24VDC,Can,12I,6relay,display
Partno.
Articleno.
EC4P-221-MRXD1
106393
Expandable: Inputs/outputs and bus systemsIndividual laser inscription possible with EC4-COMBINATION-* #107600
Program
Expandable: Inputs/outputs and bus systems
individual laser inscription possible with EC4-COMBINATION-*
Description
easyNet/CANopen on board
Inputs
Digital
12
of which can be used as analog
Outputs
Relay 10 A (UL)
Additional features
Display & keypad
Supply voltage
Approbationen
Product Standards
IEC: see Technical Data; UL508; CSA-C22.2 No. 0-M; CSA-C22.2 No. 142-M; CE
marking
E135462
NRAQ
012528
2252-01
UL listed, CSA certified
No
No
IEC: IP20, UL/CSA Type: -
UL File No.
UL CCN
CSA File No.
CSA Class No.
NA Certification
Specially designed for NA
Current Limiting CB
Degree of Protection
General
24 V DC
Standards
EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27
Dimensions (W x H x D)
mm
107.5 x 90 x 72 without/79 with adapter for MCC (6 SU)
Weight
kg
0.3
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using 3 fixing brackets
ZB4-101-GF1 (accessories)
Solid
mm
Flexible with ferrule
Standard screwdriver
Max. tightening torque
Terminalcapacities
0.2/4 (AWG 22 - 12)
mm
0.2/2.5 (AWG 22 - 12)
mm
3.5 x 0.8
Nm
0.6
Operating ambient temperature
-25 55, low temperatures to IEC 60068-2-1, high temperatures to IEC
60068-2-2
Condensation
Take appropriate measures to prevent condensation
LCD display (clearly legible)
0 - 55
Storage
-40 - +70
Relative humidity, non-condensing (IEC/EN 60068-2-30)
5 - 95
Air pressure (operation)
hPa
795 - 1080
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations (IEC/EN 60068-2-6)
Hz
Constant amplitude 0.15 mm
Hz
10 - 57
Constant acceleration 2 g
Hz
57 - 150
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15
g/11 ms
Impacts 18
Drop to IEC/EN 60068-2-31
Drop
height
mm
50
Free fall, packaged (IEC/EN 60068-2-32)
Mounting position
Vertical or horizontal
Climaticenvironmentalconditions
Ambientconditions,mechanical
11/22/2011
HPL-ED2011 V2.0 EN (UX111)
1/6
Electromagneticcompatibility(EMC)
Overvoltage category/pollution degree
II/2
Electrostatic discharge (ESD)
applied standard
IEC EN 61000-4-2, Level 3
Air discharge
kV
Contact discharge
kV
Electromagnetic fields (RFI), to IEC EN 61000-4-2
V/m
10
Radio interference suppression
EN 55011 Class B, EN 55022 Class B
Burst
applied standard
IEC/EN 61000-4-4, level 3
Supply cables
kV
Signal lines
kV
power pulses (Surge)
2 kV (supply cables, symmetrical, EASY...AC)
0.5 kV (supply cables, symmetrical, easy-DC)
according to IEC/EN 61000-4-5
Radiated RFI (IEC/EN 61000-4-6)
10
Clearance in air and creepage distances
EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
EN 50178
Back-up of real-time clock
Insulationresistance
Back-upofreal-timeclock
Backup time (hours)
Service life (years)
Accuracy of the real-time clock
s/
day
Rated operational voltage
Ue
24 DC (-15/+20%)
Permissible range
20.4 - 28.8 V DC
Residual ripple
Input current
normally 140 mA at rated operating voltage
Voltage dips
ms
10
(IEC/EN 61131-2)
Heat dissipation
Normally 3.4W
Processor
Infineon XC161
Memory
Retentivememory
Write cycles of the retentive memory
Powersupply
CPU
part no. 5 ( 0.5 hYear)
10000000000 (10 ) (Read-write cycles)
Program code/data
kByte
256/14 segments of 16 KB each
Marker/retentive data
KByte
16/4/4/8
Cycle time for 1 k of instructions (Bit, Byte)
ms
<0.3
Data transfer rate
kBit/
s
4.8, 9.6, 19.2, 38.4, 57.6, 115.2 (character format: 8 bit data, no parity, 1
stop bit)
Connection types
RJ45-bus
Potential isolation
none
Master mode
Interfaces
PRG interface (RS232C/RS485)
Data transfer rate
kbit/
s
0.3, 0.6, 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6
Character formats
8E1, 8O1, 8N1, 8N2, 7E2, 7O2, 7N2, 7E1
Quantity of modules
190 bytes
Number of modules
190 bytes
500 kBit/s, 25 m250 kBit/s, 60m125 kBit/s, 125 m50 kBit/s, 300 m20 kBit/s,
700 m10 kBit/s, 1000 m
CANopen/easyNet
Data transfer rate
11/22/2011
HPL-ED2011 V2.0 EN (UX111)
2/6
Potential isolation
From power supply
Yes
Potential isolation
Yes
Potential isolation
Yes
Bus termination (first and last station)
EASY-NT-R plug (incl. bus terminating resistor 120 )
Connection types
2 x RJ45, 8 pole
Master mode
Number
Mode slave
Stations
Number max. 126
PDO type
Asynchronous, cyclic, acyclic
Control contact rated current
to DS301V4
Number
12
Inputs can be used as analog inputs
4 (I7, I8, I11, I12)
Status Display
LCD-Display (falls vorhanden)
Potential isolation
from the outputs
to network easyNet, easyLink
Rated operational voltage
Ue
V
DC
24
Rated operating voltage L (sinusoidal)
Ue
V
DC
< 5 (I1 - I6, I9 - I10) < 8 (I7, I8, I11, I12) at signal "0"
> 15.0 (I1 - I6, I9, I10) > 8.0 (I7, I8, I11, I12) at signal "1"
Input current on 1 signal
At 24 V DC
mA
3.3 (I1 to I6)
2.2 (I7, I8)
3.3 (I9, I10)
2.2 (I11, I12)
Deceleration time
ms
normally 0.02 (I1 - I4), normally 0.25 (I5 - I12) (from ''0'' to "1")
normally 0.02 (I1 - I4), normally 0.25 (I5 - I12) (from ''0'' to "1")
Cable length
100 (unshielded)
Incremental counter
Digitalinputs24VDC
Number of counter inputs
1 (I1, I2, I3, I4)
Value range
32 Bit
Counter frequency
kHz
Pulse shape
Square
Counter inputs
I1, I2
Reference input
I3
Input for reference switch
I4
Counter inputs I1 and I2, I3 and I4
Signal offset
90
Rapid counter inputs
Number
2 (I1, I2) at 16 Bit or 1 (I1) at 32 Bit
Value range
16/32 Bit
Cable length, screened
< 20
Counter frequency
kHz
< 50
Pulse shape
Square
Number
4 (I7, I8, I11, I12)
Potential isolation
from the outputs
to PC interface, memory card, easyNet, easyLink
Input type
DC voltage
Signal range
0-10 V DC
Resolution
0.01 V analog
0.01 V digital
10 Bit (value 0 - 1023)
Input impedance
11.2
Accuracy of actual value
Two EASY devices
Within a single device
2, (I7, I8, I11, I12) 0.12 V
Analoginputs
11/22/2011
HPL-ED2011 V2.0 EN (UX111)
40
3/6
Conversion time, analog/digital
ms
each CPU cycle
Input current
mA
<1
Cable length
< 30, screened
Outputs in groups of
Parallel switching of outputs for increased output
Not permissible
Protection of an output relay
Miniature circuit-breaker B16 or fuse 8 A (slow)
Potential isolation
from power supply
from the inputs
in groups
300 V AC safe isolation according to EN 50178
600 V AC basic isolation
Lifespan, mechanical
Operations
Contacts
Conventional thermal current (10 A UL)
Recommended for load: 12 V AC/DC
mA
> 500
Short-circuit-proof cos = 1, characteristic B16 at 600 A
16
Short-circuit-proof cos = 0.5 to 0.7, characteristic B16 at 900 A
16
Rated impulse withstand voltage Uimp of contact coil
kV
Rated operational voltage
Ue
V
AC
250
Rated insulation voltage
Ui
V
AC
250
Safe isolation according to EN 50178
V
AC
300 between coil and contact
300 between two contacts
Making capacity
Operations
300000
Operations
200000
Operations
300000
Operations
200000
1000 W at 230/240 V AC
Operations
25000
500 W at 115/120 V AC
Operations
25000
Relayoutputs
AC-15, 250 V AC, 3 A (600 ops./h)
DC-13, L/R
150 ms, 24 V DC, 1 A (500 S/h)
Breaking capacity
AC-15, 250 V AC, 3 A (600 Ops./h)
DC-13, L/R
150 ms, 24 V DC, 1 A (500 S/h)
Filament bulb load
Fluorescent lamp load
Fluorescent lamp load 10 x 58 W at 230/240 V AC
10
10
With upstream electrical device
Operations
25000
Uncompensated
Operations
25000
Operations
25000
Mechanical operations
Switching frequency
Hz
10
Resistive load/lamp load
Hz
Inductive load
Hz
0.5
Uninterrupted current at 240 V AC
10
Uninterrupted current at 24 V DC
AC
Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional,
compensated
Switching frequency
UL/CSA
10
10
Control Circuit Rating Codes (utilization category)
B 300 Light Pilot Duty
Max. rated operational voltage
V
AC
300
Max. thermal uninterrupted current cos = 1 at B 300
Max. make/break capacity cos 1 at B 300
VA
3600/360
R 300 Light Pilot Duty
DC
Control Circuit Rating Codes (utilization category)
11/22/2011
HPL-ED2011 V2.0 EN (UX111)
4/6
Max. rated operational voltage
V
DC
300
Max. thermal uninterrupted current at R 300
Max. make/break capacity at R 300
VA
28/28
Voltage type of supply voltage
DC
Expandable
YES
With display
YES
Number of HW-interfaces RS232
Number of HW-interfaces serial TTY
Max. number of integrated digital inputs
12
Supporting protocol for LON
No
With time switch
No
Max. number of integrated analog outputs
Number of HW-interfaces RS485
Max. number of integrated digital outputs
Protection type (IP)
IP20
Number of Industrial Ethernet HW interfaces
Number of HW-interfaces RS422
Switching current
Max. number of integrated analog inputs
With relay output
YES
Number of HW-interfaces other
TechnicaldataaccordingtoETIM4.0
Dimensions
Additionalproductinformation(links)
IL05003003Z (AWA2724-2334) easyControl: Compact controller
ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL05003003Z2010_11.pdf
IL05013018Z (AWA2528-2175) Power supply unit, Communication module
ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL05013018Z2010_11.pdf
AWB2724-1587 Programmable logic controller easy Control EC4-200 English
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/h1584g.pdf
AWB2724-1587 Programmable logic controller easy Control EC4-200 franais
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/h1584f.pdf
AWB2724-1587 Programmable logic controller easy Control EC4-200 Deutsch
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/h1584d.pdf
11/22/2011
HPL-ED2011 V2.0 EN (UX111)
5/6
AWB2724-1584 Programmable logic controller easy Control EC4-200 English
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/h1584g.pdf
AWB2724-1584 Programmable logic controller easy Control EC4-200 franais
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/h1584f.pdf
AWB2724-1584 Programmable logic controller easy Control EC4-200 Deutsch
ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/h1584d.pdf
Approvals and certificates
https://wss.moeller.net/approbationen/?lang=en
From the Control Relay to the Automation System
http://www.moeller.net/binary/ver_techpapers/ms13en_easycontrol.pdf
Labeleditor
ftp://ftp.moeller.net/MFD/EASY-SOFT-PRO/labeleditor_206.exe
11/22/2011
Eaton Industries GmbH
http://www.moeller.net/en
07/2011 by Eaton Industries GmbH
HPL-ED2011 V2.0 EN
6/6