FIRE RESISTANT CABLES
FP200 GOLD
FP
FIRE RESISTANT CABLES
FP200 GOLD
BS7629-1
Clause 26.2
FP200 GOLD
>
The original highly durable and dressable, easy to terminate
and install re resistant cable. Approved for re detection and
re alarm critical signal paths in BS5839-1:2002 "standard"
application areas, voice alarm systems to BS5839-8:1998
(Amd 2006) and emergency lighting systems to BS5266-1:2005.
Thechangesto cabletest methodsand requirements rst introduced
by BS5839-1:2002 Fire detection and re alarm systems for
buildings - Part 1: Code of practice for system design, installation,
commissioning and maintenance mean that re resistant
cables must now be approved against new test requirements.
APPROVALS
>
In addition to approvals to BS7629-1 and BS6387 Category CWZ,
FP200 Gold has received BASEC and LPCB approval to BS58391:2002 for 'standard' applications. This includes approval to
EN50200 Classi cation PH30 and the new integrated re, shock and
water test BS8434-1 for 30 minutes. FP200 Gold is also approved
to EN 50200 classi cation PH60 as required by BS5266-1:2005.
DATA CAPABILITY
>
FP200 Gold has excellent data/signal transmission characteristics
making it ideal for voice alarm, addressable and networked
systems.
INSTALLATION
>
In accordance with the new BS5839-1and BS5266-1
requirements, cables must be supported by a xing that
can withstand the same re conditions as the cable. To meet
this requirement the use of Prysmian AP LSOH coated metal
P - clips or the new FP Fire xTM rapid xing system
is recommended.
CABLECHARACTERISTICS
Temperature
Range
- 20 to +70C
Bending Radius
Fixed r=6D
Mechanical Impact
Medium
Fire Performance
BSEN60332- 1- 2
BSEN50266- 2- 4
Flexibilty
Rigid
Halogen Free
BSEN50267- 2- 1
Low Smoke Emissions
BSEN61034- 2
Fire Resistant
BS6387 Category CWZ
EN50200 PH30 & PH60
BS8434- 1 30min
KEY APPLICATIONS
CORE IDENTIFICATION
>
>
>
>
oo
ooo
oooo
Fire detection and re alarm systems for buildings
Voice alarm systems
Emergency lighting
Other essential service circuits
SCREEN
CABLE DESCRIPTION
Laminated aluminium tape screen bonded to sheath
and in contact with full size tinned annealed copper
circuit protective conductor which provides
automatic screen earthing.
CONDUCTOR
Plain annealed copper solid (1.0 - 2.5 mm2) or stranded
(4.0 mm2) circular conductor complying with B6360 class
1 or class 2.
SHEATH
INSULATION
Robust thermoplastic LSOH sheath; Colour - White or Red
Other colours to special order. For external exposure the
use of a white sheath is recommended.
TM
High performance damage resistant Insudite .
British Standard Type EI5.
Mean
overall
diameter
brown-blue
brown-black-grey
blue-brown-black-grey
Nominal
cross
sectional
area
Conceptual
Construction
Approximate
cable
weight
Maximum
conductor
resistance
at 20C
Current
Current
rating DCor rating DCor
single phase single phase
AC
AC
Enclosed
Clipped direct
Amps
Amps
Volt drop
DCor single
phase
AC
mm2
no./mm
mm
kg/km
ohms/km
1.0
1/1.13
8.0
78
18.1
13
15
44
1.5
1/1.38
8.1
93
12.1
16.5
19.5
2.5
1/1.78
9.5
140
7.4
23
27
4.0
7/0.85
11.6
195
4.6
30
1.0
1/1.13
8.2
88
18.1
1.5
1/1.38
8.4
116
2.5
1/1.78
10.4
180
4.0
7/0.85
12.3
1.0
1/1.13
1.5
2.5
4.0
Recommended accessories
1 LSOH
2 Nylon
LSOH
gland
FP FirefixTM
fixing
clips
AP7
251/GL2520
UFPNF02*
29
AP7
251/GL2520
UFPNF02*
18
AP9
251/GL2520
36
11
AP11
252/GL2520
13
15
44
AP7
251/GL2520
UFPNF02*
12.1
16.5
19.5
29
AP8
251/GL2520
UFPNF04*
7.4
23
27
18
AP10
252/GL2520
248
4.6
30
36
11
AP12
252
8.5
107
18.1
13
15
44
AP8
251/GL2520
UFPNF04*
1/1.38
10
143
12.1
16.5
19.5
29
AP9
251/GL2520
1/1.78
11.9
225
7.4
23
27
18
AP11
252/GL2520
7/0.85
13.5
310
4.6
30
36
11
AP13
254
*R- RED
W- WHITE
mV/A/m
fixing
clips
Two core
Three core
Four Core
Notes to table
FP200 Goldis also available in multi-core versions (7,12 & 19 core con gurations)
1 Recommended clip spacing 300 mm horizontal and 400mm vertical.
2 Brass glands may be used as an alternative.
Minimum recommneded installation temperature 0C. Installation methods for current rating in accordance with BS7671/IEEWiring Regulations.
The tabulated ratings are based upon a 30C ambient temperature and 70C operating temperature.
For other ambient temperatures or where cables are grouped together, appropriate rating factors should be applied.
Temperature ratings factor
Correction Factors for groupings
Ambient Rating Factors C
Rating Factor
Number of circuits
Rating Factor
25
1.03
0.80
30
1.00
0.70
35
0.94
0.65
40
0.87
0.60
45
0.79
0.57
50
0.71
0.54
Sales enquiries
Tel: +44 (0) 8457 678345
Fax: +44 (0) 23 8029 5465
Technical helpline
Tel: +44 (0) 23 8029 5222
Fax: +44 (0) 23 8029 5002
Information hotline
Tel: +44 (0) 23 8029 5029
Fax: +44 (0) 23 8029 5437
[email protected]
Prysmian Cables & Systems Limited
Chickenhall Lane
Eastleigh
Hampshire
SO50 6YU
United Kingdom
www.prysmian.co.uk