Instrumentation
Instrumentation
Just like pressure switches, a differential pressure switch can be calibrated to a known set point. You
can do a quick calibration of a differential pressure switch the same way you calibrate a pressure switch.
However for more accurate calibrate, the procedure is slightly modified.
I.Quick calibration procedure for a Differential Pressure Switch
Equipment required includes:
a. A variable pressure source
b. A digital multimeter or continuity test lamp
c. A test gauge
Calibration Equipment setup
Calibration Steps
Step 1:
Connect the variable pressure source to a test gauge and the HI side pressure port of switch
Step 2:
Connect the test lamp or multimeter (set to the ohmmeter setting) across C-Common and NO-Normal
Open switching element contacts as shown above
Step 3:
Raise pressure and note test gauge reading when circuit closes
Step 4:
Slowly drop pressure and note test gauge reading when circuit opens
Step 5:
Adjust set point screw to increase or decrease set point
Step 6:
Repeat steps 3, 4 and 5 until contacts change at desired increasing or decreasing differential pressure set
point
II.Accurate Calibration Procedure
To accurately calibrate a differential pressure switch, we need to simulate the required service
conditions.
Equipment required for this calibration process are:
a. Differential pressure gauge (preferably a digital type)
b. Variable pressure source
c. Block, bleed and equalizer valves
d. Continuity test lamp or digital multimeter
First determine whether the set point occurs on increasing or decreasing differential pressure and
calibrate using either of:
a. Set point on Increasing Differential Pressure
b. Set point on Decreasing Differential Pressure
Calibration Steps for Set point on Increasing Differential Pressure
Connect the setup as shown below and then proceed with the steps
Calibration steps
Step 1:
Connect the continuity test lamp or digital multimeter across the C-Common and NO-Normally Open
switching element/contacts
Step 2:
Close the bleed valves, open the equalizer valve and raise pressure equally on both HI and LO sides to
the static pressure that the differential pressure switch will see under normal operating conditions
Step 3:
With static pressure stable, close the equalizer valve to isolate the HI side from the LO side
Step 4:
Keep HI side pressure steady, slightly open the LO side bleed valve to reduce the LO side pressure
(increase diffrential pressure) until desired diffrential pressure set point appears on diffrential pressure
gauge. Close bleed valve to stablize differential pressure. Check the status of the electrical contacts
against the following possible scenarios and follow the instructions that match the status of the contact:
a. Set point is Okay if (see diagram above): Contacts make precisely at increasing differential
pressure set point, repeat Steps 2-4 as desired to verify calibration. Calibration is complete.
b. Contacts are Open Set point too High: If contacts are open when increasing differential
pressure is reached, adjust set point screw until contacts make. Repeat steps 2-4.
c. Contacts Closed Set point Too Low: If contacts are closed when increasing differential
pressure is reached, adjust set point screw until contacts break. From this point, adjust set point
again until contacts make. Repeat steps 2-4.
Calibration Steps for Set point on Decreasing Differential Pressure
Step 1:
Connect the continuity test lamp or digital multimeter across the C-Common and NO-Normally Open
switching element/contacts
Step 2:
Close the bleed valves, open the equalizer valve and raise pressure equally on both HI and LO sides to
the normal operating static pressure
Step 3:
With normal HI side pressure stable, close the equalizer valve to isolate the HI side from the LO side
Step 4:
Slightly open the LO side bleed valve to reduce LO side pressure ( increase differential pressure) until
the normal operating differential pressure appears on the differential pressure gauge. Close the bleed
valve to stabilize differential pressure. Contacts should close ( make) by the time normal operating
differential pressure is reached. If the contacts are still open at normal operating differential pressure,
adjust the set point screw until the contacts make.
Step 5:
Keeping the HI side pressure steady, slightly open the equalizer valve to increase LO side pressure
(decrease differential pressure) until the desired differential pressure set point appears on the differential
pressure gauge. Close the equalizer valve to stabilize differential pressure. Check the status of the
electrical contacts against the following differential pressure scenarios and follow the instructions that
match the status of the contacts:
a. Set point is Okay if (see diagram above): Contacts break precisely at decreasing differential
pressure set point, repeat Steps 2-5 as desired to verify calibration. Calibration is complete.
b. Contacts are Open Set point too High: If contacts are open when deecreasing differential
pressure is reached, adjust set point screw until contacts make. From this point, adjust set point
screw again until contacts break. Repeat steps 2-5.
c. Contacts Closed Set point Too Low: If contacts are closed when decreasing differential
pressure is reached, adjust set point screw until contacts break. Repeat steps 2-5.
As shown in the diagram above, current supplied from the power supply flows through the loop wires
with resistance, RW, to the trasmitter and the 4-20mA transmitter regulates the current flow within the
loop. The current allowed by the transmitter is called the loop current and it is proportional to the
parameter that is being measured. The loop current flows back to the controller through the wire, and
then flow through resistor, R, to ground and returns to the power supply. The current flowing through R
produces a voltage that is easily measured by the analog input of a controller. For a 250 ohm resistor, the
voltage will be 1VDC at 4mA and 5VDC at 20mA.
As the diagram above showns, there are four basic components in the 4-20mA current loop namely:
a.
b.
c.
d.
Next, we take this percentage value and translate it into a 4-20mA current value using formula:
Current=(16mA)(P/100%)+(4mA)=(16mA)(20%/100%)+(4mA)=7.2mA
Therefore, the transmitter should output a Process Value signal of 7.2mA at a temperature 60 F.
An electronic loop controller outputs a signal of 8mA to a direct-responding control valve (where
4mA is shut and 20mA is wide open). How far open should be control valve be at this Manipulated
Variable signal level?
Solution:
We must convert the milliamp signal value into a percentage of valve travle. This means determining the
percentage value of the 8mA signal on the 4-20mA range. First we need to manipulated the percentagemilliamp formula to solve for percentage (P):
Current=(16mA)(P/100%)+(4mA)
P/100%=[(Current-4mA0/(16mA)]
P=[(Current-4mA)/(16mA)]x100%=[(8mA-4mA)/(16mA)]x100%=25%
Therefore, the control valve should be 25% open when the MV signal is at a value of 8mA
Additional learning resources:
Now that you understand basic control signal used in instrumentation. You could also check out this
book measurement and control basics. It is a very good book for beginners to instrumentation and
control. Established technicians and engineers could also get the book for their library.
Closely related to the concept of the 4-20mA signal and 3-15PSI signal is the art of calibration. Many
technicians and experts in instrumentation and control will agree with me that calibration is a critical
aspect of plant management and process safety. To learn the art of calibration you might check out these
books:
-A Technicians guide to calibration
-Calibration Handbook. This book teaches you how to develope and management a calibration program
in your plant
How Direct Acting and Reverse Acting Control Valve Loops Work
transmitter is from the signal loop. The 4mA zero-end current is sufficient do drive the internal circuitry
of the transmitter and the current from 4 to 20mA represents the range of the measured process variable.
The power supply and the instruments are usually mounted in the control room. The schematic diagram
below shows the wire transmitter configuration:
Note that in all the transmitter wire configurations shown above, a load resistor of 250ohm is used.
Ususally process controllers used in instrumentation systems are not equipped to directly accept
milliamp input signals, but rather voltage signals. For this reason a precision resistor is connected across
the input terminals of the controllers to convert current signals from transmitters into standardized
analog voltage signals that controllers can understand.
A voltage signal range of 1 to 5 volts is standard, although some models of controllers use different
voltage ranges and therefore require different precision resistor values. If the voltage range is 1-5 volts
and the current range is 4-20mA, the precision resistor value must be 250 ohms.
In the transmitter wire configurations discussed above, it is assumed that a voltage signal range of 1-5V
and a standard current signal of 4-20mA are used.
The above block diagram is further simplified to give the one below:
As shown above in fig A, the smart transmitter consists of the following basic parts:
a. Process Sensor
b. An analog to digital converter (ADC)
c. A microprocessor
d. A digital to analog converter (DAC)
These basic parts can be organized into three basic sections as shown in fig B:
a. Input section
b. Conversion Section
c. Output section
Input Section:
The input section comprises the process sensor or transducer and the Analog to Digital Converter
(ADC). The sensor measures the process variable of interest (be it pressure, temperature, flow etc)
which is then converted into a proportional electrical signal. The measured electrical signal is then
transformed to a digital count by the Analog to DigitalConverter (ADC). This digital count,
representative of the process variable (PV), is then fed into the conversion section which contains the
microprocessor.
However, the microprocessor must rely upon some form of equation or algorithm to relate the raw count
value of the electrical measurement to the actual process variable (PV) of interest such as temperature,
pressure, or flow. The principal form of this algorithm is usually established by the manufacturers of the
smart transmitters, but most HART transmitters include commands to perform field adjustments. This
type of adjustment is often referred to as a sensor trim. The output of the input section is a digital
representation of the process variable (PV). When you read the process variable using a hand held field
communicator, this is the value that you see.