Automatic
transfer
switches
ATK series
Planet-SWITCH
Planet-SWITCH
Planet-DIN
Planet-DIN
Planet-LOGIC
Planet-LOGIC
Automatic transfer switches
Order code Description
Qty
per
pkg
Wt
[kg]
ATK20
Automatic transfer switch,
24VDC auxiliary supply
0.700
ATK40
Automatic transfer switch,
230VAC auxiliary supply
0.900
PACR
IP54 front protection cover
0.107
DIMENSIONS (mm)
62
31
52
ATK...
ATK
AUTOMATIC
TRANSFER
SWITCH
General characteristics
The automatic transfer switch ATK is used for the
automatic changeover of the load from the main line to
a secondary line.
It is made of a single unit in an insulated housing and
has two outgoings for the automatic and/or manual
control of contactors or circuit breakers.
MANUAL CHANGEOVER
This mode consents to the manual changeover from one
source to another and viceversa.
AUTOMATIC CHANGEOVER
This mode automatically enables the switching of two
lines within a time period, adjustable between 0.5 and
120 seconds.
The control of the two line contactors or circuit breakers
is achieved in a safe and reliable manner by means of a
safety system with internal electromechanical interlock
of the ATK unit.
POWER ON
ALARM
SECONDARY
LINE
144
PACR
MAIN
LINE
AUT ON/OFF
MAIN LINE ON
SEC LINE ON
OPEN ALL LINES
TEST
SETUP
LOAD
144
138.5
138.5
WIRING DIAGRAM
Operational characteristics
 Rated supply voltage: 24VDC (ATK20) 230VAC (ATK40)
 Voltage range: 0.7-1.35% Us (ATK20)
0.8-1.2% Us (ATK40)
 Maximum current consumption: 250mA (ATK20) 45mA (ATK40)
 Rated current: 100mA (ATK20) - 35mA (ATK40)
 Connection time: 100%
 Maximum voltage ripple: 10% (ATK20)
 Power loss ride through (MPU circuit): 300ms
 Galvanic isolation between control network and
internal circuits
 True RMS control of supplt voltage
 Microprocessor supervision of functions
 Membrane keypad and 3 digit display
 11 signalling LEDs
 Adjustable tripping limits and time
 AUT-MAN-TEST operating mode
 1 Main L-L voltage measurement input
 1 Secondary L-L voltage measurement input
 100-415VAC rated voltage control
 70-500VAC L-L voltage range
 50 or 60Hz rated frequency
 Full scale measurement accuracy: 1% 1digit
 2 output relays (16A Ith changeover contact) for Main
and Secondary contactor or circuit breaker control
 1 alarm output relay (8A Ith changeover contact)
 IP41 on front, IP54 with sealable cover (order
separately)
 IP20 at rear.
Set up
The set up contemplates the following setting parameters:
 Max voltage limit for Main and Secondary lines
 Min voltage limit for Main and Secondary lines
 Min-Max limit tripping delay for Main and
Secondary lines
 Min-Max limit delay at voltage return for Main and
Secondary lines
 Changeover/interlock control time for circuit breakers
control of Main and Secondary lines.
Reference standards
Compliant with standards: IEC/EN50081-1,
IEC/EN50082-2, IEC/EN61010-1, IEC/EN60068-2-6,
IEC/EN60068-2-27, IEC/EN60529, IEC/EN61000-4-11
and EN50011.
LOVATO ELECTRIC S.P.A.
CONTROL SOLUTIONS
FOR INDUSTRY
VIA DON E. MAZZA, 12
24020 GORLE (BG) ITALY
TEL. +39 0354282111
INTERNATIONAL SALES DIPARTMENT:
TEL. +39 0354282281
FAX +39 0354282400
Web: www.LovatoElectric.com
E-mail: [email protected]
PD39 GB 03 02
Selling points
 Microprocessor supervision
 Easy and simple installation
 RMS voltage measurements (full scale accuracy: 1%
1digit)