Lecture 7 Three-Phase Transformers
Lecture 7 Three-Phase Transformers
Ahsan Page 1
Lecture 7
Three-phase Transformers
As we have discussed previously:
3-phase generation is usually at 13.2 kV
Transmission 110, 132, 275, 400 and 700 kV
At load centers 6.6 kV, 4.6 kV, 2.3 kV
Utilization voltages 440 V, 220 V, 110 V.
Three-phase transformers are used quite
extensively in transmission and
distribution circuits of a power system.
Common points of utilization are:
a) Between generators are
transmission systems
b) Between transmission and
subtransmission systems
c) Between subtransmission and
distribution systems.
Fig: 3-Phase Real Power Transformer
Fig: Diagram of an electrical system
Dr. Ahsan Page 2
The primary and secondary windings may be connected in either star or delta
configurations. As a result, four types of three-phase transformers are in common use:
1. Wye-wye (Y-Y) (i) most economical for small, high voltage transformer,
less insulation is required as
2. Wye-delta (Y-) step-down, distribution transformer
3. Delta-wye (-Y) step-up, generation station transformer
4. Delta-delta (-) (i) economical for large, low voltage transformer (ii) no
internal phase shift (iii) open-delta V-V operation.
Formation of Three-phase Transformers
Three single-phase transformers
connected in a three-phase bank
Three sets of windings wrapped on a
common core
Dr. Ahsan Page 3
( ) a Y Y
A
B
C
N
I
a
aV
3
aV
a
b
c
n
I
V
3
V
A
B
C
a
b
c
n
I
V
3
V
( ) d Y
3
aV
3I
a
I
a
a
b
c
( ) c Y
A
B
C
V
aV
I
a
3
I
a
3
I
( ) b Y
A
B
C
N
a
b
c
3
I
3
I
a
I
3aV
V
aV
Dr. Ahsan Page 4
Advantages of 3-phase Transformer
As compared to a bank of single-phase transformers, the main advantages of a three-
phase transformer are:
(i) It occupies less floor space for equal rating
(ii) Weighs less
(iii) Costs about 15% less, and further
(iv) Only one unit is to be handled and connected
Disadvantages:
One main drawback in a three-phase transformer is that if one phase becomes
disabled, then the whole transformer has to be removed from service for repairs ( the
shell type may be operated open V but this is not always feasible).
However, in the case of a 3-phase bank of single-phase transformers, if one
transformer goes out of order, the system can still be run open- at reduced capacity
or the faulty transformer can be replaced by a single spare.