EWG 01.
1, RWG 4020, potentiometer
Technical data Electronic position transmitters/potentiometer
EWG 01.1
Contactless and wear-free sensing of the valve position by means of Hall sensors for signalling the valve position.
Data
3-wire or 4-wire system
2-wire system
Output current IA
0 20 mA, 4 20 mA
4 20 mA
Power supply UV1)
24 V DC (18 32 V)
24 V DC (18 32 V)
Max. current consumption
LED off = 26 mA, LED on = 27 mA
20 mA
Max. load RB
600
(UV 12 V)/20 mA
Impact of power supply
0.1 %
Load inuence
0.1 %
Temperature impact
< 0.1 /K
60 C to +80 C2)/+90 C2)
Ambient temperature
Notes on table
1) Power supply
Power supply possible via: AC, AM controls or external power supply
2) Ambient temperature
Depending on temperature range of the actuator: Refer to name plate
Wiring
3-wire system
2-wire system
EWG 01.1
EWG 01.1
EWG 01.1
4-wire system
Plug/socket connector XK
for customer connection
Plug/socket connector XK
for customer connection
20 21 22 23 24
21 22 23 24
2 3
Plug/socket connector XK
for customer connection
20 21 22 23 24
0 20 mA
4 20 mA
+24 V 0 V
4 20 mA
+24 V 0 V
0 20 mA
4 20 mA
LED
S1 (0/4 mA)
S2 (20 mA)
Measuring point 1 (+)
2-wire system
Measuring point 2 () 0/4 20 mA
3-wire and 4-wire system
Setting:
Setting is performed via push buttons S1 (0/4 mA) and S2 (20 mA). Refer to operation instructions relating to actuator.
Inverse operation: Observe inversed assignment of push buttons S1 and S2 during setting.
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.
Y004.388/001/en
Issue 1.15
Page 1/3
EWG 01.1, RWG 4020, potentiometer
Technical data Electronic position transmitters/potentiometer
RWG 4020
On the basis of the actual potentiometer value, the RWG generates a current signal for signalling the valve position.
Data
3-wire or 4-wire system
2-wire system
Output current IA
0 20 mA, 4 20 mA
4 20 mA
24 V DC (18 32 V)
14 V DC + (I x RB), max. 30 V
1)
Power supply UV
Max. current consumption
24 mA at 20 mA output current
20 mA
Max. load RB
600
(UV 14 V)/20 mA
Impact of power supply
0.1 %/V
0.1 %/V
Load inuence
0.1 %/(0 600 )
0.1 %/100
Temperature impact
< 0.3 /K
60 C to +80 C2)/+90 C2)
Ambient temperature
Transmitter potentiometer
5 k
Notes on table
1) Power supply
Power supply possible via: AC, AM controls or external power supply
2) Ambient temperature
Depending on temperature range of the actuator: Refer to name plate
Wiring
2-wire system
3-wire system
4-wire system
RWG 4020
RWG 4020
RWG 4020
Plug/socket connector XK
for customer connection
Plug/socket connector XK
for customer connection
20 21 22 23 24
21 22 23 24
0 20 mA
4 20 mA
+24 V 0 V
4 20 mA
Plug/socket connector XK
for customer connection
20 21 22 23 24
+24 V 0 V
(20 mA)
(0/4 mA)
N
3-wire and 4-wire system
0 20 mA
4 20 mA
R2
Measuring point 1 (+)
Measuring point 2 () 0/4 20 mA
2-wire system
Setting:
Refer to the operation instructions relating to actuator.
Inverse operation: For inverse operation, exchange terminals 7 (red/RD) and 5 (black/BK) on position transmitter board.
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.
Y004.388/001/en
Issue 1.15
Page 2/3
EWG 01.1, RWG 4020, potentiometer
Technical data Electronic position transmitters/potentiometer
Potentiometer
Travel sensor for recording the valve position.
Data
Precision wire
potentiometer
Precision lm
potentiometer
Precision wire
potentiometer
in tandem version
Precision lm
potentiometer
in tandem version
Recommended for
OPEN-CLOSE duty
Modulating duty
OPEN-CLOSE duty
Modulating duty
Independent linearity
1%
Resistance (standard)
0.2 k
5 k
0.2/0.2 k
1 k/5 k
Resistance (option)3)
0.1 k
0.5 k
1.0 k
2.0 k
5.0 k
1 k
0.5/0.5 k
1.0/1.0 k
0.1/5.0 k
0.2/5.0 k
1.0/5.0 k
5.0/5.0 k
1 k/1 k
5 k/5 k
Resistance tolerance
+/ 5 %
+/ 10 %
+/ 5 %
+/ 10 %
Rated power
1.5 W
0.5 W
1.5 W
0.5 W
Max. wiper current
30 mA
0.1 mA
30 mA
0.1 mA
Lifetime
100,000 cycles
5106 cycles
100,000 cycles
5106 cycles
+/ 1.5 %
+/ 2.0 %
60 to +120 C
60 to +90 C
60 to +120 C
60 to +90 C
Synchronous operation
2)
Ambient temperature
Notes on table
2) Ambient temperature
Depending on temperature range of the actuator: Refer to name plate
3) Resistance (option)
Further options on request
The position of the valve can be transmitted as a continuous signal by a potentiometer. The potentiometer is installed in the control unit of the actuator.
We recommend:
Using the potentiometer as voltage divider. Depending on the supply voltage, suitable series resistors are to be provided. Please observe max. rated
power.
For the tandem version, two signals can be evaluated by two potentiometers, e,g, one signal for external controls or one signal for AUMA AC integral
controls.
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.
Y004.388/001/en
Issue 1.15
Page 3/3