GEP550-1
Diesel Generator Set Exclusively from your Cat dealer
Output Ratings
Generating Set Model Prime* 500.0 kVA 400.0 kW * Refer to ratings definitions on page 4. Ratings at power 0.8 Ratings at .8 power factor. factor Standby* 550.0 kVA 440.0 kW -
380-415V,50Hz
Technical Data
Engine Make & Model: Alternator Model: Base Frame Type: Circuit Breaker Type: Frequency: Engine Speed: RPM Fuel Tank Capacity: litres (US gal) Fuel Consumption, Prime: l/hr (US gal/hr) Fuel Consumption, Standby : l/hr (US gal/hr) 97.2 (25.7) 106.8 (28.2) Perkins 2506A-E15TAG2 LL6114F Heavy Duty Fabricated Steel 3 Pole MCCB 50 Hz 1500 928 (245.2) 60 Hz -
Engine Techncial Data
Physical Data
Manufacturer: Model: No. of Cylinders/Alignment: Cycle: Induction: Cooling Method: Governing Type: Governing Class: Compression Ratio: Displacement: l (cu.in) Bore/Stroke: mm (in) Moment of Inertia: kg m (lb. in) Engine Electrical System: -Voltage/Ground: -Battery Charger Amps: Weight: kg (lb) - Dry: - Wet: 24/Negative 70 1633 (3600) 1714 (3779) Perkins 2506A-E15TAG2 6 / In Line 4 Stroke Turbocharged Air To Air Charge Cooled Water Electronic ISO 8528 G2 16.0:1 15.2 (927.6) 135.0 (5.3)/167.0 (6.6) 4.29 (14660) BMEP: kPa (psi) -Standby: -Prime: Regenerative Power: kW 2717.0 (394.0) 2471.0 (358.4) 50.0 -
Lubrication system
Oil Filter Type: Total Oil Capacity l (US gal): Oil Pan l (US gal): Oil Type: Cooling Method: Eco, Full Flow 62.0 (16.4) 53.0 (14.0) API CI4 15W-40 Water
Performance
Engine Speed: RPM Gross Engine Power: kW (hp) -Standby: -Prime:
50 Hz
1500 487.0 (653.0) 443.0 (594.0)
60 Hz
-
Fuel System
Fuel Filter Type: Replaceable Element Recommended Fuel: 110% Load
Air System
Air Filter Type: Combustion Air Flow: m/min (cfm) -Standby: -Prime: Max. Combustion Air Intake Restriction: kPa (in H2O) Radiator Cooling Air Flow: m/min (cfm) External Restriction to Cooling Air Flow: Pa (in H2O)
50 Hz
Paper Element 18" 32.0 (1130) 30.5 (1077) 6.2 (24.9) 660.0 (23308) 125 (0.5)
60 Hz
Class A2 Diesel Fuel Consumption: l/hr (US gal/hr) 100% Load 75% Load 50% Load
Prime 50 Hz 60 Hz Standby 50 Hz 60 Hz 106.8 (28.2) 80.7 (21.3) 55.0 (14.5) 106.8 (28.2) 97.2 (25.7) 73.6 (19.4) 50.4 (13.3) -
(based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)
Cooling System
Cooling System Capacity: l (US gal) Water Pump Type: Heat Rejected to Water & Lube Oil: kW (Btu/min) -Standby: -Prime: Heat Radiation to Room: kW (Btu/min) -Standby: -Prime: Radiator Fan Load: kW (hp)
50 Hz
38.3 (10.1)
60 Hz
-
Exhaust System
Silencer Type: Silencer Noise Reduction Pressure Drop Across Silencer System: kPa (in Hg) Silencer Noise Reduction
50 Hz
Level 1
60 Hz
SD150 (1) 0.34 (0.100) 15 6.8 (2.0) 87.0 (3072) 81.0 (2860) 528 (982) 514 (957) -
Centrifugal
166.0 (9440) 157.0 (8928) 49.0 (2787) 47.0 (2673) 16.0 (21.5)
Level: dB Max. Allowable Back Pressure: kPa (in. Hg) Exhaust Gas Flow: m/min (cfm) -Standby: -Prime: Exhaust Gas Temperature: C (F) m/min (cfm) -Standby: -Prime:
Cooling system designed to operate in ambient conditions up to 50C (122F). Contact your local Olympian dealer for power ratings at specific site conditions.
Consult your Olympian representative for more information
Alternator Performance Data
50 Hz Data Item
415/240V 400/230V 230/115V 200/115V 380/220V 220/110V 220/127V
60 Hz
Motor Starting Capability* kVA
1296
1213
1106
1438
Short Circuit Capacity** %
300
300
300
300
300
300
300
300
300
Reactances: Per Unit
Xd X'd X''d
2.850 0.150 0.103
3.070 0.160 0.111
3.400 0.180 0.123
2.330 0.120 0.084
Reactances shown are applicable to standby ratings. * Based on 30% voltage dip. ** With optional Permanent Magnet generator or AREP excitation.
Alternator Technical Data
Physical Data
Manufacturer: Model: No. of Bearings: Insulation Class: Winding Pitch - Code: Wires: Ingress Protection Rating: Excitation System: AVR Model: OLYMPIAN LL6114F 1 H 2/3 - 6 12 IP23 SHUNT R450
Operating Data
Overspeed: RPM Voltage Regulation (steady state) (% ): Wave Form NEMA = TIF: Wave Form IEC = THF: Total Harmonic Content LL/LN: Radio Interference: 2250 +/- 0.5 50 2.0% 2.0%
Supression is in line with European Standard EN61000-6
Radiant Heat: kW (Btu/min) -50 Hz: -60 Hz: 26.7 (1518) -
Consult your Olympian representative for more information
Technical Data
3 Phase Ratings and Performance at 50 Hz, 1500 RPM 3 Phase Ratings and Performance at 60 Hz, RPM
Voltage
kVA
415/240V 400/230V 380/220V 230/115V 220/127V 220/110V 200/115V 500.0 500.0 500.0 500.0 460.0 500.0 500.0
Prime
kW
400.0 400.0 400.0 400.0 368.0 400.0 400.0
Standby
kVA
550.0 550.0 550.0 550.0 506.0 550.0 550.0
Voltage
kW
440.0 440.0 440.0 440.0 404.8 440.0 440.0
Prime
kVA kW
Standby
kVA kW
Weights & Dimensions
Weights: kg (lb)
Net (+ lube oil) Wet (+ lube oil & coolant) Fuel, lube oil & coolant 3920 (8642) 3958 (8726) 4742 (10454)
Dimensions: mm (in)
Length Width Height 3700 (145.7) 1100 (43.3) 2143 (84.4)
Note: General configuration not to be used for installation. See general dimension drawings for detail.
Definitions
Standby Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
General Data
Documents
A full set of operation and maintenance manuals and circuit wiring diagrams.
Quality Standards Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. BS4999, BS5000, BSEN60034, BSEN61000, IEC60034.
Warranty
All equipment carries full manufacturer's warranty.
Standard Reference Conditions
Note: Standard reference conditions 25C (77F) air inlet temp, 100m (328ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
Information contained in this publication may be considered confidential.
Market: International LEHF6376-02 (09/10) LEHF6376-03 (09-10) 278-687 Information contained is in recommended this publication may be considered confidential. Discretion when distributing. Discretion is recommended when distributing. Materials and specifications are subject to change without notice. Materials and specifications are subject to change without notice. CAT, CATERPILLAR, their respective logos OLYMPIAN, "Caterpillar Yellow", and the "Power Edge" trade dress, as well as CAT, CATERPILLAR, their respective logos, OLYMPIAN, Caterpillar Yellow, the Power Edge trade dress as well as corporate and and product identity used herein, are trademarks andmay may not be used without permission. corporate product identity used herein, are trademarksof of Caterpillar Caterpillar and not be used without permission.
www.Cat-ElectricPower.com 2010 Caterpillar All rights reserved. Printed in U.S.A.