RELAY SETTING FOR TRANSFORMER PTN.
: HANG DONG A1
Prepared by: M.S.Negi; Checked by: Mr. S. Midha Flovel Energy Pvt. Ltd. INDIA
P
a
g
e
1
REV-0
Type of Relay: MICOM P632; Schneider
Power Transformer data
Sl.N Parameters Details
1. Power 11.5 MVA
2. HV Voltage 115 kV
3. LV Voltage 6.3 kV
4. CTR HV 60/1 A
5. CTR LV 1100/1 A
6. NCT 60/1 A
7. Bus PTR 115kV/110V
8. Transformer percentage imp 10.5 %
9. Transformer vector group Ynd11, + 5% in step of 2.5%
T-CT2
N
C
T
T-CT1
HV
LV
52HT
89T
89TE-2
89TE-1
B-CVT
RELAY SETTING FOR TRANSFORMER PTN. : HANG DONG A1
Prepared by: M.S.Negi; Checked by: Mr. S. Midha Flovel Energy Pvt. Ltd. INDIA
P
a
g
e
2
1) PARAMETERS > CONFIG. PARAMETERS
1. 1) CONFIG. PARAMETERS: COMM1
Function group COMM1 With
Line idle state Light on / high
prot. variant ALSTOM D
Baud rate 19.2 kBaud
Parity bit Even
Dead time monitoring Yes
Mon. time polling 25 s
Octet comm. address 1
Test monitor on No
1. 2) CONFIG. PARAMETERS: INP:
010.220 Filter 0
153.087 Fct. assignm. U 2001 LOGIC Input 1 EXT
153.090 Fct. assignm. U 2002 LOGIC Input 2 EXT
153.093 Fct. assignm. U 2003 LOGIC Input 3 EXT
153.096 Fct. assignm. U 2004 LOGIC Input 4 EXT
153.088 Oper. mode U 2001 Active "high"
153.091 Oper. mode U 2002 Active "high"
153.094 Oper. mode U 2003 Active "high"
153.097 Oper. mode U 2004 Active "high"
1. 3) CONFIG. PARAMETERS: OUT:
151.201 Fct. assignm. K 2001 LOGIC Output 1
151.204 Fct. assignm. K 2002 Without function
151.207 Fct. assignm. K 2003 V/ f tV/f> elapsed
151.210 Fct. assignm. K 2004 DIFF Trip signal
151.213 Fct. assignm. K 2005 REF_1 Trip signal
151.216 Fct. assignm. K 2006 DTOC1 Trip signal tIN>
151.219 Fct. assignm. K 2007 DTOC1 Trip signal tI>
151.222 Fct. assignm. K 2008 MAIN Prot. ext. enabled
151.202 Oper. mode K 2001 ES updating
151.205 Oper. mode K 2002 ES updating
151.208 Oper. mode K 2003 ES updating
RELAY SETTING FOR TRANSFORMER PTN. : HANG DONG A1
Prepared by: M.S.Negi; Checked by: Mr. S. Midha Flovel Energy Pvt. Ltd. INDIA
P
a
g
e
3
1. 4) CONFIG. PARAMETERS: LED:
085.184 Fct.assig. H 1 green MAIN Healthy
085.001 Fct.assig. H 2 yell. MAIN Blocked/faulty
085.004 Fct.assig. H 3 yell. SFMON Warning (LED)
085.007 Fct.assig. H 4 red MAIN Gen. trip command 1
085.057 Fct.assig. H 4 green Without function
085.010 Fct.assig. H 5 red DIFF Trip signal
085.060 Fct.assig. H 5 green Without function
085.013 Fct.assig. H 6 red DTOC1 Trip signal tIN>
085.063 Fct.assig. H 6 green Without function
085.016 Fct.assig. H 7 red DTOC1 Trip signal tI>
085.066 Fct.assig. H 7 green Without function
085.019 Fct.assig. H 8 red REF_1 Trip signal
085.069 Fct.assig. H 8 green Without function
085.022 Fct.assig. H 9 red V/ f tV/f> elapsed
085.072 Fct.assig. H 9 green Without function
085.025 Fct.assig. H10 red Without function
085.075 Fct.assig. H10 green Without function
1. 5) CONFIG. PARAMETERS: DIFF:
Function group DIFF With
1. 6) CONFIG. PARAMETERS: REF_1:
Function group REF_1 With
1. 7) CONFIG. PARAMETERS: REF_2:
Function group REF_2 Without
1. 8) CONFIG. PARAMETERS: DTOC1:
Function group DTOC1 With
1. 9) CONFIG. PARAMETERS: DTOC2:
Function group DTOC2 Without
1. 10) CONFIG. PARAMETERS: IDMT1:
Function group IDMT1 Without
RELAY SETTING FOR TRANSFORMER PTN. : HANG DONG A1
Prepared by: M.S.Negi; Checked by: Mr. S. Midha Flovel Energy Pvt. Ltd. INDIA
P
a
g
e
4
1. 11) CONFIG. PARAMETERS: IDMT2:
Function group IDMT2 Without
1. 12) CONFIG. PARAMETERS: V<>:
Function group V <> Without
1. 13) CONFIG. PARAMETERS: f <>:
Function group f <> Without
1. 14) CONFIG. PARAMETERS: V/f:
Function group V/f With
1. 15) CONFIG. PARAMETERS: LOGIC:
Function group LOGIC With
2) PARAMETERS >> FUNCTION PARAMETERS >> GLOBAL >> MAIN
003.030 Device on-line Yes (=on)
003.012 Test mode USER Yes
010.030 Nominal frequ. fnom 50 Hz
010.049 Phase sequence A - B - C
019.020 Inom C.T.prim.,end a 1100 A
019.021 Inom C.T.prim.,end b 60 A
019.027 Inom C.T.Yprim,end a 1100 A
019.028 Inom C.T.Yprim,end b 60 A
010.002 Vnom V.T. prim. 6.3 kV
010.024 Inom device, end a 1.0 A
010.025 Inom device, end b 1.0 A
010.142 IY,nom device, end a 1.0 A
010.143 IY,nom device, end b 1.0 A
010.009 Vnom V.T. sec. 110 V
010.140 Conn.meas.circ. IP,a Standard
010.150 Conn.meas.circ. IP,b Standard
010.141 Conn.meas.circ. IY,a Standard
010.151 Conn.meas.circ. IY,b Standard
RELAY SETTING FOR TRANSFORMER PTN. : HANG DONG A1
Prepared by: M.S.Negi; Checked by: Mr. S. Midha Flovel Energy Pvt. Ltd. INDIA
P
a
g
e
5
3) PARAMETERS >> FUNCTION PARAMETERS >> PARAMETERS SUBSET1:
3.1) MAIN:
019.017 Vnom prim. end a PS1 6.3 kV
019.018 Vnom prim. end b PS1 115.0 kV
010.200 Phase reversal a PS1 No swap
010.204 Phase reversal b PS1 No swap
3.2) DIFFERENTIAL PROTECTION:
072.152 Enable PS1 Yes
019.010 Vec.gr. ends a-b PS1 0
072.142 Idiff> PS1 0.15 Iref
072.143 Idiff>> PS1 5.0 Iref
072.144 Idiff>>> PS1 30.0 Iref
080.000 Idiff>(CTS) PS1 0.20 Iref
072.145 m1 PS1 0.20 (Bias setting m1=20%)
072.146 m2 PS1 0.70 (Bias setting m2=70%)
072.147 IR,m2 PS1 4.0 Iref
072.148 Op.mode rush rst. PS1 Not phase-selective
072.159 RushI(2f0)/I(f0) PS1 20 % (2
nd
Harmonic blocking)
072.155 0-seq. filt.a en. PS1 Yes
072.156 0-seq. filt.b en. PS1 NO
072.158 Overflux.bl. en. PS1 No
072.160 Ov. I(5f0)/I(f0) PS1 100 % (5
th
Harmonic blocking)
010.162 Op.del.,trip sig. PS1 0.00 s
072.006 Hyst. effective PS1 Yes
Vector group end a-b 11
Vector group end a-c 11
3.3) REF PROTECTION:
072.141 Enable PS1 Yes
072.149 Operating mode PS1 Low impedance / SUM(IP)
080.006 Bl.f.DIFF trigg. PS1 No
080.003 CTS effective PS1 No
072.150 Idiff> PS1 0.10 Iref
072.151 Idiff>>> PS1 10.0 Iref
072.162 m1 PS1 0.20
072.163 m2 PS1 1.50
072.164 IR,m2 PS1 1.00 Iref
RELAY SETTING FOR TRANSFORMER PTN. : HANG DONG A1
Prepared by: M.S.Negi; Checked by: Mr. S. Midha Flovel Energy Pvt. Ltd. INDIA
P
a
g
e
6
3.4) DTOC_1 PROTECTION (For HV Side):
CT ratio: 60/1
Transformer rated current: =52.71A.
Secondary current =52.71/60 =0.878A
Current setting =1.2 x 0.878 =1.05 A
Time delay =3 sec.
Highset to be set at 10 times IDMT set current I,e 0.878 x 10 = 8.78A
Timer Setting: 0.02 sec.
076.050 Enable PS1 Yes
076.067 Block tim.st. IN PS1 Without
076.066 Gen.starting mode PS1 With start. IN/Ineg
076.065 tGS PS1 0.00 s
076.063 Rush restr.enabl PS1 No
076.051 I> PS1 1.05 Inom
076.052 I>> PS1 1.10 Inom
076.053 I>>> PS1 8.78 Inom
076.151 I>dynamic PS1 1.00 Inom
076.152 I>>dynamic PS1 1.00 Inom
076.153 I>>>dynamic PS1 1.00 Inom
076.057 tI> PS1 3.00 s
076.058 tI>> PS1 0.50 s
076.059 tI>>> PS1 0.02 s
076.197 Ineg> PS1 0.25 Inom
3.5) V/f PROTECTION:
081.210 Enable PS1 Yes
081.211 V/ f>(alarm) PS1 1.10 Vnom/fnom
081.212 V/ f(t)> PS1 1.25 Vnom/fnom
081.213 V/ f>> PS1 1.45
081.214 tV/f> PS1 1 s (Alarm)
081.217 t at V/f=1.05 PS1 Max
081.218 t at V/f=1.10 PS1 Max
081.219 t at V/f=1.15 PS1 Max
081.220 t at V/f=1.20 PS1 55 s
081.221 t at V/f=1.25 PS1 40 s
081.222 t at V/f=1.30 PS1 20 s
081.223 t at V/f=1.35 PS1 8 s
081.224 t at V/f=1.40 PS1 5 s
081.225 t at V/f=1.45 PS1 4 s
081.226 t at V/f=1.50 PS1 3.5 s
081.227 t at V/f=1.55 PS1 3 s
081.228 t at V/f=1.60 PS1 2 s
081.230 Reset time PS1 2 s
081.229 tV/f>> PS1 Blocked
RELAY SETTING FOR TRANSFORMER PTN. : HANG DONG A1
Prepared by: M.S.Negi; Checked by: Mr. S. Midha Flovel Energy Pvt. Ltd. INDIA
P
a
g
e
7
3.6) BREAKER FAILURE PROTECTION:
Select. meas. input End HV SIDE
I< 0.10 Inom
t1 3p 0.15 s
t2 0.25 s
Delay/starting trig. 0.00 s
Delay/fault beh. CB 0.12 s
4) Settings for E/F: 51 (MICOM P111)
CT ratio: 60/1
Transformer rated current: =57.70 A.
Secondary current =57.70/60 =0.961A
E/ F to be set 10% of the full load current - 0.1 x 0.961 =0.096A
Timer Setting: 2 sec.
5) Settings for 6.3kV Bus Earth Fault Relay: (64BG)
MAKE TYPE SETTING RANGE SETTING PTR
AREVA VDG14 5.4 ~20 A 5.4 Volts 6300/ 110V
6) Settings for 115kV Bus Diff. protection Relay: (87B)
MAKE TYPE SETTING RANGE SETTING CTR
AREVA CAG34 1.0 ~4.0 A 1.0 A 60/1A
7) Temperature Protection:
Winding temperature : Alarm : 85
0
C
Winding temperature : Trip : 90
0
C
Oil temperature : Alarm : 75
0
C
Oil temperature : Trip : 80
0
C