DeltaV Product Data Sheet

January 2013 Page 1

S-series SD Plus Controller

S-series SD Plus Controller

The S-series SD Plus Controller and the DeltaV I/O subsystem make rapid installation easy

Scalable controllers

Introduction

Quick Assembly

The DeltaV S-Series controllers provide


communication and control functions and integrate
field devices and the other nodes on the control
network. The SX, SQ and SD Plus controllers
provide a choice to match the controller capacity to
the requirements of the process. They also provide
new ease of use features that eliminate mounting
screws and accelerate cabinet assembly.

Easy to use
Field Proven architecture
Designed for Digital Marshalling
Advanced Controls

Control strategies and system configurations created


on earlier DeltaV systems can be used with this
controller. The SD Plus Controller provides all the
features and functions of the M-Series controllers
with the added support for CHARM based Digital
Marshalling.
The control languages executed in the controllers
are described in the Control Software product data
sheet.

www.DeltaV.com

DeltaV Product Data Sheet

S-series SD Plus Controller

January 2013 Page 2

Benefits

Hardware redundancy is automatically detected with


zero configuration effort.

Scalable controllers. The SD Plus controller


complements the SX controller by providing a smaller
controller platform at a reduced price for those small to
moderate applications:

Speed. The SD Plus controller supports all the


features youve come to expect from the DeltaV
system: self-addressing, automatic I/O detection. All
these features are designed to make your projects
execute fasterjust plug and play!

Redundant architecture. The SD Plus controller


supports 1:1 redundancy for increased availability.
Redundant SD Plus controllers can be upgraded to
SX controllers onlinerobust!

Late Changes. You can easily upgrade an SD Plus


controller to an SX to handle project scope changes
late in the project. Simply replace the SD Plus with
the SX and all existing configuration, documentation
and hardware design remain the same forgiving.

Field Proven Architecture. The S-Series controllers


are an evolution of DeltaV M-Series hardware. The new
design delivers installation and robustness enhancement
while still using the same processor and OS that has
proven itself in the field. All S-series I/O cards run the
latest software enhancements of corresponding M-Series
I/O cards and deliver the same field proven, reliable
operation.

Quick Assembly. The S-Series hardware has been


redesigned for speed of project execution. Carriers snap
to standard DIN rails and controllers and S-series IO snap
into position without the use of retaining screws.

Easy to use. Controllers are also easy to configure.


Simply connect the SD Plus to the DeltaV network and
Auto-Sense it from DeltaV Explorer. Add the controller and
all its IO interfaces to the system database and all
components are automatically addressed and
communicating. There are no dip switches or jumpers to
set.

Control strategies are developed using IEC-61131


programming techniques: Function Blocks, Sequential
Function Charts and Structured Text.
Automatic diagnostic and event reporting with time
stamps applied in the controller

Set control execution to match process dynamics and


controller scheduling adjusts automatically.

Reference any parameter by its module name,


regardless of its location in the system.

Synchronized system clock for consistent time based


event driven actions across the system.

Online expandable IO carriers allow new cards to be


added online, with autosense capability, for modular
system growth

The SD Plus Controller

Designed for Digital Marshalling. The S-Series


controllers have highly distributable I/O capabilities with
CHARMs based Electronic Marshalling. Electronic
Marshalling I/O can be mounted anywhere, facilitating
system design and expansion while reducing overall
system footprint over traditional marshalled I/O
Subsystems.

Advanced Controls. The SD Plus controller supports


all the advanced control features that are expected in a
world class Digital Control System:

Batch Software

Model Predictive Control

Neural Networks

DeltaV Product Data Sheet

S-series SD Plus Controller

January 2013 Page 3

Product Description
The SD Plus controller executes control logic based on the
process signals derived from the I/O subsystem and
provides communication to the rest of the DeltaV control
system for operator interaction and data collection.

The capacity limits of the SD Plus Controller may vary


depending on the particular application, amount of
CHARM I/O Signals and as well control performance
requirements.

Each controller node can be installed as a simplex or


redundant node. Redundancy is provided by adding a
second controller and power supply mounted adjacent to
the primary controller. The controllers are connected to the
I/O carriers, which are mounted to the right of the
controller carriers. Up to 8 carriers with 8 cards each can
be connected to the local bus I/O, for a total of 64
traditional I/O cards. In addition to the 8 local I/O carriers,
each controller can communicate with an additional 16
Remote I/O units hosting traditional card based I/O.

The WirelessHART I/O card (WIOC) provides redundant


communication for up to 100 WirelessHART devices,
providing high availability and reliability of wireless data.
Up to 16 Wireless HART I/O cards can communicate to
one controller, each providing up to 100 signals.

In addition to traditional I/O cards, the local bus supports


fieldbus technologies, including FOUNDATION fieldbus,
Profibus DP, DeviceNet and AS-I protocols. The I/O
subsystem also supports Serial interface cards as well as
the Ethernet I/O interface. These various I/O products
provide a wide range of interfaces to meet the needs of
your control application.
The SD Plus Controller also supports CHARMs and
WirelessHART IO cards. The CHARM I/O Card (CIOC)
connects via the redundant Ethernet ports of the controller
to provide a highly distributed and flexible I/O solution
called Electronic Marshalling. Up to 16 CIOCs can
communicate to one controller, each providing up to 96
individually configurable signal types.

Control modules are automatically scheduled by the


controller, based on their assigned scan rates. This allows
each control function to be optimized based on the
process dynamics. Modules scan times can be set as fast
as 100 ms, and as slow as 60 seconds. The number of
control modules that can be assigned to a controller
depends on the complexity and scan rate of each module,
and the available CPU and memory. The SD Plus
controller should be used for small to medium applications
with a maximum of 750 individual I/O signals.
The SD Plus controller is designed for harsh environments
and is rated for G3 corrosive environments, with an
operating temperature range from -40 to 70 C. It is ideally
suited for remote installation, close to the process
equipment. For more traditional installations with central
marshalling cabinets, CHARM I/O Cards can be mounted
in standard I/O cabinets providing Electronic Marshalling.
CHARM I/O Cards can also be used for highly distributed
I/O applications.

S-series controller hardware dimensions

DeltaV Product Data Sheet

S-series SD Plus Controller

January 2013 Page 4

Hardware Specifications
Specifications for the SD Plus Controller
DST Limit

750

SCADA tags

3200

Max data values sent

2000/second

Max data values received

250/second

Max unsolicited client nodes

64

Module Execution rates

100ms, 200ms, 500ms, 1s, 2s, 5s, 10s, 30s, 60s

User Memory

48 MB

Fuse protection (internal)

3.0 A, non-replaceable fuses

Power dissipation

5.0 W typical, 7.0 W maximum


Environmental specifications:

Operating temperature

-40 to 70 C (-40 to 158 F)

Storage temperature

-40 to 85 C (-40 to 185 F)

Relative humidity

5 to 95%, non-condensing

Protection rating

IP 20, NEMA 12

Airborne contaminants

ISA-S71.04-1985 Airborne Contaminants Class G3


Conformal coating

Shock (normal operating


conditions)

10 g -sine wave for 11 ms

Vibration (operative limit)

1 mm peak-to-peak from 5 Hz to 13.2 Hz, 0.7 g from 13.2 Hz to 150


Hz
LED Indicators:

Green Power

Indicates DC power is applied.

Red Error

Indicates an error condition.

Green Active

Indicates that the controller is operating as the primary controller.

Green Standby

Indicates that the controller is operating as a backup controller

Yellow flashing Pri. CN

Indicates valid primary control network communication.

Yellow, flashing Sec. CN

Indicates valid secondary control network communication.


External connections:

Primary Control Network

8-pin RJ-45 connector

Secondary Control Network

8-pin RJ-45 connector

DeltaV Product Data Sheet

S-series SD Plus Controller

January 2013 Page 5

Certifications
The following certifications are available on the SD Plus
controller.

CE:

The following certifications have been submitted for


Hazardous Locations and for Marine applications. Please
verify with the appropriate certifying agency for a specific
list of approved components

EN 60079-15:2005

- EMC- EN 61326-1:2006
- LVD- EN 61010-1:2001

Certifying agency: Nemko


Certificate Number: TBD

CSA:

Refer to document TBD


"DeltaV Scalable Process System Zone 2
Installation Instructions"

- CLASS 2252 05 - PROCESS CONTROL


EQUIPMENT:
CAN/CSA-C22.2 No. O-M91 General RequirementsCanadian Electrical Code, Part II
CAN/CSA-C22.2 No. 61010-1-04 Safety
Requirements for Electrical Equipment for
Measurement, Control, and Laboratory Use,
Part 1: General Requirements

CENELEC Zone 2 ATEX/IEC EX

FM Approval
Class 1 Division 2 Hazardous Locations
Certifying agency: FM Approvals
Certificate Number: TBD

Refer to document TBD


"DeltaV Scalable Process System Class 1
Division 2 installation Instructions

Complies with NAMUR NE21 per DeltaV Digital


Automation System NAMUR NE21 Installation Instructions
12P2822.

Marine Certifications:
IACS E10:2006 Rev.5 Control, protection &
Safety
-

ABS Certificate of Design Assessment


Bureau Veritas Certificate
DNV Marine Certificate
Lloyds Register

GOST Hazardous Area certification Zone 2


(Russian)

Other country specific certifications may also be available.


Verify with your local Emerson sales office to confirm any
certification requirements not listed here.
.

DeltaV Product Data Sheet

S-series SD Plus Controller

January 2013 Page 6

Ordering Information
Description
SD Plus Controller

Model Number
SE3006

Prerequisites

For each controller you will need a Power/Controller carrier. Please refer to the S-series I/O Carrier product data sheet for
details.

Each controller requires a dedicated system power supply. Please refer to the S-series Power Supplies product data
sheet for details.

To locate a sales office near you, visit our website at:


www.EmersonProcess.com/DeltaV
Or call us at:
Asia Pacific: 65.6777.8211
Europe, Middle East: 41.41.768.6111
North America, Latin America:
+1 800.833.8314 or
+1 512.832.3774

For large power, water, and wastewater applications


contact Power and Water Solutions at:
www.EmersonProcess-powerwater.com
Or call us at:
Asia Pacific: 65.6777.8211
Europe, Middle East, Africa: 48.22.630.2443
North America, Latin America: +1 412.963.4000

Emerson Process Management 2013. All rights reserved. For Emerson Process Management trademarks and service marks, go to:
http://www.emersonprocess.com/home/news/resources/marks.pdf.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be
construed as warrantees or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed
by our terms and conditions, which are available on request. We reserve the right to modify or improve the design or specification of such products at any time
without notice.

www.DeltaV.com