Burner control unit BCU 370
Product brochure GB
6.1.3.2 Edition 12.05
For modulating, forced draught burners for gas of unlimited
capacity in intermittent or continuous operation
Control of fan and butterfly valve
Simple system set-up thanks to optional tightness control
and integrated ignition unit
Easy start-up and maintenance thanks to Manual operating
mode
Enhanced flexibility and simplified logistics thanks to
programmable functions
Easy servicing thanks to informative operating, warning and
fault messages
Optionally available with integral field bus interface for
simple wiring
EC type-tested and certified, CSA and FM approved
www.kromschroeder.com
2 BCU 370 Edition 12.05
Burner control unit
BCU 370.
Application
The BCU 370 burner control unit controls, ignites and monitors industrial forced draught
burners of unlimited capacity in intermittent
or continuous operation.
It can be used for directly ignited forced
draught burners or forced draught burners ignited with pilot burner. The BCU 370
activates the blower and sets the connected
butterfly valve to pre-purging and ignition
position. After pre-purge and burner start,
the Enable signal is issued to an external
controller which positions the butterfly valve
in accordance with the output demand.
Post-purge occurs after the end of burner
operation. The burner control unit BCU 370
monitors the gas and air pressure. An optionally integrated tightness control function
checks the valves with an external gas pressure switch.
Programmability by means of the optical
interface and BCSoft PC software guarantees optimum adaptation to the relevant application. Adjustable start-up attempts and
automatic restart which can be activated
ensure the high availability of the burner
equipment.
The quick-start option allows standard-compliant start-up of the forced draught burner
without pre-purge after normal shutdown.
This avoids unnecessary admission of air into
the combustion chamber. The heat output
is available as quickly as possible after a
temperature demand.
The program status, the unit parameters and
the level of the flame signal can be read directly from the unit. An integrated Manual
mode allows manual start of the burner and
setting of the butterfly valve position independently of the central control system. The
BCSoft operator-control and setting software
provides a powerful tool for start-up and
servicing.
To reduce the installation and wiring costs
Kromschrder offers an optional Profibus-DP
interface to transfer the activation signals
and feedbacks.
BCU 370 Edition 12.05 3
Example applications
L1
21
Modulating-controlled forced draught
burner
The BCU 370 controls the blower and moves
the butterfly valve to pre-purging and ignition
position. It issues the Enable signal to the
control system after start-up of the burner.
BCU 370..I1
25
28
26
24
20
19
0 90
90 0
22
DG min
3 7
DG
DL
V1
VG
5 29 30 31
V2
VG..L
18
17
13
GIK
IC 20
B VA
DL
32
UV
S
23
Modulating-controlled forced draught
burner with tightness control
In addition to controlling the forced draught
burner, the burner control unit also monitors the fail-safe function of the two solenoid
valves for gas via the DG. gas pressure
switch.
L1
21
BCU 370..I1..D3
25
28
26
24
DG
3 7
DL
V1
11
DG
5 29 30 31
V2
DG
pe/2 VG..L
VG
DL
32
18
17
13
DG min
GIK
IC 20
B VA
UV
22
20
19
0 90
90 0
23
BCU 370 Edition 12.05 4
Modulating-controlled forced draught
burner with pilot burner and tightness
control
A pilot burner ignites the main burner and is
switched off during the main burners safety
time.
L1
21
BCU 370..D3
25
28
26
24
DG min
DG
37
DL
45
V1 V2
11
6 29 30 31
DG V3
DG
pe/2
VG
13
18
17
GIK
VG..L
VG
DL
32
IC 20
B VA
UV
S
22
20
19
0 90
90 0
23
5 BCU 370 Edition 12.05
Technical data
Mains voltage:
BCU..W: 230 V AC, -15/+10%, 50/60 Hz, or
BCU..Q: 120 V AC, -15/+10%, 50/60 Hz,
for grounded or ungrounded mains.
Operation and fault signalling contacts:
Dry Contact, max. 1 A, 253 V, not fused
internally.
Reset/Information button: Max. number of
operating cycles: 1000.
Flame control with UV sensor or ionisation
sensor.
Fuse in BCU, replaceable, F1: T 5A H, pursuant to IEC 60127-2/5.
Flame signal for:
Ionisation control: 128 A,
UV control: 135 A.
Permissible UV sensors:
Kromschrder models UVS 1, 5, 6, 8 and
UVD 1.
For intermittent or continuous operation.
Weight: Approx. 1.8 kg.
Air pressure check during pre-purge and
operation by external air pressure switch
DL.
PROFIBUS-DP
Manufacturer ID: 0x08EC.
Maximum length of ignition cable with integrated electronic ignition: 1 m.
Maximum length of ionisation/UV cable:
50 m (164 ft).
ASIC type: SPC3.
SYNC- and FREEZE-capable.
Baud rate detection: Automatic.
Min. cycle time: 0.1 ms.
Max. number of operating cycles: 250,000.
Diagnostic bytes: 6 (DP Standard).
Ambient temperature:
BCU 370: -20+60 C (-4+140 F),
BCU 370..I: -10+60 C (14+140 F),
no condensation permitted.
Certification
Enclosure: IP 54 pursuant to IEC 529.
Housing made of impact-resistant and
heat-resistant plastic. Plug-in upper section with operating and display elements.
Lower section with connection terminals,
earthing strip and pre-wired neutral bus
with spacious wiring chamber.
1x M25 multiple screw connector,
4x 7mm cable grommets,
2x M20 multiple screw connectors,
2x 7 mm cable grommets, and loosely
enclosed
1x or 2x M16 plastic screw connector(s) for
the ignition cable(s).
Voltage to inputs, valves, fan, controller
enable, actuator and ignition unit = mains
voltage.
Power consumption: Approx. 9 VA plus approx. 50 VA for integrated ignition.
Input voltage signal inputs:
Rated value
120 V AC
Signal 1
80126.5 V
Signal 0
020 V
230 V AC
160253 V
040 V
Input current signal 1: Typ. 2 mA
Output to ignition transformer:
No-switch contacts via semi-conductor.
Contact rating:
Valves: Max. 1 A, cos j = 1,
Butterfly valves: Max. 1 A, cos j = 1,
Ignition: Max. 1 A, cos j = 0.3,
Controller enable signal:
Max. 1 A, cos j = 1,
the contacts may be loaded with a max.
total of 2.5 A,
Fan: Max. 3 A, start-up current:
Max. 6.5A < 1 s.
The outputs may be loaded with a max.
total of 4 A.
Parameter bytes: 7 (DP Standard).
EC type-tested and certified
pursuant to
Gas Appliances Directive (90/396/EEC) in
conjunction with EN 298,
Low Voltage Directive (73/23/EEC) in conjunction with the relevant standards,
Electromagnetic compatibility 89/336/
EEC in conjunction with the relevant
standards relating to radiation.
AGA
Approval No. 6478 in preparation
CSA and FM approved
Canadian Standards Association Class:
3335-01 and 3335-81 Systems (Gas-)Automatic Ignition and Components
Factory Mutual Research Class: 7611 Combustion Safeguards and Flame Sensing
System
Suitable for applications pursuant to NFPA
85 and NFPA 86
PROFIBUS User Organisation
BCU 370..B1
PUO = PROFIBUS User Organisation,
Certificate no. Z00692 pursuant to
EN50170-2
6 BCU 370 Edition 12.05
Selection
Order example
BCU 370WI1FEU0D1
BCU 370: for modulating-controlled forced draught burners
W Q I1 I2 I3 F E U0 U1 D1 D3 B1* -3*
BCU 370
** **
Type = BCU
Mains voltage
230 V AC, 50/60 Hz = W
120 V AC, 50/60 Hz = Q
Ignition
Electronic ignition, single-pole = I1
Electronic ignition, double-pole = I2**
Electronic ignition, double-pole
with neutral conductor
= I3**
Without ignition
= no specification
Fan control = F
Valve control = E
Flame control
Ionisation control (continuous or intermittent op.)
or UV control (intermittent op. with UVS) = U0
UV (continuous operation with UVD 1) = U1
DGmax. monitoring
= D1
Integrated tightness control = D3
For PROFIBUS-DP = B1*
Three-point step control via PROFIBUS-DP = -3*
= standard
= available
Detailed information on this
product
www.docuthek.com
Contact
www.kromschroeder.com Sales
Elster GmbH
Postfach 2809 49018 Osnabrck
Strotheweg 1 49504 Lotte (Bren)
Germany
T +49 541 1214-0
F +49 541 1214-370
[email protected]
www.kromschroeder.com
www.elster.com
Kromschrder, a product
brand of the Elster Group
We reserve the right to make technical modifications
in the interests of progress.
Copyright 2007 Elster Group
All rights reserved.