HEAT LOAD ESTIMATE
Client
Medical College
City : KOTAYAM
Space used : DEPARTMENT OF ORTHODONTICS
Date : 23/01/2010
Floor lvl
SECOND
Total Area in sqft
1399.68
Latitude
8.29
Height ft
13
Suntime
16 :00
Volume cuft
18195.84
DP
Grs./ lb
DB
WB F
RH%
Enthalpy
Btu/lb
Item
Summer
95
80
52.5
188
44
Monsoon
85
80
80.65
212
44
Room
74
100
27.5
Diff
21
88
16.5
Area sqft Sun gain
Factor
TD
Btu / hr
Summer
Outdoor air details
Solar heat gain through glass
North
East
11
0.56
0.00
11
0.56
0.00
South
119.4
13
0.56
869.23
West
164
0.56
0.00
North East
11
0.56
0.00
North West
103
0.56
0.00
South East
11
0.56
0.00
South West
127
0.56
0.00
Fresh air
Fresh air
cfm
change
909.792
ESHF
0.79
ADP Deh. RiseDeh. Cfm
56
15.84
4086
Solar heat gain through walls
North
19
0.44
0.00 Deh rise
( 1- BF)* ( RM DB - ADP)
East
23
0.44
0.00 Deh cfm
ERSH / 1.08 * temp rise
South
442.2
21
0.44
West
4085.93 Supply cfmERSH / 1.08 * DESIRED Td
17
0.44
North East
16
0.44
0.00
0 Outlet Td ERSH / 1.08 * De hum CFM
North West
11
0.44
0.00
South East
23
0.44
0.00
South West
19
0.36
0.00
Transmission gain through roof/ ceiling/partitions
Roof
0.48
0.00
Ceiling
1399.68
16
0.48
10749.54
Floor
1399.68
16
0.48
10749.54
Partition
16
0.40
0.00
All glass
21
1.10
0.00
50
280
Internal heat gain
People
Equipment kw
2.96 3410
14000.00
1.00
10093.60
Lights watts
1200
3.41
1.25
Subtotal
5115.00
55662.84
2783.14
Safety factor 5%
Room sensible heat
58445.99
SA duct gain 2.5%
1461.15
SA fan gain 5%
2922.30
Fresh Air
3 ####
2.4
1.08
7074.54
Reheat
Effective room sensible heat
69903.98
Latent heat
People
50
270
13500.00
Subtotal
13500.00
675.00
Safety factor 5%
Room latent heat
14175.00
Fresh Air
3 ####
2.4
0.68
4454.34
Effective room latent heat
18629.34
Effective room total heat
88533.32
Outdoor Air Heat
Fresh Air Sens
909.79
20 0.88
1.08
17293.33
Fresh air lat
909.79
73 0.88
0.68
39742.63
RA gain
RA fan gain
Grand Total
Tons TR
145569.27
12.13
HEAT LOAD ESTIMATE
Client
Medical College
City : KOTAYAM
Space used : DEPARTMENT OF ORAL&MAXILLOFACIAL SURGERY(SELECTED AREAS )Date : 23/01/2010
Floor lvl
Ground Floor
P G CLINIC
Total Area in sqft
1049.76
Latitude
8.29
Height ft
13
Suntime
16 :00
Volume cuft
13646.88
DB
WB F
RH%
DP
Grs./ lb
Enthalpy
Btu/lb
Item
Summer
95
80
52.5
188
44
Monsoon
85
80
80.65
212
44
Room
74
100
27.5
Diff
21
88
16.5
Area sqft Sun gain
Factor
TD
Btu / hr
Summer
Outdoor air details
Solar heat gain through glass
North
East
Fresh air Fresh air
11
0.56
0.00
11
0.56
0.00
South
89.55
13
0.56
651.92
West
164
0.56
0.00
North East
11
0.56
0.00
North West
103
0.56
0.00
South East
11
0.56
0.00
South West
127
0.56
0.00
cfm
change
682.344
ESHF
0.82
ADP Deh. RiseDeh. Cfm
56
15.84
2793
Solar heat gain through walls
North
19
0.44
0.00 Deh rise
( 1- BF)* ( RM DB - ADP)
East
23
0.44
0.00 Deh cfm
ERSH / 1.08 * temp rise
South
421.2
21
0.44
West
3891.89 Supply cfm ERSH / 1.08 * DESIRED Td
17
0.44
North East
16
0.44
0.00
0 Outlet Td
North West
11
0.44
0.00
South East
23
0.44
0.00
South West
19
0.36
0.00
Transmission gain through roof/ ceiling/partitions
Roof
0.48
0.00
Ceiling
1049.76
16
0.48
8062.16
Floor
1049.76
16
0.48
8062.16
Partition
16
0.40
0.00
All glass
21
1.10
0.00
25
280
Internal heat gain
People
Equipment kw
1.72 3410
7000.00
1.00
5865.20
ERSH / 1.08 * De hum CFM
Lights watts
960
3.41
1.25
Subtotal
4092.00
37625.33
1881.27
Safety factor 5%
Room sensible heat
39506.59
SA duct gain 2.5%
987.66
SA fan gain 5%
1975.33
Fresh Air
3 ####
2.4
1.08
5305.91
Reheat
Effective room sensible heat
47775.49
Latent heat
People
25
270
6750.00
Subtotal
6750.00
337.50
Safety factor 5%
Room latent heat
7087.50
Fresh Air
3 ####
2.4
0.68
3340.76
Effective room latent heat
10428.26
Effective room total heat
58203.75
Outdoor Air Heat
Fresh Air Sens
682.34
20 0.88
1.08
12969.99
Fresh air lat
682.34
73 0.88
0.68
29806.97
RA gain
RA fan gain
Grand Total
Tons TR
100980.71
8.42
HEAT LOAD ESTIMATE
Client
Medical College
City : KOTAYAM
Space used : DEPARTMENT OF ORAL&MAXILLOFACIAL SURGERY(SELECTED AREAS
Date) : 23/01/2010
Floor lvl
Ground Floor
OPERATION THEATRE
Total Area in sqft
699.84
Latitude
8.29
Height ft
13
Suntime
16 :00
Volume cuft
9097.92
DP
Grs./ lb Enthalpy
DB
WB F
RH%
Btu/lb
Item
Summer
95
80
52.5
188
44
Monsoon
85
80
80.65
212
44
Room
74
100
27.5
Diff
21
88
16.5
Area sqftSun gain
Factor Btu / hr
TD
Summer
Outdoor air details
Solar heat gain through glass
North
East
Fresh air Fresh air
11
0.56
0.00
29.85
11
0.56
183.88
South
59.7
13
0.56
434.62
West
164
0.56
0.00
North East
11
0.56
0.00
North West
103
0.56
0.00
South East
11
0.56
0.00
South West
127
0.56
0.00
cfm
change
454.896
ESHF
0.88
ADPDeh. RiseDeh. Cfm
56
15.84
2111
Solar heat gain through walls
North
19
0.44
0.00 Deh rise
110.55
23
0.44
1118.77 Deh cfm
South
221.1
21
0.44
2042.96 Supply cfmERSH / 1.08 * DESIRED Td
West
East
17
0.44
North East
16
0.44
0.00
North West
11
0.44
0.00
South East
23
0.44
0.00
South West
19
0.36
0.00
0 Outlet Td ERSH / 1.08 * De hum CFM
Transmission gain through roof/ ceiling/partitions
Roof
0.48
0.00
Ceiling
699.84
16
0.48
5374.77
Floor
699.84
16
0.48
5374.77
Partition
16
0.40
0.00
All glass
21
1.10
0.00
10
280
Internal heat gain
People
Equipment kw
2.48 3410
2800.00
1.00
( 1- BF)* ( RM DB - ADP)
ERSH / 1.08 * temp rise
8456.80
Lights watts
720
3.41
1.25
Subtotal
3069.00
28855.56
1442.78
Safety factor 5%
Room sensible heat
30298.34
SA duct gain 2.5%
757.46
SA fan gain 5%
1514.92
Fresh Air
3 ####
2.4
1.08
3537.27
Reheat
Effective room sensible heat
36107.99
Latent heat
People
10
270
2700.00
Subtotal
2700.00
135.00
Safety factor 5%
Room latent heat
2835.00
Fresh Air
3 ####
2.4
0.68
2227.17
Effective room latent heat
5062.17
Effective room total heat
41170.16
Outdoor Air Heat
Fresh Air Sens
454.90
20
0.88
1.08
8646.66
Fresh air lat
454.90
73
0.88
0.68
19871.31
RA gain
RA fan gain
Grand Total
Tons TR
69688.14
5.81
HEAT LOAD ESTIMATE
Client
Medical College
City : KOTAYAM
Space used : DEPARTMENT OF ORAL&MAXILLOFACIAL SURGERY(SELECTED AREAS
Date
) : 23/01/2010
Floor lvl
Ground Floor
STERILISATION AREA
Total Area in sqft
58.38
Latitude
8.29
Height ft
13
Suntime
16 :00
Volume cuft
758.94
DB
WB F
RH%
DP
Grs./ lb
Enthalpy
Btu/lb
Item
Summer
95
80
52.5
188
44
Monsoon
85
80
80.65
212
44
Room
74
100
27.5
Diff
21
88
16.5
Area sqftSun gain
Factor Btu / hr
TD
Summer
Outdoor air details
Solar heat gain through glass
Fresh air Fresh air
North
11
0.56
0.00
East
11
0.56
0.00
South
13
0.56
0.00
West
164
0.56
0.00
North East
11
0.56
0.00
North West
103
0.56
0.00
South East
11
0.56
0.00
South West
127
0.56
0.00
cfm
change
37.947
ESHF
0.73
ADP Deh. RiseDeh. Cfm
56
15.84
161
Solar heat gain through walls
North
19
0.44
0.00 Deh rise
( 1- BF)* ( RM DB - ADP)
East
23
0.44
0.00 Deh cfm
ERSH / 1.08 * temp rise
South
21
0.44
0.00 Supply cfmERSH / 1.08 * DESIRED Td
West
17
0.44
North East
16
0.44
0.00
0 Outlet Td ERSH / 1.08 * De hum CFM
North West
11
0.44
0.00
South East
23
0.44
0.00
South West
19
0.36
0.00
Transmission gain through roof/ ceiling/partitions
Roof
0.48
0.00
Ceiling
58.38
16
0.48
448.36
Floor
58.38
16
0.48
448.36
Partition
16
0.40
0.00
All glass
21
1.10
0.00
280
Internal heat gain
People
Equipment kw
0.08 3410
840.00
1.00
272.80
Lights watts
40
3.41
1.25
Subtotal
170.50
2180.02
109.00
Safety factor 5%
Room sensible heat
2289.02
SA duct gain 2.5%
57.23
SA fan gain 5%
114.45
Fresh Air
3 37.95
2.4
1.08
295.08
Reheat
Effective room sensible heat
2755.77
Latent heat
People
270
810.00
Subtotal
810.00
40.50
Safety factor 5%
Room latent heat
850.50
Fresh Air
3 37.95
2.4
0.68
185.79
Effective room latent heat
1036.29
Effective room total heat
3792.06
Outdoor Air Heat
Fresh Air Sens
37.95
20
0.9
1.08
721.30
Fresh air lat
37.95
73
0.9
0.68
1657.65
RA gain
RA fan gain
Grand Total
Tons TR
6171.00
0.51
HEAT LOAD ESTIMATE
Client
Medical College
City : KOTAYAM
Space used : DEPARTMENT OF CONSERVATIVE DENTISTRY
Date : 23/01/2010
Floor lvl
THIRD (P.G CLINIC)
Total Area in sqft
1166.4
Latitude
8.29
Height ft
13
Suntime
16 :00
Volume cuft
15163.2
DB
WB F
RH%
DP
Grs./ lb
Enthalpy
Btu/lb
Item
Summer
95
80
52.5
188
44
Monsoon
85
80
80.65
212
44
Room
74
100
27.5
Diff
21
88
16.5
Area sqft Sun gain
Factor
TD
Btu / hr
Summer
Outdoor air details
Solar heat gain through glass
North
East
Fresh air Fresh air
11
0.56
0.00
119.4
11
0.56
735.50
South
13
0.56
0.00
West
164
0.56
0.00
North East
11
0.56
0.00
North West
103
0.56
0.00
South East
11
0.56
0.00
South West
127
0.56
0.00
cfm
change
758.16
ESHF
0.83
ADP Deh. Rise Deh. Cfm
56
15.84
2998
Solar heat gain through walls
North
19
0.44
0.00 Deh rise
582.6
23
0.44
5895.91 Deh cfm
South
21
0.44
West
East
0.00 Supply cfmERSH / 1.08 * DESIRED Td
17
0.44
North East
16
0.44
0.00
North West
11
0.44
0.00
South East
23
0.44
0.00
South West
19
0.36
0.00
0 Outlet Td ERSH / 1.08 * De hum CFM
Transmission gain through roof/ ceiling/partitions
Roof
0.48
0.00
Ceiling
1166.4
16
0.48
8957.95
Floor
1166.4
16
0.48
8957.95
Partition
16
0.40
0.00
All glass
21
1.10
0.00
25
280
1.64
3410
Internal heat gain
People
Equipment kw
7000.00
1.00
( 1- BF)* ( RM DB - ADP)
ERSH / 1.08 * temp rise
5592.40
Lights watts
720
3.41
1.25
Subtotal
3069.00
40208.72
2010.44
Safety factor 5%
Room sensible heat
42219.16
SA duct gain 2.5%
1055.48
SA fan gain 5%
2110.96
Fresh Air
758.16
2.4
1.08
5895.45
Reheat
Effective room sensible heat
51281.04
Latent heat
People
25
270
6750.00
Subtotal
6750.00
337.50
Safety factor 5%
Room latent heat
7087.50
Fresh Air
758.16
2.4
0.68
3711.95
Effective room latent heat
10799.45
Effective room total heat
62080.50
Outdoor Air Heat
Fresh Air Sens
758.16
20
0.88
1.08
14411.11
Fresh air lat
758.16
73
0.88
0.68
33118.85
RA gain
RA fan gain
Grand Total
Tons TR
109610.46
9.13
HEAT LOAD ESTIMATE
Client
Medical College
City : KOTAYAM
Space used : DEPARTMENT OF CONSERVATIVE DENTISTRY
Date : 23/01/2010
Floor lvl
THIRD
Total Area in sqft
2099.52
Latitude
8.29
Height ft
13
Suntime
16 :00
Volume cuft
27293.76
U G CLINIC
DB
WB F
RH%
DP
Grs./ lb Enthalpy
Btu/lb
Item
Summer
95
80
52.5
188
Monsoon
85
80
80.65
212
44
Room
74
100
27.5
Diff
21
88
16.5
Area sqft Sun gain
44
Factor Btu / hr
TD
Summer
Outdoor air details
Solar heat gain through glass
Fresh airFresh air
North
11
0.56
0.00
East
11
0.56
0.00
South
179.1
13
0.56
1303.85
West
164
0.56
0.00
North East
11
0.56
0.00
North West
103
0.56
0.00
South East
11
0.56
0.00
South West
127
0.56
0.00
cfm
change
1364.7
ESHF
0.84
ADPDeh. Rise Deh. Cfm
56
15.84
6430 1.Plain Glass( cl E) has to be changed from .
Solar heat gain through walls
North
19
0.44
0.00 Deh rise
( 1- BF)* ( RM DB - ADP)
East
23
0.44
0.00 Deh cfm
ERSH / 1.08 * temp rise
South
663.3
21
0.44
6128.89 Supply cfmERSH / 1.08 * DESIRED Td
West
17
0.44
0 Outlet Td ERSH / 1.08 * De hum CFM
North East
16
0.44
0.00
North West
11
0.44
0.00
South East
23
0.44
0.00
South West
19
0.36
0.00
Transmission gain through roof/ ceiling/partitions
Roof
0.48
0.00
Ceiling
2099.52
16
0.48
16124.31
Floor
2099.52
16
0.48
16124.31
Partition
16
0.40
0.00
All glass
21
1.10
0.00
2.Light & Equipmnet load to be taken as pe
3.Roof facor,as normal building.
4.Roof factor to be filled when the Roof is e
5.Ceiling facor to be filled up in case of Floo
6.Floor facor when ,we have floor below th
7.The caliculation table only for large areas
Internal heat gain
People
50
280
14000.00
Equipment kw
7.08
3410
1.00
24142.80
Lights watts
2400
3.41
1.25
10230.00
Subtotal
88054.17
4402.71
Safety factor 5%
Room sensible heat
92456.88
SA duct gain 2.5%
2311.42
SA fan gain 5%
4622.84
Fresh Air
3 1364.69
2.4
1.08
10611.81
Reheat
Effective room sensible heat
110002.96
Latent heat
People
50
270
13500.00
Subtotal
13500.00
675.00
Safety factor 5%
Room latent heat
Fresh Air
14175.00
3 1364.69
2.4
0.68
6681.51
Effective room latent heat
20856.51
Effective room total heat
130859.47
Outdoor Air Heat
Fresh Air Sens 1364.69
20 0.88
1.08
25939.99
Fresh air lat
73 0.88
0.68
59613.94
1364.69
RA gain
RA fan gain
Grand Total
Tons TR
216413.40
18.03
ass( cl E) has to be changed from .56 to.1.0
Equipmnet load to be taken as per site conditions.
or,as normal building.
tor to be filled when the Roof is exposed.
acor to be filled up in case of Floor on top.
cor when ,we have floor below the Space to be airconditioend/\
culation table only for large areas of Above 500 sq ft.
HEAT LOAD ESTIMATE
Client
Medical College
City : KOTAYAM
Space used : DEPARTMENT OF ORTHODONTICS
Date : 23/01/2010
Floor lvl
SECOND
Total Area in sqft
1399.68
Latitude
8.29
Height ft
13
Suntime
16 :00
Volume cuft
18195.84
DB
WB F
RH%
DP
Grs./ lb
Enthalpy
Btu/lb
Item
Summer
95
80
52.5
188
44
Monsoon
85
80
80.65
212
44
Room
74
100
27.5
Diff
21
88
16.5
Area sqft Sun gain
Factor
Btu / hr
TD
Summer
Outdoor air details
Solar heat gain through glass
North
East
11
0.56
0.00
11
0.56
0.00
South
119.4
13
0.56
869.23
West
164
0.56
0.00
North East
11
0.56
0.00
North West
103
0.56
0.00
South East
11
0.56
0.00
South West
127
0.56
0.00
Fresh air
Fresh air
cfm
change
909.792
ESHF
0.79
ADP Deh. Rise Deh. Cfm
56
15.84
Solar heat gain through walls
North
19
0.44
0.00 Deh rise
( 1- BF)* ( RM DB - ADP)
East
23
0.44
0.00 Deh cfm
ERSH / 1.08 * temp rise
South
442.2
21
0.44
West
4085.93 Supply cfm ERSH / 1.08 * DESIRED Td
17
0.44
North East
16
0.44
0.00
0 Outlet Td
North West
11
0.44
0.00
South East
23
0.44
0.00
South West
19
0.36
0.00
Transmission gain through roof/ ceiling/partitions
Roof
0.48
0.00
Ceiling
1399.68
16
0.48
10749.54
Floor
1399.68
16
0.48
10749.54
Partition
16
0.40
0.00
All glass
21
1.10
0.00
50
280
2.96
3410
Internal heat gain
People
Equipment kw
14000.00
1.00
10093.60
ERSH / 1.08 * De hum CFM
4086 1.Plain Glass( cl E) has to be ch
2.Light & Equipmnet load to be
3.Roof facor,as normal building
4.Roof factor to be filled when
5.Ceiling facor to be filled up in
6.Floor facor when ,we have flo
7.The caliculation table only fo
Lights watts
1200
3.41
1.25
Subtotal
5115.00
55662.84
2783.14
Safety factor 5%
Room sensible heat
58445.99
SA duct gain 2.5%
1461.15
SA fan gain 5%
2922.30
Fresh Air
909.79
2.4
1.08
7074.54
Reheat
Effective room sensible heat
69903.98
Latent heat
People
50
270
13500.00
Subtotal
13500.00
675.00
Safety factor 5%
Room latent heat
Fresh Air
14175.00
3
909.79
2.4
0.68
4454.34
Effective room latent heat
18629.34
Effective room total heat
88533.32
Outdoor Air Heat
Fresh Air Sens 909.79
20
0.88
1.08
17293.33
Fresh air lat
73
0.88
0.68
39742.63
909.79
RA gain
RA fan gain
Grand Total
145569.27
Tons TR
12.13
1.Plain Glass( cl E) has to be changed from .56 to.1.0
2.Light & Equipmnet load to be taken as per site conditions.
3.Roof facor,as normal building.
4.Roof factor to be filled when the Roof is exposed.
5.Ceiling facor to be filled up in case of Floor on top.
6.Floor facor when ,we have floor below the Space to be airconditioend/\
7.The caliculation table only for large areas of Above 500 sq ft.