PRESSURIZATION CALCULATIONS:
ZONE 1
Method 1
Q= Kf *Al*(DP) 1/2
NOTES
Q= Kf *Al*(DP)
1/2
Flow/Leakage area calculations: Structural Component Number of Height Length item (ft) (ft) 48 3 3 3 7 7 Depth (ft) Area (ft2) Flow Area (ft2) 0.300 10.500 Total Leakage Area (ft2) 14.40 31.50
Flow area values taken from: ASHRAE Design of Smoke Management * half of the geometric area was used in calculating the flow area for the open doors
21
Total Total Flow Area: (summed from Table 1) Coefficient: Pressure Difference: Volumetric Flow Rate: Al Kf DP = = = = = 45.90 ft2 2610 0.05 in H20 26787.87 cfm 26787.87 cfm SC- 05 SPF/25-2 SPF/49-1 Total
45.90
PRESSURIZATION CALCULATIONS:
ZONE 1
Method 1
Q= Kf *Al*(DP) 1/2
NOTES
Q= Kf *Al*(DP)
1/2
Flow/Leakage area calculations: Structural Component Number of Height Length item (ft) (ft) 50 3 3 3 7 7 Depth (ft) Area (ft2) Flow Area (ft2) 0.300 10.500 Total Leakage Area (ft2) 15.00 31.50
Flow area values taken from: ASHRAE Design of Smoke Management * half of the geometric area was used in calculating the flow area for the open doors
21
Total Total Flow Area: (summed from Table 1) Coefficient: Pressure Difference: Volumetric Flow Rate: Al Kf DP = = = = = 46.50 ft2 2610 0.05 in H20 27138.04 cfm 27138.04 cfm
46.50
PRESSURIZATION CALCULATIONS:
ZONE 1
Method 1
Q= Kf *Al*(DP) 1/2
NOTES
Q= Kf *Al*(DP)
1/2
Flow/Leakage area calculations: Structural Component Number of Height Length item (ft) (ft) 5 3 3 3 7 7 Depth (ft) Area (ft2) Flow Area (ft2) 0.300 10.500 Total Leakage Area (ft2) 1.50 31.50
Flow area values taken from: ASHRAE Design of Smoke Management * half of the geometric area was used in calculating the flow area for the open doors
21
Total Total Flow Area: (summed from Table 1) Coefficient: Pressure Difference: Volumetric Flow Rate: Al Kf DP = = = = = 33.00 ft2 2610 0.05 in H20 19259.25 cfm 19259.25 cfm
33.00
STAIR CASE 05
PRESSURIZATION CALCULATIONS:
ZONE 1
Method 1
Q= Kf *Al*(DP) 1/2
NOTES
Q= Kf *Al*(DP)
1/2
Flow/Leakage area calculations: Structural Component Number of Height Length item (ft) (ft) 48 0 3 3 7 7 Depth (ft) Area (ft2) Flow Area (ft2) 0.300 10.500 Total Leakage Area (ft2) 14.40 0.00
Flow area values taken from: ASHRAE Design of Smoke Management * half of the geometric area was used in calculating the flow area for the open doors
21
Total Total Flow Area: (summed from Table 1) Coefficient: Pressure Difference: Volumetric Flow Rate: Al Kf DP = = = = = 14.40 ft2 2610 0.2 in H20 16808.08 cfm 16808.08 cfm SC- 05 SPF/25-2 SPF/49-1 Total
14.40
STAIR CASE 05
PRESSURIZATION CALCULATIONS:
ZONE 1
Method 1
Q= Kf *Al*(DP) 1/2
NOTES
Q= Kf *Al*(DP)
1/2
Flow/Leakage area calculations: Structural Component Number of Height Length item (ft) (ft) 50 0 3 3 7 7 Depth (ft) Area (ft2) Flow Area (ft2) 0.300 10.500 Total Leakage Area (ft2) 15.00 0.00
Flow area values taken from: ASHRAE Design of Smoke Management * half of the geometric area was used in calculating the flow area for the open doors
21
Total Total Flow Area: (summed from Table 1) Coefficient: Pressure Difference: Volumetric Flow Rate: Al Kf DP = = = = = 15.00 ft2 2610 0.2 in H20 17508.41 cfm 17508.41 cfm
15.00
1 staircase 7 fan capacity installed at 14 CASE 1 ALL DOOR CLOSED with bypass damper open Measured pressure at level 8 Measured pressure at level 6 Measured pressure at level 4 Measured pressure at level 2 Measured pressure at level 1 case 2 With one door open(level1) & with bypass damper closed Measured pressure at level 8 Measured pressure at level 5 Measured pressure at level 3 Measured pressure at level 2 With Three door open(level 1,3 &4) & with bypass damper closed Measured pressure at level 8 Measured pressure at level 7 Measured pressure at level 6 Measured pressure at level 5 Measured pressure at level 2 220pa 215pa 210pa 205pa 200pa air flow esp 27000 cfm 620 pa Serving level 1 - level 8
case 3
1 staircase 5 fan capacity installed at 49 fan capacity installed at 25 CASE 1 ALL DOOR CLOSED with bypass damper open Measured pressure at level 48 Measured pressure at level 40 Measured pressure at level 30 Measured pressure at level 20 Measured pressure at level GF Measured pressure at level B3 case 2 With one door open(level 5) & with bypass damper closed Measured pressure at level 48 Measured pressure at level 30 Measured pressure at level 3 Measured pressure at level 1 Measured pressure at level B1 Measured pressure at level B3 With Three door open(level GF,3 &4) & with bypass damper closed Measured pressure at level 48 Measured pressure at level 40 Measured pressure at level 30 Measured pressure at level 5 Measured pressure at level 2 Measured pressure at level 2 Measured pressure at level B1 Measured pressure at level B3 125pa 122pa 120pa 118pa 108pa 106pa air flow esp 27000 cfm 620 pa 11000cfm 550pa Serving level 48 Basement 3
case 3