Floating Neutral Impacts in Power Distribution
Floating Neutral Impacts in Power Distribution
Flo ating Ne utral Imp ac ts in Po we r Dis trib utio n (p ho to b y Mard ix Limite d ; Fic kr)
Introduction
If the Neutral Conductor is opened, broke or lost at either of its source side (Distribution Transformer, Generator or at Load side Distribution Panel of Consumer), the distribution systems neutral conductor will float or lose its ref erence ground Point. T he f loating neutral condition can cause voltages to f loat to a maximum of its Phase volts RMS relative to ground, subjecting to its unbalancing load Condition. Floating Neutral conditions in the power network have dif f erent impact depending on the type of Supply, type of installation and Load balancing in the Distribution. Broken Neutral or Loose Neutral would damage to the connected load or create hazardous Touch Voltage at equipment body. Here We are trying to understand the Floating Neutral Condition in T-T distribution System.
As the Potential of such an isolated Star Point or Neutral Point is always changing and not f ixed so its called Floating Neutral.
negative. T his gets more complicated in three phase power, because now we have to consider phase angle, but the concept is exactly the same. If we are connected in Star connection with a neutral, then the neutral conductor will have zero current on it only if the three phases have the same current on each. If we do vector analysis on this, adding up sin(x), sin(x+120), and sin(x+240), we get zero . T he same thing happens when we are delta connected, without a neutral, but then the imbalance occurs out in the distribution system, beyond the service transf ormers, because the distribution system is generally a Star Connected. T he neutral should never be connected to a ground except at the point at the service where the neutral is initially grounded (At Distribution Transformer). T his can set up the ground as a path f or current to travel back to the service. Any break in the ground path would then expose a voltage potential. Grounding the neutral in a 3 phase system helps stabilize phase voltages. A non-grounded neutral is sometimes ref erred to as a floating neutral and has a f ew limited applications.
Sometimes broken neutrals can be indicated by f lickering lights or tingling taps. If you have f lickering lights or tingly taps in your home, you may be at risk of serious injury or even death.
Low Reading
If Neutral to ground voltage is low at the receptacle than system is healthy, If It is high, then you still have to determine if the problem is mainly at the branch circuit level, or mainly at the panel level. Neutral to ground voltage exists because of the IR drop of the current traveling through the neutral back to the Neutral to ground bond. If the system is correctly wired, there should be no Neutral to Ground bond except at the source transf ormer (at what the NEC calls the source of the Separately Derived System, or SDS, which is usually a transf ormer). Under this situation, the ground conductor should have virtually no current and theref ore no IR drop on it. In ef f ect, the ground wire is available as a long test lead back to the Neutral to ground bond.
High Reading:
A high reading could indicate a shared branch neutral, i.e., a neutral shared between more than one branch circuits. T his shared neutral simply increases the opportunities f or overloading as well as f or one circuit to af f ect another.
Zero Reading:
A certain amount of Neutral to ground voltage is normal in a loaded circuit. If the reading is stable at close to 0V. T here is a suspect an illegal Neutral to ground bond in the receptacle (of ten due to lose strands of the neutral touching some ground point) or at the subpanel. Any Neutral to ground bonds other than those at the transf ormer source (and/or main panel) should be removed to prevent return currents f lowing through the ground conductors. Top
upon the load balancing of the system. T his type of Neutral Floating may damage the customer equipment connected to the Supply. Under normal condition current f low f rom Phase to Load to Load to back to the source (Distribution Transf ormer). When Neutral is broken current f rom Red Phase will go back to Blue or Yellow phase resulting Line to Line voltage between Loads. Some customer will experience Overvoltage while some will experience Low voltage.
4) High Eart hing Resist ance of Neut ral at Dist ribut ion Transf ormer:
Good Earthing Resistance of Earth Pit of Neutral provide low resistance path for neutral current to drain in earth. High Earthing Resistance may provide high resistance Path f or grounding of Neutral at Distribution Transf ormer. Limit earth resistance suf f iciently low to permit adequate f ault current f or the operation of protective devices in time and to reduce neutral shif ting.
linear loads. T he problem is that zero sequence current From nonlinear loads, primarily third harmonic, will add up arithmetically and return on the neutral. In addition to being a potential saf ety problem because of overheating of an undersized neutral, the extra neutral current creates a higher Neutral to ground voltage. T his Neutral to ground voltage subtracts f rom the Line to Neutral voltage available to the load. If youre starting to f eel that shared neutrals are one of the worst ideas that ever got translated to copper.
the artif icial resulting neutral will be f loating, such that the voltages present at the dif f erent equipments will no longer be 240V but somewhere between 0 (not exactly) and the 440 V (also not exactly). Meaning that on one line Phase to Phase, some will have less than 240V and some will have higher up to near 415. All depends on the impedance of each connected item. In an unbalance system, if the neutral is disconnected f rom the source, the neutral becomes f loating neutral and it is shif ted to a position so that it is closer to the phase with higher loads and away f rom the phase with smaller load. Let us assume an unbalance 3 phase system has 3 KW load in R-phase, 2 KW load in Y-phase and 1 KW load in B-phase. If the neutral of this system is disconnected f rom the main, the f loating neutral will be closer to R-phase and away f rom B-phase. So, the loads with B-phase will experience more voltage than usual, while the loads in R-phase will experience less voltage. Loads in Y-phase will experience almost same voltage. T he neutral disconnect f or an unbalanced system is dangerous to the loads. Because of the higher or lower voltages, the equipment is most likely to be damaged. Here we observe that Neutral Floating condition does not impact on 3 Phase Load but It impacts only 1 Phase Load only Top
Conclusion
A Floating Neutral ( Disconnected Neutral) f ault condition is VERY UNSAFE because If appliance is not working and someone who does not know about the Neutral Floating could easily touch the Neutral wire to f ind out why appliances does not work when they are plugged into a circuit and get a bad shock. Single phase Appliances are design to work its normal Phase Voltage when they get Line Voltage Appliances may Damage. Disconnected Neutral f ault is a very unsaf e condition and should be corrected at the earliest possible by troubleshooting of the exact wires to check and then connect properly. Published at Electrical Notes & Articles