System Report - Shadi Khel C1
System architecture
PV Array 4.8 kW
Battery 12 Hoppecke 10 OPzS 1000
Inverter 1.9 kW
Rectifier 1.9 kW
Electrical
Component
Production Fraction
(kWh/yr)
PV array 7,448 100%
Total 7,448 100%
Load
Consumption Fraction
(kWh/yr)
AC primary load 3,052 100%
Total 3,052 100%
Quantity Value Units
Excess electricity 3,694 kWh/yr
Unmet load 28.2 kWh/yr
Capacity shortage 33.2 kWh/yr
Renewable fraction 1.000
PV
Quantity Value Units
Rated capacity 4.80 kW
Mean output 0.850 kW
Mean output 20.4 kWh/d
Capacity factor 17.7 %
Total production 7,448 kWh/yr
Quantity Value Units
Minimum output 0.00 kW
Maximum output 4.42 kW
PV penetration 242 %
Hours of operation 4,381 hr/yr
Levelized cost 0.0358 $/kWh
Battery
Quantity Value
String size 12
Strings in parallel 1
Batteries 12
Bus voltage (V) 24
Quantity Value Units
Nominal capacity 24.0 kWh
Usable nominal capacity 16.8 kWh
Autonomy 47.8 hr
Lifetime throughput 41,256 kWh
Battery wear cost 0.000 $/kWh
Average energy cost 0.000 $/kWh
Quantity Value Units
Energy in 2,612 kWh/yr
Energy out 2,249 kWh/yr
Storage depletion 2.39 kWh/yr
Losses 361 kWh/yr
Annual throughput 2,425 kWh/yr
Expected life 17.0 yr
Converter
Quantity Inverter Rectifier Units
Capacity 1.90 1.90 kW
Mean output 0.35 0.00 kW
Minimum output 0.00 0.00 kW
Maximum output 1.85 0.00 kW
Capacity factor 18.3 0.0 %
Quantity Inverter Rectifier Units
Hours of operation 6,152 0 hrs/yr
Energy in 3,392 0 kWh/yr
Energy out 3,052 0 kWh/yr
Losses 339 0 kWh/yr
System Report - Shadi Khel C2
System architecture
PV Array 2.6 kW
Battery 12 Hoppecke 8 OPzS 800
Inverter 1.1 kW
Rectifier 1.1 kW
Electrical
Component
Production Fraction
(kWh/yr)
PV array 4,086 100%
Total 4,086 100%
Load
Consumption Fraction
(kWh/yr)
AC primary load 1,937 100%
Total 1,937 100%
Quantity Value Units
Excess electricity 1,699 kWh/yr
Unmet load 12.5 kWh/yr
Capacity shortage 17.5 kWh/yr
Renewable fraction 1.000
PV
Quantity Value Units
Rated capacity 2.60 kW
Mean output 0.466 kW
Mean output 11.2 kWh/d
Capacity factor 17.9 %
Total production 4,086 kWh/yr
Quantity Value Units
Minimum output 0.00 kW
Maximum output 2.40 kW
PV penetration 210 %
Hours of operation 4,381 hr/yr
Levelized cost 0.0353 $/kWh
Battery
Quantity Value
String size 12
Strings in parallel 1
Batteries 12
Bus voltage (V) 24
Quantity Value Units
Nominal capacity 19.2 kWh
Usable nominal capacity 13.4 kWh
Autonomy 60.4 hr
Lifetime throughput 32,904 kWh
Battery wear cost 0.000 $/kWh
Average energy cost 0.000 $/kWh
Quantity Value Units
Energy in 1,697 kWh/yr
Energy out 1,461 kWh/yr
Storage depletion 1.56 kWh/yr
Losses 234 kWh/yr
Annual throughput 1,575 kWh/yr
Expected life 20.0 yr
Converter
Quantity Inverter Rectifier Units
Capacity 1.10 1.10 kW
Mean output 0.22 0.00 kW
Minimum output 0.00 0.00 kW
Maximum output 1.10 0.00 kW
Capacity factor 20.1 0.0 %
Quantity Inverter Rectifier Units
Hours of operation 6,172 0 hrs/yr
Energy in 2,152 0 kWh/yr
Energy out 1,937 0 kWh/yr
Losses 215 0 kWh/yr
System Report - Shadi Khel C3
System architecture
PV Array 3.7 kW
Battery 12 Hoppecke 8 OPzS 800
Inverter 1.5 kW
Rectifier 1.5 kW
Electrical
Component
Production Fraction
(kWh/yr)
PV array 5,741 100%
Total 5,741 100%
Load
Consumption Fraction
(kWh/yr)
AC primary load 2,418 100%
Total 2,418 100%
Quantity Value Units
Excess electricity 2,761 kWh/yr
Unmet load 20.6 kWh/yr
Capacity shortage 25.4 kWh/yr
Renewable fraction 1.000
PV
Quantity Value Units
Rated capacity 3.70 kW
Mean output 0.655 kW
Mean output 15.7 kWh/d
Capacity factor 17.7 %
Total production 5,741 kWh/yr
Quantity Value Units
Minimum output 0.00 kW
Maximum output 3.41 kW
PV penetration 235 %
Hours of operation 4,381 hr/yr
Levelized cost 0.00644 $/kWh
Battery
Quantity Value
String size 12
Strings in parallel 1
Batteries 12
Bus voltage (V) 24
Quantity Value Units
Nominal capacity 19.2 kWh
Usable nominal capacity 13.4 kWh
Autonomy 48.3 hr
Lifetime throughput 32,904 kWh
Battery wear cost 0.000 $/kWh
Average energy cost 0.000 $/kWh
Quantity Value Units
Energy in 2,121 kWh/yr
Energy out 1,826 kWh/yr
Storage depletion 2.10 kWh/yr
Losses 293 kWh/yr
Annual throughput 1,969 kWh/yr
Expected life 16.7 yr
Converter
Quantity Inverter Rectifier Units
Capacity 1.50 1.50 kW
Mean output 0.28 0.00 kW
Minimum output 0.00 0.00 kW
Maximum output 1.50 0.00 kW
Capacity factor 18.4 0.0 %
Quantity Inverter Rectifier Units
Hours of operation 6,152 0 hrs/yr
Energy in 2,686 0 kWh/yr
Energy out 2,418 0 kWh/yr
Losses 269 0 kWh/yr
System Report - Shadi Khel C4
System architecture
PV Array 5.1 kW
Battery 12 Hoppecke 12 OPzS 1500
Inverter 2.5 kW
Rectifier 2.5 kW
Cost summary
Total net present cost $ 24,193
Levelized cost of energy $ 0.508/kWh
Operating cost $ 1,893/yr
Electrical
Component
Production Fraction
(kWh/yr)
PV array 7,919 100%
Total 7,919 100%
Load
Consumption Fraction
(kWh/yr)
AC primary load 3,724 100%
Total 3,724 100%
Quantity Value Units
Excess electricity 3,334 kWh/yr
Unmet load 35.5 kWh/yr
Capacity shortage 41.2 kWh/yr
Renewable fraction 1.000
PV
Quantity Value Units
Rated capacity 5.10 kW
Mean output 0.904 kW
Mean output 21.7 kWh/d
Capacity factor 17.7 %
Total production 7,919 kWh/yr
Quantity Value Units
Minimum output 0.00 kW
Maximum output 4.70 kW
PV penetration 211 %
Hours of operation 4,381 hr/yr
Levelized cost 0.0357 $/kWh
Battery
Quantity Value
String size 12
Strings in parallel 1
Batteries 12
Bus voltage (V) 24
Quantity Value Units
Nominal capacity 36.0 kWh
Usable nominal capacity 25.2 kWh
Autonomy 58.7 hr
Lifetime throughput 61,632 kWh
Battery wear cost 0.000 $/kWh
Average energy cost 0.000 $/kWh
Quantity Value Units
Energy in 3,218 kWh/yr
Energy out 2,771 kWh/yr
Storage depletion 2.99 kWh/yr
Losses 444 kWh/yr
Annual throughput 2,988 kWh/yr
Expected life 20.0 yr
Converter
Quantity Inverter Rectifier Units
Capacity 2.50 2.50 kW
Mean output 0.43 0.00 kW
Minimum output 0.00 0.00 kW
Maximum output 2.33 0.00 kW
Capacity factor 17.0 0.0 %
Quantity Inverter Rectifier Units
Hours of operation 6,189 0 hrs/yr
Energy in 4,138 0 kWh/yr
Energy out 3,724 0 kWh/yr
Losses 414 0 kWh/yr
System Report - Shadi Khel C5
System architecture
PV Array 2.6 kW
Battery 12 Hoppecke 8 OPzS 800
Inverter 1.1 kW
Rectifier 1.1 kW
Cost summary
Total net present cost $ 20,064
Levelized cost of energy $ 0.812/kWh
Operating cost $ 1,570/yr
Electrical
Component
Production Fraction
(kWh/yr)
PV array 4,035 100%
Total 4,035 100%
Load
Consumption Fraction
(kWh/yr)
AC primary load 1,933 100%
Total 1,933 100%
Quantity Value Units
Excess electricity 1,651 kWh/yr
Unmet load 15.7 kWh/yr
Capacity shortage 21.2 kWh/yr
Renewable fraction 1.000
PV
Quantity Value Units
Rated capacity 2.60 kW
Mean output 0.461 kW
Mean output 11.1 kWh/d
Capacity factor 17.7 %
Total production 4,035 kWh/yr
Quantity Value Units
Minimum output 0.00 kW
Maximum output 2.39 kW
PV penetration 207 %
Hours of operation 4,381 hr/yr
Levelized cost 0.0286 $/kWh
Battery
Quantity Value
String size 12
Strings in parallel 1
Batteries 12
Bus voltage (V) 24
Quantity Value Units
Nominal capacity 19.2 kWh
Usable nominal capacity 13.4 kWh
Autonomy 60.4 hr
Lifetime throughput 32,904 kWh
Battery wear cost 0.000 $/kWh
Average energy cost 0.000 $/kWh
Quantity Value Units
Energy in 1,695 kWh/yr
Energy out 1,459 kWh/yr
Storage depletion 1.57 kWh/yr
Losses 234 kWh/yr
Annual throughput 1,574 kWh/yr
Expected life 20.0 yr
Converter
Quantity Inverter Rectifier Units
Capacity 1.10 1.10 kW
Mean output 0.22 0.00 kW
Minimum output 0.00 0.00 kW
Maximum output 1.10 0.00 kW
Capacity factor 20.1 0.0 %
Quantity Inverter Rectifier Units
Hours of operation 6,164 0 hrs/yr
Energy in 2,148 0 kWh/yr
Energy out 1,933 0 kWh/yr
Losses 215 0 kWh/yr
System Report - Shadi Khel C6
System architecture
PV Array 2.1 kW
Battery 12 Hoppecke 6 OPzS 300
Inverter 0.7 kW
Rectifier 0.7 kW
Electrical
Component
Production Fraction
(kWh/yr)
PV array 3,263 100%
Total 3,263 100%
Load
Consumption Fraction
(kWh/yr)
AC primary load 1,125 100%
Total 1,125 100%
Quantity Value Units
Excess electricity 1,882 kWh/yr
Unmet load 10.4 kWh/yr
Capacity shortage 12.4 kWh/yr
Renewable fraction 1.000
PV
Quantity Value Units
Rated capacity 2.10 kW
Mean output 0.372 kW
Mean output 8.94 kWh/d
Capacity factor 17.7 %
Total production 3,263 kWh/yr
Quantity Value Units
Minimum output 0.00 kW
Maximum output 1.94 kW
PV penetration 287 %
Hours of operation 4,380 hr/yr
Levelized cost 0.0357 $/kWh
Battery
Quantity Value
String size 12
Strings in parallel 1
Batteries 12
Bus voltage (V) 24
Quantity Value Units
Nominal capacity 7.20 kWh
Usable nominal capacity 5.04 kWh
Autonomy 38.9 hr
Lifetime throughput 12,168 kWh
Battery wear cost 0.000 $/kWh
Average energy cost 0.000 $/kWh
Quantity Value Units
Energy in 945 kWh/yr
Energy out 814 kWh/yr
Storage depletion 0.842 kWh/yr
Losses 131 kWh/yr
Annual throughput 877 kWh/yr
Expected life 13.9 yr
Converter
Quantity Inverter Rectifier Units
Capacity 0.70 0.70 kW
Mean output 0.13 0.00 kW
Minimum output 0.00 0.00 kW
Maximum output 0.68 0.00 kW
Capacity factor 18.3 0.0 %
Quantity Inverter Rectifier Units
Hours of operation 6,137 0 hrs/yr
Energy in 1,250 0 kWh/yr
Energy out 1,125 0 kWh/yr
Losses 125 0 kWh/yr