Protection Devices Price List 2012

This document provides a price list and specifications for various protection relay devices. It lists the protection functions, hardware features, communication capabilities, and optional components available for different relay models. Some key models include the MRA4, MRI4, MRDT4, and MRU4 relays, which provide functions like phase current protection, earth fault protection, transformer differential protection, and voltage and frequency monitoring. The document also outlines options for combined protection and control devices as well as standard protection devices in high tech, professional, and basic lines.

Uploaded by

Valentin Agache
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
399 views6 pages

Protection Devices Price List 2012

This document provides a price list and specifications for various protection relay devices. It lists the protection functions, hardware features, communication capabilities, and optional components available for different relay models. Some key models include the MRA4, MRI4, MRDT4, and MRU4 relays, which provide functions like phase current protection, earth fault protection, transformer differential protection, and voltage and frequency monitoring. The document also outlines options for combined protection and control devices as well as standard protection devices in high tech, professional, and basic lines.

Uploaded by

Valentin Agache
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Price_list_Protection_EPS_PD_2012_EN_Rev.

New 3




Protection devices

MRA4 MRI4 MRDT4 MRU4
Protection functions ANSI
Phase current stages (non-directional) 50/51 6 4
Phase current stages (non-directional and directional) 50/51/67 6
Transformer differential protection (2 windings) 87T 2
Generator differential protection (high stabilized) 87G (64REF) 2
Voltage restrained current protection 51V z
Voltage controlled current function 51C z
Earth current stages (nondirectional) 50N/51N 4 4
Earth current stages (non-directonal and directional) 50N/51N/67N 4
Negative sequence stages (current) 46 2 2 2
Overload protection with thermal replica 49 z z z
Voltage stages 27/59 6 4
Residual voltage stages 59N 2 2
Frequency stages 81 U/O 6 6
Inrush detection IH2 (2
nd
harmonic) z z z
Voltage transformer supervision 60FL z z
Current transformer supervision 60L z z z
Auto reclosing 79 z z
Negative / positive sequence stages (voltage) 47 6 6
Trip/auxiliary function 86 z z z
Circuit breaker failure protection 50 BF z z z
Trip circuit supervision 74TC z z z z
Frequency gradient df/dt (ROCOF) 81R z z
Vector surge 78 z z
Power protection:
P, Q, Qr, S, Pr
32F, 37F, 32Q,
37Q, 37QR,
32S, 37S, 37R
6

Power factor cos (M) 55 2
QU protection (undervoltage- directional reactive power
protection)



Protection parameter sets 4 4 4 4
Reverse interlocking z z z
Event/fault/disturbance recorder z z z z
Measuring functions
Currents: IL1, IL2, IL3, IE, I0, I1, I2,
IL1H2, IL2H2, IL3H2, IEH2

z z z
Thermal overload - z z z
Voltages: VL1, VL2, VL3, VL12, VL23, VL31, VE,
V0, V1, V2

z

z
Frequency f z z
Power: P, Q, S, Pr, PF (cos M), Wp+, Wp-, Wq+, Wq- z
Hardware
Number of binary output relays
1
7 6 7 6
Number of optional binary output relays
1
6/O 6/O
Number of digital inputs
1
8 8 8 8
Number of optional digital inputs*
1
8/O 8/O
Communication
IEC61850 (RJ45 interface) * * * *
MODBUS RTU (via fibre optic (FO) or RS485) O O O O
IEC60870-5-103 (with fibre optic (FO) or RS485) O O O O
Modbus TCP/IEC61850 prepared (RJ45 interface) O O O O
Profibus DP (with LWL or RS485) O O O O
IRIG-B interface (time synchronization) z

O = optional, z = standard,
1
= depends on type of device, * information on availability on request.


4 Price_list_Protection_EPS_PD_2012 EN_Rev. New



Protection devices

MCA4 MRM4 MRMV4 MRGV4*
Protection functions ANSI
Phase current stages (non-directional) 50/51 6 6
Phase current stages (non-directional and directional) 50/51/67 6 6
Transformer differential protection (2 windings) 87T
Voltage restrained current protection 51V z z z
Voltage controlled current function 51C z z z
Earth current stages (nondirectional) 50N/51N 4 4
Earth current stages (non-directonal and directional) 50N/51N/67N 4 4
Negative sequence stages (current) 46 2 2 2 2
Overload protection with thermal replica 49 z z z z
Voltage stages 27/59 6 6 6
Residual voltage stages 59N 2 2 2
Frequency stages 81 U/O 6 6 6
Inrush detection IH2 (2
nd
harmonic) z z
Voltage transformer supervision 60FL z z z
Current transformer supervision 60L z z z z
Auto reclosing 79 z
Negative / positive sequence stages (voltage) 47 6 6 6
Trip/auxiliary function 86 z z z z
Circuit breaker failure protection 50 BF z z z z
Trip circuit supervision 74TC z z z z
Frequency gradient df/dt (ROCOF) 81R z z z
Vector surge 78 z z z
Power protection:
P, Q, Qr, S, Pr
32F, 37F, 32Q,
37Q, 37QR,
32S, 37S, 37R
6 6 6
Power factor cos (M) 55 2 2 2
QU protection (undervoltage- directional reactive power
protection)

z

z
Synchro Check 25 z z
Motor Start supervision z z
Locked rotor protection 49S/51 2 2
JAM protection 50J z z
I< underload protection steps 37 2 2
Overexcitation V/Hz 24 z
Loss of excitation 40 z
100% stator earth fault protection 59TN/27TN z
Protection parameter sets 4 4 4 4
Reverse interlocking z z z z
Event/fault/disturbance recorder z z z z
Start/trend recording z z
Control
Control function for up to 6 switchgears z
Control function for 1 switchgear z z
Logic (up to 80 equations) z z z


Price_list_Protection_EPS_PD_2012_EN_Rev. New 5



MCA4 MRM4 MRMV4 MRGV4*
Measuring functions
ANSI

Currents: IL1, IL2, IL3, IE, I0, I1, I2,
IL1H2, IL2H2, IL3H2, IEH2

z z z z
Thermal overload - z z z z
Voltages: VL1, VL2, VL3, VL12, VL23, VL31, VE,
V0, V1, V2

z z z
Frequency f z z z
Power: P, Q, S, Pr, PF (cos M), Wp+, Wp-, Wq+, Wq- z z z
Hardware
Number of binary output relays
1
7 6
1
/4
1
7 11
Number of optional binary output relays
1
6/O 6/O
Number of digital inputs
1
8 8
1
/4
1
8 16
Number of optional digital inputs*
1
8/O
Number of analogue inputs and outputs 0/1
1
0/4 2/2
Communication
IEC61850 (RJ45 interface) O * O O
MODBUS RTU (via fibre optic (FO) or RS485) O O O O
IEC60870-5-103 (with fibre optic (FO) or RS485) O O O O
Modbus TCP/IEC61850 prepared (RJ45 interface) O O O O
Profibus DP (with LWL or RS485) O O O O
IRIG-B interface (time synchronization) z z z z

O = optional, z = standard,
1
= depends on type of device, * information on availability on request.


6 Price_list_Protection_EPS_PD_2012 EN_Rev. New


System Line


O = Optional z = Standard
Combined protection and control devices
CSP2-F5 CSP2-L CSP2-T25
Protection functions ANSI
Phase current (nondirectional) Number of stages 50/51 3 2 2
Phase current (directional) Number of stages 50/51/67 3 2 2
Earth fault (nondirectional) Number of stages 50N/51N 2 2 2
Earth fault (directional) Number of stages 67N 2 2 2
Restricted Earth Fault Number of stages 64REF 2
Negative sequence (current) Number of stages 46 2
Overload protection with thermal replica 49 z z z
Voltage Number of stages 27/59 2/2 2/2 2/2
Residual voltage Number of stages 59N 2 2 2
Overexcitation (u/f) 24 2
Voltage transformer supervision (fuse failure) z z z
Frequency Number of stages 81 4 4
Power Number of stages 32 F/R 2/2
Differential protection 87 Cable Transformer
Auto reclosing (AR) 79 z z z
AR fast trip z z z
AR-Start by Non-Corresponding of CB z z z
Switch onto fault protection (SOTF) z z z
Trip-/Auxiliary function 86 z z z
Control circuit supervision (incl. trip circuit) (CCS) 74 TC z z z
Circuit breaker failure protection (CBF) 50 BF z z z
Programmable protection logic z z z
Programmable logic functions z z z
Parameter switch z z z
Backward interlocking z z z
Fault recorder
(Optionally with extended storage range)
z z z
Measuring functions
Phase currents z z z
Earth current z z z
Negative sequence current z
Differential currents z z
Stabilizing currents z z
Phase-to-phase voltages z z z
Phase-to-neutral voltages z z z
Frequency z z z
Power z
Power factor z
Energy counter z
Analog temperature measuring z
Statistic measuring functions
Currents z z z
Voltages z z z
Frequency z z z
Power z *
Switching cycles z z z
Sum of short circuit currents z z z
Control functions
Local/remote control (by key switches) z z z
Number of controllable switching devices 5 3 5
Number of recordable switching devices 5 5 5
Number of signal relays 10 6 6
Number of configurable inputs 16 12 16
Commands outputs with defined switching and operation
times
z z z
Supervision functions
Fault/differential position z z z
Programmable field interlocking z z z
Tap changer monitoring z
Communication
IEC 60870-5-103 (Optional: fibre optic (FO)/RS485) O O O
PROFIBUS DP (Optional: fibre optic (FO)/RS485) O O O
MODBUS RTU (Optional: fibre optic (FO)/RS485) O O O
Price_list_Protection_EPS_PD_2012_EN_Rev. New 7
High Tech Line/Professional Line/Basic Line

Standard protection devices
Protection functions and features High Tech Line
Professional
Line
Basic Line
Individual functions ANSI MR IR X B
Phase current (nondirectional) 50/51 I* I*
Phase current (directional) 50/51/67 I* RI
Earth fault (nondirectional) 50N/51N I* I* I*
Earth fault (directional) 67N I* I*
Circuit breaker failure protection BF I*

Negative sequence (current) 46 S

S
Voltage 27/59 U* U* U* U
Residual voltage 59N U* U* U*
DC voltage 27DC/39DC U* U*
Phase balance (voltage) 47 U* A A
Frequency 81 F3 F F
Vector surge 78 G
Power 32 P P P
Differential protection 87 D* D*
Rotor earth fault (DC) 64 R R
Auto reclosing 79 K
Trip-/Auxiliary function 86 L
Field failure (Impedance) 40 Q
Exciter failure (DC) 40/76 R E
Trip circuit supervision 74 TC T
Phase sequence 47 U* U*
Speed 14 Z
Combinations
Phase current and earth current
(directional or nondirectional)
50/51/67
50N/51N/67N
I*
Phase current and earth current and
CB failure and AR (nondirectional)
50/51/50N/
51N/BF/79
IK
Phase current and earth current and
thermal replica (nondirectional)
50/51/50N/
51N/49
IT*
Voltage and frequency 27/59/81 UF
Voltage and negative sequence 27/59/47 UA
Mains decoupling (U/f/vector) 27/59/81/78 N3* RN N*
Mains decoupling (U/f/df/dt) 27/59/81 N3* RW N*
Motor protection (various functions)
37/46/48
49/50/51
M* M
Generator protection
27/59/81/78/
50/51/
50N/51N/BF
G*
Line features
Housing technology 19/flush mounting z z
DIN rail installation

z z
Panel mounting O O

Display (measuring values and parameters) z only RW RI RN
Indication of primary measuring values z
1

Interface z O
Setting via buttons z only RW RI RN
Setting via potentiometer z z
Setting via DIP-switches z z

Fault recorder z


Disturbance recorder, clock, 2 parameter sets z
1

Number of output relays 5 1 or 2 2 2
Password protection z

with software

Parameter software (HTL/PLSoft4) O

* Various types with this prefix z = Standard O = Optional
1
with High Tech Line devices type MR_3 only

8 Price_list_Protection_EPS_PD_2012 EN_Rev. New
Wi Line


Self powered time overcurrent
protection relays
Protection functions
and features
WIB1 WIC1 WIP1 WIM1
Single functions ANSI
Phase current (independent) 50/51 z z z z
Phase current (multi-characteristic) 50/51 z z z z
Short circuit protection 50/51 z z z z
Number of overcurrent elements z z 2 2
Earth current (multi-characteristic) 50N/51N z O
*1
z
Number of earth current elements 2 1 2
Line features
DIN rail mounting z
Panel mounting z z z z
Primary conductor
Display (Measuring values and
parameters)
z
Setting via PC Software O z
Setting via buttons z
Setting via rotary switch O z
Setting via DIP-switches z O
Setting via code jumpers
Standard CT (1A /5A) 1 A 1 A or 5 A
Special CT (sec. rated current)
Wide
range
Wide
range

Connection for test winding O z
LED activation indicator z z
Rated frequency Hz 50/60 50/60 50/60 50/60
Fault recorder z z z
Clock z
Password protection z z z
Electro impulse-/Relay contact output E E both R or E
Flag indicator output 2 1 1
Number of output relays
W = change-over contact
3W
2/3W
(R-type)
Input remote tripping z z z z
Interface z z O
RS 485 Interface with Pro Open Da-
ta protocol
O
RS 485 Interface with MODBUS RTU
protocol
O
Additional power supply O

z = Standard O = Optional
*1
= only DEFT
*2
= 1-pole