Power TRF Relay Setting - HD-A1 PDF

This document provides relay settings for a transformer protection relay. It includes: 1) Details of the transformer such as its power rating, voltages, and current transformer ratios. 2) Settings for the configuration parameters of the protection relay including communication settings, input/output mapping, and LED assignments. 3) Settings for the protection elements within the relay including differential, restricted earth fault, time-overcurrent, and voltage/frequency protection.

Uploaded by

honghoaso1
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
539 views7 pages

Power TRF Relay Setting - HD-A1 PDF

This document provides relay settings for a transformer protection relay. It includes: 1) Details of the transformer such as its power rating, voltages, and current transformer ratios. 2) Settings for the configuration parameters of the protection relay including communication settings, input/output mapping, and LED assignments. 3) Settings for the protection elements within the relay including differential, restricted earth fault, time-overcurrent, and voltage/frequency protection.

Uploaded by

honghoaso1
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

RELAY SETTING FOR TRANSFORMER PTN.

: HANG DONG A1
Prepared by: M.S.Negi; Checked by: Mr. S. Midha Flovel Energy Pvt. Ltd. INDIA

P
a
g
e
1

REV-0
Type of Relay: MICOM P632; Schneider



Power Transformer data
Sl.N Parameters Details
1. Power 11.5 MVA
2. HV Voltage 115 kV
3. LV Voltage 6.3 kV
4. CTR HV 60/1 A
5. CTR LV 1100/1 A
6. NCT 60/1 A
7. Bus PTR 115kV/110V
8. Transformer percentage imp 10.5 %
9. Transformer vector group Ynd11, + 5% in step of 2.5%


T-CT2
N
C
T
T-CT1
HV
LV
52HT
89T
89TE-2
89TE-1
B-CVT







RELAY SETTING FOR TRANSFORMER PTN. : HANG DONG A1
Prepared by: M.S.Negi; Checked by: Mr. S. Midha Flovel Energy Pvt. Ltd. INDIA

P
a
g
e
2



1) PARAMETERS > CONFIG. PARAMETERS
1. 1) CONFIG. PARAMETERS: COMM1

Function group COMM1 With
Line idle state Light on / high
prot. variant ALSTOM D
Baud rate 19.2 kBaud
Parity bit Even
Dead time monitoring Yes
Mon. time polling 25 s
Octet comm. address 1
Test monitor on No

1. 2) CONFIG. PARAMETERS: INP:

010.220 Filter 0
153.087 Fct. assignm. U 2001 LOGIC Input 1 EXT
153.090 Fct. assignm. U 2002 LOGIC Input 2 EXT
153.093 Fct. assignm. U 2003 LOGIC Input 3 EXT
153.096 Fct. assignm. U 2004 LOGIC Input 4 EXT
153.088 Oper. mode U 2001 Active "high"
153.091 Oper. mode U 2002 Active "high"
153.094 Oper. mode U 2003 Active "high"
153.097 Oper. mode U 2004 Active "high"

1. 3) CONFIG. PARAMETERS: OUT:

151.201 Fct. assignm. K 2001 LOGIC Output 1
151.204 Fct. assignm. K 2002 Without function
151.207 Fct. assignm. K 2003 V/ f tV/f> elapsed
151.210 Fct. assignm. K 2004 DIFF Trip signal
151.213 Fct. assignm. K 2005 REF_1 Trip signal
151.216 Fct. assignm. K 2006 DTOC1 Trip signal tIN>
151.219 Fct. assignm. K 2007 DTOC1 Trip signal tI>
151.222 Fct. assignm. K 2008 MAIN Prot. ext. enabled
151.202 Oper. mode K 2001 ES updating
151.205 Oper. mode K 2002 ES updating
151.208 Oper. mode K 2003 ES updating







RELAY SETTING FOR TRANSFORMER PTN. : HANG DONG A1
Prepared by: M.S.Negi; Checked by: Mr. S. Midha Flovel Energy Pvt. Ltd. INDIA

P
a
g
e
3


1. 4) CONFIG. PARAMETERS: LED:

085.184 Fct.assig. H 1 green MAIN Healthy
085.001 Fct.assig. H 2 yell. MAIN Blocked/faulty
085.004 Fct.assig. H 3 yell. SFMON Warning (LED)
085.007 Fct.assig. H 4 red MAIN Gen. trip command 1
085.057 Fct.assig. H 4 green Without function
085.010 Fct.assig. H 5 red DIFF Trip signal
085.060 Fct.assig. H 5 green Without function
085.013 Fct.assig. H 6 red DTOC1 Trip signal tIN>
085.063 Fct.assig. H 6 green Without function
085.016 Fct.assig. H 7 red DTOC1 Trip signal tI>
085.066 Fct.assig. H 7 green Without function
085.019 Fct.assig. H 8 red REF_1 Trip signal
085.069 Fct.assig. H 8 green Without function
085.022 Fct.assig. H 9 red V/ f tV/f> elapsed
085.072 Fct.assig. H 9 green Without function
085.025 Fct.assig. H10 red Without function
085.075 Fct.assig. H10 green Without function

1. 5) CONFIG. PARAMETERS: DIFF:

Function group DIFF With

1. 6) CONFIG. PARAMETERS: REF_1:

Function group REF_1 With

1. 7) CONFIG. PARAMETERS: REF_2:

Function group REF_2 Without

1. 8) CONFIG. PARAMETERS: DTOC1:

Function group DTOC1 With

1. 9) CONFIG. PARAMETERS: DTOC2:

Function group DTOC2 Without

1. 10) CONFIG. PARAMETERS: IDMT1:

Function group IDMT1 Without



RELAY SETTING FOR TRANSFORMER PTN. : HANG DONG A1
Prepared by: M.S.Negi; Checked by: Mr. S. Midha Flovel Energy Pvt. Ltd. INDIA

P
a
g
e
4

1. 11) CONFIG. PARAMETERS: IDMT2:



Function group IDMT2 Without

1. 12) CONFIG. PARAMETERS: V<>:

Function group V <> Without

1. 13) CONFIG. PARAMETERS: f <>:

Function group f <> Without

1. 14) CONFIG. PARAMETERS: V/f:

Function group V/f With

1. 15) CONFIG. PARAMETERS: LOGIC:

Function group LOGIC With




2) PARAMETERS >> FUNCTION PARAMETERS >> GLOBAL >> MAIN

003.030 Device on-line Yes (=on)
003.012 Test mode USER Yes
010.030 Nominal frequ. fnom 50 Hz
010.049 Phase sequence A - B - C
019.020 Inom C.T.prim.,end a 1100 A
019.021 Inom C.T.prim.,end b 60 A
019.027 Inom C.T.Yprim,end a 1100 A
019.028 Inom C.T.Yprim,end b 60 A
010.002 Vnom V.T. prim. 6.3 kV
010.024 Inom device, end a 1.0 A
010.025 Inom device, end b 1.0 A
010.142 IY,nom device, end a 1.0 A
010.143 IY,nom device, end b 1.0 A
010.009 Vnom V.T. sec. 110 V
010.140 Conn.meas.circ. IP,a Standard
010.150 Conn.meas.circ. IP,b Standard
010.141 Conn.meas.circ. IY,a Standard
010.151 Conn.meas.circ. IY,b Standard




RELAY SETTING FOR TRANSFORMER PTN. : HANG DONG A1
Prepared by: M.S.Negi; Checked by: Mr. S. Midha Flovel Energy Pvt. Ltd. INDIA

P
a
g
e
5


3) PARAMETERS >> FUNCTION PARAMETERS >> PARAMETERS SUBSET1:
3.1) MAIN:

019.017 Vnom prim. end a PS1 6.3 kV
019.018 Vnom prim. end b PS1 115.0 kV
010.200 Phase reversal a PS1 No swap
010.204 Phase reversal b PS1 No swap

3.2) DIFFERENTIAL PROTECTION:

072.152 Enable PS1 Yes
019.010 Vec.gr. ends a-b PS1 0
072.142 Idiff> PS1 0.15 Iref
072.143 Idiff>> PS1 5.0 Iref
072.144 Idiff>>> PS1 30.0 Iref
080.000 Idiff>(CTS) PS1 0.20 Iref
072.145 m1 PS1 0.20 (Bias setting m1=20%)
072.146 m2 PS1 0.70 (Bias setting m2=70%)
072.147 IR,m2 PS1 4.0 Iref
072.148 Op.mode rush rst. PS1 Not phase-selective
072.159 RushI(2f0)/I(f0) PS1 20 % (2
nd
Harmonic blocking)
072.155 0-seq. filt.a en. PS1 Yes
072.156 0-seq. filt.b en. PS1 NO
072.158 Overflux.bl. en. PS1 No
072.160 Ov. I(5f0)/I(f0) PS1 100 % (5
th
Harmonic blocking)
010.162 Op.del.,trip sig. PS1 0.00 s
072.006 Hyst. effective PS1 Yes
Vector group end a-b 11
Vector group end a-c 11

3.3) REF PROTECTION:


072.141 Enable PS1 Yes
072.149 Operating mode PS1 Low impedance / SUM(IP)
080.006 Bl.f.DIFF trigg. PS1 No
080.003 CTS effective PS1 No
072.150 Idiff> PS1 0.10 Iref
072.151 Idiff>>> PS1 10.0 Iref
072.162 m1 PS1 0.20
072.163 m2 PS1 1.50
072.164 IR,m2 PS1 1.00 Iref




RELAY SETTING FOR TRANSFORMER PTN. : HANG DONG A1
Prepared by: M.S.Negi; Checked by: Mr. S. Midha Flovel Energy Pvt. Ltd. INDIA

P
a
g
e
6

3.4) DTOC_1 PROTECTION (For HV Side):


CT ratio: 60/1
Transformer rated current: =52.71A.
Secondary current =52.71/60 =0.878A
Current setting =1.2 x 0.878 =1.05 A
Time delay =3 sec.
Highset to be set at 10 times IDMT set current I,e 0.878 x 10 = 8.78A
Timer Setting: 0.02 sec.
076.050 Enable PS1 Yes
076.067 Block tim.st. IN PS1 Without
076.066 Gen.starting mode PS1 With start. IN/Ineg
076.065 tGS PS1 0.00 s
076.063 Rush restr.enabl PS1 No
076.051 I> PS1 1.05 Inom
076.052 I>> PS1 1.10 Inom
076.053 I>>> PS1 8.78 Inom
076.151 I>dynamic PS1 1.00 Inom
076.152 I>>dynamic PS1 1.00 Inom
076.153 I>>>dynamic PS1 1.00 Inom
076.057 tI> PS1 3.00 s
076.058 tI>> PS1 0.50 s
076.059 tI>>> PS1 0.02 s
076.197 Ineg> PS1 0.25 Inom

3.5) V/f PROTECTION:

081.210 Enable PS1 Yes
081.211 V/ f>(alarm) PS1 1.10 Vnom/fnom
081.212 V/ f(t)> PS1 1.25 Vnom/fnom
081.213 V/ f>> PS1 1.45
081.214 tV/f> PS1 1 s (Alarm)
081.217 t at V/f=1.05 PS1 Max
081.218 t at V/f=1.10 PS1 Max
081.219 t at V/f=1.15 PS1 Max
081.220 t at V/f=1.20 PS1 55 s
081.221 t at V/f=1.25 PS1 40 s
081.222 t at V/f=1.30 PS1 20 s
081.223 t at V/f=1.35 PS1 8 s
081.224 t at V/f=1.40 PS1 5 s
081.225 t at V/f=1.45 PS1 4 s
081.226 t at V/f=1.50 PS1 3.5 s
081.227 t at V/f=1.55 PS1 3 s
081.228 t at V/f=1.60 PS1 2 s
081.230 Reset time PS1 2 s
081.229 tV/f>> PS1 Blocked


RELAY SETTING FOR TRANSFORMER PTN. : HANG DONG A1
Prepared by: M.S.Negi; Checked by: Mr. S. Midha Flovel Energy Pvt. Ltd. INDIA

P
a
g
e
7



3.6) BREAKER FAILURE PROTECTION:

Select. meas. input End HV SIDE
I< 0.10 Inom
t1 3p 0.15 s
t2 0.25 s
Delay/starting trig. 0.00 s
Delay/fault beh. CB 0.12 s


4) Settings for E/F: 51 (MICOM P111)

CT ratio: 60/1
Transformer rated current: =57.70 A.
Secondary current =57.70/60 =0.961A
E/ F to be set 10% of the full load current - 0.1 x 0.961 =0.096A
Timer Setting: 2 sec.

5) Settings for 6.3kV Bus Earth Fault Relay: (64BG)

MAKE TYPE SETTING RANGE SETTING PTR
AREVA VDG14 5.4 ~20 A 5.4 Volts 6300/ 110V

6) Settings for 115kV Bus Diff. protection Relay: (87B)

MAKE TYPE SETTING RANGE SETTING CTR
AREVA CAG34 1.0 ~4.0 A 1.0 A 60/1A


7) Temperature Protection:

Winding temperature : Alarm : 85
0
C
Winding temperature : Trip : 90
0
C
Oil temperature : Alarm : 75
0
C
Oil temperature : Trip : 80
0
C