Carrier Ahu .-39fx - PD

The document describes an air handling unit product. It provides details on the components, casing construction, dimensions, dampers, filters, fans, motors, drives, coils, heaters, heat recovery systems, humidifiers, sound attenuators, application guide, options, specifications, selection tools, and conversion tables.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (4 votes)
3K views60 pages

Carrier Ahu .-39fx - PD

The document describes an air handling unit product. It provides details on the components, casing construction, dimensions, dampers, filters, fans, motors, drives, coils, heaters, heat recovery systems, humidifiers, sound attenuators, application guide, options, specifications, selection tools, and conversion tables.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 60

Product

Data

39FD/FX
Central Station
Air Handling Units

Nominal 1000 m3/hr to 160,000 m3/hr

Features/Benefits
Flexible modular
construction offers
several configurations of
unit height and width to
meet installation space
requirements
The units are fabricated
from heavy gauge
galvanized powder
painted steel sheet with
linear gasket between
panels to ensure sturdy
construction and
excellent leak tight
Units are offered with
double skin panels in 25
mm (39FD) or 50mm
(39FX) thickness
Fan and motor packages
are mounted on common
bases with vibration
isolators to ensure
moving parts are isolated
from the casing structure
Units can be delivered in
complete or partial
sections or knockeddown for on site
assembly
Manufactured at an ISO
9001 listed facility to
guarantee quality

Copyright 2004 Carrier Corporation

Form 39F-2PD-S

Table of Contents

Carrier 39F

Introduction

Identification

Quick Selection

Components

Casing

Dimension

Dampers

Filters

12

Fans

17

Motor

22

Drives

26

Coils

27

Electric Heaters

30

Heat Recovering System

33

Humidifiers

36

Sound Attenuators

39

Application Guide

40

Options

43

Guide Specifications

45

Selection Tools and Sample Selection

51

Conversion Table

56

Back

Introduction

Carrier 39F

The purpose of this catalogue is to guide consulting engineers in the preliminary selection of Carrier Air
Handling Units. However, if required, your local Carrier office will assist to provide a computerized selection
to confirm or complete your preliminary selection.
This catalogue consists of:

A description of the various component parts


available to be combined in the order best
suited to your requirements.

Technical data sheets, dimensions, weights,


specifications, charts, etc.

Component specification and international


standard compliance.
Product features and application.

QUALITY
The quality and reliability of any system depends
on the quality of the component parts. Therefore,
inline with other Carrier products our 39F Series
Air Handlers are manufactured in conformity with
Carriers Quality concept with vendor items
subjected to rigorous inspection. Components
installed in Air Handlers are manufactured, tested
or rated in compliance to international standards.
FLEXIBLE MODULAR CONSTRUCTION
This adaptable unit design which is based upon a
wide range of standard panel sizes frequently
enables Carrier to offer several configurations of
unit height and width, so that the aesthetic or
practical dictates of confined plant room space or
rooftop silhouettes can be easily met.
Major sections of the Air Handling Unit such as
fan, coil, filter, etc, can be arranged in the sequence
dictated by the job requirements, and separated by
access sections where necessary, giving complete
flexibility of design.
The units can be delivered in sections for indoor or
outdoor installation, completely assembled,
partially assembled or knocked-down for on-site
assembly.
RIGID AND LEAKTIGHT CONSTRUCTION
The Carrier series 39F Air Handling Unit is
fabricated from heavy gauge galvanized powder
painted steel sheet, which is folded to form sturdy
side, top and bottom panels and a rigid Penta
Post supporting frame.
Panels and frame are secured using internally
bolted fixings so that welding is minimized and the
integrity of the galvanized finish is maintained.
Gasket liner between panels and frame ensures
excellent leaktight and also as thermal and acoustic

insulation. This bolted construction, and the use of


standardized components facilitates the removal of
panels for maximum access to fans, coils, filters,
etc.
WIDE RANGE OF SIZES
23 standard sizes provide air quantities from,

1000 m3/hr to 78,810 m3/hr cooling duty

Up to 90,855 m3/hr heating only duty

For duties in excess of the above, please contact


your Carrier office.
FLEXIBILITY IN PANEL CONSTRUCTION
Units are offered with double skinin 25 mm
(Model 39FD) and 50mm (Model 39FX)
thickness.
VIBRATION ISOLATION
Centrifugal fan/motor packages are mounted on
common bases with rubber or spring vibration
isolators and flexible cuffs ensuring that all moving
parts are independently isolated from the casing
structure.
AESTHETICS
The standard construction features galvanized
panel and frame finished in light gray polyester
powder paint, capable of withstanding 1000 hours
of direct salt spray according to ASTM B117.
ACCESSIBILITY AND MAINTENANCE
The easily removable panels and quick release
access doors offer complete accessibility to fans,
coils, filters and dampers. Additional access
sections can be provided between coils and filters if
required.
All component parts are standard and
interchangeable. Filters are commercially available
standard items conforming to international
standards and sizes.
INDIVIDUALIZED PRODUCT LINE
All 23 standard sizes are available as Customized
adapted exactly to meet specific job requirements.
For example: Non-standard coil materials, variable
fan speed control, humidifiers,
heaters,
attenuators, etc.

Back

Carrier 39F

Identification

The 39F line of Carrier Air Handling Units is base


on Modular system

The unit length is determined by the number and


size of the component parts required.

The number of modules respectively in height and


in width determines the cross-section available for
airflow and encodes the unit size.

The side for services (connections and access) is


defined as right hand or left hand in the direction of
the airflow.

Example:

39

_____

AIR HANDLING UNIT

F = MODEL
D = 25 mm or X = 50 mm
HEIGHT in modules
WIDTH in modules
COIL HEADER LOCATION
0 = internal header
4 = external header with header box
UNIT SERIAL NUMBER
Left Hand

Right Hand

1 module
Air Flow

Height
4 modules
Length
dependent on length and
number of component parts
1 module

Width
5 modules

Back

Quick Selection

Carrier 39F

The air volume entering the finned coil section determines the unit size as follows,
1.5 m/s minimum velocity (cooling or heating)

3.15 m/s maximum velocity for cooling coil


with droplet eliminator

2.6 m/s maximum velocity for cooling coil


without droplet eliminator
AIR VOLUME
m3/hr x 1000

4.5 m/s maximum velocity for heating coil

AIR QUANTITY RANGE


, m3/hr x 1000
9 10 11 12 13 14 15 17 20 30 40 50 60 70 80 90 100

39FD/X-220
39FD/X-230
39FD/X-240
39FD/X-330
39FD/X-340
39FD/X-350
39FD/X-360
39FD/X-370
39FD/X-440
39FD/X-450
39FD/X-460
39FD/X-470
39FD/X-480
39FD/X-550
39FD/X-560
39FD/X-570
39FD/X-580
39FD/X-660
39FD/X-670
39FD/X-680
39FD/X-770
39FD/X-780
39FD/X-7100

Min. to Max Airflow for Cooling Coil


@ Extedded Coils (Enlarged Coil Face Area)
Airflow for Cooling Coils
Airflow for Heating Coils

Example:
To determine the size of a unit delivering 30000 m3/hr of air (unit supplied with cooling and heating coil), two
selections are possible,
-

size 570 (standard unit) with droplet


eliminator, coil section 2.77m2 face area

30000 = 3.0 m/s (max 3.15 m/s)


3600 x 2.77

size 580 (customized unit) without droplet


eliminator, coil section 3.26m2 face area

30000 = 2.55 m/s (max 3.15 m/s)


3600 x 3.26

Back

Components

Carrier 39F

LIST OF COMPONENTS AND THEIR CASING LENGTH


Airflow from left to right
Component

Legend

Symbol

Length
in Module M

Empty box

CV

L=nxM
L max = 10 M

Door

PO

L = 580 mm
combined in 2 M

Damper on outside
of case :
full face
half face

RA
RM

L = 150 mm
External protrusion from case

Box with one damper

RI

L = 1 module

RD

Unit size:
220 to 480
550 to 680
770 to 7100

L=
2M
3M
4M

Combination mixing box


with three dampers

RT

Unit size:
220 to 480
550 to 680
770 to 7100

L=
4M
6M
8M

Side withdrawal filters :


metallic flat
synthetic flat
vee filter

FM
FI
FV

Front or back withdrawal


filters :
metallic filters
synthetic flat
vee filter

FM
FI
FV

L=2M
with access door upstream or
downstream
L = 0 if filters are built into
mixing box

Soft bag filter


Rigid bag filter

FP
FR

L = 2 M with access via mix box


3 M with downstream access
4 M with upstream access

Mixing box
with two dampers

L=1M
With side panel for quick access

Component

Legend

Length
in Module M

Symbol

L = 2 M with access via mix box


3 M with upstream access

Roll filter

FD

Absolute filter
or
carbon filter

FA
FC

Hot water coil

BC

1 to 4 rows
5 to 8 rows

Electric heating coil

BE

L=1M

Cooling coil

BF

L=2M

Plate recouperator

ES
EH
EP

L = 3 to 8 M
See section on heat recovery

Run around heat


Recovery coils

EB

L=2M
2 sections required

Humidifier
1 or 2 spray tree(s)

HU

1 spray tree
2 spray trees

Supply or
exhaust fan

VS
VE

L = See section for fans

Sound attenuator

SL

L = 3 4 5 or 6 M
See section on sound attenuator

L = 2 M with access via mix box


3 M with upstream access

L=1M
L = 2M

L=4M
L=6M

Back

Carrier 39F

Casing

GENERAL
The 39F casings comes with double skin features and consist of penta post frame, fixed and removable panels,
and internal insulation. The casing constructions are designed with air-tightness, thermal and acoustical
insulated features. The sturdy construction of panels reinforced with solid polyurethane insulation and frames
are from galvanized, minimized spangle (G90) and are aesthetically finished with 50 micron light gray powder
paint. The casing or section arrangements are flexible depends on the requirements.

Frame
The frame is made up of 3 components,
penta post frame
corner piece
intermediate post
1.

Penta post frame


Forms the overall shape of the section and
receives the panels. The penta post is
manufactured from press formed, galvanized
steel sheet, externally painted and internally
insulated with styrofoam of 32 kg/m3 density.

2.

Corner piece
Completes corner section by connecting penta
post in three planes. Manufactured from
galvanized steel sheet, press formed, welded
and externally painted.

3.

Intermediate post
Recessed to accept panels and stiffens the case
assembly. Made of galvanized steel sheet,
press formed to a top hat shape, externally
painted and internally insulated.

Panels
Two types of panels,
fixed panel
access panel
1.

Fixed panel
Form the insulated enclosure of the case and
give it rigidity and air-tightness, they consist
of,
external sheet metal (outer skin)
insulation
internal protective cover (inner skin)
gasket liner
All panels come in double-skin configuration.
The external galvanized sheet metal 24 gauge
thickness is painted. The pre-painted internal
protective cover over the integrated
polyurethane insulation comes with galvanized
24 gauge to form solid and sturdy panel.

2.

Access panel
Constructed in similar manner as fixed panel
with similar material and dimension. Three
types are available,

3.

Removable panel fixed to frame with


external screws for easy service access
and it comes as standard at coil section,
heater section and fan section.
Quick removable panel access panel
secured to frames by latches for quick liftoff release and easy removable at filter
section.
Hinged door equipped with either latch
or lock type to facilitate the maintenance
and service at fan section or mixing box.

Paint
Oven-baked gray polyester powder, 50
microns thick provides an excellent weather
protection. Tested at different condition for
gloss, adhesion, impact resistance, over-baked
resistance and salt spray resistance in
compliance to ASTM B117.

Insulation
All panels are with thermal and acoustical insulated
that compliance with NFPA 90 A & B.
Panels come with 30-50 kg/m3 density range for
polyurethane insulation as standard.
Frames are insulated with 32 kg/m3 density
styrofoam.

Sectioning Casing
Sectioning casing will be determined by selection
software and it can be modified according to actual
used. For special casing configuration, please
contact your nearest Carrier office.

Recommendations
For expose external installation a weatherproof
roof plus a base frame must be provided. Protective
inlet and discharge hoods are available as options.
Units are suitable for operation in external ambient
temperatures of 30C to +80C.

Back

Carrier 39F

Dimensions

GENERAL

Example:

The physical size and internal dimensions of the


Air Handling Unit is determined by the number of
modules. Each module has a constant value of
315mm. Module dimensions are the same for both
39FD and 39FX series but the external dimensions
will be different due to different panel thickness.

Consider unit 39FD360 with 8 modules long,

The length of the unit is found from the sum of


component part (in modules) required.

In the case of 39FX series, replace 25 mm with 50


mm.

Height = (3 x 315 mm) + (2 x 25 mm) = 995 mm


Width = (6 x 315 mm) + (2 x 25 mm) = 1940 mm
Length = (8 x 315 mm) + (2 x 25 mm) = 2570 mm

OVERALL DIMENSIONS

Number of modules
Unit size

39FD box (mm)*

Height (H)

Width (W)

Max section
Length (L)**

Height (H)

Width (W)

Max section
Length (L)**

220
230
240

2
2
2

2
3
4

10
10
10

680
680
680

680
995
1310

3200
3200
3200

330
340
350
360
370

3
3
3
3
3

3
4
5
6
7

10
10
10
10
10

995
995
995
995
995

995
1310
1625
1940
2255

3200
3200
3200
3200
3200

440
450
460
470
480

4
4
4
4
4

4
5
6
7
8

10
10
10
10
7

1310
1310
1310
1310
1310

1310
1625
1940
2255
2570

3200
3200
3200
3200
2255

550
560
570
580

5
5
5
5

5
6
7
8

10
10
10
7

1625
1625
1625
1625

1625
1940
2255
2570

3200
3200
3200
2255

660
670
680

6
6
6

6
7
8

10
10
7

1940
1940
1940

1940
2255
2570

3200
3200
2255

770
780
7100

7
7
7

7
8
10

10
7
7

2255
2255
2255

2255
2570
3200

3200
2255
2255

* For 39FX units add 50mm to H, W and L


** Max length for any one section. No limit to the total number of sections used
***Dimensions do not include dampers, connections, extended coil, accessories
and others.

Back
GENERAL
Functions
1.

Antifreeze (for minimal leakage)

2.

Two-way or three-way mixing

3.

Bypass

4.

Multizone

Carrier 39F

Dampers

Features

Bushings are from sintered bronze (oilite) or hard


nylon, press-seated into the frame. Blades are
interconnected by means of linkage and require low
torque, even at high-pressure differential.
Interconnection on fresh, return and exhaust air
dampers is made with pushrods that are delivered
pre-installed by factory. Accessory actuators act
on two or three extended shafts and are selected to
match damper torque.
Damper spindle located either left or right hand
upon request.

Standard construction flange case frame from


1.5 mm galvanized steel sheet at both side.

Less resistance sintered bronze (oilite) bushing


and self lubricating bearings means free of
maintenance.

Temperature 30C to +80C

Oppose blades with single skin and laminar


profile blade design provide low resistance to
airflow. Parallel blade offered as option.

Maximum pressure differential 2000 Pa

Maximum velocity 9 m/s

Fitted with close gap between case and blades


and with lip formed seal between damper
blades and back seat seal which provide low
leakage, Class IV according to UL555S.

INSTALLATIONS

Low sound level and low air pressure losses


with of hollow aerodynamic profile damper
blades.

U-formed damper frame serves as a flange for


ductwork connection.

Low torque requirement and precise control


with external spindle, side linkage and oppose
blade operation.

Non-welded damper blades made of GI


material ensures corrosion resistant

CONSTRUCTION

RECOMMENDATIONS
Limits of application:

The dampers are located on the outside of mixing


boxes except on external installations where
dampers are internally mounted.

DAMPER SIZES
Standard 39F Air Handling Units damper sizes are
as attached tables.
DAMPER TORQUE
Damper Torque, M1 (Nm), can be determined from the
following relation,
M1 = x P x A x 10-2

Steel frame, flanged but not drilled, from


galvanized sheet steel.

Where,
:

Torque coefficient, cm

Blades are galvanized sheet steel of single skin and


laminar profile, designed to prevent twisting.

P :

Total pressure drop, Pascal (or N/m2)

A:

Damper cross-sectional area, m2

Wider blades are reinforced to ensure stronger


blades at higher face velocity and minimized air
leakage.
Shafts are made of 12mm dia, cadmium plated
steel.

References for torque coefficient pressure drop and


standard damper sizes as per curves and table
attached in Page 11.

Standard damper size


Length (mm)

Height

M
o
d
u
l
e

Module
(mm)

10

183

183

498

813

1128

1443

1758

2073

2388

2703

3018

498

183

498

813

1128

1443

1758

2073

2388

2703

3018

813

183

498

813

1128

1443

1758

2073

2388

2703

3018

1128

183

498

813

1128

1443

1758

2073

2388

2703

3018

1443

183

498

813

1128

1443

1758

2073

2388

2703

3018

1758

183

498

813

1128

1443

1758

2073

2073

183

498

813

1128

1443

1758

2073

10

Pressure Drop Curve

11

Torque Coefficient Curve

Back

Carrier 39F

Filters

GENERAL

Recommended filters for 39F Air Handling Unit


are tested by AFTL (American Filter Testing
Laboratory) as per ASHRAE 52.1-1992 test
method for performance, arrestance grade and
flame protection. The media is made of synthetic
polyester fiber (except for metallic filter media)
with no electro-static present, non-flammable,
washable and heat resistant up to 1000C.

Standard filter type for 39F Air Handling Units are:


Flat pre-filter 100% synthetic media,
washable, flame retarded, and U.L.Class 2
Rated.
Metallic Aluminum media, washable and
rust proof.
V-pleated - 100% synthetic media, washable,
flame retarded, and UL Class 2 Rated.

Soft bag Synthetic or fiber media, flame


retarded, and U.L. Class 2 Rated (from 50% up
to 65% Efficiency) and U.L. Class 1 Rated
(from 85% up to 95% Efficiency).
Rigid bag - Synthetic polyester media, flame
retarded, and U.L. Class 1 and 2 Rated.
Absolute will depend to the application.
Please contact Carrier office for further
information.

It is important to know the type and size of


particles in order to select the correct filter type.
The chart below illustrates various type of particles
and their sizes and some guidance for appropriate
filter to be selected.

0.0001

0.001

0.01

0.1

10

100

1000

10000

Mist
Smog

Haze

Oil fire smoke

Rain

Flyashes

Tobacco smoke

Ashes

Soot
Gas molecules

POLLUTANTS

Metallic dust
Cement dust
Pigments
Suspended dust
Virus

Pollen
Precipitating dust
Bacteria

Heavy industrial
Hair

Dust dangerous
to the lungs

Filters of average efficiency

FILTERS

Filters of high efficiency


Filters of very high efficiency
Char coal filters

Type of particles in microns and recommended filters

12

FILTER CHARACTERISTICS
Efficiency

ASHRAE 52.1-92 FILTER TEST METHOD

The definition of filter efficiency is the capability


of the filter to retain particles. The filter efficiency
is supplied together with an indication of test
method being used or else the definition is
meaningless.

ASHRAE test method is the procedure by which


practically all filter manufacturers describe the
filter performance.
Eurovent classification of
filters established filter categories that based on
ASHRAE test method. These categories are:

quantity of retained dust


Efficiency (%) = ----------------------------------x 100
total emitted quantity of dust

EU1 = Arrestance less than 65%


EU2 = Arrestance from 65% up to 80%
EU3 = Arrestance from 80% up to 90%

Pressure drop
The loss pressure drop through filters is a function
of the air velocity and the state of filter saturation.
In selecting fans for air handling units, it is
recommended that pressure loss through filters is
taken as 150% of the pressure loss of clean filters.

EU4 = Arrestance from 90% or greater


EU5 = Efficiency from 40% up to 70%
EU6 = Efficiency from 60% up to 80%
EU7 = Efficiency from 80% up to 90%

Saturation time

EU8 = Efficiency from 90% up to 95%

Saturation time is an indication of the capacity of


the filter to hold a certain amount of dust during a
given time and at a given air velocity. The
saturation time depends on the degree of site
pollution. This data is essential for establishing life
expectancy and preservation of filter efficiency.

EU9 = Efficiency greater than 95%

Filter

Method of measure

Type of measure

Average efficiency

Relation to weight

Gravimetric

High efficiency

Relation to transparency

Opacimetric

Very high efficiency or absolute

Quantity of particles

Counting and DOP

Method and type of measure


RECOMMENDATION

INSTALLATION

Filters should always be installed inside the air


handling units. Absolute filters should be supplied
with a prefilter of an opacimetric efficiency of 80
to 85%.

Depending on the type of filter, the following


recommendations are made:

The amount of dust accumulated should regularly


be checked by measuring the pressure drop across
the filter and this should not exceed 300 Pa.
The pressure drop on absolute filters should not
exceed twice the clean pressure loss. These
recommendations refer to normal air contamination
in average urban areas. Special solutions must be
sought for air contamination created in industrial
locations.
Filters exposed to high radiant temperature (above
120C) such as steam coils, electric resistance
heaters or similar, should be protected by inserting
a heat rejecting screen between the heat source and
the filter (optional feature).

13

1.

In slide rails for side withdrawal and filters of


average efficiency, such as flat metallic or
synthetic filters Synthetic V-shape filters.

2.

In frames for front or rear withdrawal for


filters of high and very high efficiency
Bag filters, soft and rigid
Absolute filters
Charcoal filters
The use of prefilters (of average efficiency) is
recommended to extend the life of high
efficiency filters. These are mounted in frame
for front withdrawal.

Automatic roll filters Roll filters are not available


for the sizes 220, 230, 240, 330. For detail
specification please contact Carrier office.

Filter standard comparison.


NORMS

METHOD OF MEASURE

ASHRAE 52.1-92
AFNOR X 44012

GRAVIMETRIC

SCALE
50

65

70

80

OPACIMETRIC

30

GRAVIMETRIC

EUROVENT 4/5

EU2

EU1

EU3

90

95

100 %

40

50

60

GRAVIMETRIC

EU5

B1

B53

Type of
Filter

14

Frame

Average

15

Installation
Efficiency

Flat
metallic

Gravimetric
73%

Flat
synthetic

Gravimetric
85%

Roll filter
fiber glass

Gravimetric
85%

V Shape
synthetic

Gravimetric
90 -95%

Soft bag

Opacimetric
50%
85%
95%
Opacimetric
50%
85%
95%

90

95

98

100 %

EU7

EU8 EU9

C2

C3

67

87

B52

OPACIMETRIC

Degree of
Efficiency

EU6

C1

GRAVIMETRIC

85

B2

OPACIMETRIC
BRITISH
BS 2831
BS 6540 PART 1

80

EU4

OPACIMETRIC
GERMAN
DIN 24185E

70

Filter
Face Velocity
Thickness
mm
Slide
Recomm
Max
Channel
m/s
m/s
x

97

Fire Class
Utilization
(ASHRAE
Characteristics
52.1-92)

25
50

2.5

3.0

M1

Washable

25

2.0

3.5

M1

Prefilter

50

2.5

3.2

M1

Constant pressure
drop

50
75

2.5
2.5

3.0
3.0

M1
M1

Good relationship
efficiency / space
requirement

x
x
x

547

3.5

4.0

M1

Large air quantities

x
x
x

292

2.7

3.2

M1

Verticle or
variable
air flow

292

2.5

2.8

M1

In special
frame
x
x

High
Rigid bag

Very High Absolute

DOP
99.99%

Operating rooms
or similar

Type and characteristics of filter used in 39F units


M1 : Non flammable
For special filter, please contact your nearest Carrier office.
14

Pressure loss (Clean filters)


Flat synthetic fiber and metallic filters

Rollfilter
125

Pressure loss (Pa)

Pressure loss (Pa)

1000

100

Synthetic 25mm
10

Metallic 50mm
1

100
75
50
25
0

0.1

0.5

10

1.5

2.5

3.5

Face velocity (m/s)

Face velocity (m/s)

Pleated filters

Soft bag filter


200

125
100

50mm
90% GRA

75

75mm
50mm

50

75mm

25

Pressure loss (Pa)

180

95% GRA

Pressure loss (Pa)

160

95% OPA

140
120

85% OPA

100
80

50% OPA

60
40
20
0

0
0

0.5

1.5

2.5

Face velocity (m/s)

Face velocity (m/s)

Rigid bag filter

Absolute filter

300

300

250

95% OPA

Pressure loss (Pa)

Pressure loss (Pa)

200

85% OPA
150

50% OPA

100
50

250
200
150
100
50
0

0
1

1.5

2.5

Face velocity (m/s)

15

3.5

0.0

0.5

1.0

1.5

2.0

Face velocity (m/s)

2.5

3.0

Weights and dimensions of filters used in 39F units


Unit size

Pleated 50mm

Prefilter 25mm

Bag filter (soft)

Dimensions (mm) and number of filters

39F

l/s max at
2.5 m/s

Weight
(kg)

l/s max at
3.5 m/s

Weight
(kg)

l/s max
at 4 m/s

Weight
(kg)

220
230
240

860
1310
1740

3
4
6

4400
6550
8850

2
3
4

5050
7500
10100

2
4
4

330
340
350
360
370

1970
2650
3130
3970
4630

6
9
11
13
15

9900
13350
16600
20050
23300

4
6
7
9
10

11350
15300
19000
22900
26600

5
8
9
11
13

440
450
460
470
480

3500
4360
5260
6110
7010

11
14
17
20
22

17650
21950
26500
30800
35350

8
10
11
13
15

20200
25100
30300
35150
40350

8
11
12
15
16

550
560
570
580

5470
6610
7680
8810

18
21
25
28

27600
33300
38700
44400

12
14
17
19

31500
38050
44200
50750

15
17
21
33

2
3
3
4

660
670
680

7890
9170
10510

25
29
34

39750
46150
53000

17
20
23

45400
52750
60550

18
23
24

6
6
8

770
780
7100

10720
12320
15390

35
40
50

54050
62050
77600

24
27
34

61800
70950
88650

29
31
39

3
4
5

914 x 610

1
2
2
3
3

914 x 305

610 x 610

610 x 305

1
1
2

1
1
1
4
4
6
6
8
1
1

2
2

2
3
3
4

6
8
10

Filters 50mm pleated, 25mm prefilters, soft bag filters in frames


Absolute

Unit size
39F

l/s max
2.8m/s

at

Bag filters (rigid)


Weight
(kg)

l/s max
3.2 m/s

at

Weight
(kg)

Dimensions (mm) and number of filters

610 x 610

610 x 305

220
230
240

940
940
1890

26
26
52

1080
1080
2170

7
7
14

330
340
350
360
370

1920
2890
3360
4330
4810

47
68
81
102
115

2190
3310
3830
4960
5490

12
17
21
26
29

1
2
2
3
3

440
450
460
470
480

3900
4850
5850
6790
7790

84
110
126
152
168

4460
5540
6680
7760
8900

20
27
30
37
40

4
4
6
6
8

550
560
570
580

5780
7260
8210
9680

136
165
191
220

6610
8310
9390
11070

34
41
48
54

4
6
6
8

4
3
5
4

660
670
680

8780
10180
11700

189
228
252

10040
11640
13360

45
56
60

9
9
12

770
780
7100

11600
12470
16970

267
304
380

13250
15530
19390

66
74
93

9
12
15

6
4
5

Absolute19
filters and rigid bag filters in frames

2
2
4
2
2
3
3
4

2
2

16

Back

Carrier 39F

Fans

GENERAL
Fans offered for the 39F Air Handling Units are
from high performance centrifugal fans. The fan
quality, airside and acoustics performances of the
fans are tested in compliance with international
standard either AMCA or DIN. The fans are
able to operate in a temperature range of 20C to
+80C. Fan housing is made of galvanized steel;
phosphated with lap joint and treated with high
quality are anti-corrosion protected.

Construction
1.

Fan casings are constructed of galvanized steel


with a series of punched holes or nutserts
allowing the fixing of accessories such as
frames or support legs thus providing a variety
of discharge positions.

2.

The impeller is galvanized finished for forward


curve blade and epoxy painted for backward
airfoil blade. All impeller are statically and
dynamically balanced to the operating fan
speed as a single unit to specification G25 in
accordance to DIN ISO Standard 1940.

3.

Both forward and backward impellers are with


laminar design and airfoil impellers are with
aerodynamic design.

4.

Fans are securely fixed to mild steel shaft


machined to close tolerance (g6) and coated
with colored wax to protect from corrosion.
Shafts are precision trued and ground. The
drive side is machined to fit standard V-belt
pulleys and the shaft ends are grooved and
keyed.

5.

Types of bearing supplied as standard depend


on fan class and size, and another type
supplied as an option,
Standard Fan - size 160 to 1000 for
forward and backward curve fans (airfoil
fan up to size 710). Radial insert ball
bearings with spherical outer ring
mounted within cast iron housing
supported from the fan casing by tabular
struts.
Option Fan - size 400 to 1000 (reinforced
airfoil fan). Self-aligning double row ball
bearing secured by adapter sleeve,
mounted within cast iron housing.
Option Fan - size 400 to 1000 (optionsuper reinforced). Self-aligning double
row ball bearings within standard
plummer blocks, mounted on robust
pedestal.
All
bearings are pre-lubricated and
maintenance free. Nominal life expectancy is
designed up to 40,000 L10 operating hours
(according to DIN ISO 281 Section 1). Rated
bearing life can reach up to 200,000 L10 hours.

6.

Carrier 39FD/FX offers an optional Inlet Vane


Controller / Inlet Guide Vane (IGV) depends

Fan Laws

For a given distribution system and specific air


weight, the following laws in relation to
volume, pressure and fan power applied
dependent upon fan speed.

The volume (V) changes as the fan speed (n)


changes
n2
V2 = V1
n1

The pressure (p) changes with the square of the


speed (n)
n2 2
P2 = P1

n1

The absorbed power (PW) changes with the


cube of the speed (n)
n2 3
Pw2 = Pw1

n1

As the specific weight of the air changes, the


air quantities remain constant.
The pressure and the absorbed power change
with the specific weight.
n2
n2
and
V2 = V1
V2 = V1
n1
n1

Reference Values

The fan curves refer to a specific weight of 1.2


kg/m3 at a temperature of 20C at atmospheric
pressure of 101.3 kPa (760 mm Hg) and a
relative humidity of 50%.
DESCRIPTION
Types of Fans (Click here for Fan Curves)
39FD,FX Air Handling Units are supplied with
double inlet double width (DIDW) centrifugal
blowers of either,

17

forward curved
backward curved
airfoil curve

on requirements and applications. The IGV is


mounted directly inside each inlet cone with no
external projection. The vane blades are nonaerofoil, galvanized metal pieces which run in
plastic bearings to reduce chatter sound. The
blades can be adjusted from 0 to 90 angle by a
single actuator for double inlet or hand control
if required.

fan panel discharge with a fire retardant flexible


connection. Supply air duct can be directly
connected to the discharge panel flange.
Standard fan and motor casing is supplied with
hinged access door at drive side.
RECOMMENDATIONS

INSTALLATION

The air to be handled in the unit must be clean


and non-corrosive.

Fan, motor and drives are mounted on a fan and


motor base (FMB) that is isolated from the Air
Handling Unit by a set of anti vibration isolators at
the bottom and fan discharge is connected to the

Each Air Handling Unit can have a choice of


several fan types with best efficiency and lowest
sound level should be selected for a specific
installation.

FAN ARRANGEMENT
Fan installation for 39FD/FX comes in different arrangements as per application requirements. Different
configurations are shown below.

UBF

UBR

BHR

THR

DBF

DBR

THF

BHF

Fan arrangement
FAN SHAFT SIZES FORWARD, BACKWARD & (AIRFOIL)

Fan sizes
Diameter, mm

Fan sizes
Diameter, mm

160

180

20(20) 20(20)

400

450

30(28) 35(28)

200

225

20(20) 20(20)

500

560

35(28) 40(38)

250

280

315

355

20(20)

25(24)

25(24)

30(24)

630

710

800

900

40(38)

50(48)

50(48)

710

1000

60(55) 60(55)

IGV TORQUE BACKWARD & (AIRFOIL)

Fan sizes

355

400

450

500

560

630

Torquemax*, Nm

11

15(17)

20(25)

33(37)

35(39)

45(55)

800

900

1000

65(78) 108(128) 131(157) 164(196)

* Maximum torque at the pivot is reached at maximum fan speed and least favorable blade angle, figure include a safety margin

18

FAN OUTLET OPENING

Fan sizes

160

180

200

225

250

280

315

355

L, mm

205

229

256

288

322

361

404

453

Fan sizes

400

450

500

560

630

710

800

900

1000

L, mm

507

569

638

715

801

898

1007

1130

1267

(Click here for Fan Curves)

19

Fan and Motor Assembly on the Fan and Motor Base (FMB)

20

Forward curve impeller

Backward curve impeller

Airfoil fan with standard reinforced fan housing (IGV installed)

21

Back

Carrier 39F

Motors

Features

Standard features on motors used with Carrier 39F


centrifugal fans are as below.
Motors are of Totally Enclosed Fan Cooled
(TEFC) type with finned casing surface.

Construction

Index of Protection IP 55 that protect motor


from dust and water.

Metal frame from aluminum and steel for


excellence heat transfer, strength and
ruggedness.

Single and dual speed motor.

3-phase, DOL, Star-Delta induction motor with


six terminals.

Comply with IEC Standard with UL listing*.

Motors are with standard foot mounted, finned


housing with integral feet of 4 to 6 screw holes.
Shaft is from steel and shaft end fitted with screw
and closed keyway.
Motors are cooled as
surface-cooled machine using the ambient air
circulating round the machine as per IEC 34.6
method IC 41. Terminal box is IP 55 protection.
All standard motor are supplied with wiring
diagram that available in the terminal box. Earth
terminal is located in the terminal box.
Motor Sizing

PTO (thermal overload protection normally


closed), protecting motor when temperature
reaches 170C

Motor selection shall consider the mechanical


losses in transmitting the load from motor shaft to
fan shaft.
Mechanical losses factor, K, are
recommended as follow.

Insulation class F at 50C ambient temperature


and continuos duty.

K = 1.20 for fan with brake kW is 10kW and


below.

Voltage tolerance +/- 10% and frequency


tolerance +/- 5%.

K = 1.15 for fan with brake kW is above 10kW.

Normal operating condition compliance with


IEC 34-1 within ambient -160C and +400C at
below 1000 meter altitudes and at 1050 hPa
(mbar) atmospheric pressure.

50Hz Two Poles Motor - Technical data


RPM
Frame size
Power
kW
63MA
63MB
71MA
71MB
80MA
80MB
90S
90L
100L
112M
132SR
132SH
160MR
160MH
160L
180M
200LR
200LH
225M
250M
280S

0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75

* For High Efficiency Motor Only

2800
2800
2800
2800
2810
2810
2820
2820
2825
2890
2890
2860
2910
2925
2930
2955
2960
2965
2967
2970
2973

Standard motor is with power supply 3ph/


230V/400V/ 50Hz.
Motor data published are
based to these parameters. Other applications are
also available, please contact Carrier office.

FLC
400V

Power
Factor

LRC/FLC

Weight
kg

Shaft
Diameter
mm

0.6
0.7
1.1
1.4
1.8
2.5
3.3
4.7
6
8
11
15
21
28
34
39
52
64
72
98
128

0.71
0.74
0.75
0.78
0.80
0.83
0.85
0.85
0.88
0.86
0.84
0.85
0.87
0.88
0.88
0.90
0.91
0.90
0.89
0.90
0.91

3.3
3.5
3.7
3.9
4.9
5
5
5.1
6.5
6.8
6.5
6
6
7.2
7.6
8
7.6
7.5
7
6.9
7.5

4.5
4.7
5.6
7.0
10.6
11.5
13.6
15.8
17.8
25.5
32.0
36.0
91.0
103.0
120.0
148.0
244.0
270.0
335.0
410.0
355.0

11
11
14
14
19
19
24
24
28
28
38
38
42
42
42
48
55
55
55
60
65

22

50 Hz Four Poles Motor - Technical data


RPM
Frame size
Power
kW

FLC
400V

Power
Factor

LRC/FLC

Weight
kg

Shaft
Diameter
mm

1380
1380
1380
1380
1400
1400
1400
1400
1415
1405
1430
1450
1455
1455
1460
1460
1460
1460
1475
1475
1480
1483
1485

0.5
0.7
0.9
1.2
1.7
2.1
2.8
3.8
5.3
6.8
8.6
11.3
15.2
18
21
29
36
43
58
66
79
94
125

0.63
0.64
0.65
0.66
0.70
0.73
0.75
0.76
0.78
0.80
0.80
0.81
0.83
0.82
0.80
0.83
0.82
0.81
0.81
0.88
0.88
0.90
0.90

2.80
2.90
3.10
3.20
3.40
3.60
3.50
3.80
5.30
5.50
6.20
6.30
6.50
7.00
7.00
7.50
6.00
6.00
7.00
6.30
7.00
7.30
7.30

4.4
4.7
5.4
6.7
9.7
11.3
12.7
15.5
17.0
21.0
27.5
41.0
46.0
52.0
105.0
126.0
136.0
154.0
253.0
320.0
345.0
425.0
565.0

11
11
14
14
19
19
24
24
28
29
28
38
38
38
42
42
48
48
55
60
60
65
75

60 Hz Two Poles Motor - Technical data


Frame size
Power
RPM
kW

FLC
400V

Power
Factor

LRC/FLC

Weight
kg

Shaft
Diameter
mm

0.6
0.7
1.1
1.4
1.8
2.5
3.3
4.7
6
8.4
10
14.3
20
27
32
39
52
64
72
98
128

0.68
0.68
0.70
0.78
0.79
0.80
0.85
0.80
0.87
0.86
0.92
0.90
0.90
0.90
0.92
0.90
0.91
0.90
0.89
0.90
0.91

3.6
3.8
4.2
4.4
5.5
5.6
5.7
5.8
6.8
6.5
6.5
6.6
6
7.2
7.6
9
8
8
7.7
7.5
8

4.5
4.7
5.6
7.0
10.6
11.5
13.6
15.8
17.8
25.5
32.0
36.0
91.0
103.0
120.0
148.0
244.0
270.0
335.0
410.0
355.0

11
11
14
14
19
19
24
24
28
28
38
38
42
42
42
48
55
55
55
60
65

63MA
63MB
71MA
71MB
80MA
80MB
90S
90L
100LR
100LH
112M
132S
132M
132MH
160M
160L
180M
180L
200L
225S
225M
250M
280S

63MA
63MB
71MA
71MB
80MA
80MB
90S
90L
100L
112M
132SR
132SH
160MR
160MH
160L
180M
200LR
200LH
225M
250M
280S

23

0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
9
11
15
18.5
22
30
37
45
55
75

0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75

3240
3420
3450
3450
3450
3440
3420
3450
3450
3495
3490
3465
3515
3525
3525
3555
3560
3565
3565
3565
3568

60 Hz Four Poles Motor - Technical data


Frame size
Power
RPM
kW
63MA
63MB
71MA
71MB
80MA
80MB
90S
90L
100LR
100LH
112M
132S
132M
132MH
160M
160L
180M
180L
200L
225S
225M
250M
280S

0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
9
11
15
18.5
22
30
37
45
55
75

1708
1708
1715
1700
1740
1725
1720
1715
1730
1720
1725
1740
1740
1740
1765
1765
1770
1770
1770
1780
1785
1785
1785

FLC
400V

Power
Factor

LRC/FLC

Weight
kg

Shaft
Diameter
mm

0.5
0.7
0.9
1.3
1.6
2.1
2.7
3.6
5.3
6.7
8.4
11
15
18.5
21
29
36
43
55
66
79
94
125

0.60
0.60
0.64
0.65
0.70
0.73
0.74
0.75
0.75
0.80
0.83
0.83
0.82
0.82
0.85
0.84
0.82
0.82
0.85
0.88
0.88
0.90
0.90

2.8
2.9
3.1
3.2
3.4
3.6
3.5
3.8
5.3
5.5
6.8
7
7
7.5
7.5
7.5
6.5
7
6.5
6.8
7.5
7.5
7.5

4.4
4.7
5.4
6.7
9.7
11.3
12.7
15.5
17.0
21.0
27.5
41.0
46.0
52.0
105.0
126.0
136.0
154.0
253.0
320.0
345.0
425.0
565.0

11
11
14
14
19
19
24
24
28
29
28
38
38
38
42
42
48
48
55
60
60
65
75

Installation
Motor is mounted on an adjustable base so that belt tension can be easily adjusted. Dependent upon motor
power and fan size the motor can be installed:

on the base frame at the back of the fan

on the base frame at the side of the fan

on the fan casing (max motor power 5.5 kW)

24

Terminal block and connections


Standard motors are fitted with six terminals and these terminals are marked complying with IEC 34.8. Terminal
connection and wiring diagrams are supplied in terminal box. Sample wiring connections are as below diagram.

25

Back

Carrier 39F

Drives

Transmission of power from fan motor to fan is provided by means of a set of pulleys and matching v-belts.
The pulleys are taperlocked to the fan and motor shaft. Optional variable pitch pulley fixed to the motor shaft
is available for motor size up to 5.5 kW. Carrier 39F Air Handling Units are supplied with optimized pulleys
and belts sizes and pre-installed by factory. Proper drives sizing and installation will ensure fan to rotate at
required designed speed and at the same time help to optimize fan and motor bearing life.
Pulley with taper bushing

Wedge belts

Common pulleys supplied in 39F Air Handling


Units are:

Common wedge belts supplied in 39F Air Handling


Units are:

1.

Block pulleys

1.

SPA 13W X 8H X Length

2.

Web pulleys

2.

SPB 17W X 11H X Length

3.

Arm pulleys

3.

SPC 22W X 14H X Length

4.

SPD 32W X 19H X Length

5.

SPZ 10W X 6H X Length

Common pulleys for wedge belts (SPA, SPB and SPZ) application.

26

Back
FEATURES

Carrier 39F Air Handling Units offering


several coil applications such as chilled water,
hot water, direct expansion (DX) and steam
coil.
Coils performances are rated accordance to
ARI 410.
Coil designed and manufactured as per Carrier
Standard and according to ANSI and DIN
Standard.
Coils come in a cartridge type construction
with a single pair as standard or dual
connection pairs as option.

Header and connection for DX coil application


is made of copper with sweat connection while
for water coils are with steel header connection
and threaded end (11 TPI) is supplied as
standard.

All water coil headers are equipped with drain


and vent connections.

Tubes are mechanically expanded to collar


fins.

Slide-in and slide-out construction on coil


track provides easy coil removal for service
and maintenance.

Coils are factories tested at 300 psig and


maximum working pressure is 230 psig.

All coils shall have counter flow arrangement.

Coil frames are from galvanized steel and


painted.

DX coil is equipped with distributor head and


tube feeders to the coil circuiting.

Other coil specifications and features please contact


your nearest Carrier office.
SELECTION
Coil calculation and optimization is done by
selection software. Flexible coil standard features
and offerings shall be as follows,
1.

No of rows: 1 up to 10 rows.

2.

Fin spacing: 1.8mm (14 fpi), 2mm (13 fpi),


2.3mm (11 fpi), 2.5mm (10 fpi), 3mm (8 fpi)

3.

Copper tube thickness: 0.35mm for 1/2 tube

4.

Aluminum fin thickness: 0.12mm for 1/2 tube

5.

Coil circuiting: Optimize by selection software

6.

Coil options available such as Cu/Cu coil,


steel coil and Blygold coating.

27

Carrier 39F

Coils

All other types or materials of coil with


configuration other than as described above are
selected and supplied on request. For details and
more information on other specifications and
features, please contact your nearest Carrier office.
RECOMMENDATIONS
For standard or customized coils, recommended
maximum allowable face velocity is:
v = 4.5m/s

heating coil or dry coil

v = 3.15m/s

dehumidifying cooling coils with


droplet eliminator

v = 2.5m/s

dehumidifying cooling
without droplet eliminator

coils

Where necessary, a droplet eliminator is


automatically included by the computer selection
program. Water circuits provided for standard coils
are factory selected to limit the pressure loss to 100
kPa on hot water coils and to 250 kPa on chilled
water coils.
A U-trap of height equal to twice the fan static
pressure must be provided on site by installer. This
will ensure proper flow of condensate water out
from the drain pan.
CONDENSATE DRAIN PAN
Condensate drain pan shall be from galvanized,
minimum spangle G90 material and internally
coated with corrosion resistance and elastic black
asphalt. The internal coating material complies
with NFPA 90 A for flame spread and smoke
generation. The drain pan is mounted onto a slider
track with drain pan with bottom sloped from 0.4
up to 0.7 angle to ensure complete and positive
drainage to meet with ASHRAE 62-89
requirement. Insulated drain pan is available as
standard.
COIL CONSTRUCTION AND
INSTALLATION
Coils are assembled and installed in a two modules
length coil casing. Hot water coil or other dry coil
application required only one module casing
length. For wet coil application, coil is mounted
inside a drain pan. Top coil and bottom drain pan
are supported with Z-Profiles to secure to it
position. Z-Profiles also provides access to slide
the coil and drain pan to ease installation and coil
maintenance works. Coil casings are with external
mounting screw panels access for maintenance
purposes.

Face
velocity

(m/s)

2.65

2.70

2.75

2.80

55
60
Pressure (Pa)
loss
Air pressure loss through droplet eliminator

2.85

2.90

65

2.95

3.00

70

3.05

3.10

75

80

Chilled water coil sitting.


Notes:
1. Coil section length (refer dimensions in table below)
2. Dimensions are based on 25mm thick casing
3. For 50mm thick casing, add 25mm to the following dimensions,
a. W
b. Z
c. 125mm
d. 89.5mm

Standard Coil Sitting and External Fitting Table


Unit Size

No. of Rows

340

1
2
4

350

360

3.15

1-1/4"

141

92

163

712

1-1/4"
2-1/2"

150.5
171

73
82

147
164

728
694

2-1/2"

168.5

137

164

694

2-1/2"

166

192

164

694

1-1/4"

141

92

163

712

1-1/2"

150.5

73

150

722

2-1/2"

171

82

164

694

2-1/2"

168.5

137

164

694

3"

166

192

170

681

1-1/4"

141

92

163

712

2
4

2-1/2"
2-1/2"

146
171

82
82

164
164

694
694

3"

168.5

137

170

681

3"

166

192

170

681

Continue on next page

28

Unit Size
370

440

450

460

470

480

550

560

570

580

29

No. of Rows

1-1/2"

141

92

166

706

2
4

2-1/2"
3"

146
157.5

82
109

164
170

694
681

3"

168.5

137

170

681

3"

166

192

170

681

1-1/4"

141

92

164

1028

1-1/4"

150.5

73

147

1045

2-1/2"

171

82

164

1012

2-1/2"

168.5

137

164

1012

2-1/2"

166

192

164

1012

1
2

1-1/4"
1-1/2"

141
150.5

92
73

164
150

1028
1039

2-1/2"

171

82

164

1012

2-1/2"

168.5

137

164

1011

3"

166

192

170

999

1-1/4"

141

92

164

1028

2-1/2"

146

82

164

1012

2-1/2"

171

82

164

1012

3"

168.5

137

170

999

8
1

3"
1-1/2"

166
141

192
92

170
166

999
1023

2-1/2"

146

82

164

1012

3"

157.5

109

170

999

3"

168.5

137

170

999

3"

166

192

170

999

1-1/4"

141

92

164

1028

2-1/2"

146

82

164

1012

3"

157.5

109

170

999

6
8

3"
3"

168.5
166

137
192

170
170

999
999

1-1/4"

141

92

164

1346

1-1/2"

150.5

73

150

1357
1329

2-1/2"

171

82

164

2-1/2"

168.5

137

164

1329

3"

166

192

170

1316

1-1/4"

141

92

164

1346

2-1/2"

146

82

164

1329

4
6

2-1/2"
3"

171
168.5

82
137

164
170

1329
1316
1316

3"

166

192

170

1-1/2"

141

92

166

1341

2-1/2"

146

82

164

1329

3"

157.5

109

170

1316

3"

168.5

137

170

1316

3"

166

192

170

1316

1-1/4"

141

92

164

1346

2
4

2-1/2"
3"

146
157.5

82
109

164
170

1329
1316

3"

168.5

137

170

1316

3"

166

192

170

1316

Back

Electric Heaters

General

Access Panel

Electric heater shall be of the cartridge type.

Heaters shall be framed with a slide in-out


track so that the complete assembly is
removable.

Carrier 39F

Totally removable panel shall be assembled at


both casing wall and bolted externally for airtightness, easy remove and reassemble panel to
facilitate access for servicing and maintenance.

Standard Electric Heater Open Wire Type

Standard electric heater shall be from Open


Wire Type.

SELECTION
Example:

Heating wire shall be of composition 80% Ni


and 20% Cr.

Unit 39FD 570 with 8300 l/s.

Temperature increase of 12C is required.

Heater assembly, the basic components shall


be include airflow switch, power & control
terminal board, grounding lug and primary &
secondary over load temperature sensor.

Heating load
Q = 1.21 x t x V
Q = 1.21 x 12 x 8300 = 120,500 W

Components are assembled inside terminal box


integrated with heating elements frame
assembly.

Frames shall be from a heavy gauge (G16)


galvanized steel frame.

Remote Control Panel (option)

Remote Control Panel shall include basic


components such as a de-energizing magnetic
control contactor per stage or each 48 AMP
circuit within a stage, a magnetic back-up
contactor for each 48AMP circuit, power &
control terminal board, grounding lug and high
& low voltage terminal boards.
Control Panels box shall be made from
painted galvanized steel and weatherproof
construction.

From Standard Heater Table, 105 kW would


result in 10.5C temperature increase or 126
kW would result in 12.5C temperature
increase.
With either selection a four-step control is feasible.
Non-standard heater size and non-standard heater
steps are also available.
Please consult Carrier
office for non-standard heater requirements.

FINNED CLOSED WITH OTHER SUPPLY


VOLTAGES
If standard heaters are used with non-standard
power supplies, there will be an incidence on the
effective capacity of the heaters in virtue of the law
List below the variation of power
P = U2/R.
supplies and incidence.

Closed Finned Heater Type (option)

Supply Voltage at
3 phase.

Incidence

Heating element is made of composition 80%


Ni and 20% Cr.

220

Under power 10 %

230

Power = Nominal

Assembly of the heating element is secured


inside the stainless steel spherical sheathed fins
copper tube.

240

Over power 9 %

380

Under power 10 %

Heating component is according to AISI 321


and AISI 430.

415

Over power 7.5 %

440

Under power 10 %

Heating elements are wired in star or delta


according to the power supply and pre wired to
the terminal block in the wiring box.

460

Power = Nominal

480

Under power 10 %

Safety thermostat (rating at 16 (2) A / 380 V )


with a 98 C ( +0/-16 C ) cut out is supplied
and it is manually reset. Heating elements are
mounted to a heavy gauge (G16) galvanized
steel frame.

Heater elements are wired and connected


depending to the supply voltage and number of
supply phases. Addition to this each supply
voltage will require specific minimum element in
respective group. For non-standard heater
application please consult Carrier office.

30

Closed Type Heater

31

Standard Heater for Carrier 39F AHU 400V/ 3 phase.


Model

220

230

240

330

340

350

360
370
380

440

Heating
power
(kW)
6
6
12
18
24
9
18
27
36
54
63
12
24
36
48
60
9
18
27
36
45
54
72
15
30
45
60
75
90
105
120
30
45
60
75
90
135
21
42
63
84
105
147
168
15
30
45
60
75
90
105
120
135
165

steps

3-3
6
6-6
6-6-6
6 - 6 - 12
9
9-9
9-9-9
9 - 9 - 18
9 - 9 - 18 - 18
9 - 18 - 18 - 18
12
12 - 12
12 - 12 - 12
12 - 12 - 24
3 X 12 - 24
9
9-9
9-9-9
9 - 9 - 18
9 - 9 - 9 - 18
9 - 9 - 18 - 18
4 X 18
15
15 - 15
15 - 15 - 15
15 - 15 - 30
3 X 15 - 30
15 - 15 - 30 - 30
15 - 15 - 30 - 45
15 - 30 - 30 - 45
15 - 15
15 - 15 - 15
15 - 15 - 30
3 X 15 - 30
15 - 15 - 30 - 30
3 X 15 - 30 - 30
21
21 - 21
21 - 21 - 21
21 - 21 - 42
21 - 21 - 21 - 42
21 - 21 - 42 - 63
21 - 21 - 42 - 84
15
15 - 15
15 - 15 - 15
15 - 15 - 30
3 X 15 - 30
15 - 15 - 30 - 30
15 - 15 - 30 - 45
15 - 15 - 30 - 60
15 - 15 - 15 - 30 - 60
15 - 30 - 60 - 60

Model

450

460
470
480

550

560
570
580

660
670
680

770
780

7100

Heating
power
(kW)
30
45
60
75
90
105
150
180
21
63
84
105
126
147
189
60
75
90
105
120
135
42
63
84
105
126
147
168
189
63
105
126
147
168
189
210
231
252
147
168
189
210
231
252
273
294
189
210
231
252
273
294

steps

15 - 15
15 - 15 - 15
15 - 15 - 30
3 X 15 - 30
15 - 15 - 30 - 30
15 - 15 - 30 - 45
15 - 15 - 30 - 30 - 60
4 X 45
21
21 - 21 - 21
21 - 21 - 42
21 - 21 - 21 - 42
21 - 21 - 42 - 42
21 - 21 -42 - 63
3 X 21 - 42 - 84
15 - 15 - 30
3 X 15 - 30
15 - 15 - 30 - 30
15 - 15 - 30 - 45
15 - 15 - 30 - 60
15 - 15 - 15 - 30 - 60
21 - 21
21 - 21 - 21
21 - 21 - 42
21 - 21 - 21 - 42
21 - 21 - 42 - 42
21 - 21 - 42 - 63
21 - 21 - 42 - 84
3 X 21 - 42 - 84
21 - 21 - 21
21 - 21 - 21 - 42
21 - 21 - 42 - 42
21 - 21 - 42 - 63
21 - 21 - 42 - 84
3 X 21 - 42 - 84
21 - 21 - 42 - 42 - 84
21 - 21 - 42 - 63 - 84
21 - 21 - 42 - 63 - 105
21 - 21 - 42 - 63
21 - 21 - 42 - 84
3 X 21 - 42 - 84
21 - 21 - 42 - 42 - 84
21 - 21 - 42 - 63 - 84
21 - 21 - 42 - 63 - 105
21 - 21 - 42 - 84 - 105
21 - 21 - 42 - 84 - 126
3 X 21 - 42 - 84
21 - 21 - 42 - 42 - 84
21 - 21 - 42 - 63 - 84
21 - 21 - 42 - 63 - 105
21 - 21 - 42 - 84 - 105
21 - 21 - 42 - 84 - 126

Standard Heater - heating powers and number of steps

32

Back

Heat Recovering System

GENERAL
The recovery of thermal energy from exhaust air
will increase the overall efficiency of an air
conditioning system.
Recovered heat
E% = --------------------- x 100
Recoverable heat
The heat recover heat is dependent on the
prevailing external conditions.
The amount of latent heat recovered is normally
small compared with the sensible heat recovery and
is therefore not taken into account in above
equation. However, in mid-winter it is possible that
condensation in the exhaust air circuit might occur.
The three types of heat recovery units are offered:
1.

Plate recouperators: single unit, standard and


high efficiency

2.

Run around coil: flexible, simple installation


and minimal space requirement

3.

Heat wheel

PLATE RECOUPERATORS
Description
Operation
The design provides for two airflows to pass
crossways between the heat exchanger plates. The
colder air when passing through the unit absorbs
heat contained in the outgoing airflow. The two
airflow is completely isolated by the sealed
construction of the heat exchanger, which is
designed for sensible heat transfer only. Neither
dust nor odors are transmitted.
Construction
A group of aluminum plates are located diagonally
in the recouperator casing which is formed of
galvanized sheets riveted together. Silicone seal
assures complete air tightness. The lower part of
the casing forms a watertight pan to recover
possible condensate.
Models
Three are offered of which two are of different
efficiency due to different plate dimensions:
ES: Standard Efficiency
EH: High Efficiency
EP: With an air bypass (BP)
Recommendations
Limitations
The heat recovery units with aluminum plates can
be used for:
-

33

temperatures up to 150C

Carrier 39F

a maximum pressure differential of up to 1000


Pa
a non corrosive atmosphere

Condensation
Depending on the operating conditions, the exhaust
air might be cooled below its dewpoint with
resultant condensation. A condensate discharge
must therefore be provided on the exhaust airside.
Freeze-up
Direct intake of sub-zero air into the unit might
cause freezing of the exchanger. The temperature at
which freezing might occur depends on the
temperature and the relative humidity of the
exhaust air as well as on the proportion of outside
air to exhaust air.
Freezing can be prevented by increasing the outside
air temperature either with preheat or by recycling
a part of the exhaust air or by bypassing a part of
the outside air.
Installation
The casing of the independent vertical heat
recovery unit is connected to other components of
the air handling unit. As with all air to air heat
exchangers, plate recouperators give their best
efficiency when they are situated at the suction side
of the fan.
The supply and exhaust fans should be wired for
simultaneous operation.
The condensate discharge tubing (PVC 32 mm) is
connected at the bottom of the pan and passed
through a lateral opening in the unit casing for
connection to a U-trap and discharge.
Available for unit size of 4-module height and
below with airflow not exceeding 15 000 m3/hr.
RUN AROUND COILS
Two coils, the one located in the exhaust air
stream, the other in the supply air stream is
interconnected with a pump in a closed circuit.
Heat passes from the hot exhaust air to the cold
water in the tubes of the heat pick-up coil. The
pump then passes this warm water to the heat
rejection coil where the heat passes into the cold
supply air thus cooling the water and warming the
air. Cold water returns to the heat pick-up coil and
the cycle is repeated.
Selection of the coils is made from 39F computer
selection software and based on the following data:
- air handling unit size
- supply air and exhaust air quantities,
temperatures and humidities
- glycol concentration (if used)

Advantages
- two completely separate airflow
- flexible duct arrangement
- simple installation
- great reliability
- low initial cost
- simple maintenance

divided into two half moon sections. Stale air from


the conditioned space is exhausted through one half
while outdoor air is drawn through the other half in
the counter flow pattern. At the same time wheel
is rotated slowly.
Sensible heat is transferred as the metallic substrate
picks up and stores heat from the warmer air stream
and gives it up to the cooler section.

HEAT WHEEL
ASHRAE Standard 62-1989 that recommended
level of outside air brought into buildings has been
increased. This imposes much higher latent and
sensible loads on cooling and heating equipment.
Heat wheel is designed to recovers total energy
(sensible and latent) to meets the requirements of
indoor Air Quality (IAQ), humidity control and to
save energy.

Latent heat is transferred as the synthesized


metallic substrate condenses moisture from the air
stream that has the higher humidity ratio through
adsorption (with a simultaneous release of heat)
and releases of moisture through evaporation (and
heat pick-up) into the air stream that has a lower
humidity ratio.
Selection detail is made from 39F computer
selection software. Further inquiries please contact
Carrier office.

The wheel made of aluminum heat storing matrix


and with galvanized casing. The wheel is
positioned in 39F Air Handling Unit so that it is

COIL FACE VELOCITY

Unit size
Volume
(l/s)

39F

230

240

330

340

350

360

370

440

450

460

dP
(Pa)

56

80

61

60

EP

61

ES

55
59

70

EP

60

ES

55
59

70

EP

60

ES

57
60

70

EP

63

ES

60
65

50

EP

65

ES

60
65

50

EP

65

ES

60
65

50

EP

65

ES

60
65

50

EP

65

ES

63
65

50

EP

66

ES

61
63

70

EP

66

ES

61
63

70

66

65

ES
220

1.5 m/s
Effic.
(%)

EH

EH

EH

EH

EH

EH

EH

EH

EH

EH

EH

290

500

720

800

1200

1550

1900

2300

1625

2200

2650

EP
ES: standard efficiency
EH: high efficiency
EP: bypass model

Volume
(l/s)

2.6 m/s
Effic.
(%)

dP
(Pa)

51

150

54

110

60

54

90

50
53

130

70

54

90

50
53

135

70

55

90

52
55

130

70

58

70

55
60

100

50

60

70

55
59

110

50

60

70

55
59

110

50

60

70

55
59

110

55

60

70

57
60

110

60

63

90

57
59

130

70

62

90

57
59

130

62

120

500

900

1280

1450

2050

2700

3300

3950

2800

3800

4600

Volume
(l/s)

2.9 m/s
Effic.
(%)

dP
(Pa)

50

170

54

130

120

53

170

49
53

150

130

53

180

49
52

150

140

54

190

51
55

150

130

57

130

55
59

110

105

60

140

54
59

120

110

59

150

54
59

125

110

59

150

54
59

120

110

59

150

57
59

130

115

62

150

56
59

145

130

62

150

56
58

145

62

140

550

1000

1400

1600

2250

3050

3700

4400

3200

4200

5150

Volume
(l/s)

3.15 m/s
Effic.
(%)

dP
(Pa)

49

200

53

140

140

53

200

48
52

170

150

52

210

49
51

170

155

53

220

51
54

160

150

57

150

54
58

130

110

59

165

53
58

130

125

59

165

53
58

130

125

59

165

53
58

140

120

59

170

56
58

145

130

61

185

56
58

160

140

61

185

56
58

160

61

150

600

1100

1500

1750

2000

3300

4000

4800

3400

4600

5500

Volume
(l/s)

4.5 m/s
Effic.
(%)

dP
(Pa)

50

230

160

51

250

250

49

280

170

50

290

240

50

290

175

51

310

250

52

270

170

56

285

170

52

290

56

200

130

57

220

190

52

330

56

220

135

57

220

190

52

330

56

220

130

57

220

190

56

230

135

57

230

190

57

250

150

60

250

210

57

260

150

60

260

210

57

270

60

250

850

1650

2150

2500

3550

4760

5750

6850

4900

6550

7950

34

Correction factors for plate recouperators

35

Freezing limit for plate recouperators

Back

Humidifiers

GENERAL
Air humidification can be obtained by:
- adiabatic process (constant heat)
- isothermal process (constant temperature)
Adiabatic Humidification (with water spray)
At constant enthalpy part of the sensible heat
content of the air is converted into latent heat of
evaporation. The efficiency of that process is
defined by:
Xl Xe
E% = ------------ x 100
Xs Xe

Xe = quantity of water vapor in the air entering the


humidifier (g/kg)
Xs = quantity of water vapor at saturation in the air
entering the humidifier (g/kg)
Isothermal Humidification (steam injection)
At constant temperature the amount of water in the
air is increased and with it the enthalpy of the air.
DESCRIPTION

The adiabatic or spray humidifier used with


the 39F units consists of:

Painted and bolted galvanized sheet metal


panels (welding eliminated) and internally
coated for water tightness.

Water sump with level control and furnished


with the following openings:
- drain
- overflow
- water supply with float valve
- suction connection with screen

One or two rows of galvanized stand pipes


with atomizing plastic spay nozzles providing
a fine water mist for maximum efficiency
(spray
nozzles
easily
removed
for
maintenance)
Vertical galvanized steel eliminator plates
specially formed, and installed upstream and
downstream to provide droplet elimination
Porthole for assembly inspection
furnished on sizes 220, 230 and 240)

2.

Long humidifier (high efficiency)


Two rows of spray nozzles directed against the
airflow. Maximum efficiency: 84% at 2.2 m/s
coil face velocity. Overall length: 6 modules =
1940 mm.

The following condition must be met:


electrical interlock between pump and fan
motor
supply of filtered and treated water (pH = 7)
continuous bleed-off to prevent salt
accumulation in sump
a drain U-trap twice the height of the fan static
pressure
adequate protection against freezing
INSTALLATION
The humidifier forms an independent section to be
connected to the other unit sections by using the
accessories fixings supplied with the unit for this
purpose.
Since the sump is located at the bottom of the
humidifier and below the airflow, support legs for
the other sections of the air handling units have to
be provided to maintain uniform level. These
support legs are factory supplied as optional
accessories.
The recirculating pump must be field connected
and located at the same height as the sump. A free
space of 600 mm for this installation is required.
SELECTION
Example:
Unit 39FD 570, entering air 7500 l/s at 2.7 m/s
(standard coil face velocity), entering air at 25C
and Xe = 3 g/kg water vapor.
-

Required; leaving air Xl = 7.5 g/kg

From the psychrometric chart read ; saturation


of entering air Xs = 8.5 g/kg

(not

Inspection maintenance door

Recirculating centrifugal pump, field supply &


field mounted

Note: units are supplied single skin, un-lagged.

Two models of humidifiers are available:


1. Short humidifier (medium efficiency)
With one row of spray nozzles directed against
the airflow. Maximum efficiency: 79% at 2.2
m/s coil face velocity. Overall length: 4
modules = 1310 mm.

RECOMMENDATIONS

Xl = quantity of water vapor in ht e air leaving the


humidifier (g/kg)

Carrier 39F

7.5 3
Efficiency E% = ---------- x 100 = 82%
8.5 3

From humidifier efficiency curve at 2.7 m/s


For one spray tree: E = 74%
For two spray trees: E = 80%

36

Two spray trees humidifier satisfies the


requirements

The actual leaving air conditioners are


Xl = 0.80 x (8.5 3.0) +3 = 7.4 g/kg
Leaving air temperature: 14.5C with 75% r.h.

Humidifier Face Velocity (m/s)


1.5

1.75

2.25

Humidifier Face Velocity (m/s)


2.5

1.5

Efficiency (%)

90

Pressure Loss (Pa)

100

2 spray trees

80

1 spray tree

70
60
50
2

2.2

2.4

2.6

2.8

3.2

150
140
130
120
110
100
90
80
70
60
50
40

2.25

2.5

2 spray trees

1 spray tree
2

3.4

1.75

Coil Face Velocity (m/s)

2.2

2.4

2.6

2.8

3.2

3.4

Coil Face Velocity (m/s)

Efficiencies and airside pressure losses through humidifiers

Weight of humidifiers and water charges


Unit size
39F

37

1 spray tree

2 spray tree

Weight (kg)

Water charge (kg)

Weight (kg)

Water charge (kg)

220
230
240

170
205
220

140
215
290

240
295
310

210
320
430

330
340
350
360
370

230
260
315
365
410

215
290
370
430
520

330
375
460
535
605

320
430
550
720
770

440
450
460
470
480

335
375
430
490
545

290
370
430
520
600

485
550
635
720
810

430
550
720
770
885

550
560
570
580

425
490
560
620

370
430
520
600

640
730
810
930

550
720
770
885

660
670
680

560
635
690

430
520
600

835
950
1065

720
770
885

770
780
7100

705
790
955

520
600
750

1065
1200
1450

770
885
1110

Dimensional drawing

Water level

Physical data
1 tree counter flow
Unit size
39F

A (mm)

B (mm)

220
230
240

995

680
995
1310

650
1150
1650

0.24
0.42
0.58

0.55
0.55
0.55

1"
1"
1"

1"
1"
1"

0.32
0.72
1.01

0.55
0.55
0.75

1"
1"
1" 1/4

1"
1"
1" 1/4

1310

995
1310
1625
1940
2255

1900
2650
3550
4350
5150

0.68
0.94
1.32
1.51
1.83

0.55
0.75
0.75
0.75
1.5

1"
1" 1/4
1" 1/4
1" 1/4
2"

1"
1" 1/4
1" 1/4
1" 1/4
2"

1.18
1.65
2.40
2.67
3.19

0.75
0.75
1.5
1.5
1.5

1" 1/4
1" 1/4
2"
2"
2"

1" 1/4
1" 1/4
2"
2"
2"

3700
4950
6000
7150
8300

1.31

1625

1310
1625
1940
2255
2570

1.13
2.54
2.94

0.75
0.75
1.5
1.5
1.5

1" 1/4
1" 1/4
2"
2"
2"

1" 1/4
1" 1/4
2"
2"
2"

2.28
3.06
3.72
4.44
5.15

1.5
1.5
4
4
4

2"
2"
2"
2"
2"

2"
2"
2"
2"
2"

1625
1940
2255
2570

6600
8000
9550
11083

2.33
2.83
3.39
3.92

1.5
1.5
4
4

2"
2"
2"
2"

2"
2"
2"
2"

4.07
4.96
5.22
6.88

4
4
4
3

2"
2"
2"
2" 1/2

2"
2"
2"
2"

330
340
350
360
370
440
450
460
470
480
550
560
570
580

1940

Recirculated
water volume
l/s

Pump
kW

Suction
dia

2 trees counter flow

Max air
volume
l/s

Supply
dia

Recirculated
water volume
l/s

Pump
kW

Suction
dia

Supply
dia

660
670
680

2255

1940
2255
2570

9650
11550
13400

3.43
4.08
4.72

4
4
4

2"
2"
2"

2"
2"
2"

6.00
7.14
8.31

4
3
3

2"
2" 1/2
2" 1/2

2"
2"
2"

770
780
7100

2570

2255
2570
3200

13550
15700
20100

4.79
5.50
4.95

4
4
3

2"
2"
2" 1/2

2"
2"
2"

8.38
9.72
12.60

3
3
3

2" 1/2
2" 1/2
2" 1/2

2"
2"
2"

38

Back
GENERAL

Where a significant reduction to fan noise is


required attenuators can be provided.

INSTALLATION

DESCRIPTION
Sound absorption is achieved by installing mineral
wool splitters (non-combustible class MO fire
code), fixed in galvanized steel frames and
mounted parallel to the airflow.
Various splitter lengths are available to provide a
range of attenuator performances.
The sides exposed to the air stream are covered
with a glass fiber scrim to avoid erosion to the
mineral wool by the air stream.
The standard thickness of the splitters is 200 mm.
RECOMMENDATIONS
Following limits are to be observed
-

Carrier 39F

Sound Attenuators

Maximum air velocity between panels: 20 m/s

Maximum temperature: 100C

The splitters are installed within the 39F unit and


form an integral part of it. They can be located in
the discharge or inlet sides of supply or return fan.
DIMENSIONS
The height is determined by the height of the air
handling unit.
The amount of sound absorption depends on the
splitter length.
The length of the splitter casing takes into the
account the space required for uniform airflow after
leaving the attenuator splitters.
MANUAL PRESELECTION
Deduct silencer sound attenuation figures (table
below) from fan sound power spectrum to arrive at
sound level leaving the attenuator.
Exact calculations are made by computer program.

63Hz

125Hz

250Hz

500Hz

1kHz

2kHz

4kHz

8kHz

Forward curve

10

12

13

15

19

23

Backward curve

11

15

19

23

Octave band

Deduct values (dB) from overall sound level figures obtained from fan curves to arrive at fan sound power
spectrum

Splitter length

63Hz

125Hz

250Hz

500Hz

1kHz

2kHz

4kHz

8kHz

3 modules

10

16

24

30

33

26

18

4 modules

11

22

30

37

40

34

23

5 modules

13

28

38

42

45

40

27

6 modules

16

32

44

48

50

45

30

Deduct values (dB) from fan sound power spectrum to arrive at sound level leaving attenuator

39

Back

Application Guide

Carrier 39F

Parts of the considerations while selecting an AHU are the space area available for installation and the unit
application.
This
limitation
will
determine
the
unit
size
and
unit
configuration.
SERVICE CLEARANCE

CONDENSATE DRAIN

Allow adequate clearance for servicing and


maintenance access (filter and coil removal, motor
and fan shaft servicing). Avoid any piping, conduit
or ductwork that might obstruct the service door
access and space. For sufficient clearance space
guideline please refer to the Installation Operating
Manual.

Install a trapped condensate drain


appropriate location to avoid back
condensate water and to ensure proper
Guide line of U-trap installation as
operating

line at
flow of
drainage.
per the
manual.

UNIT CONFIGURATIONS

Horizontal Draw Through Unit

Vertical Draw Through I-unit

Vertical Draw Through L-unit

40

Multizone Unit

Unit with Return and Supply Fan

Unit with Air Washer and Plate Recouperator

41

(Front view)

Unit with Heat Wheel

Unit with Recovery Coil

42

Back
A. CASING
1.

Galvanized and painted steel roofing


The roof sheets are cross-braked for added
stiffness and to facilitate water runoff and are
overhung on all sides.
Slip joints assure water tightness between
adjacent sheet.

2.

3.

Sub base 100 mm high, galvanized and


painted
39F unit sections are self supporting and do
not rely on a base for additional stiffening.
However, bases are sometimes required to
provide sufficient height for a U-trap below
the cooling coil drain pan or to raise units from
roof slab in external locations.

2.

1.

Support feet
In galvanized painted sheet metal, 315 mm
high, to compensate for the added height due
to the humidifier sump. These feet are to be
placed under the edges of all other sections.

2.

Inspection light
In cast iron and glass, to IP 55

D. FANS
1.

Variable volume control


For variable volume systems: Inlet guide vanes
(for backward curved fans) or variable speed
motors (eddy current coupling, or frequency
inverter control) are available.

2.

Fan drain
This connection is located on the bottom of the
fan volute and serves to drain any
condensation which might form on the inside
of the fan.

3.

Inspection door
Available on all fan sizes, serves as access to
the fans for interior inspection and cleaning of
the volute and the fan impeller.

Air discharge hood


In galvanized, painted sheet metal, designed to
prevent ingress of water.
A fine wiremesh bird screen is provided.

5.

Flexible connections
For specifications calling for total unit to be
vibration isolated.
In fabric non-flammable class M1 with
connecting flanges in galvanized painted steel.
Can be installed on suction and / or discharge
side.

6.

Bulkhead light
75 watts light bulb under glass cover, with
switch and a connection box all to IP 55.
Wiring upon request.

7.

Inspection window
In strong plexiglass, 180 mm dia.
Together with bulkhead light allows quick
inspection of the inside of the casing while unit
is in operation.

B. FILTERS
1.

Pressure control
U-tube pressure gauge 0 to 500 Pa.
Inclined tube pressure gauge 0 to 500 Pa.
Furnished for field installation. The pressure
connection tappings are factory installed.
Differential air pressure switch adjustable from
10 to 1250 Pa.

43

Air diffusion screen


For filters installed downstream from the fan
discharge and to assure a uniform air
distribution.

C. HUMIDIFIERS

Air inlet hood


In galvanized, painted sheet metal sized and
sloped to avoid water entrapment.
A fine wiremesh bird screen is provided.

4.

Carrier 39F

Options

E. MOTOR
1.

Vee belt guard


Made of galvanized expended steel.

2.

Variable pitch pulleys


Can be installed on the motor shaft and / or the
fan shaft to allow fan speed variation between
+ or 20% for one variable pulley and + or
50% for a pair of variable pitch pulleys. This
system is limited to maximum two grooves at
the pulley and the motor power of maximum
5.5 kW. Adjustment can only be made
manually and when the fan is stationary.

3.

Standby motor
Situated opposite to the run motor and
furnished with a set of belts and pulley (belts
not fitted).

F. EXPLOSION PROOF CONSTRUCTION


Applied where the possibility of flammable
gasses exist. Flameproof motors and switches
and fan non-spark rings can be provided. The

Note:

request for such modifications must indicate


the protection classification specified.

High front velocity may result in unacceptable


front filter velocity (to be checked)

G. New Flexair Options


1.

2.

Rail mounted soft bag filter


Takes only two modules long including easy
removal panel.

3.

Frequency inverters and PTC sensors


For variable volume systems to match exactly
fan quadratic power input curves.

Notes:
a. for 95% opacimetric efficiency (EU 9)
available from factory with two module
length filter sections.
b. available from factory for the following
sizes, 39FD/FX 220,230 and 240

4.

Coil protection against corrosion


To increase resistance to corrosion depending
on application data, following protections are
available:

High velocity droplet eliminators


Made of M1 propylen (Germany : B2)

Cu/Al + Polyal.

Cu/Cu coil.

Pre-coaed fin.

Allow coil face velocity up to 4m/s

44

Back

Guide Specifications

GENERAL
39FD/FX Series Central Station Air Handling Units are
designed based on Carrier Moduflex Series. The
design of the Central Station Air Handling Units is
based on the use of standardized modular panels and
penta-post construction of perimeter frames. The
standard and reference for design and performances for
39FD/DX Central Station AHUs components shall
conform mostly to American standard and
EUROVENT Standard
Standard units configuration shall be horizontal or
vertical draw-through or blow-through types.

Part-1 Central Station AHUs Guide


Specification General
1.01
39FD/FX Series:
1.01.01 39FD; 25-mm panel thickness
1.01.02 39FX; 50-mm panel thickness
1.02
Standard Size Range:
1.02.01 23 model sizes from 220 7100
1.03
Standard AHU Face Area Range:
1.03.01 From 0.4 m2 up-to 6.95 m2
1.04
Standard Airflow Range, CMH:
1.04.01 Cooling: 1,300 62,550
(Up-to 78,810 with eliminator)
1.04.02 Heating: up to 90,855
1.04.03 Cool, Heat & Vent: Up-to 160,000 (special)
1.05
1.05.01
1.05.02
1.05.03
1.05.04
1.05.05

1.07
Standard Air Movement
1.07.01 DIDW fans forward, backward and aerofoil
Plenum (option)
1.07.02 VAV with VFD or IGV
1.07.03 TEFC, IP55 Fan Motor
1.07.04 Wedge Belts SPA, SPB, SPC, SPD, SPZ
1.07.05 Fixed Pulleys Block Web, Arm, VPP
1.07.06 Rubber & Spring Vibration Isolators
1.07.07 Single Skin Blades Damper

1.08
Quality Assurance
1.08.01 Manufactured in facility registered to ISO
9001:2000 / EN ISO 9001:2000 / ANSI/ASQC
Q9001:2000
1.08.02 9F Flex Air Selection Program
1.08.03 AHU designed accordance to EN 1886 and
ARI 430
1.08.04 Insulation & seal meets NFPA 90A
requirements for flame spread and smoke
generation.
1.08.05 Casing to withstand 500-hours salt spray
exposure per ASTM B117
1.08.06 Air filters performance according to ASHRAE
Standard 52-76 or EUROVENT Standard 5/6
1.08.07 Coil performance rating according to ARI 410
1.08.08 Electric Heater manufactured accordance to
NEC and UL Space Heating Standard No 1996
1.08.09 Fan performance accordance to DIN or
AMCA
1.07.10 Fan motor manufactured to conform to IEC
Standard

Standard Heating and Cooling


Cooling & Dehumanization CWC & DXC *
Sensible Heating HWC, EHTR & STC
Pre-cooled & Re-heat HPE (option), RAC
Heat Recovering HPE (option), HPLE, HWE
Humidified SH (option), SWH

1.06
Standard Air Management
1.06.01 IAQ DSC, STL, Std. Air Filter &
Humidifiers
1.06.02 IAQ Odor, chemical ACF (option)
1.06.03 Pre-filtering up to HEPA-filtering
(EU 2 up to EU 12)
1.06.04 2 & 3-Way Air Mixing Plenum
1.06.05 Multi-zoning (option)
1.06.06 Coil by-pass (option)
1.06.07 Sound Attenuator

* Nomenclature Page 50
1.06.03 TEFC, IP55 Fan Motor

45

Carrier 39F

Part-2
2.01

Casing Construction (Standard)


General

Part-2
2.04

Casing Construction (Standard)


Weather Protection

2.01.01 39FD/FX Central Station Air Handling Units


casing construction should be fabricated from highest
grade galvanized steel.

2.04.03 Casing 50-mm (39FX) shall be able to hold


up-to 70% RH @ 32oC (90oF) ambient weather without
condensation at outer skin.

2.01.02 Construction of panel and frames are folded to


form sturdy Side/Top/Bottom panels and a rigid
structure Penta-post frames.

2.05

Indoor Air Quality

2.01.03 The construction should serve thermal


protection, reducing machine noise, absorbing vibration
and avoiding air leakage.

2.05.01 The unit casing shall have double skin


construction to avoid material insulation expose to
conditioned area and to allow access in the AirHandling unit without damaging the insulation.

2.01.04 Modular sizes of panel and penta-post should


be easily assemble and reassemble.

2.06

2.01.05 The construction and material used should be


environment friendly, clean and safe.
2.02

Penta-post Frame

2.02.01 Heavy-duty formed penta-post frame is


designed for rigidity and is made from highest-grade
hot-dip galvanized steel with minimal spangle finish
grade G90 galvanized coating according to ASTM
A525 compliance to UL 465.
2.02.02 Frames shall be painted for extra protection.
2.03

Double Skin Panel

Penta-post And Panel Seal

2.06.01 Panels and frames shall be assembled with a


closed cell self-adhesive neoprene foam gasket layer
installed in between them to prevent air leakage, reduce
vibration noise, minimized thermal losses.
2.06.02 A closed cell self-adhesive neoprene foam
gasket layer shall avoid external water to penetrate
inside the unit and shall block infiltration of heat and
external contamination into the conditioned space area
inside the unit.
2.06.03 A closed cell self-adhesive neoprene foam
gasket is with K-value of 0.04 W/M.C, flammability
Class HB according to UL 94, working temperature
reaching 120 oC and maximum water absorption 5%.

2.03.01 Modular panel is design to be rigid and sturdy.


2.03.02 Double skin construction and sandwiched with
superior polyurethane insulation between the panel
interior and exterior skins to furnish compressive
strength up to 30 psi.
2.03.03 Polyurethane insulation is non-combustible, Kvalue 0.019 W/M.C sturdy that shall provide superior
thermal resistance across the panel.
2.03.04 Panel exterior skin shall be made from highestgrade hot-dip galvanized steel, a minimal spangle grade
G90 coating.
2.03.05 Panel interior skin shall be made from primed
or pre-painted galvanized steel for extra protection.
2.04

Weather Protection

2.04.01 External surface shall be coated with highly


durable heat hardened polyester based powder paint
with 50 microns film thickness.
2.04.02 The paint shall conform to ASTM D-2201 and
ASTM D-2092 in different condition for gloss,
adhesion, impact resistance, oven backed resistance and
can withstand up to 1000 hours salt spray resistance
test, exceeding 500 hours according to ASTM B117.

2.07

Casing Assembly - Air Leakage

2.07.01 The construction of panels to the penta-post


frames shall provide minimum air leakage Class A
according to EUROVENT Standard EN 1886.
2.08

Access Panels

2.08.01 The fixing of panel to the penta-post frames


with bolts shall provide additional access to ease
mobility for major service work on large and heavy
component such as coil, fan and motor.
2.08.02 Access door panel equipped with hard nylon
hinges and metal lock, accessible internally and
externally for safety release. This access door type
shall be at the fan section and the mixing box section.
2.08.03 Quick release and totally removable access
door shall be at filter section with side rail mounting.
2.09

Roof

2.09.01 Roof shall be install when AHU is installed in


open outdoor space to flash water from top panels
(optional).

46

Part-2
2.10

Casing Construction (Standard)


Roof Curb

2.10.01 Roof curb shall be from heavy gauge (3-mm)


galvanized steel (option); folded to form strong and
rigid structure.
2.10.02 Standard roof curb height shall be 100-mm.

Part-3

Air Mixing Section

3.01
General
3.01.01 Dampers construction should be fabricated
from galvanized steel for sturdy and rigid structure.
The damper construction should operate with minimal
torque and minimal pressure losses.
3.02

Blades

3.02.01 Standard dampers blades shall be with a


single skin type, made from galvanized steel and can
operate in parallel or oppose blades position at minimal
pressure losses.
3.02.02 Blades are equipped with rubber seal and fitted
close gap within blades allowing a minimum air leak
Class IV according to UL555S.
3.02.03 Side seal damper blades with air leakage Class
II is available as an option.
3.02.04 Shafts are with 12 mm diameter; seated on
non-corrosive bronzed or nylon bushing for less
resistance, free maintenance and lowest torque.
3.02.05 Extended shaft length is provided for provision
to electrical motor actuator to regulate dampers blades
opening and closing.
3.02.06 Frames are made from galvanized steel,
reinforced at very 1200-mm and flanged at both ends to
facilitate external ductwork or sand trap louvers
connection.
3.02.07 Metal linkage made from steel pushrods is
installed for dampers assembled in top-rear position to
allow damper to interconnected at open and closed
position.

Part-4
4.01

Air Filter Section


General

4.01.01 Air filter section should accommodate


standard filters media to deliver clean air requirements
for occupants, machines, processes, indoors
environment and ventilation system.
4.01.02 All air filters with dust spot efficiency up to
98%; the performances should be tested according to
ASHRAE Standard 52-76 or EUROVENT Standard
4/5.
4.01.03 Higher Dust Spot Efficiency; the filter
performance should be accordance to DOP-test.
4.02

Preliminary Filter

4.02.01 Preliminary
synthetics media.

filter

shall

be

made

from

4.02.02 Synthetics filter media shall be in flat form or


pleated form.
4.02.03 Aluminum filter shall be from wire mesh form.
4.02.04 Preliminary air filters (synthetics and
aluminum) shall be with hard cupboard or galvanized
steel frames.
4.02.05 Preliminary filters with steel frame shall be
cleanable and washable.
4.02.06 Preliminary filter shall be flame resistance
Class-2 according to UL 900.
4.02.07 Aluminum filter thickness shall be up to 50mm depth, 73% Gravimetric Efficiency (Average
Weight Arrestance , Am between 65 to 80) equivalent to
EU2.
4.02.08 Panel synthetics filter thickness shall be 25mm, 85% Gravimetric Efficiency (Average Weight
Arrestance, Am between 80% to 90%) equivalent to
EU3.
4.02.09 Pleated synthetics V-filter, pleated depth shall
be up to 75-mm, 90% Gravimetric Efficiency (Average
Weight Arrestance, Am at 90%) equivalent to EU4.

3.02.08 Damper blades quadrant shall be assembled to


guide blades opening and closing position.

4.03

3.02.09 Flexible damper connection can be assembled


externally to the casings frame to disconnect potential
vibration transmitted to/from AHU/building.

4.03.01 Soft bag filters is up to 630-mm depth


synthetics bag media and supported with galvanized
steel frames.

3.02.10 Hinged type access door is assembled at


mixing box section.

4.03.02 Soft bag filter shall be flame resistance Class-1


according to UL 900.

Secondary Filter

4.03.03 Air filter efficiency ranged up to 90%


Opacimetric Efficiency or Dust Spot Efficiency
(Average Atmospheric, photometric, Em up to 95;
EU9).

47

Part-4
4.04

Air Filter Section


HEPA/Absolute Filter

4.04.01 Absolute filter is up to 630-mm depth


synthetics or glass fiber bag media and supported with
galvanized steel or aluminum frames.
4.04.02 Absolute filter shall be flame resistance Class1 according to UL 900.
4.04.03 Absolute air filter DOP-efficiency ranged from
95% up to 99.99% equivalent to EU10 up to EU12.
4.05

Filter Mounting Frame

4.05.01 Mounting frame is made from galvanized steel


and filter can be accessed on to the mounting frame
from front (front or rear access or existing frame
mounting) or slide (side mounting) type.
4.05.02 Frame mounting frame or rails should be
sealed for a minimal air leak Class F5-7 according to
EUROVENT Standard EN 779.
4.06

Access Door

4.06.01 Filter sections access door for Front Filter


Mounting shall be equipped with hard nylon hinges
and metal lock, accessible internally and externally for
safety release.
4.06.02 Filter sections access door for Slide Rail
Filter Mounting; shall be a quick release and totally
removable access door type.

Part-5
5.01

Water & DX Coil Section


General

5.01.01 Coils shall be of the cartridge type.


5.01.02 Coils are mounted on a condensate drain pan
(for cooling coil) with a slide in-out coil track so that
the complete assembly is wholly removable for easy
maintenance.

Part-5
5.02

Water & DX Coil Section


Coil Construction

5.02.04 Coil Frames are made from galvanized steel


and painted for additional protection.
5.02.05 Coil assembly shall sit within coil section face
area and seal to the casing wall to avoid air by-pass.
5.02.06 Water coil - headers are made from seamless
copper pipe and extended to outside pipe connection
with threaded end (11 TPI) steel tube.
5.02.07 DX coil headers shall be all copper tubes with
sweat connection type.
5.02.08 Coils shall be counter flow and equipped
with vent and drain (drain and vent - water coil only).
5.02.09 Coils shall be tested at 300-psig submerged
under water; designed to operate up to 230 psig (16
Bar) at 200F (93C).
5.02.10 Extended header connections out side the coil
section shall be protected with metal shield to avoid any
damage during transportation.
5.03

Condensate Drain Pan

5.03.01 Drain pan shall be mounted in slanted angle


for complete and positive drainage.
5.03.02 Drain connection shall be at one sided of the
drain pan.
5.03.03 Drain pan shall be from galvanized steel and
internally coated with corrosion resistance elastic black
asphalt; complies with NFPA 90 A for flame spread and
smoke generation.
5.03.04 Bottom of the drain pan shall be insulated to
avoid condensation.
5.03.05 Stainless steel drain pan can be available
alternative to galvanized steel.

5.01.03 Coil shall be manufactured according to ANSI


or DIN Standard and coils performance shall be rated
according to ARI 410.

5.03.06 Stacked coils with intermediate drain pan shall


be assembled for a coil with fin height greater than
1397-mm.

5.02

5.03.07 Intermediate drain pan shall have an extended


drain tube to guide condensate water from top drain pan
to the lower drain pan. This shall avoid lower fin to
clog with extensive condensate water.

Coil Construction

5.02.01 Standard coil fins material shall be aluminum


or copper or pre-coated aluminum. Aluminum coated
steel fin is standard for steam coil.
5.02.01 Fins density can be from 8 FPI up-to 14 FPI
5.02.03 Fins shall be a collar type; assembled with
OD copper tubes (steel fins and steel tube for steam
coils) and mechanically bonded to copper tube for
greater heat transfer coefficient.

5.04

Moisture Eliminator

5.04.01 Metallic eliminator shall be installed at down


stream of the coil when ever face velocity approaching
2.5 m/s (2.3 m/s for fresh air coil at highly humid
condition).

48

Part-5
5.05

Water & DX Coil Section


Access Panel

5.02.01 Removable panel shall be assembled at coil


sections casing wall.
5.05.02 Panels shall be bolted externally for airtightness, easy removal and quick reassemble to
facilitate access for servicing and maintenance.

Part-6
6.01

Electric Heater Section


General

6.01.01 Electric heater shall be of the cartridge type.


6.01.02 Heaters shall be framed with a slide in-out
track so that the complete assembly is removable.

Part-6
6.04

Electric Heater Section


Closed Finned Heater Type - (option)

6.04.05 Heating elements are wired in star or delta


according to the power supply and pre wired to the
terminal block in the wiring box.
6.04.06 Safety thermostat (rating at 16 (2) A / 380 V )
with a 98 C ( +0/-16 C ) cut out is supplied and it is
manually reset. Heating elements are mounted to a
heavy gauge (G16) galvanized steel frame.
6.05

Access Panel

6.05.01 Totally removable panel shall be assembled at


both casing wall and bolted externally for air-tightness,
easy remove and reassemble panel to facilitate access
for servicing and maintenance.

6.02 Standard Electric Heater Open Wire Type


6.02.01 Standard electric heater shall be from Open
Wire Type.
6.02.02 Heating wire shall be of composition 80% Ni
and 20% Cr.
6.02.03 Heater assembly, the basic components shall
be include airflow switch, power & control terminal
board, grounding lug and primary & secondary over
load temperature sensor.
6.02.04 Components are assembled inside terminal box
integrated with heating elements frame assembly.

Part-7
7.01

Fan And Drive Section


General

7.01.01 Fan shall be forward, backward and airfoil


curved, double inlet and double width (DIDW)
centrifugal type.
7.01.02 Fan performance shall be rated in accordance
to DIN 24 163 (Fans Performance Testing,
Standardized Test Airways) in reference to AMCA
Standard 210-99.

6.02.05 Frames shall be from a heavy gauge (G16)


galvanized steel frame.

7.01.03 Sound level shall be rated in accordance to


DIN 45635 Part 38 Noise Measurement of Machine:
Fan in reference to AMCA Standard 300-96.

6.03

7.02

Remote Control Panel (option)

6.03.01 Remote Control Panel shall include basic


components such as a de-energizing magnetic control
contactor per stage or each 48 AMP circuit within a
stage, a magnetic back-up contactor for each 48AMP
circuit, power & control terminal board, grounding lug
and high & low voltage terminal boards.
6.03.02 Control Panels box shall be made from
painted galvanized steel and weatherproof construction.
6.04

Closed Finned Heater Type (option)

6.04.01 Heating element is made of composition 80%


Ni and 20% Cr.
6.04.02 Assembly of the heating element is secured
inside the stainless steel spherical sheathed fins copper
tube.
6.04.03 Heating component is according to AISI 321
and AISI 430.

49

Fan Construction

7.02.01 Blades of the fans shall be from galvanized


steel.
7.02.02 Backward and airfoil fans blades shall be
treated with epoxy paint.
7.02.03 Wheel shall be statically and dynamically
balance within fan operating speed in compliance to
DIN ISO Standard 1940.
7.02.04 Standard fan bearings are eccentric clamp
bearing type, single row ball bearing, mounted in
pressed steel housing, pre-lubricated and sealed for life.
7.02.05 Reinforced fan bearings are self-aligning
double rows ball bearing, mounted in cast iron housing
and re-grease able.
7.02.06 Bearings nominal life expectancy shall be
40,000 L10 operating hours (according to DIN ISO 281
Section 1). Rated bearing life can reach up to 200,000
L10 hours.

Part-7
7.02

Part-7

Fan And Drive Section


Fan Construction

7.04

7.02.07 For VAV application, Inlet Guide Vane (IGV)


can be available for backward and aerofoil fan; fan size
range from 400 to 1000 (option).
7.02.08 Fan window and fan drainage valve can be
available (option).
7.03

Fan Motor

7.03.01 Design and performance shall be according to


IEC Standards.
7.03.02 Fan motor shall be suitable to operate with
Variable Frequency Drive (VFD) or Frequency Inverter
(FI).

Fan And Drive Section


Fan And Motor Mounting Frame (FMB)

7.04.03 Motor rail shall be a slide rail type for flexible


belt tensioning.
7.04.04 FMB shall be isolated from floor panel with
anti-vibration rubber isolators (spring isolator as option)
7.04.05 Fan shall be isolated to discharge panel with
flexible fan connection.
7.05

Pulleys And Belts

7.05.01 Fan drive package shall consist of fan and


motor pulleys and assembled with Wedge belts.
7.05.02 Variable pitch pulley shall be available at
motor drive up to 15 HP (11 kW) - option.

7.03.03 Standard fans motor shall be a Totally


Enclosed Fan Cooled type (TEFC).

7.06

7.03.04 Motors frame shall be from aluminum or cast


iron.

7.06.01 Fan Section access shall be with hard nylon


hinges and metal lock, accessible internally and
externally for safety release.

7.03.05 Index of Protection, shall be with IP 55;


motor shall be protected against dust and protected
against jets of water from all direction.
7.03.06 Insulation Class F (Tmax 155
Temperature Rise Class B (T 80K).

C) and

7.03.07 Motor shall able to operate at 50C operating


temperature.
7.03.08 Motor shall have a thermal reserve to spare for
overheating when induced by voltage fluctuation at
10%; compliance to IEC 34-1.
7.03.08 Thermal Overload Protection Normally
Closed Thermostat (PTO) shall be a standard
accessory.
Note: PTO shall provide general surveillance for non-transient
overload. Bi-metallic strip with normally closed contact is
indirectly heated when line current passes through the strip
and shall shut down or restores supply circuits as necessary.
PTO connection shall be mounted to control circuit and
suitable for manual or automatic reset.

7.03.09 Positive Temperature Coefficient thermistor


(PTC) shall provide general surveillance for transient
overload and shall be mounted and connected to a relay
in control circuit (option).

7.04

Access Door

Fan And Motor Mounting Frame (FMB)

7.04.01 Fan and motor shall be installed on a common


base frame.
7.04.02 FMB shall be fabricated from heavy gauge
galvanized steel or cast iron steel.

Nomenclatures
ACF
AHU
AMCA
ANSI
ARI
ASHRAE
ASQC
ASTM
CMH
CWC
DIDW
DIN
DOP
DSC
DXC
EHTR
EN
FMB
FPI
HEPA
HPE
HPLE
HWC
HWE
IAQ
IEC
IGV
IP 55
ISO
NEC
OD
RAC
STC
STH
STL
SW
TEFC
UL
VAV
VFD

Activated Carbon Filter


Air Handling Unit
Air Movement And Control Association Int. Inc.
American National Standards Institute
Air-Conditioning & Refrigeration Institute
American Society of Heating, Refrigerating And AirConditioning Engineers, Inc.
American Society For Quality Control
American Standardization Testing Material
Cubic Meter Per Hour
Chilled Water Cooled
Double Intake Double Width
Deutscher International Norms
Dioctylphthalate
Double Skin Casing
Direct Expansion Coil
Electric Heater
European Committee for Standardization
Fan & Motor Base
Fin Per Inch
High Efficiency Particulate Air
Heat Pipe Exchanger
Heat Plate Exchanger
Hot Water Coil
Heat Wheel Exchanger
Indoor Air Quality
International Electrotechnical Commission
Inlet Guide Vane
Index Of protection 55
International Standards Organization
National Electric Code
Outside Diameter
Run Around Coils
Steam Coil
Steam Humidifier
Sand Trap Louver
Spray Washer Humidifier
Totally Enclosed Fan Cooled
Underwriters Laboratory
Variable Air Volume
Variable Frequency Drive

50

Back

Selection Tools and Sample Selection

Carrier 39F

Following is an example of an AHU selection by utilizing some of the tools made available such as Carrier
Flexair Software, Psychrometric chart and a fan curve.
STEP 1: AHU Requirements
All parameters and detail specifications needed for selection can be obtained from unit application, customer
requirements or consultant guidelines. Such information is the key and basis of an AHU selection. Example of
required inputs are as follows,
a.

Panel thickness of 25mm double skin externally painted

b.

EU7 soft bag filtration mounted on existing frame with prefilter

c.

2 steps 30kW heating capacity electric battery heater

d.

Cooling requirements,
i. total capacity: 72.8 kW
ii. air on condition: 29C / 47%
iii. air off condition: 13.1C / 98%
iv. water entering temperature: 7.2C
v. water temperature rise: 5.6C
vi. airflow: 9612 m3/hr
vii. face velocity: 2.6 m/s

e.

Forward curve fan with horizontal discharge

f.

Motor service factor of 1.33

g.

Adjustable pulley drive type

STEP 2: Flexair Selection


From adequate information given above, the Flexair Selection software can be made use of to enhance the AHU
selection effectively. The software will assist in the AHU component selection section by section until the whole
complete unit is done. In each section several options of component can be choose from to give flexibility in the
selection while maintaining the AHU specifications.
A summary printout of the complete unit is readily available with sketch detailing the component layout for easy
reference makes the software a powerful tool for Sales and Application Engineers. For more information on
Flexair please contact your nearest Carrier office.
STEP 3: Performance Checks
To justify whether a good selection has been made, especially on airside, a quick double check can be
performed by using a fan curve. The operating point of the selected fan can be plotted on its fan curve to ensure
the selected fan is operating in a safe region where the performance of the fan is at its optimal.
Another tool that can be made use of is the Psychrometric Chart. The airside performance of the cooling coil can
be plotted on the chart where the quality of air before and after the cooling coil could be determined. The two
operating points (coil on-off conditions) would also determine the total, sensible and latent cooling of the air
passing through the coil.
STEP 4: Finalizing Selection and Placing Order
Once the selection has been finalized, an order can be placed by filling the Order Entry Data List Mandatory
form along with a copy of the Flexair summary printout.

51

Flexair Summary Printout Example

Component
description
AHU size

Module size
for component

Access
orientation

Section
pressure drop

Unit physical
information
for reference

Component
performance
Physical
description

52

A 315

Sections
breakdown

1022

Component
layout

9612

53

AIR ON
CONDITION
AIR OFF
CONDITION

13.1

29
54

39F - ORDER ENTRY DATA LIST MANDATORY


When placing an order, please ensure that the following data are properly specified. This would enable
us to serve you better and avoid any delay and to avoid potential error in processing your order.
ORDER NO.
(PLEASE FILL IN THE TABLE STATING THE SIDE OF SERVICE)
No

AHU Index

39F
Model

39F
Size

Qty

Coil
Headers

Fan
Section
Access

Filter
Section
Access

Fan
Discharge

Side
Damper

1
2
3
4
5
6
7
8
9
10
Notes:
1
2
3
4

Side of Service reference is by looking the 39F AHUs in the same direction or the airflow.
Side of Service for fan, motor and drive set is same as per the Fan Section Access Door.
Please indicate RH=Right Hand Side or LH=Left Hand Side when filling the above table.
Fan Discharge Configuration, please refer to below sketch and indicate the discharge configuration
in the above table (in the Fan Discharge Configuration column).

UBF

UBR

BHR

THR

DBF

DBR

THF

BHF

Fan arrangement
5 PLEASE SPECIFY POWER SUPPLY :

_____ VOLT/_____PH/_____HZ

6 Please state any special option and/or instruction (if any). Use additional sheet if require.

55

Back

Carrier 39F

Conversion Table
From
LENGTH
inches
feet
yards
miles

To

Multiply by

millimeters
meters
meters
kilometers

mm
m
m
km

AREA
Square inches
Square feet
Square yards

square millimeters
square meters
square meters

mm
2
m
2
m

654.2
0.0929
0.8361

VOLUME
Cubic feet
Cubic yards
Quarts
US Gallons
Cubic centimeters

cubic meters
cubic meters
liters
liters
milliliters

m
3
m
l
l
ml

0.0283
0.7646
0.9464
3.7854
1

MASS
Pounds
Metric ton (2000lb)
US ton (2240lb)

kilograms
tons (1000kg)
tons (1000kg)

kg
t
t

0.4536
0.907
1.016

TEMPERATURE
F
C
C

C
F
Kelvin

C
F
K

(F-32)1.8
(C x 1.8)+32
C + 273.15

ENERGY
BTU
Kilowatt-hour

kilojoules
kilojoules

kj
kj

1.055
3600

POWER
Horsepower

kilowatts

kW

0.746

HEAT FLOW
BTU/hr
BTU/hr
Tons (refrigeration)
Tons (refrigeration)

watts
kilocalories/hr
kilowatts
kilocalories/hr

W
kcal/hr
kW
kcal/hr

25.4
0.3048
0.9144
1.609

0.2931
0.2519
3.517
3024

HEAT TRANSFER COEFFICIENT


2
2
BTU/hr/ft /F
watts/m /C
2
2
kcal/hr/m /C
watts/m /C

W/m /C
2
W/m /C

5.678
1.163

VOLUME FLOW
CFM
CFM
CFM
GPM (US)
GPM (Imperial)
3
m /hr

cubic meter/sec
liter/sec
cubic meter/hour
liter/sec
liter/sec
liter/sec

m /s
l/s
3
m /hr
l/s
l/s
l/s

0.000472
0.472
1.699
0.0631
0.0757
0.2778

VELOCITY
FPM

meter/sec

m/s

0.0051

PRESSURE
in.of water (iwg)
ft of water (H2O)
Pounds/sq.in (psi)
Pounds/sq.in (psi)
ft of water (H2O)
Pounds/sq.in (psi)

kilopascal (kN/m )
kilopascal
kilopascal
kilogram/sq.centimeter
bar
bar

kPa
kPa
kPa
2
kg/cm
bar
bar

0.249
2.99
6.895
0.0703
0.03
0.0693

56

57

Notes

58

Carrier Corporation

Carrier
A United Technologies Company

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

59
Form 39F-2PD-S