SMC Flex With Datalinks - D735 Devicenet - Option

SMC-Flex only supports 16-bit Datalinks. Device can be configured to return up to 8 additional pieces of parameter information.

Uploaded by

Sergio Suarez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
606 views5 pages

SMC Flex With Datalinks - D735 Devicenet - Option

SMC-Flex only supports 16-bit Datalinks. Device can be configured to return up to 8 additional pieces of parameter information.

Uploaded by

Sergio Suarez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

SMC-Flex Datalink Configuration Reference 1/9/2012

SMC-Flex Datalink Configuration



Datalinks are supported in the SMC-Flex. A Datalink is mechanism used by most drives to
transfer data to and from the controller without using an Explicit Message. The SMC-Flex
only supports 16-bit Datalinks, therefore the device can be configured to return up to 8
additional pieces of parameter information. By default the 8 parameters (parameter# 1, 2,
3, 4, 5, 6, 11, 12) are returned in the I/O message when all 4 output Datalinks are
configured. These parameters identify the following values:
Parameter #1 = Voltage Phase A-B
Parameter #2 = Voltage Phase B-C
Parameter #3 = Voltage Phase C-A
Parameter #4 = Current Phase A
Parameter #5 = Current Phase B
Parameter #6 = Current Phase C
Parameter #11 = Power Factor
Parameter #12= Motor Thermal Usage (MTU)

Keep in mind that the returned parameters can be changed by simply changing the values in
programmed in parameters #89 through #103. Also, only output Datalinks are configured by
default. Input Datalinks can be configured, but have limited functionality when used with
the SMC-Flex.

The following example uses all 4 Datalinks. The communication interface used is the 20-
Comm-D DPI to DeviceNet module.



SMC-Flex Datalink Configuration Reference 1/9/2012


SMC-Flex Datalink Configuration Reference 1/9/2012

The next step in the configuration is to enable the 20-Comm-D to allow the Datalinks. To do
this the following parameters in the 20-Comm-D need to be configured. Depending on the
configuration tool you are using, these parameters values may be different. The example is
shown using RSNetWorx for DeviceNet:

Parameter #148 DPI I/O Cfg Enable each of the Datalinks being used.
Parameter #160 M-S Input Enable each of the Datalinks being used.
Parameter #161 M-S Output Enable each of the Datalinks being used.



SMC-Flex Datalink Configuration Reference 1/9/2012






















SMC-Flex Datalink Configuration Reference 1/9/2012

The last step in mapping the information to the scanner/controller is to select the
appropriate message size. Below is a table that describes the correct I/O size depending on
the number of Datalinks enabled.
Rx
Size
Tx
Size
Logic Status /
Command (16bit)
Reference /
FeedBack (16bit)
DataLinks
A B C D
4 4 x x
8 8 x x x
12 12 x x x x
16 16 x x x x x
20 20 x x x x x x

With the SMC-Flex in the Scanlist insure that the I/O information is correct by selecting
the Edit I/O Parameters. A sample screen is shown below. If these values are different
than what is desired, change them and then click O.K. This may cause some information to
be re-mapped so make sure that you are aware of where it is being mapped.



In this case the output information from the SMC-Flex has been mapped into the following
locations. Keep in mind that the ControlLogix platform is separated into 32-bit words.


DeviceNet Scanner View
from RSNetWorx
ControlLogix Memory Table
from RSLogix5000