West 6170-2

The West 6170 is a process controller designed to control valve motors using PID or on-off control modes. It has inputs for thermocouples, RTDs, and linear signals, and can provide control outputs via relays or solid state relays. Additional features include dual setpoint selection, ramping setpoint, auto/manual tuning, and RS485 communications. It is intended for use in controlling motorized valves and has a unique VMD tuning algorithm for that application.

Uploaded by

stev_zoran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
527 views2 pages

West 6170-2

The West 6170 is a process controller designed to control valve motors using PID or on-off control modes. It has inputs for thermocouples, RTDs, and linear signals, and can provide control outputs via relays or solid state relays. Additional features include dual setpoint selection, ramping setpoint, auto/manual tuning, and RS485 communications. It is intended for use in controlling motorized valves and has a unique VMD tuning algorithm for that application.

Uploaded by

stev_zoran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

West 6170

1/16 DIN Valve Motor Controller

The West 6170 is a process controller designed specifically to drive


valve motors, with a unique VMD tuning algorithm.

Motorised Valve Control


Two process alarms
Loop alarm
RS485 comms

Ramping setpoint
Auto/manual tuning
Dual setpoint selection
PC configuration

Technical Data
Features
Control Types
Valve Control
Auto/Manual
Output Configuration
Alarm 1 & 2 Types
Human Interface
PC Configuration
Input
Thermocouple
RTD
DC Linear
Impedance
Accuracy
Sampling
Sensor Break Detection
Outputs & Options
Control Relays
Solid State (Triac)
Outputs
Alarm Relay
Retransmit Outputs
Communications
Dual Setpoint Selection
Operating &
Environmental
Temperature & RH
Power Supply
Front Panel Protection
Approvals and
Certification

6170 Spec Sheet 07/00

Full PID with Pre-tune, Self-tune, Manual Tuning, or On-Off control


Open loop Valve Motor Drive. Slide-wire feedback from valve is not required
Selectable from front panel, with bumpless transfer
Up to 3 total. 2 for control (Open/Close Valve), 1 for Alarm or retransmit PV or SP (optional)
Process high, process low, SP deviation, band, logical OR and hysteresis. Also 1 loop alarm
4 button operation, dual 4 digit 10mm & 8mm high LED displays, plus 3 LED indicators
Off-line configuration from serial port to dedicated config socket (comms option not required)
J, K, R, S, T, B, L, & N.
3 Wire PT100, 50 per lead maximum (balanced)
0-20/4-20mA, 0-50/10-50mV, 0-5/1-5/0-10/2-10V. Scaleable -1999 to 9999, dec point
available
>100M for Thermocouple and mV ranges, 47K for V ranges and 4.7 for mA ranges
+/- 0.25% of input span +/- 1 LSD (T/C CJC better than 0.7C)
4 per second, 14 bit resolution approximately
<2 secs (except zero based DC ranges), control O/Ps turn off, *high alarms activate (*low
for RTD, mA or V).
Contacts SPDT 2Amp resistive at 120V AC (motor drive) or 240V AC ( via contactor),
>500,000 operations
0.01 to 1 Amp AC 20 to 280V, 47 to 63Hz
Contacts SPDT 2Amp resistive at 240V AC , >500,000 operations
0-20/4-20mA into 500 max, 0-10/0-5V into 500 min. Accuracy typically +/- 0.25%
2 Wire RS485, 1200 to 9600 Baud, West ASCII
Selects between 2 SPs using volt free or TTL input (SP1 = -0.6 to 0.8V, SP2 = 2 to 24V)

0 to 55C (-20 to 80C storage), 20% to 95%RH non-condensing


90 to 264V 50/60Hz (optional 20 to 55V AC/22 to 65V DC), approx 4 Watts
IEC IP66 (Behind panel protection is IP20)
CE, UL & ULc

Dimensions

Panel Cut-out

10mm (approx)
110mm

45mm +0.5

48mm

45mm +0.5

48mm

Connection Details

Field Reconfiguration
Input
Configurable to any type, no extra parts
required
Output 1
Type is fixed as ordered. Relay or Triac
(Valve Open)
Output 2
Type is fixed as ordered. Relay or Triac
(Valve Close)
Output 3
Configurable as Alarm via plug-in Relay
or SSR modules, or retransmit PV or SP
using DC Linear module
Option Slot
Configurable as RS485 comms or dual
setpoint selection, via plug-in modules

Order Code
N6171/
Input type
3 Wire RTD or DC mV
Thermocouple
DC mA
DC Voltage

1
2
3
4

Output 1
Relay Control (Valve Open)
Triac Control (Valve Open)

1
8

Output 2
Relay Control (Valve Close)
Triac Control (Valve Close)

1
8

Z x

xx

00
02
10
12
30
32
0
1
2
3
4
5
7

Options and Power Supply


No Options/90-264V AC line supply
No Options/24-48V AC or DC line supply
RS485 Comms/90-264V AC line supply
RS485 Comms/24-48V AC or DC supply
Dual Setpoint/90-264V AC line supply
Dual Setpoint/24-48V AC or DC supply
Output 3
Not fitted
Relay Alarm 1 output
DC for SSR Alarm 1 output
DC 0-10V Re-Transmit PV or SP
DC 0-20mA Re-Transmit PV or SP
DC 0-5V Re-Transmit PV or SP
DC 4-20mA Re-Transmit PV or SP