Substation Automation and Protection Training
PCM 600 Application Configuration CAP 531
ABB Power Technologies AB, 2007 2007-09-07 1
Substation Automation and Protection Training
Application Configuration CAP 531
CAP 531 IS THE MASTER TOOL!
You MUST start the engineering from CAP 531. After COMPILING the graphic configuration, CAP 531 passes IMPORTANT INFORMATION to other subtools:
PCM 600 receives the list of used functions SMT receives the list of hardware cards and used virtual I/O GDE receives the used control and measurement blocks
ABB Power Technologies AB, 2007 2007-09-07 3
Substation Automation and Protection Training
Application Configuration CAP 531
In CAP 531 the application configuration is drawn without considering the hardware set-up of the IED.
ABB Power Technologies AB, 2007
The association VIRTUAL I/O PHISICAL I/O is done in SIGNAL MATRIX
2007-09-07 4
Substation Automation and Protection Training
Application Configuration CAP 531
ABB Power Technologies AB, 2007 2007-09-07 5
Substation Automation and Protection Training
CAP 531 On Line Software Library Synchronization
ONLINE / UPLOAD OPTIONS
IF YOU HAVE THE IED connected to the PC, the fastest way to get the PC function library synchronized with the IED library is to run Upload Options:
BEFORE UPLOAD OPTIONS: PC contains more functions than IED
ABB Power Technologies AB, 2007
AFTER UPLOAD OPTIONS: PC contains the same functions than IED
2007-09-07 6
Substation Automation and Protection Training
CAP 531 On Line Software Library Synchronization
EDIT / FUNCTION SELECTOR
ABB Power Technologies AB, 2007 2007-09-07 7
Substation Automation and Protection Training
CAP 531 Draw the Configuration
ABB Power Technologies AB, 2007 2007-09-07 8
Substation Automation and Protection Training
CAP 531 Insert a Work Sheet
Select the terminal and choose the menu Edit / Insert:
Enter the name of the work sheet
ABB Power Technologies AB, 2007 2007-09-07 9
Substation Automation and Protection Training
CAP 531 Insert Function Blocks
Choose the menu Object / Function Block:
ABB Power Technologies AB, 2007 2007-09-07 10
Substation Automation and Protection Training
CAP 531 Insert Function blocks
In the window choose the correct function block and click on Ok.
ABB Power Technologies AB, 2007
The function block will appear on your work sheet.
2007-09-07 11
Substation Automation and Protection Training
CAP 531 Connect Function Blocks
Click on the button and start connecting the signals
ABB Power Technologies AB, 2007 2007-09-07 12
Substation Automation and Protection Training
CAP 531 Variables
This configuration: Is equivalent to this one:
ABB Power Technologies AB, 2007 2007-09-07 13
Substation Automation and Protection Training
CAP 531 Cross Referenced vs Not Cross Referenced
CROSS REFERENCES
If you want a variable to be cross-referenced in CAP print-out, just drag the variable to cross the red dashed line shown by CAP 531 when you choose the menu Layout / Page Borders.
ABB Power Technologies AB, 2007
Cross Referenced Variables
NOT Cross Referenced Variables
2007-09-07 14
Substation Automation and Protection Training
CAP 531 Graphic Buttons
Zoom Out Zoom In Select Zoom Area Select Mark Mode
ABB Power Technologies AB, 2007
Create Variable Insert Function Block Free Text
Select Drawing Mode
2007-09-07 15
Substation Automation and Protection Training
CAP 531 CAD Features
ABB Power Technologies AB, 2007 2007-09-07 16
Substation Automation and Protection Training
CAP 531 Insert a Template
ABB Power Technologies AB, 2007 2007-09-07 17
Substation Automation and Protection Training
CAP 531 Page Layout
With CAP 531 you have the possibility to associate a page layout to your drawing with all the important data: - customer name - issue date - drawing number - etc. It is also possible to customize the page layout according to your customer needs.
ABB Power Technologies AB, 2007 2007-09-07 18
Substation Automation and Protection Training
CAP 531 Page Layout
From Page Preview you can see how the drawing will be printed out:
ABB Power Technologies AB, 2007 2007-09-07 19
Substation Automation and Protection Training
CAP 531 Compiling the Configuration
When the Application Configuration is ready you have to compile it Note: The Graphic Application Configuration does not contain any Input/Output information. It only contains VIRTUAL I/O information!
ABB Power Technologies AB, 2007 2007-09-07 20
Substation Automation and Protection Training
CAP 531 Downloading the Configuration
The successfully compiled configuration can be downloaded into the IED:
ABB Power Technologies AB, 2007 2007-09-07 21
Substation Automation and Protection Training
CAP 531 Downloading Phase
1) Secret Upload Options (reading)
2) Download of operative configuration
(writing)
ABB Power Technologies AB, 2007 2007-09-07 22
Substation Automation and Protection Training
CAP 531 Downloading Phase
3) Uploading of configuration (reading)
4) Comparing PC configuration against uploaded one
ABB Power Technologies AB, 2007 2007-09-07 23
Substation Automation and Protection Training
CAP 531 Downloading Phase
5) If Compare is not Ok you are requested to download again
6) If Compare is Ok : Download of graphic information of configuration (the so called zip file) (writing)
ABB Power Technologies AB, 2007 2007-09-07 24
Substation Automation and Protection Training
CAP 531 Exit CAP531 and go back to PCM 600
When you exit CAP 531 containing a successfully compiled configuration, the list of used functions is associated to your IED in PCM 600 structure.
ABB Power Technologies AB, 2007 2007-09-07 25
Substation Automation and Protection Training
CAP 531 Uploading application configuration from IED
UPLOAD THE CONFIGURATION
ABB Power Technologies AB, 2007
You can upload the graphic configuration from the terminal into the PC.
2007-09-07 26
Substation Automation and Protection Training
CAP 531 Uploading application configuration from IED
ABB Power Technologies AB, 2007
COMPILE and EXIT CAP531!
2007-09-07 27 Substation Automation and Protection Training
CAP 531 Uploading application configuration from IED This happens while you exit CAP531:
ABB Power Technologies AB, 2007 2007-09-07 28
Substation Automation and Protection Training
CAP 531 Compare Configurations
CAP 531 has the possibility to compare the configuration located into the PC with the configuration stored into the terminal. This process is very useful to check if the configuration stored in the terminal is the same configuration which was downloaded during the commissioning or during the last download.
ABB Power Technologies AB, 2007 2007-09-07 29
Substation Automation and Protection Training
CAP 531 Compare Configurations
If these two different configurations will be compared, a window with the list of differences will be produced:
ABB Power Technologies AB, 2007 2007-09-07 30
Substation Automation and Protection Training
CAP531 On-line/Debug
ABB Power Technologies AB, 2007 2007-09-07 31
Substation Automation and Protection Training