Discover
TeSys U: starter-controller
Standard TeSys U
The Standard TeSys U replaces conventional components in a smaller space b The Standard TeSys U starter-controller incorporates all the conventionally associated functions: circuit breaker + contactor + thermal relay. b It considerably reduces wiring time. b The electrical coordination of the components is intrinsically ensured.
DB124011
equivalent to >
Space-saving Time-saving Safety
L1 L2 L3 L1
S1
The Standard TeSys U meets 80 % of protection motor control requirements The functions embedded in the Standard TeSys U unit are those which are commonly deployed in simple solutions: b Adjustable protection against overloads and short-circuits b ON/OFF control of one direction of rotation b The wiring diagram illustrates ON/OFF pushbutton control. TeSys U incorporates "coil" terminals A1-A2 and "self-holding auxiliary contacts" 13-14.
DB123408
OFF
S2 ON
Conventional control diagram Preservation of know-how
7
A1 A2 13 14
10
1/52
Discover (continued)
Advanced TeSys U
Furthermore, this version significantly extends the control possibilities. Advanced TeSys U incorporates the basic functions (protection, motor control) to which one or more functions that are usually carried out with automation modules can be added: motor status remote indication, protection trip remote indication, remote reset, overload alarm, transmission over bus, alphanumeric display, etc.
1 2
DB124012
equivalent to >
3
Space-saving Economical optimisation
Input / output card Communication interface 3 LCD display unit
By also allowing variable speed control b Advanced TeSys U connected to the XYZ variable speed controller also constitutes a natural variable speed control solution. It makes it possible to maintain the homogeneity of a motor control panel already well equipped with TeSys U starter-controllers.
DB124016
6
Homogeneity Simplicity Performance
10
1/53
Discover (continued)
Standard TeSys U
Creating a motor feeder with TeSys U requires combination of at least a power base and a control unit. The plug and play principle of this product allows other modules to be added to provide access to additional functions.
DB124014
Standard TeSys U - non-reversing
2 This configuration consists of a power base, a control unit and possibly an auxiliary contact module. It is used to protect a motor and to switch it ON/OFF. B A LUB12 or LUB32 power base This power base incorporates the power components: terminal blocks, switching mechanism and power contacts. It also includes a set of NO-NC auxiliary contacts and their terminal blocks. C B LUCA, LUCL control unit These control units incorporate the detection and protection functions with respect to: b overload short circuit b phase failure phase imbalance b earth fault protection (equipment protection only). The LUCL control unit is exclusively used with the variable speed controller. C Additional auxiliary LUF signalling contacts D LUA signalling contacts b Indicate that the protective device has tripped.
2
5 3 4
3
1 2
D
Power supply terminal block ON/OFF/Reset control handle 3 "Motor" terminal block 4 "Coil" power supply terminal 5 Built-in auxiliary contacts
5
DB124013
LU2B 12 - LU2B 32 Reverser control assembly
Standard TeSys U - non-reversing and reversing
LU2B12 Reversing power base allowing a motor to be controlled in both directions of operation. It incorporates the power components and the auxiliary contacts used to remotely indicate the direction of rotation. The NO-NC auxiliary contacts used to remotely indicate the ON/OFF status are to be ordered separately, in the same way as the LUCA control module.
10
1/54
Discover (continued)
Advanced TeSys U
For advanced applications or applications incorporating communication
1 2
Power supply terminal block ON/OFF/Reset control handle 3 "Motor" terminal block
Advanced TeSys U - non-reversing
This version consists of a power base, an advanced control unit and possibly an information or communication module for the measurement and alarm functions. They complement the main ON/OFF control function. A LUB120, LUB320 power base
DB124032
B 1 A C 2
This power base incorporates the power components: terminal blocks, switching mechanism and power contacts. It also incorporates the auxiliary contacts (terminal block not included).
B LUCB, LUCC, LUCD supervisable control units detection / tripping / measurement C LUCM control unit with display detection / tripping / measurement
load parameter, alarm, log display, etc.
3 E
D Thermal overload signalling LUF module, Motor load indication LUF module Motor overload alarm LUF module
E LUL communication modules F AS-Interface, Modbus, Profibus DP, CANopen, DeviceNet or Advantys STB
F LUA signalling contacts indicate that the protective device has tripped
6
Plug-in integrated auxiliary contact terminal block
DB124015
Advanced TeSys U - non-reversing and reversing
An LU2M reverser block is added according to the principle of the Standard TeSys U. No preassembled reverser assembly in the Advanced TeSys U version. A reverser assembly can be built by ordering the different parts separately. This makes it possible to modify the installation or to create assemblies that incorporate a communication module.
10
1/55
Choose
Help with choosing units and modules
DB124017
Power base
For assembling components, connecting to the process, ON / OFF operation, resetting.
Standard TeSys U
LUB12 LUB32
2
Control unit
This unit is essential for providing all the electrical protection functions.
Standard control unit
LUCA Class 10 - 3-phase (see page 1/71)
DB124019
Magnetic control unit
LUCL For use with a variable speed controller or a soft starter (see page 1/134)
DB124019 DB124024
Some of these also provide advanced measurement, alarm and display functions.
b Protection against overloads and short-circuits. b Protection against phase failure and phase imbalance. b Earth fault protection (equipment protection only). b Manual reset.
b Short-circuit protection. b Manual reset. b Motor thermal overload protection must be provided by the variable speed controller or the soft starter.
Auxiliary contact module
DB124029
Indication of pole status or cause of tripping
Auxiliary contact module pole status LUFN (see page 1/65)
Auxiliary contact module protection status LUF A1C (depending on configuration) (see page 1/65)
DB124030
For additional remote indication contacts.
Auxiliary contact module (protection status, pole status) on RJ connector LUF C00 (see page 1/78)
9
Code showing the compatibility of modules with control units.
10
1/56
Choose (continued)
Help with choosing units and modules
DB124018
Advanced TeSys U
LUB120 LUB320
2
Control and diagnostic unit
LUCB Class 10 - 3-phase LUCC Class 10 - single-phase LUCD Class 20 - 3-phase (see page 1/71)
DB124019
Multi-function control unit
LUCM Classes 5 to 30 single-phase and three-phase (see page 1/72)
DB124020
Same functions as the standard control unit. In addition, in conjunction with a function module: b fault differentiation with manual reset, b fault differentiation with remote or automatic reset, b thermal overload alarm, b indication of motor load.
Same functions as the standard control unit. In addition, reset parameters can be set to manual or automatic. b protection function alarm. b indication on front panel or on remote terminal. b "log" function. b main motor parameter "monitoring" function. b differentiation of thermal overload and magnetic fault. b overload, no-load running.
Fault signalling module
For indicating the cause of tripping and allowing a reset.
DB124021 DB124022
Thermal overload signalling module and manual reset. LUF DH11 (see page 1/73)
Thermal overload signalling module and automatic or remote reset LUG DA01 and LUF DA10 (see page 1/73)
Load level module
For indicating the load level, alerting a threshold overshoot.
DB124021 DB124023
Motor load indication module. LUF V2 (see page 1/73)
Thermal overload alarm module LUF W10 (see page 1/73)
8
DB124027 DB124028
Communication module
For monitoring the status of the starter-controller from a centralised automation system.
DB124026 DB124026
CANopen communication module LUF V2 (see page 1/86)
DB124026
DeviceNet communication module LUL C09 (see page 1/92)
DB124025
Advantys stb communication module LUL C15 (see page 1/92)
DB124026
Modbus communication module LUL C033 (see page 1/94)
DB124028
10
BECKHOFF communication module LUF C14 (contact us)
AS-Interface communication module ASILUF C51 (see page 1/80)
Profibus DP communication module LUL C07 (see page 1/82)
Module for Ethernet communication LUL C033 + TeSys port (contact us)
1/57