-2 User-defined double commands.......................................................................................... 3-2 User-defined single commands or taggings ........................................................................ 3-2 Internal commands .............................................................................................................. 3-3 Message in input direction ................................................................................................... 3-4 Annunciations ...................................................................................................................... 3-4 User-defined double-point indications ................................................................................. 3-4 User-defined single-point indications or taggings ................................................................ 3-4 Setting group ....................................................................................................................... 3-4 Diagnosis ............................................................................................................................. 3-5 Alarms.................................................................................................................................. 3-5 Trip indications..................................................................................................................... 3-6 Thermobox (7XV566) .......................................................................................................... 3-7 Measured values ................................................................................................................. 3-8 Operational values............................................................................................................... 3-8 Thermal measurement......................................................................................................... 3-8 Thermobox (7XV556) .......................................................................................................... 3-9 Metered measurands........................................................................................................... 3-9 Event list ............................................................................................................................ 3-10

Glossary............................................................................................................................................. 4-1

Index................................................................................................................................................... 5-1

viii

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Data in the PROFIBUS-DP messages

1
1-2

This chapter delivers explanations to the data descriptions of the standard mapping as well as notes for evaluation of selected SIPROTEC objects and for the configuration of the standard mapping in the PROFIBUS-DP master.

1.1 1.2 1.3 1.4 1.5

Explanations

Messages in output direction: PROFIBUS-DP master to the SIPROTEC device 1-4 Messages in input direction: SIPROTEC device to the PROFIBUS-DP master 1-5 Configuration data of the standard mappings Notes to SIPROTEC objects 1-7 1-9

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

1-1

Data in the PROFIBUS-DP messages

1.1

Explanations

Note: The examples shown in this chapter 1.1 do not necessarily correspond to the real allocation of the objects in the bus mapping. Chapters 2 and 3 define the data area of the PROFIBUS-DP messages for data transfer between the PROFIBUS-DP slave of the SIPROTEC device 7UT612 and the PROFIBUS-DP master. The columns "Designation of the SIPROTEC objects" contain the texts of the SIPROTEC objects for "US English" device language. The listed SIPROTEC objects in the PROFIBUS-DP messages data area are sorted after byte offset, beginning with 0. Variables with data type greater than or equal to 1 byte The offset defines the start of the most significant byte in the message, e.g.:

Offset 12

Designation of the SIPROTEC objects IA S1=

Comments Operat. meas. current A side 1

Scaling Internal (32767 corresponds to...) object no. 32767 A 721

The measured value IA S1 is assigned to data byte 12 (most significant byte of the measured value) and data byte 13 (least significant byte of the measured value) in the PROFIBUS-DP message Bit variables (SP/SC, DP/DC) The offset indicates the byte which contains the bit value and the position of bit 0 of the bit variable, e.g. (input message):

Offset 0/0 0/1

Designation of the SIPROTEC objects Breaker ON/OFF OFF Circuit breaker Breaker ON/OFF ON Designation of the SIPROTEC objects Relay TRIP

Comments

Internal object no.

Offset 2/0

Comments 1 = Relay GENERAL TRIP command

Internal object no. 511

The checkback signal from the circuit breaker (as double-point indication) is located in data byte 0, bit position 20 (bit 0) and 21 (bit 1). The single-point indication Relay TRIP is located in byte 2, bit position 20.

1-2

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Data in the PROFIBUS-DP messages

Note: The definition of the data types (single-point indication, measured value etc.) are contained in the manual "SIPROTEC Communication module, PROFIBUS-DP - Communication profile" (ref. to page i).

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

1-3

Data in the PROFIBUS-DP messages

1.2

Messages in output direction: PROFIBUS-DP master to the SIPROTEC device


The messages in PROFIBUS-DP output direction (ref to chap. 2.1) allow: command outputs through the output relays of the SIPROTEC devices (external commands), manipulation of taggings (internal commands), transmission of measured values to the SIPROTEC device. Note: The allocation of the output relays to the switching devices and to the output channels is defined during parameterization of the SIPROTEC devices. Depending on the device composition there may be less than indicated output relays (and corresponding PROFIBUS-DP message positions) available in the SIPROTEC device.

1-4

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Data in the PROFIBUS-DP messages

1.3

Messages in input direction: SIPROTEC device to the PROFIBUS-DP master


The messages in PROFIBUS-DP input direction (ref. to chap. 2.2) allow: polling of switching devices' status and binary inputs, transmission of annunciations, measurands and meter values to the PROFIBUSDP master.

1.3.1

Annunciations

Note: The allocation of the input channels to the binary inputs is defined during parameterization of the devices. Depending on the device composition and the existing protection packages not all of the indicated binary inputs or protection annunciations (and corresponding PROFIBUS-DP message positions) may be available in the SIPROTEC device.

1.3.2

Measured values

Note: Depending on the device composition not all of the indicated analog inputs (and corresponding PROFIBUS-DP message positions) may be available in the SIPROTEC device. The given default scaling values for the measured values of the currents in the standard mappings apply to installations with the following nominal operating values: ILxS1 = SN / ( 3 * VNSide1) 100,01 ... 1000,00 A ILxS2 = SN / ( 3 * VNSide2) 1,01 ... 10,00 kA SN VNSide1 VNSide2 = Rated apparent power of the transformer (parameter address 0249) = Rated primary voltage Side 1 (parameter address 0240) = Rated primary voltage Side 2 (parameter address 0243)

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

1-5

Data in the PROFIBUS-DP messages

Note: Changes of the scaling of the measured values are possible in adaption to the concrete installation environment. You find information about this in the manual SIPROTEC Communication module, PROFIBUS-DP - Communication profile (ref. to page i). If other measured values than routed per default shall be transmitted via PROFIBUS-DP, then the positions of the not required measured values have to be released in the DIGSI Configuration matrix first (remove the cross in the associated column Destination system interface). For this the protection function of the SIPROTEC device in which the measured values currently routed are available must if necessary be activated. Example: The device 7UT612 shall be used as 1 phase busbar protection. To release the positions of the measured values routed per default for transformer protection select Protection Object = 3 phase Transformer first and remove the measured values from Destination system interface. After this the positions are available for new routing with device configuration Protection Object = 1 phase Busbar.

1.3.3

Metered measurands

Note: The scaling of the metered measurands at binary inputs (pulse counters) depends on the externally connected pulse generator. The type of update (cyclic, with or without deletion) and the update interval must be programmed for the metered measurands with the parameterization software DIGSI.

1-6

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Data in the PROFIBUS-DP messages

1.4

Configuration data of the standard mappings


There are two standard mappings (standard mapping 3-1 and standard mapping 3-2) available for the SIPROTEC device 7UT612.

Standard mapping 3-1

The standard mapping 3-1 contains: Output direction: 2 double commands 6 single commands Input direction: 4 double-point indications 88 single-point indications 20 measured values (integer) 2 metered measurands (unsigned long)

Standard mapping 3-2

The standard mapping 3-2 contains: Output direction: Handshake byte for event list via PROFIBUS-DP 2 double commands 6 single commands Input direction: 4 double-point indications 88 single-point indications 20 measured values (integer) 2 metered measurands (unsigned long) Handshake byte and three message blocks for event list via PROFIBUS-DP

Configuration data

Standard mapping 3-1: 1FH 1FH 1FH 1BH 21H (60 bytes input-, 2 bytes output direction) Standard mapping 3-2: 1FH 1FH 1FH 1BH DFH 23H (92 bytes input-, 4 bytes output direction)

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

1-7

Data in the PROFIBUS-DP messages

PROFIBUS-DP master

At the configuration of a PROFIBUS-DP slave of the SIPROTEC devices in the parameterization system of the PROFIBUS-DP masters are to select the following modules for the 7UT612 standard mapping and to allocate associated addresses in the I/O addressing range of the PROFIBUS-DP master: Standard mapping 3-1:
Module 0 1 2 3 4 Order number Input - 16 Bytes Input - 16 Bytes Input - 16 Bytes Input - 12 Bytes Output - 2Bytes Input address Adr_Ix Adr_Ix + 16 Adr_Ix + 32 Adr_Ix + 48 Adr_Ox Output address

Standard mapping 3-2:


Module 0 1 2 3 4 5 Order number Input - 16 Bytes Input - 16 Bytes Input - 16 Bytes Input - 12 Bytes Input - 16 Words, consistent Output - 4 Bytes Input address Adr_Ix Adr_Ix + 16 Adr_Ix + 32 Adr_Ix + 48 Adr_Ix + 60 Adr_Ox Output address

Addr_Ix and Addr_Ox indicate arbitrary (as a rule even) addresses in the I/O addressing range of the PROFIBUS-DP master. Addr_Ix (base address of the inputs) is identical with offset 0 of the PROFIBUS-DP message data of the SIPROTEC device in input direction (ref. to chap. 2.2 and 3.2). Addr_Ox (base address of the outputs) is identical with offset 0 of the PROFIBUS-DP message data of the SIPROTEC device in output direction (ref. to chap. 2.1 and 3.1). Note: There is dependently on the PROFIBUS-DP master in addition possibly the demand to put the base address of the inputs on a value divisible by four so that accesses on the metered measurands (unsigned long values, ref. to chap. 2.2.3 and 3.2.3) can be correctly carried out in the PROFIBUS-DP master.

1-8

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Data in the PROFIBUS-DP messages

1.5

Notes to SIPROTEC objects


This chapter contains notes for the use and evaluation of certain SIPROTEC objects. Note: The description of the standard mappings (ref. to chap. 2 and 3) contains the preallocation of the mapping files at delivery or at first assignment of a mapping in DIGSI to the SIPROTEC device. Changes of the allocation and the scaling of the measured values are possible in adaptation to the concrete installation enviroment. You find information about this in the manual "SIPROTEC Communication module, PROFIBUS-DP - Communication profile" (ref. to page i). If a mapping file is assigned to a SIPROTEC device and if the data size of the PROFIBUS-DP message of this SIPROTEC device is changed by choice of a new mapping file then assignments which are not available in the existing mapping file remain unassigned furthermore. These must afterwards be routed again on Source system interface or Destination system interface using the DIGSI Configuration matrix.

1.5.1

Changing the setting group


In order to change the setting group, the value "10" = ON must be transmitted for the corresponding pair of bits and afterwards be reset to "00" = "Quiescent status" (controlled by an impulse from the PROFIBUS-DP master). Switching ON one setting group automatically switches OFF the current active setting group. Transmission of the value "01" = OFF is insignificant for the change of the setting group and is refused by the device. A change of the setting group is only possible via PROFIBUS-DP if the parameter Change to Another Setting Group (parameter address = 302) has the value Protocol.

References

Standard mapping 3-1: ref. to chap. 2.1.3 Standard mapping 3-2: ref. to chap. 3.1.4

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

1-9

Data in the PROFIBUS-DP messages

1-10

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Standard mapping 3-1

2
2-2 2-3

This chapter describes the data in the PROFIBUS-DP messages between the PROFIBUS-DP master and the SIPROTEC device 7UT612.

2.1 2.2

Message in output direction Message in input direction

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

2-1

Standard mapping 3-1

2.1
2.1.1

Message in output direction


User-defined double commands
User-defined double commands with double-point indications as checkback indication can be routed on these position as Source system interface using the DIGSI Configuration matrix.

Offset 0/0 0/1 0/2 0/3

Designation of the SIPROTEC objects <user-defined> OFF not pre-allocated <user-defined> ON <user-defined> OFF not pre-allocated <user-defined> ON

Comments

Internal object no. -

2.1.2

User-defined single commands or taggings


User-defined single commands or taggings can be routed on these position as Source system interface using the DIGSI Configuration matrix.

Offset 0/4 0/5 0/6 0/7

Designation of the SIPROTEC objects <user-defined> OFF not pre-allocated <user-defined> ON <user-defined> OFF not pre-allocated <user-defined> ON

Comments

Internal object no. -

2.1.3

Internal commands
Ref. to chap. 1.5.1 for additional notes regarding Changing the setting group.

Offset 1/0 1/1 1/2 1/3 1/4 1/5 1/6 1/7

Designation of the SIPROTEC objects Setting Group A

Comments

Internal object no. -

Setting Group A Setting Group B

Activation of setting group A -

Setting Group B Setting Group C

Activation of setting group B -

Setting Group C Setting Group D

Activation of setting group C -

Setting Group D

Activation of setting group D

2-2

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Standard mapping 3-1

2.2
2.2.1
2.2.1.1

Message in input direction


Annunciations
User-defined double-point indications User-defined double-point indications (e.g. checkback indications of double commands) can be routed on these position as Destination system interface using the DIGSI Configuration matrix.

Offset 0/0 0/1 0/2 0/3 0/4 0/5 0/6 0/7

Designation of the SIPROTEC objects <user-defined> OFF not pre-allocated <user-defined> ON <user-defined> OFF not pre-allocated <user-defined> ON <user-defined> OFF not pre-allocated <user-defined> ON <user-defined> OFF not pre-allocated <user-defined> ON

Comments

Internal object no. -

2.2.1.2

User-defined single-point indications or taggings User-defined protection annunciations, single-point indications or taggings can be routed on these position as Destination system interface using the DIGSI Configuration matrix.

Offset 1/0 1/1 1/2 1/3

Designation of the SIPROTEC objects <user-defined> <user-defined> <user-defined> <user-defined> not pre-allocated not pre-allocated not pre-allocated not pre-allocated

Comments

Internal object no. -

2.2.1.3

Setting group
Internal object no. -

Offset 1/4 1/5 1/6 1/7

Designation of the SIPROTEC objects Group A Group B Group C Group D

Comments 1 = Setting group A is active 1 = Setting group B is active 1 = Setting group C is active 1 = Setting group D is active

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

2-3

Standard mapping 3-1

2.2.1.4

Diagnosis
Internal object no. 51 52 140 160 501 511 -

Offset 2/0 2/1 2/2 2/3 2/4 2/5 2/6

Designation of the SIPROTEC objects Device OK ProtActive Error Sum Alarm Alarm Sum Event Relay PICKUP Relay TRIP <user-defined>

Comments 1 = Update of the device replica in the SIPROTEC device completed after initial start or restart 1 = At least one protection function is active 1 = Error with a summary alarm ON 1 = Alarm summary event ON 1 = Relay PICKUP (group signal) 1 = Relay GENERAL TRIP command not pre-allocated 1 = Data in the PROFIBUS-DP message are valid. (This indication is created by the PROFIBUS-DP slave; not available in DIGSI and not relocatable.)

2/7

Data valid

2.2.1.5

Differential protection
Internal object no. 5631 5671 5672 5673 5674 5691 5692

Offset 3/0 3/1 3/2 3/3 3/4 3/5 3/6

Designation of the SIPROTEC objects 87 picked up 87 TRIP 87 TRIP Phase A 87 TRIP Phase B 87 TRIP Phase C 87-1 TRIP 87-2 TRIP

Comments 1 = 87 Differential protection picked up 1 = 87 TRIP 1 = 87 TRIP Phase A 1 = 87 TRIP Phase B 1 = 87 TRIP Phase C 1 = 87 TRIP by 87-1 1 = 87 TRIP by 87-2

2.2.1.6

Restricted ground fault protection


Internal object no. 5817 5821

Offset 3/7 4/0

Designation of the SIPROTEC objects 87G Picked Up 87G TRIP 1 = 87G Picked Up 1 = 87G TRIP

Comments

2-4

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Standard mapping 3-1

2.2.1.7
Offset 4/1 4/2

Time overcurrent protection (general)


Designation of the SIPROTEC objects 50(N,G) PU 50/51(N,G) TRIP Comments 1 = 50(N,G)/51(N,G) O/C PICKUP 1 = 50(N,G)/51(N,G) TRIP Internal object no. 1761 1791

2.2.1.8

Time overcurrent protection (50/51)


Internal object no. 1762 1763 1764 1805 1815 1820 1825 7565 7566 7567 1998

Offset 4/3 4/4 4/5 4/6 4/7 5/0 5/1 5/2 5/3 5/4 5/5

Designation of the SIPROTEC objects 50/51 Ph A PU 50/51 Ph B PU 50/51 Ph C PU 50-2 TRIP 50-2 TRIP 51 picked up 51 TRIP Ia InRush PU Ib InRush PU Ic InRush PU 50/51 Dset.ACT

Comments 1 = 50/51 Phase A picked up 1 = 50/51 Phase B picked up 1 = 50/51 Phase C picked up 1 = 50-2 TRIP 1 = 50-2 TRIP 1 = 51 picked up 1 = 51 TRIP 1 = Phase A InRush picked up 1 = Phase B InRush picked up 1 = Phase C InRush picked up 1 = Dynamic settings 50/51 are ACTIVE

2.2.1.9

Time overcurrent protection (50N/51N)


Internal object no. 1766 1903 1906 1907 1909 7568 1999 -

Offset 5/6 5/7 6/0 6/1 6/2 6/3 6/4 6/5

Designation of the SIPROTEC objects 50N/51NPickedup 50N-2 TRIP 50N-1 TRIP 51N picked up 51N TRIP 50/51N InRushPU 50/51N Dset.ACT <user-defined>

Comments 1 = 50N/51N picked up 1 = 50N-2 TRIP 1 = 50N-1 TRIP 1 = 51N picked up 1 = 51N TRIP 1 = 50/51N InRush picked up 1 = Dynamic settings 50N/51N are ACTIVE not pre-allocated

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

2-5

Standard mapping 3-1

2.2.1.10 Time overcurrent protection (50G/51G)


Internal object no. 1765 1833 1836 1837 1839 7564 2000 -

Offset 6/6 6/7 7/0 7/1 7/2 7/3 7/4 7/5

Designation of the SIPROTEC objects 50G/51GPickedup 50G-2 TRIP 50G-1 TRIP 51G picked up 51G TRIP Gnd InRush PU 50/51G Dset.ACT <user-defined>

Comments 1 = 50G/51G picked up 1 = 50G-2 TRIP 1 = 50G-1 TRIP 1 = 51G picked up 1 = 51G TRIP 1 = Ground InRush picked up 1 = Dynamic settings 50G/51G are ACTIVE not pre-allocated

2.2.1.11 Thermal overload protection


Internal object no. 1515 1516 1521 1541 1542 1543 1544

Offset 7/6 7/7 8/0 8/1 8/2 8/3 8/4

Designation of the SIPROTEC objects 49 O/L I Alarm 49 O/L Alarm 49 Th O/L TRIP 49 ht. spot Al. 49 ht.spot TRIP 49 al.rate Al. 49 ag.rt. TRIP

Comments 1 = 49 Overload Current Alarm (I alarm) 1 = 49 Thermal Overload Alarm 1 = 49 Thermal Overload TRIP 1 = 49 Thermal Overload hot spot Th. Alarm 1 = 49 Thermal Overload hot spot Th. TRIP 1 = 49 Thermal Overload aging rate Alarm 1 = 49 Thermal Overload aging rate TRIP

2.2.1.12 Unbalanced load protection


Internal object no. 5159 5165 5166 5170

Offset 8/5 8/6 8/7 9/0

Designation of the SIPROTEC objects 46-2 picked up 46-1 picked up 46-TOC pickedup 46 TRIP 1 = 46-2 picked up 1 = 46-1 picked up

Comments

1 = 46-TOC pickedup 1 = 46 TRIP

2.2.1.13 Circuit breaker failure protection


Internal object no. 1456 1457 1471

Offset 9/1 9/2 9/3

Designation of the SIPROTEC objects 50BF int Pickup 50BF ext Pickup 50BF TRIP

Comments 1 = 50BF (internal) PICKUP 1 = 50BF (external) PICKUP 1 = 50BF TRIP

2-6

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Standard mapping 3-1

2.2.1.14 Time overcurrent protection (50 1Ph)


Internal object no. 5971 5975 5979

Offset 9/4 9/5 9/6

Designation of the SIPROTEC objects 50 1Ph Pickup 50 1Ph-1 TRIP 50 1Ph-2 TRIP

Comments 1 = 50 1Ph Picked up 1 = 50 1Ph-1 TRIP 1 = 50 1Ph-2 TRIP

2.2.1.15 Thermobox (7XV566)


Internal object no. 14101 14112 14113 14122 14123 14132 14133 14142 14143 14152 14153 14162 14163

Offset 9/7 10 / 0 10 / 1 10 / 2 10 / 3 10 / 4 10 / 5 10 / 6 10 / 7 11 / 0 11 / 1 11 / 2 11 / 3

Designation of the SIPROTEC objects Fail: RTD RTD 1 St.1 p.up RTD 1 St.2 p.up RTD 2 St.1 p.up RTD 2 St.2 p.up RTD 3 St.1 p.up RTD 3 St.2 p.up RTD 4 St.1 p.up RTD 4 St.2 p.up RTD 5 St.1 p.up RTD 5 St.2 p.up RTD 6 St.1 p.up RTD 6 St.2 p.up

Comments 1 = Fail: RTD (broken wire/shorted) 1 = RTD 1 Temperature stage 1 picked up 1 = RTD 1 Temperature stage 2 picked up 1 = RTD 2 Temperature stage 1 picked up 1 = RTD 2 Temperature stage 2 picked up 1 = RTD 3 Temperature stage 1 picked up 1 = RTD 3 Temperature stage 2 picked up 1 = RTD 4 Temperature stage 1 picked up 1 = RTD 4 Temperature stage 2 picked up 1 = RTD 5 Temperature stage 1 picked up 1 = RTD 5 Temperature stage 2 picked up 1 = RTD 6 Temperature stage 1 picked up 1 = RTD 6 Temperature stage 2 picked up

2.2.1.16 External trip commands


Internal object no. 4537 4557

Offset 11 / 4 11 / 5

Designation of the SIPROTEC objects Ext 1 Gen. TRIP Ext 2 Gen. TRIP

Comments 1 = External trip 1: General TRIP 1 = External trip 2: General TRIP

2.2.1.17 Trip coil monitor


Internal object no. 6865 -

Offset 11 / 6 11 / 7

Designation of the SIPROTEC objects FAIL: Trip cir. <user-defined>

Comments 1 = 74TC Failure Trip Circuit not pre-allocated

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

2-7

Standard mapping 3-1

2.2.2

Measured values
Ref. to chap. 1.3.2 for notes regarding scaling of measured values.

2.2.2.1

Operational values
Designation of the SIPROTEC objects IA S1 = IB S1 = IC S1 = IA S2 = IB S2 = IC S2 = Freq = Scaling Internal (32767 corresponds to ...) object no. 32767 A 32767 A 32767 A 327.67 kA 327.67 kA 327.67 kA 327.67 Hz 721 722 723 724 725 726 644

Offset 12 14 16 18 20 22 24

Comments Current A side 1 Current B side 1 Current C side 1 Current A side 2 Current B side 2 Current C side 2 Frequency

2.2.2.2

Thermal measurement
Designation of the SIPROTEC objects Scaling Internal (32767 corresponds to ...) object no. 327.67 % 3276.7 C/F * 3276.7 C/F * 3276.7 C/F * 327.67 (dimensionless) 327.67 % 327.67 % 801 1060 1061 1062 1063 1066 1067

Offset 26 28 30 32 34 36 38

Comments Temperat. rise for warning and trip Hot spot temperature of leg A Hot spot temperature of leg B Hot spot temperature of leg C Aging Rate Load Reserve to Stage-1 level Load Reserve to Stage-2 level

/ trip = leg A = leg B = leg C =


Ag.Rate = Res-1 = Res-2 =

* ref. to parameter Temperature unit (parameter address = 0276)

2-8

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Standard mapping 3-1

2.2.2.3

Thermobox (7XV556)
Designation of the SIPROTEC objects Scaling Internal (32767 corresponds to ...) object no. 3276.7 C/F * 3276.7 C/F * 3276.7 C/F * 3276.7 C/F * 3276.7 C/F * 3276.7 C/F * 1068 1069 1070 1071 1072 1073

Offset 40 42 44 46 48 50

Comments Temperature of RTD1 Temperature of RTD1 Temperature of RTD1 Temperature of RTD1 Temperature of RTD1 Temperature of RTD1

RTD 1 = RTD 2 = RTD 3 = RTD 4 = RTD 5 = RTD 6 =

* ref. to parameter Temperature unit (parameter address = 0276)

2.2.3

Metered measurands
Ref. to chap. 1.3.3 for notes regarding metered measurands.

Offset 52 56

Designation of the SIPROTEC objects <user-defineed> <user-defineed>

Comments not pre-allocated not pre-allocated

(2

31-1

Scaling Internal corresponds to ...) object no. -

231-1 impulses 231-1 impulses

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

2-9

Standard mapping 3-1

2-10

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Standard mapping 3-2

3
3-2 3-4

This chapter describes the data in the PROFIBUS-DP messages between the PROFIBUS-DP master and the SIPROTEC device 7UT612.

3.1 3.2

Message in output direction Message in input direction

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

3-1

Standard mapping 3-2

3.1
3.1.1

Message in output direction


Event list
Information regarding the handshake bytes as well as the retrieval methods of the event list via PROFIBUS-DP can be found in the manual SIPROTEC Communication module, PROFIBUS-DP - Communication profile.

Offset 0 1 Control_O SPARE

Designation

Comments Handshake byte for event list via PROFIBUS-DP reserved for future use (the value at this position is ignored)

Internal object no. -

3.1.2

User-defined double commands


User-defined double commands with double-point indications as checkback indication can be routed on these position as Source system interface using the DIGSI Configuration matrix.

Offset 2/0 2/1 2/2 2/3

Designation of the SIPROTEC objects <user-defined> OFF not pre-allocated <user-defined> ON <user-defined> OFF not pre-allocated <user-defined> ON

Comments

Internal object no. -

3.1.3

User-defined single commands or taggings


User-defined single commands or taggings can be routed on these position as Source system interface using the DIGSI Configuration matrix.

Offset 2/4 2/5 2/6 2/7

Designation of the SIPROTEC objects <user-defined> OFF not pre-allocated <user-defined> ON <user-defined> OFF not pre-allocated <user-defined> ON

Comments

Internal object no. -

3-2

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Standard mapping 3-2

3.1.4

Internal commands
Ref. to chap. 1.5.1 for additional notes regarding Changing the setting group.

Offset 3/0 3/1 3/2 3/3 3/4 3/5 3/6 3/7

Designation of the SIPROTEC objects Setting Group A

Comments

Internal object no. -

Setting Group A Setting Group B

Activation of setting group A -

Setting Group B Setting Group C

Activation of setting group B -

Setting Group C Setting Group D

Activation of setting group C -

Setting Group D

Activation of setting group D

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

3-3

Standard mapping 3-2

3.2
3.2.1
3.2.1.1

Message in input direction


Annunciations
User-defined double-point indications User-defined double-point indications (e.g. checkback indications of double commands) can be routed on these position as Destination system interface using the DIGSI Configuration matrix.

Offset 0/0 0/1 0/2 0/3 0/4 0/5 0/6 0/7

Designation of the SIPROTEC objects <user-defined> OFF not pre-allocated <user-defined> ON <user-defined> OFF not pre-allocated <user-defined> ON <user-defined> OFF not pre-allocated <user-defined> ON <user-defined> OFF not pre-allocated <user-defined> ON

Comments

Internal object no. -

3.2.1.2

User-defined single-point indications or taggings User-defined protection annunciations, single-point indications or taggings can be routed on these position as Destination system interface using the DIGSI Configuration matrix.

Offset 1/0 1/1 1/2 1/3

Designation of the SIPROTEC objects <user-defined> <user-defined> <user-defined> <user-defined> not pre-allocated not pre-allocated not pre-allocated not pre-allocated

Comments

Internal object no. -

3.2.1.3

Setting group
Internal object no. -

Offset 1/4 1/5 1/6 1/7

Designation of the SIPROTEC objects Group A Group B Group C Group D

Comments 1 = Setting group A is active 1 = Setting group B is active 1 = Setting group C is active 1 = Setting group D is active

3-4

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Standard mapping 3-2

3.2.1.4

Diagnosis
Internal object no. 51 52 70 140 160 501 511

Offset 2/0 2/1 2/2 2/3 2/4 2/5 2/6

Designation of the SIPROTEC objects Device OK ProtActive Settings Calc. Error Sum Alarm Alarm Sum Event Relay PICKUP Relay TRIP

Comments 1 = Update of the device replica in the SIPROTEC device completed after initial start or restart 1 = At least one protection function is active 1 = Settings calculation is running 1 = Error with a summary alarm ON 1 = Alarm summary event ON 1 = Relay PICKUP (group signal) 1 = Relay GENERAL TRIP command 1 = Data in the PROFIBUS-DP message are valid. (This indication is created by the PROFIBUS-DP slave; not available in DIGSI and not relocatable.)

2/7

Data valid

3.2.1.5

Alarms
Internal object no. 5631 5817 1761 1762 1763 1764 1820 7565 7566 7567 1766 1907 7568 1765 1837 7564 5971 1515 1516

Offset 3/0 3/1 3/2 3/3 3/4 3/5 3/6 3/7 4/0 4/1 4/2 4/3 4/4 4/5 4/6 4/7 5/0 5/1 5/2

Designation of the SIPROTEC objects 87 picked up 87G Picked Up 50(N,G) PU 50/51 Ph A PU 50/51 Ph B PU 50/51 Ph C PU 51 picked up Ia InRush PU Ib InRush PU Ic InRush PU 50N/51NPickedup 51N picked up 50/51N InRushPU 50G/51GPickedup 51G picked up Gnd InRush PU 50 1Ph Pickup 49 O/L I Alarm 49 O/L Alarm

Comments 1 = 87 Differential protection picked up 1 = 87G Picked Up 1 = 50(N,G)/51(N,G) O/C PICKUP 1 = 50/51 Phase A picked up 1 = 50/51 Phase B picked up 1 = 50/51 Phase C picked up 1 = 51 picked up 1 = Phase A InRush picked up 1 = Phase B InRush picked up 1 = Phase C InRush picked up 1 = 50N/51N picked up 1 = 51N picked up 1 = 50/51N InRush picked up 1 = 50G/51G picked up 1 = 51G picked up 1 = Ground InRush picked up 1 = 50 1Ph Picked up 1 = 49 Overload Current Alarm (I alarm) 1 = 49 Thermal Overload Alarm

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

3-5

Standard mapping 3-2

Offset 5/3 5/4 5/5 5/6 5/7 6/0 6/1 6/2 6/3 6/4

Designation of the SIPROTEC objects 49 ht. spot Al. 49 al.rate Al. 46-2 picked up 46-1 picked up 46-TOC pickedup 50BF int Pickup 50BF ext Pickup <user-defined> <user-defined> <user-defined>

Comments 1 = 49 Thermal Overload hot spot Th. Alarm 1 = 49 Thermal Overload aging rate Alarm 1 = 46-2 picked up 1 = 46-1 picked up 1 = 46-TOC pickedup 1 = 50BF (internal) PICKUP 1 = 50BF (external) PICKUP not pre-allocated not pre-allocated not pre-allocated

Internal object no. 1541 1543 5159 5165 5166 1456 1457 -

3.2.1.6

Trip indications
Internal object no. 5671 5672 5673 5674 5691 5692 5821 1791 1805 1815 1825 1903 1906 1909 1833 1836 1839 5975 5979 1521 1542 1544 5170

Offset 6/5 6/6 6/7 7/0 7/1 7/2 7/3 7/4 7/5 7/6 7/7 8/0 8/1 8/2 8/3 8/4 8/5 8/6 8/7 9/0 9/1 9/2 9/3

Designation of the SIPROTEC objects 87 TRIP 87 TRIP Phase A 87 TRIP Phase B 87 TRIP Phase C 87-1 TRIP 87-2 TRIP 87G TRIP 50/51(N,G) TRIP 50-2 TRIP 50-2 TRIP 51 TRIP 50N-2 TRIP 50N-1 TRIP 51N TRIP 50G-2 TRIP 50G-1 TRIP 51G TRIP 50 1Ph-1 TRIP 50 1Ph-2 TRIP 49 Th O/L TRIP 49 ht.spot TRIP 49 ag.rt. TRIP 46 TRIP 1 = 87 TRIP

Comments

1 = 87 TRIP Phase A 1 = 87 TRIP Phase B 1 = 87 TRIP Phase C 1 = 87 TRIP by 87-1 1 = 87 TRIP by 87-2 1 = 87G TRIP 1 = 50(N,G)/51(N,G) TRIP 1 = 50-2 TRIP 1 = 50-2 TRIP 1 = 51 TRIP 1 = 50N-2 TRIP 1 = 50N-1 TRIP 1 = 51N TRIP 1 = 50G-2 TRIP 1 = 50G-1 TRIP 1 = 51G TRIP 1 = 50 1Ph-1 TRIP 1 = 50 1Ph-2 TRIP 1 = 49 Thermal Overload TRIP 1 = 49 Thermal Overload hot spot Th. TRIP 1 = 49 Thermal Overload aging rate TRIP 1 = 46 TRIP

3-6

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Standard mapping 3-2

Offset 9/4 9/5 9/6 9/7 10 / 0 10 / 1 10 / 2

Designation of the SIPROTEC objects 50BF TRIP Ext 1 Gen. TRIP Ext 2 Gen. TRIP FAIL: Trip cir. <user-defined> <user-defined> <user-defined> 1 = 50BF TRIP

Comments

Internal object no. 1471 4537 4557 6865 -

1 = External trip 1: General TRIP 1 = External trip 2: General TRIP 1 = 74TC Failure Trip Circuit not pre-allocated not pre-allocated not pre-allocated

3.2.1.7

Thermobox (7XV566)
Internal object no. 14112 14122 14132 14142 14152 14162 14101 14113 14123 14133 14143 14153 14163

Offset 10 / 3 10 / 4 10 / 5 10 / 6 10 / 7 11 / 0 11 / 1 11 / 2 11 / 3 11 / 4 11 / 5 11 / 6 11 / 7

Designation of the SIPROTEC objects RTD 1 St.1 p.up RTD 2 St.1 p.up RTD 3 St.1 p.up RTD 4 St.1 p.up RTD 5 St.1 p.up RTD 6 St.1 p.up Fail: RTD RTD 1 St.2 p.up RTD 2 St.2 p.up RTD 3 St.2 p.up RTD 4 St.2 p.up RTD 5 St.2 p.up RTD 6 St.2 p.up

Comments 1 = RTD 1 Temperature stage 1 picked up 1 = RTD 2 Temperature stage 1 picked up 1 = RTD 3 Temperature stage 1 picked up 1 = RTD 4 Temperature stage 1 picked up 1 = RTD 5 Temperature stage 1 picked up 1 = RTD 6 Temperature stage 1 picked up 1 = Fail: RTD (broken wire/shorted) 1 = RTD 1 Temperature stage 2 picked up 1 = RTD 2 Temperature stage 2 picked up 1 = RTD 3 Temperature stage 2 picked up 1 = RTD 4 Temperature stage 2 picked up 1 = RTD 5 Temperature stage 2 picked up 1 = RTD 6 Temperature stage 2 picked up

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

3-7

Standard mapping 3-2

3.2.2

Measured values
Ref. to chap. 1.3.2 for notes regarding scaling of measured values.

3.2.2.1

Operational values
Designation of the SIPROTEC objects IA S1 = IB S1 = IC S1 = IA S2 = IB S2 = IC S2 = Freq = Scaling Internal (32767 corresponds to ...) object no. 32767 A 32767 A 32767 A 327.67 kA 327.67 kA 327.67 kA 327.67 Hz 721 722 723 724 725 726 644

Offset 12 14 16 18 20 22 24

Comments Current A side 1 Current B side 1 Current C side 1 Current A side 2 Current B side 2 Current C side 2 Frequency

3.2.2.2

Thermal measurement
Designation of the SIPROTEC objects Scaling Internal (32767 corresponds to ...) object no. 327.67 % 3276.7 C/F * 3276.7 C/F * 3276.7 C/F * 327.67 (dimensionless) 327.67 % 327.67 % 801 1060 1061 1062 1063 1066 1067

Offset 26 28 30 32 34 36 38

Comments Temperat. rise for warning and trip Hot spot temperature of leg A Hot spot temperature of leg B Hot spot temperature of leg C Aging Rate Load Reserve to Stage-1 level Load Reserve to Stage-2 level

/ trip = leg A = leg B = leg C =


Ag.Rate = Res-1 = Res-2 =

* ref. to parameter Temperature unit (parameter address = 0276)

3-8

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Standard mapping 3-2

3.2.2.3

Thermobox (7XV556)
Designation of the SIPROTEC objects Scaling Internal (32767 corresponds to ...) object no. 3276.7 C/F * 3276.7 C/F * 3276.7 C/F * 3276.7 C/F * 3276.7 C/F * 3276.7 C/F * 1068 1069 1070 1071 1072 1073

Offset 40 42 44 46 48 50

Comments Temperature of RTD1 Temperature of RTD1 Temperature of RTD1 Temperature of RTD1 Temperature of RTD1 Temperature of RTD1

RTD 1 = RTD 2 = RTD 3 = RTD 4 = RTD 5 = RTD 6 =

* ref. to parameter Temperature unit (parameter address = 0276)

3.2.3

Metered measurands
Ref. to chap. 1.3.3 for notes regarding metered measurands.

Offset 52 56

Designation of the SIPROTEC objects <user-defineed> <user-defineed>

Comments not pre-allocated not pre-allocated

(2

31-1

Scaling Internal corresponds to ...) object no. -

231-1 impulses 231-1 impulses

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

3-9

Standard mapping 3-2

3.2.4

Event list
Information regarding the handshake bytes as well as the retrieval methods of the event list via PROFIBUS-DP can be found in the manual SIPROTEC Communication module, PROFIBUS-DP - Communication profile.

Offset 60 61 62 63 64 71 72 73 74 81 82 83 84 91

Designation of the SIPROTEC objects Control_I SPARE

Comments Handshake byte for event list via PROFIBUS-DP reserved for future use (the value 0 is transmitted at this position) Identification #1 Value #1

Internal object no. -

Message block #1 Time stamp #1 Identification #2 Value #2 Message block #2 Time stamp #2 Identification #3 Value #3 Message block #3 Time stamp #3

3-10

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Glossary
CFC DC DDB file / GSD file Continuous Function Chart Double command The DDB file contains the Device Data Base (technical characteristics) of the PROFIBUS-DP communication module (PROFIBUS-DP slave). This file is required for configuration of the PROFIBUS-DP master and is supplied together with DIGSI. DIGSI DP Input data / Input direction Octet OLM Output data / Output direction PNO PROFIBUS-DP PSE Parameterization system / parameterization software for SIPROTEC devices Double-point indication Data from the PROFIBUS-DP slave to the PROFIBUS-DP master.

Term from EN 50170, one octet corresponds to 8 bits. Optical Link Module Data from the PROFIBUS-DP master to the PROFIBUS-DP slave.

PROFIBUS Nutzerorganisation (PROFIBUS International Organization) PROFIBUS - Decentralized Peripherals PROFIBUS interface module with (electrical) isolated RS485 interface for the SIPROTEC devices from Siemens. PROFIBUS interface module with fibre-optical interface for the SIPROTEC devices from Siemens. Single command Single-point indication

PSO

SC SP

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

4-1

Glossary

4-2

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Index
Numerics
46 ...............................................................2-6, 49 ...............................................................2-6, 50 1Ph ........................................................2-7, 50/51 ..........................................................2-5, 50BF ...........................................................2-6, 50G/51G .....................................................2-6, 50N/51N .....................................................2-5, 74TC ...........................................................2-7, 87 ...............................................................2-4, 87G .............................................................2-4,

M
3-6 3-6 3-6 3-6 3-7 3-6 3-6 3-7 3-6 3-6
Measured values ........................................2-8, 3-8 Input direction .............................................. 1-5 Operational values ...............................2-8, 3-8 Thermal measurement .........................2-8, 3-8 Thermobox ...........................................2-9, 3-9 Metered measurands ......................... 1-6, 2-9, 3-9

P
PROFIBUS-DP Configuration data ....................................... 1-7 Configuration in the master system ............ 1-8 Event list .................................................... 3-10 Message in input direction ...................2-3, 3-4 Message in output direction .................2-2, 3-2

A
Annunciations ..................................... 1-5, 2-3, 3-4

C
Changing the setting group ................................1-9 Circuit breaker failure protection ................2-6, 3-7 Configuration data ..............................................1-7

Q
Qualified personnel (definition) ........................P-iii

R D
Differential protection .........................................2-4 Differentialschutz ................................................2-4 Double commands .....................................2-2, 3-2 Double-point indications .............................2-3, 3-4 Restricted ground fault protection ..................... 2-4

S
Single commands .......................................2-2, 3-2 Single-point indications ..............................2-3, 3-4

E
Event list Handshake byte in input direction .............3-10 Handshake byte in output direction .............3-2 Message blocks .........................................3-10 External trip commands .....................................2-7

T
Target audience ................................................P-ii Thermal measurement ...............................2-8, 3-8 Thermal overload protection ............................. 2-6 Thermobox Indications ............................................2-7, 3-7 Measured values ..................................2-9, 3-9 Time overcurrent protection .......................2-5, 2-7

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

5-1

Index

Trip coil monitor ................................................. 2-7 Typographic conventions ................................ P-iii

V
Validity of the manual ....................................... P-ii

U
Unbalanced load protection ............................... 2-6

5-2

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Corrections To Siemens AG Dept. PTD PA D DM D13623 Berlin Germany Dear reader, printing errors can never be entirely eliminated: therefore, should you come across any when reading this manual, kindly enter them in this form together with any comments or suggestions for improvement that you may have. Corrections/Suggestions Address: Company/Dept.: From Name:

Phone no.:

Fax no.:

SIPROTEC PROFIBUS-DP - Bus mapping 7UT612 C53000-L1840-B010-03

Subject to technical alteration

Copying of this document and giving it to others and the use or communication of the contents thereof, are forbidden without express authority. Offenders are liable to the payment of damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design. Order-no.: C53000-L1840-B010-03

Siemens Aktiengesellschaft