BAT-12V17AH
12V17AH/20HR
Small-Size
Small Size VRLA batteries enjoy excellent discharge performance, and they have low self-discharge and large-current resistance
capacity. Small-size batteries are capable for a wide range of applications. Their designed service life is 3-5 years, and we provide 12-month quality warranty for them. Our batteries can meet Standard Terminal Dimensions with many demanding technical and quality requirements form our customers.
Application
167(6.57)
Emergency lighting Security and burglar alarm systems Electric toys and power tools Telephone and telecommunication equipment Computer UPS Medical equipments and instruments
181(7.13)
77(3.03)
General Features
Sealed and maintenance free operation Not restricted from air transport-complies with IATA/ICAO Special Provision A67. UL-recognized components Safety valve installation for explosion proof Excellent deep discharge recovery performance Low self-discharge ratio Long service life, float or cycle-use applications
Battery Construction
Component Positive plate Lead dioxide Negative plate Lead Container Cover
Safety valve Rubber
Terminal
Separator AGM glass
Electrolyte Sulfuric acid
Material
ABS
ABS
Copper
Page 1 of 3
BAT-12V17AH
General Specifications
Battery Model Designed Service Life Capacity (25) Dimension: mm (inch) Approx. Weight Internal Resistance 20HR (0.85A) 17.0AH Length 181 (7.13) 10HR (1.53A) 15.3AH Width 77(3.03)
12V17AH/20HR
BAT-12V17AH(12V17AH/20 HR) 5 years 5HR (2.90A) 14.5AH Height 167(6.57) 1HR (11.1A) 11.1AH Total Height 167(6.57)
5.15Kg (11.36 lbs) Fully charged at 25: 0.03 Ohm 3% of capacity declined per month at 25 40 105% Cycle use 25 100% 0 85% Stand-by use 13.50-13.80V (-20mV/) -15 65%
Self-discharge
Capacity Affected by Temp. (20HR)
Charge Voltage (25)
14.40-15.00V(-30mV/) Max. Current: 5.1A
Performance Curves and Charts
Discharge Characteristic (25)
Charge Characteristic (25)
Page 2 of 3
Percentage of Capacity Available(%)
120
100
80
60 100% D.O.D 40 50% D.O.D 30% Depth of discharge
20
0 0 200 400 600 800 1000 1200 1400
Number of cycles(Cycles)
Effect of temperature on capacity
Number of cycles Vs. Depth of Discharge
BAT-12V17AH
Constant Current Discharge Data
12V17AH/20HR
Constant Current Discharge Data Sheet (Amperes at 25) End Voltage/cell 1.80 1.75 1.70 1.65 1.60 Minute (s) 5 65.9 67.6 69.3 71.1 72.8 10 44.7 46.0 47.2 48.4 49.7 15 34.9 35.8 36.7 37.5 38.4 30 20.4 20.7 21.0 21.4 21.7 1 12.2 12.4 12.6 12.8 13.0 3 4.88 4.96 5.04 5.12 5.20 Hour (s) 5 3.24 3.31 3.37 3.44 3.50 10 1.65 1.69 1.73 1.76 1.79 20 0.84 0.85 0.90 0.91 0.92
Constant Power Discharge Data
Constant Power Discharge Data Sheet (Watts at 25) End Voltage/cell 1.80 1.75 1.70 1.65 1.60 Minute (s) 5 128 133 138 143 147 10 94.9 96.3 98.2 100 102 15 76.0 77.3 78.7 80.1 81.5 30 42.0 42.7 43.3 43.9 44.6 45 32.6 33.0 33.40 33.8 34.2 1 25.5 25.8 26.0 26.3 26.6 2 14.2 14.4 14.5 14.7 214.9 Hour (s) 3 9.94 10.0 10.1 10.2 10.3 5 6.78 6.79 6.88 6.96 7.05
End Voltage
Discharge Rate Discharge Current End VoltageV/cell 1.75 1.75 1.75 1.60
20h 10h 3h 1h
0.05C20 A (I20) 0.09C20 A (I10) 0.25C20 A (I3) 0.60C20 A (I1)
Storage Time VS Charge Time
Storage Time Top up Charging Recommendation
Page 3 of 3
Less than 6 months from production or previous top up charge Less than 12 months from production or previous top up charge Less than 6 months from production or previous top up charge Less than 12 months from production or previous top up charge
Maximum of 16 hours at a constant voltage of 2.40VPC
Maximum of 20 hours at a constant voltage of 2.40VPC
Maximum of 8 hours at a constant current of 0.1 C A
Maximum of 10 hours at a constant current of 0.1 C A
Page 4 of 3