TI00434P/00/EN/18.14
71241482
Technical Information
Deltabar M PMD55
Differential pressure measurement
Differential pressure transmitter with metal sensor; communication via HART,
PROFIBUS PA or FOUNDATION Fieldbus
Application
The Deltabar M differential pressure transmitter is used for the
following measuring tasks:
Flow measurement (volume or mass flow) in conjunction with
primary elements in gases, vapours and liquids
Level, volume or mass measurement in liquids
Differential pressure monitoring, e.g. of filters and pumps
Your benefits
Reference accuracy: 0.1%
as PLATINUM version: up to 0.075%
Turn down up to 100:1
Compact transmitter design
Quick commissioning via DIP switches
Easy and safe menu-guided operation
onsite via display module
via 4 to 20 mA with HART
via PROFIBUS PA
via FOUNDATION Fieldbus
Continuous modularity for differential pressure, hydrostatic
and pressure (Deltabar M, Deltapilot M Cerabar M), e.g.
replaceable display
universal electronics
International usage thanks to a wide range of approvals
Used for process pressure monitoring up to SIL2,
certified to IEC 61508 Edition 2.0 and IEC 61511 by
TV NORD
Deltabar M PMD55
2 Endress+Hauser
Table of contents
Document information. . . . . . . . . . . . . . . . . . . . . . . . . . .4
Document conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Terms and abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Function and system design . . . . . . . . . . . . . . . . . . . . . .7
Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Level measurement (level, volume and mass) . . . . . . . . . . . . . . 7
Flow measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Communication and data processing . . . . . . . . . . . . . . . . . . . . 10
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Signal range 4 to 20 mA HART . . . . . . . . . . . . . . . . . . . . . . . 12
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Load 4 to 20 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Dead time, Time constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Dynamic behavior: current output . . . . . . . . . . . . . . . . . . . . . . . 13
Dynamic behavior:
digital output (HART electronics) . . . . . . . . . . . . . . . . . . . . . . . 13
Dynamic behavior: PROFIBUS PA . . . . . . . . . . . . . . . . . . . . . . . 13
Dynamic behavior: FOUNDATION Fieldbus . . . . . . . . . . . . . . . 14
Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Firmware version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Protocol-specific data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Data of the FOUNDATION Fieldbus interface . . . . . . . . . . . . . 16
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Device plug connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Startup current HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Residual ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Influence of power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Performance characteristics . . . . . . . . . . . . . . . . . . . . 22
Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . 22
Long-term stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Influence of the installation position . . . . . . . . . . . . . . . . . . . . 22
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Reference accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Total performance: current output . . . . . . . . . . . . . . . . . . . . . . 23
Total Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Warm-up period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Thermal stability current output . . . . . . . . . . . . . . . . . . . . . . . . 24
Influence of the static pressure . . . . . . . . . . . . . . . . . . . . . . . . . 24
Vibration effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
General installation instructions . . . . . . . . . . . . . . . . . . . . . . . . 25
Measuring arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Wall and pipe-mounting (optional) . . . . . . . . . . . . . . . . . . . . . 26
Oxygen applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
PWIS cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Ultra pure gas applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Storage temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Climate class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Electromagnetic compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Overvoltage protection (optional) . . . . . . . . . . . . . . . . . . . . . . . 30
Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Process temperature limits (temperature at transmitter) . . . 31
Process temperature range, Seals . . . . . . . . . . . . . . . . . . . . . . . 31
Pressure specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Mechanical construction . . . . . . . . . . . . . . . . . . . . . . . 32
Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Process connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Dimensions V1 version; Impulse pipe vertical; alignment 90 33
Dimensions H1 version; Impulse pipe horizontal;
alignment 180 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Dimensions H2 version; Impulse pipe horizontal; alignment 90
35
Materials not in contact with process . . . . . . . . . . . . . . . . . . . . 36
Materials in contact with process . . . . . . . . . . . . . . . . . . . . . . . 37
Operability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Operating languages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
System integration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Certificates and approvals . . . . . . . . . . . . . . . . . . . . . . 42
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Ex approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Marine certificate (in preparation) . . . . . . . . . . . . . . . . . . . . . 42
Functional safety SIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
AD2000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
CRN approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Pressure Equipment Directive (PED) . . . . . . . . . . . . . . . . . . . . . 42
Standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
North-American practice for
installation of process seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Inspection certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Calibration; Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3 Endress+Hauser
Deltabar M PMD55
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Configuration data sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Additional documentation . . . . . . . . . . . . . . . . . . . . . . 47
Field of Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Brief operating instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Functional safety manual (SIL) . . . . . . . . . . . . . . . . . . . . . . . . . 47
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Installation/Control Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Combined certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . . . 50
HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
FOUNDATION Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Deltabar M PMD55
4 Endress+Hauser
Document information
Document conventions Safety symbols
Electrical symbols
Tool symbols
Symbol Meaning
A0011189-EN
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
A0011190-EN
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
A0011191-EN
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or moderate injury.
A0011192-EN
NOTE!
This symbol contains information on procedures and other facts, which do not result in
personal injury.
Symbol Meaning
A0018335
Direct current
A terminal at which DC voltage is present or through which direct current flows.
A0018336
Alternating current
A terminal at which AC voltage is present or through which alternating current flows.
A0018337
Direct current and alternating current
A terminal at which AC voltage or DC voltage is present.
A terminal through which alternating current or direct current flows.
A0018338
Ground connection
A grounded terminal which, from the operator's point of view, is grounded
via a grounding system.
A0018339
Protective ground connection
A terminal that must be connected to ground before other connections may be
established.
A0011201
Equipotential connection
A connection that must be made with the plant grounding system; depending on national
or company codes of practice, this may be a potential matching line or a star-shaped
grounding system, for example.
Symbol Meaning
A0011219
Phillips head screwdriver
A0011220
Flat blade screwdriver
A0013442
Torx screwdriver
A0011222
Hexagon wrench
A0011221
Allen key
GEFAHR
WARNUNG
VORSICHT
HINWEIS
Deltabar M PMD55
Endress+Hauser 5
Symbols for types of information
Symbols in graphics
Symbol Meaning
A0011182
Allowed
Indicates procedures, processes or actions that are allowed.
A0011183
Preferred
Indicates procedures, processes or actions that are preferred.
A0011184
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011193
Tip
Indicates additional information.
A0015483
Reference to documentation
Refers to the relevant device documentation.
A0015484
Reference to page
Refers to the relevant page number.
A0015486
Reference to graphics
Refers to the relevant graphic number and page number.
, , ... Series of steps
A0015488
Help in the event of a problem
Symbol Meaning
1, 2, 3, 4, ... Numbering for main positions
, , ... Series of steps
A, B, C, D, ... Views
A-A, B-B, ... Sections
A0011187
Hazardous area
Indicates a hazardous area.
A0011188
Safe area (non-hazardous area)
Indicates a non-hazardous area.
-
.
Deltabar M PMD55
6 Endress+Hauser
Terms and abbreviations
Term/abbreviation Explanation
MWP The MWP (maximum working pressure) for the individual
sensors depends on the lowest-rated element, with regard to
pressure, of the selected components, i.e. the process
connection must be taken into account in addition to the
measuring cell. Also observe the pressure-temperature
dependency. For the relevant standards and additional
information, see the " 31" section.
OPL The OPL (over pressure limit) for the sensor depends on the
lowest-rated element, with regard to pressure, of the selected
components, i.e. the process connection must be taken into
account in addition to the measuring cell. Also observe the
pressure-temperature dependency. For the relevant standards
and additional information, see the " 31" section.
LRL Lower range limit
URL Upper range limit
LRV Lower range value
URV Upper range value
TD Turn Down (TD)
Case 1:
|Lower range value| s |Upper range value|
Example:
Lower range value (LRV) = 0 mbar
Upper range value (URV) = 100 mbar
(1.5 psi)
Nominal value (URL) = 500 mbar (7.5 psi)
Turn down:
TD = URL / |URV| = 5:1
set span:
URV LRV = 100 mbar (1.5 psi)
This span is based on the zero point.
A0019783
Example: 500 mbar (7.5 psi) sensor
Case 2:
|Lower range value| > |Upper range value|
Example:
Lower range value (LRV) = 300 mbar
(-4.5 psi)
Upper range value (URV) = 0 bar
Nominal value (URL) = 500 mbar (7.5 psi)
Turn down:
TD = URL / |(LRV)| = 1.67:1
set span:
URV LRV = 300 mbar (4.5 psi)
This span is based on the zero point.
A0016451
Example: 500 mbar (7.5 psi) sensor
1 Set span
2 Zero based span
3 Nominal value upper range limit (URL)
4 Nominal measuring range
5 Sensor measuring range
LRV URL URV LRL
1 = 2
3
4
5
LRV URL URV LRL
1 = 2
3
4
5
Deltabar M PMD55
Endress+Hauser 7
Function and system design
Measuring principle
A0023081
Measuring cell of the Deltabar M
1 Sensing element
2 Overload diaphragm/Middle diaphragm
3 Filling oil
4 Process isolating diaphragm
The metal separating diaphragms (4) are deflected on both sides by the acting pressures p
1
and p
2
. A
filling oil (3) transfers the pressure to a resistance circuit bridge (semiconductor technology). The
differential-pressure-dependent change of the bridge output voltage is measured and further
processed.
Level measurement (level,
volume and mass)
Design and operation mode
A0023082
Level measurement with Deltabar M
A Version V1; vertical impulse line; 90 alignment
B Version H1; horizontal impulse line; 180 alignment
C Version H2; horizontal impulse line; 90 alignment
h Height (level)
Ap Differential pressure
Density of the medium
g Gravitation constant
Your benefits
Volume and mass measurements in any tank shapes by means of a freely programmable
characteristic curve
Choice of diverse level units
Has a wide range of uses, e.g.
for level measurement in tanks with superimposed pressure
in the event of foam formation
in tanks with agitators of screen fittings
in the event of liquid gases
for standard level measurement
1
p
2
p
1
4
2
3
4
+

h
PMD55, H1
+

h
PMD55, H2
h =
Dp
r g
+

h
PMD55, V1
h =
Dp
r g
h =
Dp
r g
A B C
Deltabar M PMD55
8 Endress+Hauser
Flow measurement Design and operation mode
A0023086
Flow measurement with Deltabar M PMD55 and Deltatop primary element
A with orifice plate
B with Pitot tube
1 Deltabar M PMD55
2 3-valve manifold
Q Flow
Ap Differential pressure, Ap = p
1
p
2
Your benefits
Choice between five flow modes of operation:
Volume flow
Norm volume flow (European norm conditions)
Standard volume flow (American standard conditions)
Mass flow
%
Choice of diverse flow units with automatic unit conversion.
Low flow cut off: when activated, this function suppresses small flows which can lead to large
fluctuations in the measured value.
Contains two totalizers as standard. One totalizer can be reset to zero.
The totalizing unit can be individually set for each totalizer. This allows independent daily and
annual quantity totalizing.

For more information about the Deltatop flow measurement system, see
TI00422P: Deltatop Differential Pressure Flow Measurement with Orifices
TI00425P: Deltatop Differential Pressure Flow Measurement with Pitot Tubes
Q Q
p
1
p
2
Q ~ Dp
+ +

1 1
2 2
p
1
p
2
Q ~ Dp
A B
Deltabar M PMD55
Endress+Hauser 9
Typical arrangements for flow measurements
A0023088
A Liquid in vertical pipe; H1 version; horizontal impulse line; 180 alignment
B Gas in horizontal pipe; V1 version; vertical impulse line; 90 alignment
C Vapour in horizontal pipe; V1 version; vertical impulse line; 90 alignment
Mounting example
A0023089
1 Valve manifold
2 Impulse line
PMD55, V1
PMD55, V1
PMD55, H1
A B C
PMD55, V1
2
2
1
1
PMD55, V1
Deltabar M PMD55
10 Endress+Hauser
Communication and data
processing
4 to 20 mA with HART communication protocol
PROFIBUS PA
The Endress+Hauser devices meet the requirements of the FISCO model.
Due to the low current consumption of 11 mA 1 mA, the following number of devices can be
operated on one bus segment if installing as per FISCO:
up to 8 Deltabar M for Ex ia, CSA IS and FM IS applications
up to 31 Deltabar M for all other applications, e.g. in non-hazardous areas, Ex nA, etc.
Further information on PROFIBUS PA can be found in Operating Instructions BA00034S "PROFIBUS
DP/PA: Guidelines for planning and commissioning" and in the PNO Guideline.
FOUNDATION Fieldbus
The Endress+Hauser devices meet the requirements of the FISCO model.
Due to the low current consumption of 16 mA 1 mA, the following number of devices can be
operated on one bus segment if installing as per FISCO:
up to 6 Deltabar M for Ex ia, CSA IS and FM IS applications
up to 22 Deltabar M for all other applications, e.g. in non-hazardous areas, Ex nA, etc.
Further information on FOUNDATION Fieldbus, such as requirements for bus system components
can be found in Operating Instructions BA00013S "FOUNDATION Fieldbus Overview".
Deltabar M PMD55
Endress+Hauser 11
Input
Measured variable Differential pressure, from which flow (volume or mass current) and level (level, volume or mass) are
derived.
Measuring range
Nominal
value
Measurement limit Smallest span
(factory
calibration)
1)
MWP OPL Min. operating
pressure
2)
Version
3)
lower (LRL) upper (URL) on one side on both sides
[mbar (psi)] [mbar (psi)] [mbar (psi)] [mbar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [mbar
abs
(psi
abs
)]
10 (0.15) 10 ( 0.15) +10 (+ 0.15) 0.5 (0.0075)
1 (15)
4)
1 (15)
4)
1.5 (22.5)
4)
0.1 (0.0015)
4)
7B
30 (0.45) 30 ( 0.45) +30 (+ 0.45) 1.5 (0.0225) 7C
100 (1.5) 100 ( 1.5) +100 (+ 1.5) 5 (0.075)
70 (1050)
5)
160 (2400)
6)
70 (1050)
5)
160 (2400)
6)
105 (1575)
5)
240 (3600)
6)
0.1 (0.0015)
5)
0.1 (0.0015)
6)
7D
500 (7.5) 500 ( 7.5) +500 (+ 7.5) 25 (0.375) 7F
1000 (15) -1000 ( 15) +1000 (+ 15) 50 (0.75) 7G
3000 (45) 3000 ( 45) +3000 (+ 45) 150 (2.25) 7H
16000 (240) 16000 ( 240) +16000 (+ 240) 800 (12) 7L
40000 (600) 40000 ( 600) +40000 (+ 600) 2000 (30) 7M
1) Recommended Turn down: Max 100:1.
Factory calibration Turn down: Max 20:1
2) The minimum operating pressure indicated in the table applies to silicone oil under reference operating conditions. Minimum operating pressure
at 85C (185F) for silicone oil: 10 mbar (0.15 psi) (abs)
3) Product Configurator, "Sensor Nominal Value" section
4) Version "2" in the Order Code - Feature 60
5) Version "6" in the Order Code - Feature 60
6) Version "7" in the Order Code - Feature 60
Nominal Pressure PN Version
1)

1) Product Configurator "Nominal Pressure PN" section
Prepared for Deltatop D
1 bar / 100 kPa/ 14.5 psi 2
70 bar / 7 MPa / 1015 psi 6
160 bar / 16 MPa / 2400 psi 7
Deltabar M PMD55
12 Endress+Hauser
Output
Output signal 4 to 20 mA with superimposed digital communication protocol HART 6.0, 2-wire
Digital communication signal PROFIBUS PA (Profile 3.02)
Digital communication signal FOUNDATION Fieldbus
Signal range
4 to 20 mA HART
3.8 mA to 20.5 mA
Signal on alarm As per NAMUR NE 43
4 to 20 mA HART
Options:
Max. alarm*: can be set from 21...23 mA (factory setting: 22 mA)
Keep measured value: last measured value is kept
Min. alarm: 3.6 mA
PROFIBUS PA: can be set in the Analog Input block,
Options: Last Valid Out Value (factory setting), Fail-safe Value, Status Bad
FOUNDATION Fieldbus: can be set in the Analog Input block,
Options: Last Good Value, Fail-safe Value (factory setting), Wrong Value
Load 4 to 20 mA
A0023090
Load diagram
1 Supply voltage 11.5 ... 30 V DC for intrinsically safe instrument versions
2 Supply voltage 11.5 ... 45 V DC (versions with plug-in connector 35 V DC) for other types of protection and for uncertified
instrument versions
R
Lmax
Maximum load resistance
U Supply voltage

When operating via a handheld terminal or via PC with an operating program, a minimum
communication resistance of 250 O must be taken into account.
Output Version
1)

1) Product Configurator "Output" section
4 to 20mA HART 2
PROFIBUS PA 3
FOUNDATION Fieldbus 4
U 11.5 V
23 mA
[ ] W
30 20 11.5 40 45
1239
1456
804
369

U
[V]
1
2
R
Lmax
3
R
Lmax
Deltabar M PMD55
Endress+Hauser 13
Dead time, Time constant
A0019786
Presentation of the dead time and the time constant
Dynamic behavior:
current output
Dynamic behavior:
digital output
(HART electronics)
Reading cycle
Acyclic: max. 3/s, typical 1/s (depends on command # and number of preambles)
Cyclic (Burst): max. 3/s, typical 2/s
The Deltabar M commands the BURST MODE function for cyclic value transmission via the HART
communication protocol.
Cycle time (update time)
Cyclic (Burst): min. 300 ms
Response time
Acyclic: min. 330 ms, typical 590 ms (depends on command # and number of preambles)
Cyclic (Burst): min. 160 ms, typical 350 ms (depends on command # and number of preambles)
Dynamic behavior:
PROFIBUS PA
Reading cycle
Cyclic: max. 30/s (dependent on the number and type of function blocks used in a closed-control
loop)
Acyclic: typical 25/s
Cycle time (update time)
Min. 100 ms. The cycle time in a bus segment in cyclic data communication depends on the number of
devices, on the segment coupler used and on the internal PLC cycle time.
Response time
Cyclic: approx. 8 to 13 ms (depends on Min. Slave Interval)
Acyclic: approx. 23 to 35 ms (depends on Min. Slave Interval)
I
63 %
100 %
t
t
1
t
2
90 %
t
3
Dead time (t
1
) [ms] Time constant T63 (= t
2
) [ms] Time constant T90 (= t
3
) [ms]
max. 60 90 210
Dead time (t
1
) [ms] Dead time (t
1
) [ms] +
Time constant T63 (= t
2
) [ms]
Dead time (t
1
) [ms] +
Time constant T90 (= t
3
) [ms]
min. 220 310 370
max. 1020 1110 1170
Dead time (t
1
) [ms] Dead time (t
1
) [ms] +
Time constant T63 (= t
2
) [ms]
Dead time (t
1
) [ms] +
Time constant T90 (= t
3
) [ms]
min. 95 185 245
max. 1195 1285 1345
Deltabar M PMD55
14 Endress+Hauser
Dynamic behavior:
FOUNDATION Fieldbus
Reading cycle
Cyclic: max. 10/s (dependent on the number and type of function blocks used in a closed-control
loop)
Acyclic: typical 5/s
Cycle time (update time)
Cyclic: min. 100 ms
Response time
Cyclic: max. 20 ms (for standard bus parameter settings)
Acyclic: typical 70 ms (for standard bus parameter settings)
Damping A damping affects all outputs (output signal, display).
Via onsite display, handheld terminal or PC with operating program, continuous from 0...999 s
Via DIP-switch on the electronic insert, switch position "on" (= set value) and "off"
(= damping switched off)
Factory setting: 2 s
Firmware version
Protocol-specific data HART
Dead time (t
1
) [ms] Dead time (t
1
) [ms] +
Time constant T63 (= t
2
) [ms]
Dead time (t
1
) [ms] +
Time constant T90 (= t
3
) [ms]
min. 105 195 255
max. 1105 1195 1255
Designation Version
1)
1) Product Configurator "Firmware version" section
01.00.zz, HART, DevRev01 78
Manufacturer ID 17 (11 hex)
Device Type Code 33 (21 hex)
Device Revision 01 (01 hex) - SW version 01.00.zz
HART specification 6
DD Revision 01 (netherlands)
02 (russian)
Device description files
(DTM, DD)
Information and files can be found:
www.endress.com
www.hartcomm.org
HART load Min. 250 O
HART device variables The measured values can be freely assigned to the device variables:
Measured values for PV (primary variable)
Pressure
Flow
Level
Tank content
Measured values for SV, TV (second and third variable)
Pressure
Level
Totalizer
Supported functions Burst mode
Additional Transmitter Status
Device Locking
Alternative operating modes
Deltabar M PMD55
Endress+Hauser 15
PROFIBUS PA
Manufacturer ID 17 (11 hex)
Ident number 1554 hex
Profile Version 3.02
SW Version 01.00.zz
GSD Revision 5
DD Revision 1
GSD File Information and files can be found:
www.endress.com
www.profibus.org
DD Files
Output values Measured values for PV (via Analog Input Function Block)
Pressure
Flow
Level
Tank content
Measured values for SV
Pressure
Measured values for QV
Totalizer
Input values Input value sent from PLC, can be shown on display
Supported functions Identification & Maintenance
Simple device identification via control system and nameplate
Condensed status
Automatic ident number adaptation and switchable to following ident
numbers:
9700: Profile-specific transmitter identification number with the
"Classic" or "Condensed" status".
1554: Identification number for Deltabar M.
Device locking: The device can be locked by hardware or software.
Deltabar M PMD55
16 Endress+Hauser
Data of the FOUNDATION
Fieldbus interface
Basic data
Virtual communication references (VCRs)
Link settings
Transducer Blocks
Device Type 0x1021
Device Revision 01 (hex)
DD Revision 0x01021
CFF Revision 0x000102
ITK Version 5.2.0
ITK Certification Driver No. IT067600
Link-Master (LAS) capable Yes
Link Master / Basic Device
selectable
Yes; Factory setting: Basic Device
Number of VCRs 44
Number of Link Objects in VFD 50
Number of FB-Schedule Objects 40
Permanent Entries 44
Client VCRs 0
Server VCRs 5
Source VCRs 8
Sink VCRs 0
Subscriber VCRs 12
Publisher VCRs 19
Slot time 4
Min. inter PDU delay 12
Max. response delay 40
Block Content Output values
TRD1 Block Contains all parameters related to the measurement Pressure or level (channel 1)
Process temperature (channel 2)
Measured pressure value
(channel 3)
Max. pressure (channel 4)
Level before linearization (channel
5)
Dp Flow Block enthlt Durchfluss und Summenzhler Parameter Totalizer 1 (channel 6)
Totalizer 2 (channel 7)
Diagnostic
Block
Contains diagnostic information Error code via DI channels
(channel 10 to 15)
Display Block Contains parameters to configure the onsite display No output values
Deltabar M PMD55
Endress+Hauser 17
Function blocks
Block Content Number
of
blocks
Execution time Functionality
Resource
Block
The Resource Block contains all the data that
uniquely identify the device. It is an electronic
version of a nameplate of the device.
1 enhanced
Analog Input
Block 1
Analog Input
Block 2
The AI Block receives the measuring data from
the Sensor Block, (selectable via a channel
number) and makes the data available to other
function blocks at its output. Enhancement:
digital outputs for process alarms, fail safe mode.
2 25 ms enhanced
Digital Input
Block
This block contains the discrete data of the
Diagnose Block (selectable via a channel
number 10 to 15) and provides them for other
blocks at the output.
1 20 ms standard
Digital Output
Block
This block converts the discrete input and thus
initiates an action (selectable via a channel
number) in the DP Flow Block or in the im TRD1
Block. Channel 20 resets the counter for max.
pressure transgressions value and Channel 21
resets the Totalizer.
1 20 ms standard
PID Block The PID Block serves as a proportional-integral-
derivative controller and is used almost
universally for closed-loop-control in the field
including cascade and feedforward. Input IN can
be indicated on the display. The selection is
performed in the Display Block
(DISPLAY_MAIN_LINE_CONTENT).
1 40 ms standard
Arithmetic
Block
This block is designed to permit simple use of
popular measurement math functions. The user
does not have to know how to write equations.
The math algorithm is selected by name, chosen
by the user for the function to be performed.
1 35 ms standard
Input Selector
Block
The Input Selector Block facilitates the selection
of up to four inputs and generates an output
based on the configured action. This block
normally receives its inputs from AI Blocks. The
block performs maximum, minimum, average
and first good signal selection. Inputs IN1 to IN4
can be indicated on the display. The selection is
performed in the Display Block
(DISPLAY_MAIN_LINE_1_CONTENT).
1 30 ms standard
Signal
Characterizer
Block
The Signal Characterizer Block has two sections,
each with an output that is a nonlinear function
of the respective input. The nonlinear function is
generated by a single look-up table with
21 arbitrary x-y pairs.
1 40 ms standard
Integrator
Block
The Integrator Block integrates a variable as a
function of the time or accumulates the counts
from a Pulse Input Block. The block may be used
as a totalizer that counts up until reset or as a
batch totalizer that has a setpoint, where the
integrated or accumulated value is compared to
pre-trip and trip settings, generating a binary
signal when the setpoint is reached.
1 35 ms standard
Additional function block information:
Instantiate Function Block YES
Number of instantiate blocks 20
Deltabar M PMD55
18 Endress+Hauser
Power supply
WARNING !
An incorrect connection compromises electrical safety!
When using the measuring device in hazardous areas, the relevant national standards and
regulations as well as the safety instructions or installation or control drawings must be observed.
47, "Safety Instructions" and "Installation/Control Drawings" sections.
All explosion protection data are given in separate documentation which is available upon request.
The Ex documentation is supplied as standard with all devices approved for use in explosion
hazardous areas 47, sections "Safety InstructionsSafety Instructions" and "Installation/
Control drawing".
According to IEC/EN61010 a suitable disconnector has to be installed for the device.
HART: Overvoltage protection HAW569-DA2B for the non-hazardous area, ATEX II 2 (1) Ex ia IIC
and IEC Ex ia can be ordered as an option (see "Ordering information" section).
Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed.
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also
provides the power supply.
Terminal assignment
A0023505
Electrical connection
1 External grounding terminal
2 Internal grounding terminal
3 Supply voltage 18
4 4...20 mA for HART devices
5 For HART and FOUNDATION Fieldbus devices: With a handheld terminal, all the parameters can be configured anywhere
along the bus line via menu operation.
6 Terminals
7 For HART devices: test terminals, see section "Taking a 4 to 20 mA test signal"
Supply voltage 4 to 20 mA HART
Taking a 4 to 20 mA test signal
A 4 to 20 mA test signal may be measured via the test terminals without interrupting the
measurement.
- +
1
2
3
4
5
6
7
Type of protection Supply voltage
Intrinsically safe 11.5 ... 30 V DC
Other types of protection
Devices without certificate
11.5 ... 45 V DC (Versions with plug-in connection 35 V DC)
Deltabar M PMD55
Endress+Hauser 19
PROFIBUS PA
Version for non-hazardous areas: 9 to 32 V DC
FOUNDATION Fieldbus
Version for non-hazardous areas: 9 to 32 V DC
Current consumption PROFIBUS PA: 11 mA 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
FOUNDATION Fieldbus: 16 mA 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
Electrical connection
PROFIBUS PA
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also
provides the power supply. For further information on the network structure and grounding, and for
further bus system components such as bus cables, see the relevant documentation, e.g. Operating
Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and the
PNO Guideline.
FOUNDATION Fieldbus
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also
provides the power supply. For further information on the network structure and grounding and for
further bus system components such as bus cables, see the relevant documentation, e.g. Operating
Instructions BA00013S "FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline.
Terminals For wire cross-sections of 0.5 to 2.5 mm (20 to 14 AWG).
Cable entry
For additional technical data, see housing section 32 ff".
Cable entry Degree of protection Version
1)
1) Product Configurator "Electrical Connection" section
M20 coupling IP66/68 NEMA 4x/6P A
M20 thread IP66/68 NEMA 4X/6P B
G " thread IP66/68 NEMA 4X/6P C
NPT " thread IP66/68 NEMA 4X/6P D
M12 connector IP66/67 NEMA 4X/6P I
7/8" connector IP66/68 NEMA 4X/6P M
HAN7D plug 90 degrees IP65 P
M16 valve connector IP64 V
Approval Type Clamping area
Standard, II1/2G Exia, IS Plastic M20x1.5 5 to 10 mm (0.2 to 0.39 in)
ATEX II1/2D, II1/2GD Exia, II3G Ex nA Metal M20x1.5 (Ex e) 7 to 10.5 mm (0.28 to 0.41 in)
Deltabar M PMD55
20 Endress+Hauser
Device plug connectors Devices with valve connector
A0023097
BN = brown, BU = blue, GNYE = green/yellow
A Electrical connection for devices with valve connector
B View of the plug connector at the device
Material: PA 6.6
Devices with Harting plug Han7D
A0019990
A Electrical connection for devices with Harting plug Han7D
B View of the plug-in connector at the device
Material: CuZn, contacts for plug-in jack and connector are gold-plated
Devices with M12 plug
PIN assignment for M12 connector
Endress+Hauser offers the following accessories for devices with an M12 connector:
Plug-in jack M 12x1, straight
Material: body PA; coupling nut CuZn, nickel-plated
Han7D
+
1 2 3
+ A B
BNBU GNYE
1 2
3
+
Han7D
+
+
+
1
5
4
6
7
8
2
3
A B
PIN assignment for M12 connector PIN Meaning
A0011175
1 Signal +
2 Not assigned
3 Signal
4 Earth
2 1
3 4
Deltabar M PMD55
Endress+Hauser 21
Degree of protection (fully locked): IP66/67
Order number: 52006263
Plug-in jack M 12x1, elbowed
Material: body PBT/PA; coupling nut GD-Zn, nickel-plated
Degree of protection (fully locked): IP66/67
Order number: 71114212
Cable 4x0.34 mm (20 AWG) with M12 socket, elbowed, screw plug, length 5 m (16 ft)
Material: body PUR; coupling nut CuSn/Ni; cable PVC
Degree of protection (fully locked): IP66/67
Order number: 52010285
Devices with 7/8" plug
PIN assignment for 7/8" connector
External thread: 7/8 - 16 UNC
Material: 316L (1.4401)
Protection: IP66/68
Cable specification HART
Endress+Hauser recommends using a twisted, shielded two-wire cable.
The outer diameter of the cable depends on the cable entry used.
PROFIBUS PA
Use a twisted, shielded two-wire cable, preferably cable type A

For further information on the cable specifications, see Operating Instructions BA00034S
"PROFIBUS DP/PA: Guidelines for planning and commissioning", the PNO Guideline 2.092
PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).
FOUNDATION Fieldbus
Use a twisted, shielded two-wire cable, preferably cable type A

For further information on the cable specifications, see Operating Instructions BA00013S
"FOUNDATION Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).
Startup current HART 12 mA or 22 mA (selectable)
Residual ripple Without influence on 4 to 20 mA signal up to 5 % residual ripple within the permitted voltage range
[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]
Influence of power supply s 0.001% of URL/V
PIN assignment for 7/8" connector PIN Meaning
A0011176
1 Signal
2 Signal +
3 Not assigned
4 Shield
2
1
4
3
Deltabar M PMD55
22 Endress+Hauser
Performance characteristics
Reference operating
conditions
As per IEC 60770-1 and IEC 61298-1, Sections 5 to 7
Ambient temperature T
U
= constant, in the range of: +21...+33C (+70...91 F)
Humidity = constant, in the range of: 5...80 % r.H
Ambient pressure p
U
= constant, in the range of: 860...1060 mbar (12.47...15.37 psi)
Position of the measuring cell: constant, in the range of: 1 horizontically and 1 vertically
P1 = high pressure side
Input of "Lo Trim Sensor" and "Hi Trim Sensor" for lower range value and upper range value
Measuring span URV - LRV
Membrane material 316L
Filling oil: silicone oil
Side flanges material: AISI 316L
Supply voltage: 24 V DC 3 V DC
Load with HART: 250 O
Long-term stability
Influence of the installation
position
The recommended maximum angle to the axis of the diaphragm is 10 and results in a measuring error
of 0.72 mbar (0.01 psi). The value is doubled for devices with inert oil.

Position-dependent zero shift can be corrected 25, section "General installation instructions".
A0023099
Resolution Current output: 1 A
Display: can be set (factory setting: presentation of the maximum accuracy of the transmitter)
Measuring cell % of URL / 1 year % of URL / 5 years
10 mbar (0.15 psi)
30 mbar (0.45 psi)
0.25 1.25
100 mbar (1.5 psi) 0.18 0.35
500 mbar (7.5 psi)
1 bar (15 psi)
3 bar (45 psi)
16 bar (240 psi)
40 bar (600 psi)
0.05 0.13
0
.
.
.
1
0
0
.
.
.
1
0

Deltabar M PMD55
Endress+Hauser 23
Reference accuracy The reference accuracy comprises the non-linearity according to limit point setting, hysteresis and
non-reproducibility as per IEC 60770.
The following applies for the root-extracting characteristic curve:
The accuracy data of the Deltabar M is taken into the accuracy calculation of the flow rate with a
factor of 0.5.
Total performance:
current output
The "Total performance" specification comprises the non-linearity including hysteresis, non-
reproducibility, the thermal change of the zero point as well as the influence of the line pressure p
st
.
The line pressure p
st
is 70 bar (1050 psi) for the 100 mbar, 500 mbar, 1 bar, 3 bar, 16 bar und 40 bar
measuring cell.
Measuring cell % of the set span
Standard Platinum
10 mbar (0.15 psi)
30 mbar (0.45 psi)
TD 1:1
TD > 1:1
=
=
0.2
(0.2 x TD)
--
100 mbar (1.5 psi) TD 1:1 to TD 4:1
TD > 4:1
=
=
0.1
(0.012 x TD + 0.052)
TD 1:1 to TD 4:1
TD > 4:1
=
=
0.075
(0.012 x TD + 0.027)
500 mbar (7.5 psi)
1 bar (15 psi)
3 bar (45 psi)
16 bar (240 psi)
40 bar (600 psi)
TD 1:1 to TD 10:1
TD > 10:1
=
=
0.1
(0.0015 x TD + 0.085)
TD 1:1 to TD 10:1
TD > 10:1
=
=
0.075
(0.0015 x TD + 0.060)
Reference accuracy Version
1)

1) Product Configurator "Reference Accuracy" section
Platinum D
Standard G
Measuring cell
% of the set span
Standard, TD 1:1 Platinum, TD 1:1
-10 to +60C
(14 to 140F)
-40 to -10C; +60 to +85C
(-40 to +14F;
140 to 185F)
-10 to +60C
(14 to
140F)
-40 to -10C; +60 to +85C
(-40 to +14F;
140 to 185F)
10 mbar (0.15 psi) 0.94 1.03 -- --
30 mbar (0.45 psi) 0.92 1.01 -- --
100 mbar (1.5 psi) 0.51 0.66 0.51 0.38
500 mbar (7.5 psi)
1 bar (15 psi)
3 bar (45 psi)
0.40 0.44 0.40 0.32
16 bar (240 psi) 0.43 0.53 0.43 0.38
40 bar (600 psi) 0.40 0.70 0.40 0.33
Deltabar M PMD55
24 Endress+Hauser
Total Error
Warm-up period 4 to 20 mA HART: s5 s
PROFIBUS PA: s8 s
FOUNDATION Fieldbus: s20 s (after a TOTAL-reset s45 s)
Thermal stability current
output
Influence of the static
pressure

The influence of the static pressure on the zero point can be calibrated out.
Vibration effects
Measuring cell % of URL / 1 year % of URL / 5 years
10 mbar (0.15 psi)
30 mbar (0.45 psi)
0.97 0.95
100 mbar (1.5 psi) 0.26 0.39
500 mbar (7.5 psi)
1 bar (15 psi)
3 bar (45 psi)
0.14 0.18
16 bar (240 psi) 0.17 0.20
40 bar (600 psi) 0.14 0.18
Measuring cell
-10 to +60C (+14 to +140F) -40 to -10C, +60 to +85C
(40 to +14F, +140 to +185F)
% of the set span
10 mbar (0.15 psi)
30 mbar (0.45 psi)
(0.31 x TD + 0.58) (0.45 x TD + 0.54)
100 mbar (1.5 psi) (0.18 x TD + 0.3) (0.3 x TD + 0.34)
500 mbar (7.5 psi)
1 bar (15 psi)
3 bar (45 psi)
(0.08 x TD + 0.3) (0.12 x TD + 0.3)
16 bar (240 psi) (0.10 x TD + 0.32) (0.15 x TD + 0.36)
40 bar (600 psi) (0.08 x TD + 0.3) (0.37 x TD + 0.32)
Measuring cell Influence on zero point Influence on span
10 mbar (0.15 psi) 0.2 % of URL / 1 bar 0.2 % of URL / 1 bar
30 mbar (0.45 psi) 0.07 % of URL / 1 bar 0.07 % of URL / 1 bar
100 mbar (1.5 psi) 0.15 % of URL / 70 bar 0.14 % of URL / 70 bar
500 mbar (7.5 psi)
1 bar (15 psi)
3 bar (45 psi)
16 bar (240 psi)
40 bar (600 psi)
0.075 % of URL / 70 bar 0.14 % of URL / 70 bar
Test standard Vibration effects
GL VI-7-2
Part 7: Guidelines for the Performance of Type Approvals
Chapter 2: Test Requirements for Electrical / Electronic Equipment and
Systems
guaranteed for
5 to 25 Hz: 1.6 mm (0.06 in);
25 to 100 Hz: 4 g
in all 3 planes
IEC 61298-3
IEC 60068-2-6
s reference accuracy to 10...60 Hz:
0.35 mm (0.01 in); 60...2000 Hz:
5 g
in all 3 planes
Deltabar M PMD55
Endress+Hauser 25
Installation
General installation
instructions
The position-dependent zero shift can be corrected directly at the device via operating keys.
Endress+Hauser offers a mounting bracket for installing the device on pipes or walls 26,
section "Wall and pipe mounting".
When measuring in media with solid proportions, such as dirty liquids, installing separators and
drain valves is useful for capturing and removing sediment.
Using a three-valve or five-valve manifold allows for easy commissioning, installation and
maintenance without interrupting the process.
General recommendations for the impulse piping can be found in DIN 19210 "Methods for
measurement of fluid flow; differential piping for flow measurement devices" or the corresponding
national or international standards.
Install the impulse piping with a continuous gradient of at least 10 %.
When routing the impulse piping outdoors, ensure that sufficient anti-freeze protection is used, e.g.
by using pipe heat tracing.
Measuring arrangement Flow measurement
Measuring arrangement for gases: Mount device above the measuring point.
Measuring arrangement for liquids and vapours: Mount the device below the measuring point.
For flow measurement in vapours, mount the condensate traps at the same level as the same the
tapping point and at the same distance from Deltabar M.
Level measurement
Measuring arrangement level measurement in open tanks
Mount device below the lower measuring connection. The low-pressure side is open to atmosphere
pressure.
Measuring arrangement level measurement in closed tanks and closed tanks with superimposed vapor
Mount device below the lower measuring connection. Always connect the low-pressure side above
the maximum level.
In the case of level measurement in closed tanks with superimposed vapor, a condensate trap
ensures pressure which remains constant on the low-pressure side.
Pressure measurement
Measuring arrangement for gases: Mount device above the measuring point.
Measuring arrangement for liquids and vapours: Mount the device below the measuring point.
For differential pressure measurement in vapor, mount the condensate traps at the same level as the
same the tapping point and at the same distance from Deltabar M.
Deltabar M PMD55
26 Endress+Hauser
Wall and pipe-mounting
(optional)
Endress+Hauser offers a mounting bracket for installing the device on pipes or walls. A bracket with
mounting accessories for pipe mounting is included with the device.

When using a valve block, the block's dimensions must be taken into account.
A0023100
Mounting bracket for wall and pipe mounting
1 Adapter plate (+ six screws and six washers)
2 Mounting bracket (+ bracket for pipe mounting and two nuts)
Please note the following when mounting:
To prevent the mounting screws from scoring, lubricate them with a multipurpose grease prior to
mounting.
In the case of pipe mounting, the nuts on the bracket must be tightened uniformly with a torque of
at least 30 Nm (22.13 lbf ft).
Ordering information:
Product Configurator "Accessory Enclosed" section, PB and PC versions
As Accessorry:
Adapter plate 7/16 - 20 UNF part number: 71098632
Adapter plate M10 part number: 71101935
Mounting bracket and adapter plate 7/16 - 20 UNF part number: 71098630
Mounting bracket and adapter plate M10 part number: 71101934
2
1
4
1
.
3

(
1
.
6
3
)
4
1
.
3
(
1
.
6
3
)
4
1
.
3

(
1
.
6
3
)
9
0
(
3
.
5
4
)
6
0

(
2
.
3
6
)
3
0

(
1
.
1
8
)
6
6
.
4
(
2
.
6
1
)
6
6
.
4
(
2
.
6
1
)
5
4
(
2
.
1
3
)
M
1
0
7
/
1
6
1
0
6
(
4
.
1
7
)
7
4
(
2
.
9
1
) 7
4
(
2
.
9
1
)
1
2
4
(
4
.
8
8
)
1
3
5

(
5
.
3
1
)
3
7
.
5

(
1
.
4
8
)
5
4

(
2
.
1
3
)
5
4
(
2
.
1
3
)
Deltabar M PMD55
Endress+Hauser 27
Typical installation arrangements
A0023109
A Installation for horizontal impulse lines, H2 version
B Installation for vertical impulse lines; V1 version
1 Deltabar M
2 Adapter
3 Mounting bracket
3
2
1
1
2
3
PMD55, V1
PMD55, H2
A
B
Deltabar M PMD55
28 Endress+Hauser
Oxygen applications Oxygen and other gases can react explosively to oils, grease and plastics, such that, among other
things, the following precautions must be taken:
All components of the system, such as measuring devices, must be cleaned in accordance with the
BAM (DIN 19247) requirements.
Ordering information:
Product Configurator "Service" section, HB version
Dependent on the materials used, a certain maximum temperature and a maximum pressure for
oxygen applications must not be exceeded.
PWIS cleaning Special cleaning of the transmitter to remove paint-wetting impairment substances, for use in paint
shops for example.
Ordering information :
Product Configurator "Service" section, HC version
Ultra pure gas applications Endress+Hauser also offers devices for special applications, such as ultra pure gas, cleaned from oil and
grease.
Ordering information :
Product Configurator "Service" section, HA version
No special restrictions regarding the process conditions apply to these devices.
P
max
for Oxygen applications T
max
for Oxygen applications Version
1)

1) Product Configurator "Seal" section
30 bar (450 psi) -18 to +60C (0 to 140F) A (FKM Viton)
Deltabar M PMD55
Endress+Hauser 29
Environment
Ambient temperature range 40 to +85C (40 to +185F)
Onsite display: -20 to +70C (-4 to 158F)
Enhanced temperature range with limitations concerning display speed and contrast: -40 to +85C
(-40 to +185F)
For devices for use in hazardous areas, see Safety instructions, Installation or Control Drawing
47, sections "Safety InstructionSafety Instructions" and "Installation/Control drawings").
Storage temperature range 40 to +90C (40 to +194F)
Onsite display: 40 to +85C (40 to +185F)
Degree of protection Ordering information :
Product Configurator "Electrical Connection" section
Climate class Class 4K4H (air temperature: 20...55C (4...+131F), relative humidity: 4...100%) fulfilled as per
DIN EN 60721-3-4 (condensation possible)
Vibration resistance
Electromagnetic
compatibility
Electromagnetic compatibility as per all the relevant requirements of the EN 61326 series and
NAMUR Recommendation EMC (NE21). Details can be found in the Declaration of Conformity (in
the Download area of "www.de.endress.com", "search area - Approvals and Certificates", "Manufact.
Declaration").
Maximum deviation: < 0.5% of span
Larger deviations possible with 10 mbar (0.15 psi) measuring cell.
Device Test standard Vibration resistance
PMD55 GL guaranteed for
5 to 25 Hz: 1.6 mm (0.06 in);
25 to 100 Hz: 4 g in all 3 planes
IEC 61298-3 guaranteed for:
10...60 Hz: 0.35 mm (0.014 in);
60...2000 Hz: 5 g in all 3 planes
PMD55
with mounting bracket
IEC 61298-3 guaranteed for:
10...60 Hz: 0.15 mm (0.006 in);
60...500 Hz: 2 g in all 3 planes
Deltabar M PMD55
30 Endress+Hauser
Overvoltage protection
(optional)
The device can be fitted with overvoltage protection.
The overvoltage protection is mounted at the factory on the housing thread (M20x1.5) for the cable
gland and is approx. 70 mm (2.76 in) in length (take additional length into account when installing).
The device is connected as illustrated in the following graphic.
For details refer to TI001013KEN, XA01003KA3 and BA00304KA2.
Ordering information :
Product Configurator "Accessory Mounted", NA version
A0023111
A Without direct shield grounding
B With direct shield grounding
1 Incoming connection cable
2 HAW569-DA2B
3 Unit to be protected
4 Connection cable
1
2
3
4
+
-
+
-
rt
sw
+
-
A
B
Deltabar M PMD55
Endress+Hauser 31
Process
Process temperature limits
(temperature at transmitter)
Process connections made of 316L:
40 to +85C (40 to +185F)
Process connections made of C22.8:
10 to +85C (+14 to +185F)
The process temperature at the transmitter can be reduced through the use of impulse lines.

For oxygen applications, observe 28 "Oxygen applications" section.
Observe the process temperature range of the seal (see also the following section "Process
temperature range, Seals").
Process temperature range,
Seals
Pressure specifications
WARNING !
The maximum pressure for the measuring device depends on the lowest rated element with
regard to pressure 11 ff, "Measuring range" section and 32 ff "Mechanical
construction" section
The measuring device must be operated only within the specified limits!
The MWP (maximum working pressure) is specified on the nameplate. This value refers to a
reference temperature of 20C (68F) or 100F (38 C) for ANSI flanges and may be applied to the
device for an unlimited time. Observe pressure-temperature dependency.
The pressure values permitted at higher temperatures can be found in the standards
EN 1092-1: 2001 Tab. 18
ASME B 16.5a 1998 Tab. 2-2.2 F316
ASME B 16.5a 1998 Tab. 2.3.8 N10276
JIS B 2220.
The MWP applies for the temperature ranges specified in the "Ambient temperature range"
( 29) and "Process temperature limits" (see above) sections.
The test pressure corresponds to the over pressure limit of the measuring instrument (Over
pressure limits OPL = 1.5 x MWP) and may fit only temporally limited, so that no permanent
damage develops.
The Pressure Equipment Directive (EC Directive 97/23/EC) uses the abbreviation "PS". The
abbreviation "PS" corresponds to the MWP (maximum working pressure) of the measuring device.
In the case of sensor range and process connections where the OPL (Over Pressure Limit) of the
pressure connection is smaller than the nominal value of the sensor, the device is set at the factory,
at the very maximum, to the OPL value of the process connection. If you want to use the entire
sensor range, select a process connection with a higher OPL value (1.5 x PN; PN = MWP).
In oxygen applications, the values for "p
max
and T
max
for oxygen service" as per 28 "Oxygen
service" section must not be exceeded.
Seal Process temperature range
1)
1) Restricions for oxygen applications, 28
Version
2)
2) Product Configurator "Seal" section
FKM Viton 20 to +85C (4 to +185F) A
PTFE 40 to +85C (40 to +185F) C
PTFE (EPDM core) 40 to +85 C (40 to +185 F)
3)
3) Only 10 mbar (0.15 psi) und 30 mbar (0.45 psi) measuring cell.
D
NBR 20 to +85C (4 to +185F) F
EPDM 20 to +85C (4 to +185F) J
Deltabar M PMD55
32 Endress+Hauser
Mechanical construction
Housing
Process connection Oval flange, connection 1/4-18 NPT IEC61518
A0023115
Designation of the process connections "P1" and "P2"
Ordering information:
Product Configurator "Process connection" section
As Accessorry: Product Configurator "Accessory Enclosed" section, version "P1"
Factory setting
P1: High pressure side (+)
P2: Low pressure side (-)
This setting can be changed via a DIP switch in the connection department of the instrument and via
the operating menu:
A0023116
DIP switches in the connection compartment of the device. DIP switch 5 defines the high pressure side.
DIP5 = off: The high pressure side is defined in the operating menu.
Menu "Setup", parameter 006: "High pressure side"; default: P1)
DIP 5 = on: P2 is the high pressure side, independent of the setting in the operating menu.
Material Weight Version
1)
1) Product Configurator "Housing" section
Housing Cover seal kg (lbs)
Aluminum, without viewing window EPDM 1.0 (2.21) A
Aluminum, with viewing window EPDM 1.1 (2.43) B
PMD55, H1 PMD55, V1
on
off
SW / P2=High
1 2 3 4 5
Deltabar M PMD55
Endress+Hauser 33
Dimensions V1 version;
Impulse pipe vertical;
alignment 90
A0023117
Engineering unit mm (in)
A Version cover without viewing window
B Version cover with viewing window.
1
1
6

(
4
.
6
)
8
0
.
5

(
3
.
1
7
)
1
2
2

(
4
.
8
)
41.30.2 (1.630.01)
5
4

0
.
3

(
2
.
1
3

0
.
0
1
)
1
0
4

(
4
.
0
)
A: 150 (5.9)
B: 164 (6.5)
M10
1
3

(
0
.
5
)
7
5

(
3
.
0
)
1
5
.
5

(
0
.
6
)
9
5

(
3
.
7
)
61 (2.4)
6
6
.
4

(
2
.
6
)
7/16
M10
7/16
1/4-18 NPT
SW8 / AF8
36 (1.4)
SW14 / AF14
Designation Material Weight Version
1)
1) Product Configuration "Process Connection" section
kg (lbs)
NPT 1/4-18 IEC61518 UNF 7/16-20 AISI 316L
3 (6.62)
HAJ
NPT 1/4-18 IEC61518 UNF 7/16-20 C22.8 HA4
NPT 1/4-18 IEC61518 M10 AISI 316L HBJ
NPT 1/4-18 IEC61518 M10 C22.8 HB4
Deltabar M PMD55
34 Endress+Hauser
Dimensions H1 version;
Impulse pipe horizontal;
alignment 180
A0023119
Engineering unit mm (in)
A Version cover without viewing window
B Version cover with viewing window.
7
5

(
3
.
0
)
6
1

(
2
.
4
)
1/4-18 NPT
A: 170 (6.7)
B: 184 (7.2)
SW8 / AF8
36 (1.4)
SW14 / AF14
SW14 / AF14
22 (0.9)
1
0
4

(
4
.
0
)
1
1
6

(
4
.
6
)
8
0
.
5

(
3
.
1
7
)
1
2
2

(
4
.
8
)
Designation Material Weight Version
1)
1) Product Configuration "Process Connection" section
kg (lbs)
NPT 1/4-18 IEC61518 UNF 7/16-20 AISI 316L
3 (6.62)
HGJ
NPT 1/4-18 IEC61518 UNF 7/16-20 C22.8 HG4
NPT 1/4-18 IEC61518 M10 AISI 316L HHJ
NPT 1/4-18 IEC61518 M10 C22.8 HH4
Deltabar M PMD55
Endress+Hauser 35
Dimensions H2 version;
Impulse pipe horizontal;
alignment 90
A0023121
Engineering unit mm (in)
A Version cover without viewing window
B Version cover with viewing window.
1
1
6

(
4
.
6
)
8
0
.
5

(
3
.
1
7
)
1
2
2

(
4
.
8
)
41.30.2 (1.630.01)
5
4

0
.
3

(
2
.
1
3

0
.
0
1
)
1
0
4

(
4
.
0
)
A: 150 (5.9)
B: 164 (6.5)
M10
1
3

(
0
.
5
)
7
5

(
3
.
0
)
1
5
.
5

(
0
.
6
)
9
5

(
3
.
7
)
61 (2.4)
6
6
.
4

(
2
.
6
)
7/16
M10
7/16
1/4-18 NPT
SW8 / AF8
36 (1.4)
SW14 / AF14
SW14 / AF14
22 (0.9)
Designation Material Weight Version
1)
1) Product Configuration "Process Connection" section
kg (lbs)
NPT 1/4-18 IEC61518 UNF 7/16-20 AISI 316L
3 (6.62)
HNJ
NPT 1/4-18 IEC61518 UNF 7/16-20 C22.8 HN4
NPT 1/4-18 IEC61518 M10 AISI 316L HOJ
NPT 1/4-18 IEC61518 M10 C22.8 HO4
Deltabar M PMD55
36 Endress+Hauser
Materials not in contact with
process
Housing
A0023122
Front view, right-hand side view, top view.
Filling oil
1
2
6
7
10
13
14
11
12 8
15 17 16
3
4 5 9
Item
number
Component part Material
1
F30 housing, RAL 5012 (blue) Die-cast aluminum with protective powder-coating
on polyester base
2
Cover, RAL 7035 (gray) Die-cast aluminum with protective powder-coating
on polyester base
3 Cover seal EPDM
4 Sight glass Mineral glass
5 Sight glass seal Silicone (VMQ)
6 Nameplates Plastic film
7 Plain washer A4
8 Screws A2-70 or A4-70
9 Screw 316L
10 External ground terminal AISI 304 (1.4301)
11 Attachement for tie-on label AISI 304 (1.4301)/ AISI 316 (1.4401)
12 Pressure compensation filter Silicone
13 Sealing ring EPDM
14 Seal of cable gland and blind plug EPDM/NBR
15 Cable gland Polyamide (PA) or CuZn nickel-plated
16 Blind plug PBT-GF30 FR
for dust ignition-proof, Ex d, FM XP and CSA XP:
AISI 316L (1.4435)
17 Cover clamp Clamp AISI 316L (1.4435), screw A4
Oil Version
1)
1) Product Configurator "Fill Fluid" section
Silicone oil 1
Inert oil 2
Deltabar M PMD55
Endress+Hauser 37
Connecting parts
A0023123
Materials in contact with
process
Side flanges
Endress+Hauser supplies side flanges made of stainless steel AISI 316L as per material numbers
1.4404 or 1.4408 or side flanges of C22.8 (Zn 5-8 / 1.0460 + Zn 5-8) with zinc plating.
Endress+Hauser recommends to use side flanges made out of 316L for applications with water.
Process isolating diaphragm
Oval flange adapters
AISI 316L (1.4404)
Vent valves
AISI 316L (1.4404)
TSE Certificate of Suitability (Transmissible Spongiform Encephalopathy)
The following applies to all process wetted device components:
They do not contain any materials derived from animals.
No additives or operating materials derived from animals are used in production or processing.
Item number Component part Material
1 Adapter plate AISI 304
2 Mounting bracket AISI 304
Screw and nuts A2-70
1 2
Material Version
1)
1) Product Configurator "Process isolating diaphragm material" section
316L A
Alloy C C
Deltabar M PMD55
38 Endress+Hauser
Operability
Operating concept Operator-oriented menu structure for user-specific tasks
Commissioning
Operation
Diagnosis
Expert level
Quick and safe commissioning
Guided menus for applications
Reliable operation
Local operation possible in several languages
Standardized operation at the device and in the operating tools
Parameters relating to measured values can be locked/unlocked using the device's write protection
switch, using the device software or via remote control
Efficient diagnostic behavior increases measurement availability
Remedial measures are integrated in plain text
Diverse simulation options
Local operation Local display (optional)
A 4-line liquid crystal display (LCD) is used for display and operation. The local display shows measured
values, dialog texts as well as fault and notice messages in plain text, thereby supporting the user at
every stage of operation. The liquid crystal display of the device can be turned in 90 stages.
Depending on the orientation of the device, this makes it easy to operate the device and read the
measured values.
Functions
8-digit measured value display including sign and decimal point, bar graph for 4 to 20 mA HART as
current display; or for PROFIBUS PA as graphic display of the standardized value of the AI Block; for
FOUNDATION Fieldbus as graphic display of the transducer output in relation to the set pressure
range.
Simple and complete menu guidance as parameters are split into several levels and groups
Each parameter is given a 3-digit ID number for easy navigation
Possibility of configuring the display to suit individual requirements and preferences, such as
language, alternating display, contrast setting, display of other measured values such as sensor
temperature etc.
Comprehensive diagnostic functions (fault and warning message, peak-hold indicators etc.)
A0016498
1 Operating keys
2 Bar graph
3 Symbol
4 Header line
5 Parameter identification number
Ordering information:
Product Configurator, "Output, Operation" section
1
3
2
4
5
E +
Deltabar M PMD55
Endress+Hauser 39
Operating keys and elements located internally on the electronic insert
Function Operation via display
HART PROFIBUS PA FOUNDATION Fieldbus
Position adjustment (zero point correction) X X X
Setting lower range value and upper range value - reference pressure present
at the device
X X X
Device reset X X X
Locking and unlocking parameters relevant to the measured value X X X
Value acceptance indicated by the green LED -- -- --
Switching damping on and off X X X
A0023125
HART electronic insert
1 Operating keys for lower range value (zero) and
upper range value (span)
2 Green LED to indicate successful operation
3 Slot for optional local display
4 DIP switch for defining high pressure side
5 DIP switch for defining operating mode and
output characteristics
6 DIP switch for alarm current SW / Alarm Min
(3.6 mA)
7 DIP switch for switching damping on/off
8 DIP switch for locking/unlocking parameters
relevant to the measured value
A0023126
PROFIBUS PA electronic insert
1 Green LED to indicate successful operation
2 Operating key for position zero adjustment or
reset (Zero)
3 Slot for optional local display
4 DIP-switch for bus address SW / HW
5 DIP-switch for hardware address
6 DIP switch for defining high pressure side
7 DIP switch for defining operating mode and
output characteristics
8 Not used
9 DIP switch for switching damping on/off
10 DIP switch for locking/unlocking parameters
relevant to the measured value
A0023127
FOUNDATION Fieldbus electronic insert
1 Operating key for position zero adjustment or
reset (Zero)
2 Green LED to indicate successful operation
3 Slot for optional local display
4 DIP switch for defining high pressure side
5 DIP switch for defining operating mode and
output characteristics
6 DIP-switch for simulation mode
7 DIP switch for switching damping on/off
8 DIP switch for locking/unlocking parameters
relevant to the measured value
on
off
S
W

/

P
2
=
H
i
g
h
S
W

/
A
l
a
r
m

m
i
n
S
W

/
d
a
m
p
i
n
g
1 2 3 4 5
on
off
Display
Zero
Span
H
A
R
T
R
FIELD COM
M
UNICATION PROTO
CO
L
S
W

/

P
2
=
H
ig
h
d
e
lt
a

p

o
n
ly
S
W

/
A
la
r
m

m
in
S
W

/
d
a
m
p
in
g
8 7 6 5 4
3
1
2
10 9 8 7 6
on
off
S
W

/

P
2
=
H
i
g
h
d
a
m
p
i
n
g
1 2 3 4 5
on:P2=
delta p
only High off:SW
1
2
3
4
5
off:SW on:
on
off
damp
not used
Address
SW
HW
Zero
on
off
Display
S
W

/
1
3
4 5
2
on
off
S
W

/

P
2
=
H
i
g
h
S
i
m
u
l
a
t
i
o
n
S
W

/
d
a
m
p
i
n
g
1 2 3 4 5
on
off
Display
Zero
s
im
u
la
t
io
n
TM
FOUNDATION
S
W

/

P
2
=
H
ig
h
S
W

/
d
a
m
p
in
g
d
e
lt
a

p

o
n
ly
8 7 6 5 4
1
2
3
Function Operation with operating keys and operating elements on the
electronic insert
HART PROFIBUS PA FOUNDATION Fieldbus
Position adjustment (zero point correction) X X X
Setting lower range value and upper range value - reference pressure present
at the device
X -- --
Device reset X X X
Locking and unlocking parameters relevant to the measured value X X X
Value acceptance indicated by the green LED X X X
Switching damping on and off X X X
Deltabar M PMD55
40 Endress+Hauser
Ordering information:
Product Configurator, "Output, Operation" section
Operating languages You can also choose another language in addition to the standard language "English":
Remote operation All software parameters are accessible depending on the position of the write protection switch on the
device.
FieldCare
FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you
can configure all Endress+Hauser devices as well as devices from other manufacturers that support the
FDT standard.
FieldCare supports the following functions:
Configuration of transmitters in offline and online mode
Loading and saving device data (upload/download)
HistoROM

/M-DAT analysis
Documentation of the measuring point
Connection options:
HART via Commubox FXA195 and the USB port on a computer
PROFIBUS PA via segment coupler and PROFIBUS interface card
Service interface with Commubox FXA291 and ToF adapter FXA291 (USB).
For further information, please contact your local Endress+Hauser Sales Center.
Field Xpert SFX100
Field Xpert is an industrial PDA with integrated 3.5" touchscreen from Endress+Hauser based on
Windows Mobile. It offers wireless communication via the optional VIATOR Bluetooth modem or via
WiFi and Endress+Hausers Fieldgate FXA520. Field Xpert also works as a stand-alone device for asset
management applications. For details refer to BA00060S/00/EN.
Commubox FXA195
For intrinsically safe HART communication with FieldCare via the USB interface. For details refer to
TI00404F/00/EN.
Designation Version
1)

1) Product Configurator "Additional Operation Language" section
English AA
German AB
French AC
Spanish AD
Italian AE
Dutch AF
Chinese AK
Japanese AL
Hardware and software for remote
operation
HART PROFIBUS PA FOUNDATION Fieldbus
FieldCare 40 ff
1)
1) Commubox FXA195 required 40 ff

2)
2) Profiboard or Proficard required 41 ff

FieldXpert SFX100 40 ff
NI-FBUS Configurator 41 ff
Deltabar M PMD55
Endress+Hauser 41
Commubox FXA291
The Commubox FXA291 connects Endress+Hauser field devices with a CDI interface
(= Endress+Hauser Common Data Interface) with the USB interface of a PC or laptop.
For details refer to TI00405C/07/EN.

For the following Endress+Hauser devices you will also need the "ToF adapter FXA291" as an accessory:
Cerabar S PMC71, PMP7x
Deltabar S PMD7x, FMD7x
Deltapilot S FMB70
ToF Adapter FXA291
The ToF adapter FXA291 connects the Commubox FXA291 with devices from the ToF platform,
pressure devices and the Gammapilot via the USB interface of a PC or laptop. For details refer to
KA00271F.
Profiboard
For connecting a PC to the PROFIBUS.
Proficard
For connecting a laptop to the PROFIBUS
FF configuration program
FF configuration program, such as NI-FBUS Configurator, to
connect devices with "FOUNDATION Fieldbus signal" into an FF-network
set FF-specific parameters
Remote operation via:
Operation with NI-FBUS Configurator:
The NI-FBUS Configurator is an easy-to-use graphical environment for creating linkages, loops, and
a schedule based on the fieldbus concepts.
You can use the NI-FBUS Configurator to configure a fieldbus network as follows:
Set block and device tags
Set device addresses
Create and edit function block control strategies (function block applications)
Configure vendor-defined function and transducer blocks
Create and edit schedules
Reading and writing of data from control and regulation systems
Invoke methods specified in the manufacturer-specific DD (e.g. basic device settings)
Display DD menus (e.g. tab for calibration data)
Download a configuration
Verify a configuration and compare it to a saved configuration
Monitor a downloaded configuration
Replace a virtual device by a real device
Save and print a configuration
System integration The device can be given a tag name (max. 8 alphanumeric characters)
Designation Version
1)
1) Product configurator "Marking" section
Tagging (TAG), see aditional spec. Z1
Bus address, see aditional spec. Z2
Deltabar M PMD55
42 Endress+Hauser
Certificates and approvals
CE mark The device meets the legal requirements of the relevant EC directives.
Endress+Hauser confirms that the device has been successfully tested by applying the CE mark.
Ex approvals ATEX
FM
CSA
NEPSI
IECEx
All explosion protection data are given in separate documentation which is available upon request. The
Ex documentation is supplied as standard with all devices approved for use in explosion hazardous
areas.
47, "Safety Instructions" section and "Installation/Control Drawings".
Marine certificate (in
preparation)
Germanischer Lloyd (GL)
American Bureau of Shipping (ABS)
Functional safety SIL The Deltabar M with 4 to 20 mA output signal has been developed to assessed and certified by TV
NORD CERT as per IEC 61508 Edition 2.0 and IEC 61511. These devices can be used to monitor the
process level and pressure up to SIL 2. For a detailed description of the safety functions with Deltabar
M, settings and functional safety data, see the "Functional safety manual - Deltabar M" SD00347P.
Ordering information: Product Configurator "Other approvals" section, "LA" version
AD2000 The pressure retaining material 316L (1.4435/1.4404) corresponds to AD2000 - W2/W10.
CRN approval Some device versions have CRN approval. For a CRN-approved device, a CRN-approved process
connection ( 44 ff, feature 110 "Process connection") must be ordered with a CSA approval
( 44 ff, feature 10 "Approval"). These devices are fitted with a separate plate bearing the
registration number 0F13907.5C.
Pressure Equipment Directive
(PED)
PMD55 corresponds to Article 3 (3) of the EC directive 97/23/EC (Pressure Equipment Directive) and
has been designed and manufactured according to good engineering practice.
Standards and guidelines DIN EN 60770 (IEC 60770):
Transmitters for use in industrial-process control systems
Part 1: Methods for inspection and routine testing
DIN 16086:
Electrical pressure measuring instruments, pressure sensors, pressure transmitters, pressure
measuring instruments,
concepts, specifications in data sheets
EN 61326-X:
EMC product family standard for electrical equipment for measurement, control and laboratory use.
North-American practice for
installation of process seals
Endress+Hauser instruments are designed according to ANSI/ISA 12.27.01 either as single seal or
dual seal devices with annunciation, allowing the user to waive the use and save the cost of installing
external secondary process seals in the conduit as required by the process sealing sections of ANSI/
NFPA 70 (NEC) and CSA 22.1 (CEC). These instruments comply with the North-American installation
practice and provide a very safe and cost-saving installation for pressurized applications with
hazardous fluids.
Further information can be found in the control drawings of the relevant devices.
Inspection certificate
Designation Version
1)
EN10204-3.1 material wetted parts, inspection certificate JA
NACE MR0175 wetted parts JB
EN10204-3.1 AD2000 material wetted parts, expecting process membrane, inspection
certificate
JF
EN10204-3.1 Helium leak test, inspection certificate KD
Deltabar M PMD55
Endress+Hauser 43
Calibration; Unit
Calibration
Service
EN10204-3.1 pressure test, inspection certificate KE
1) Product Configurator "Test, Certificate" section
Designation Version
1)
Designation Version
1)
1) Product Configurator "Calibration; Unit" section
Nominal value; mbar/bar B
Nominal value; kPa/MPa C
Nominal value; mm/mH2O D
Nominal value; inH2O/ftH2O E
Nominal value; psi F
Customized pressure; see additional specification J
Customized level; see additional spec. K
Customized flow; see additional spec. L
Adjusted for Deltatop; see additional spec. 8
Designation Version
1)
1) Product Configurator "Calibration" section
Factory calib. certificate 5-point F1
DKD/DAkkS calib. certificate 10-point F2
Designation Version
1)
1) Product Configurator "Service" section
Cleaned from oil+grease
2)
)
2) Only device, not accessory or enclosed accessory
HA
Cleaned for oxygen service
2)
HB
Cleaned from PWIS (PWIS = paint wetting impairment substances)
2)
HC
Adjusted min alarm current IA
Adjusted HART Burst Mode PV IB
Deltabar M PMD55
44 Endress+Hauser
Ordering information
Detailed ordering information is available as follows:
In the Product Congurator on the Endress+Hauser website: www.endress.com Select country
Products Select product Product page function: Congure this product
From your Endress+Hauser Sales Center: www.endress.com/worldwide
Product Configurator - the tool for individual product configuration
Up-to-the-minute configuration data
Depending on the device: direct input of information specific to the measuring point, such as
measuring range or operating language
Automatic verification of exclusion criteria
Automatic generation of the order code with its breakdown in PDF or Excel output format
Ability to order directly in the Endress+Hauser Online Shop
Configuration data sheet Pressure
If the version "J" was selected in the "Kalibration; Einheit" section of the Product Configurator, the
following configuration data sheet must be completed and included with the order.
Smallest span (factory calibration) 11
Pressure Engineering Unit
mbar mmH
2
O mmHg Pa
bar mH
2
O kPa
ftH
2
O kgf/cm
2
MPa
psi inH
2
O
Calibration Range / Output
Low range value (LRV): _________________ [Pressure engineering unit]
Upper range value (URV): _________________ [Pressure engineering unit]
Display Information
1st Value Display
1)
2nd Value Display
1)
Main Value none (Default)
Main Value [%]
Pressure
Current [mA] (HART only)
Temperature
1)
Depending on sensor and comunication variant
Damping
Damping: ___________ sec (Default 2 sec)
Deltabar M PMD55
Endress+Hauser 45
Level
If the version "K" was selected in the "Kalibration; Einheit" section of the Product Configurator, the
following configuration data sheet must be completed and included with the order.
Pressure Engineering Unit Output Unit (Scaled unit)
mbar mmH
2
O mmHg Pas Mass Length Volume Volume Percent
bar mH
2
O kPa
ftH
2
O kgf/cm
2
MPa kg m l gal %
psi inH
2
O t dm hl Igal
lb cm
mm m
3
ft
3
ft in
3
inch
Example
Empty pressure [a]:
Low pressure value (empty) ______________
[Pressure
engineering unit]
Empty calibration [a]:
Low level value (empty) ______________
[Scaled Unit]
A0023130
A 50 mbar (1 psi) / 3 m
3
(106 ft
3
)
B 500 mbar (7.5 psi) / 100 m
3
(3532 ft
3
).
Full pressure [b]:
High pressure value (full) ______________
[Pressure
engineering unit]
Full calibration [b]:
High level value (full) ______________
[Scaled Unit]
Display Information
1st Value Display
1)
2nd Value Display
1)
Main Value none (Default)
Main Value [%]
Pressure
Current [mA] (HART only)
Temperature
1)
Depending on sensor and comunication variant
Damping
Damping: ___________ sec (Default 2 sec)
+

A
B
Deltabar M PMD55
46 Endress+Hauser
Flow
If the option "L" was selected in the "Calibration; Unit" section of the Product Configurator, the following
configuration data sheet must be completed and included with the order.
Pressure Engineering Unit Flow Unit / Measured Value (PV)
mbar mmH
2
O mmHg Pa Mass Volume Volume Volume Percent
bar mH
2
O Operation
Condition
Norm
Condition
Standard
Condition
ftH
2
O kgf/cm
2
kPa
psi inH
2
O MPa kg/s m
3
/s Nm
3
/s Sm
3
/s %
kg/min m
3
/min Nm
3
/min Sm
3
/min
kg/h m
3
/h Nm
3
/h Sm
3
/h
t/s l/s Nm
3
/d Sm
3
/d
t/min l/min
t/h l/h SCFS
oz/s US Gal/s SCFM
oz/min US Gal/min SCF3
lb/s US Gal/h SCFD
lb/min ACFS
lb/h ACFM
ACFH
Default: Volume; m
3
/h
Output Characteristic
linear (HART only) square root (HART only)
Operation Point Operation Point
Max Pressure _________________ [Pressure
engineering unit]
Max Pressure _________________ [Pressure engineering
unit]
Max Flow _________________ [flow unit] Max Flow _________________ [flow unit]
LRV _________________ [Pressure engineering
unit]
LRV _________________ [flow unit]
(Lower Range Value (HART only)) (Lower Range Value (HART only))
Low flow cut off
Value: _________________ [%] (default = 5
Display Information
1st Value Display
1)
2nd Value Display
1)
Main Value none (Default)
Main Value [%]
Pressure
Current [mA] (HART only)
Temperature
Totalizer 1
Totalizer 2
1)
Depending on sensor and comunication variant
Damping
Damping: ___________ sec (Default 2 sec)
Deltabar M PMD55
Endress+Hauser 47
Additional documentation
Field of Activities Pressure measurement, powerful instruments for process pressure, differential pressure, level and
flow: FA00004P/00/EN
Technical Information EMC test procedures TI00241F/00/EN
Cerabar M: TI00436P/00/EN
Deltapilot M: TI00437P/00/EN
Operating Instructions 4 to 20 mA HART: BA00382P/00/EN
PROFIBUS PA: BA00383P/00/EN
FOUNDATION Fieldbus: BA00384P/00/EN
Brief operating instruction 4 to 20 mA HART: KA01027P/00/EN
PROFIBUS PA: KA01028P/00/EN
FOUNDATION Fieldbus: KA01029P/00/EN
Functional safety manual
(SIL)
Deltabar M (4 to 20 mA): SD00347P/00/EN
Safety Instructions
Directive Approval Category Electronics Documentation Version
1)
1) Product Configurator "Approval" section
ATEX
Ex ia IIC II 1/2 G
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA00457P/00 BA
Ex t IIIC II 1/2 D
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA00458P/00 BB
Ex d IIC II 2G 4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA00459P/00
BC
Ex nA IIC II 3 G
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA00461P/00 BD
Ex ic IIC II 3 G
4...20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA01301P/00 BG
Ex ia IIC
Ex ia D
II 1/2 G
II 1/2 D
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA00460P/00 B1
Ex ia IIC
Ex d IIC
II 1/2 G
II 2 G
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA00505P/00
8A
Directive Approval Electronics Documentation Version
1)
1) Product Configurator "Approval" section
NEPSI
Ex ia IIC 4 to 20 mA HART XA00534P/00 NA
Ex d IIC 4 to 20 mA HART XA00514P/00 NB
Directive Approval Electronics Version
1)
1) Product Configurator "Approval" section
TIIS Ex ia IICT4 4 to 20 mA HART TA
Deltabar M PMD55
48 Endress+Hauser
Installation/Control
Drawings
Directive Approval EPL Electronics Documentation Version
1)

1) Product Configurator "Approval" section
IECEx
Ex ia IIC Ga/Gb
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA00462P/00 IA
Ex d IIIC Gb
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA00463P/00 IB
Ex t IIIC Da/Db 4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA00490P/00
ID
Ex ic IIC Gc
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA00492P/00 IE
Ex ia IIC
Ex ia IIIC
Ga/Gb
Da/Db
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA00491P/00 I1
Directive Approval Electronics Documentation Version
1)
1) Product Configurator "Approval" section
INMETRO Ex ia IIC T6...T4 Ga/Gb
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA01303P/00 MA
Directive Approval Electronics Documentation Version
1)
1) Product Configurator "Approval" section
FM
IS Cl.I,II,III Div.1 Gr. A-G,
AEx ia NI Cl. I Div.2 Gr.A-D
4 to 20 mA HART
PROFIBUS PA,
FOUNDATION Fieldbus
ZD00234P/00
XA00565P/00 FA
FM XP Cl.I,II Div.1 Gr.A-G Zone 1
IIC T6 (Conduit seal not required),
Zone 1,2
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
--
FB
FM DIP Cl.II,III Div.1 Gr.E-G,
Zone 21,22
-- --
FC
FM NI Cl.I Div.2 Gr.A-D, Zone 2 -- -- FD
FM IS/XP Cl.I,II Div.1 Gr.A-G,
Zone 1,2
PROFIBUS PA,
FOUNDATION Fieldbus
XA00568P/00 F1
CSA
C/US IS Cl.I,II,III Div.1 Gr A-G
C/US IS Cl.I Div.2 Gr A-D, Ex ia
4 to 20 mA HART
PROFIBUS PA,
FOUNDATION Fieldbus
XA00557P/00
XA00559P/00 CA
CSA C/US XP Cl.I,II Div.1 Gr.B-G,
Ex d, (Conduit seal not required),
Zone 1,2
-- --
CB
CSA C/US Cl.II,III Div.1 Gr.E-G, US:
Zone 21,22
-- --
CC
CSA C/US IS/XP Cl.I,II Div.1Gr.A-
G/B-G, Zone 1,2
4 to 20 mA HART
PROFIBUS PA,
FOUNDATION Fieldbus
XA00576P/00
XA00562P/00
C1
Deltabar M PMD55
Endress+Hauser 49
Combined certificate
Directive Approval Electronics Documentation Version
1)
1) Product Configurator "Approval" section
FM/CSA FM/CSA IS + XP Cl.I,II Div.1
Gr.A-D/B-G FM IS/FM XP Cl.I,II Div.1
Gr.A-G + CSA IS/XP Cl.I,II Div.1
Gr.A-G, FM/CSA: Zone 1,2
4 to 20 mA HART
ZD00247P/00
XA00576P/00
ZD00250P/00
8B
PROFIBUS PA,
FOUNDATION Fieldbus
XA00568P/00
XA00562P/00
Deltabar M PMD55
50 Endress+Hauser
Registered trademarks
HART Registered trademark of the HART Communication Foundation, Austin, USA
PROFIBUS Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
FOUNDATION Fieldbus Registered trademark of the Fieldbus Foundation, Austin, Texas, USA
Deltabar M PMD55
Endress+Hauser 51
www.addresses.endress.com