PLC Connection Guide
Siemens S7-300 MPI
Supported Series: Siemens S7-300 series PLC
Website: http://www.siemens.com/entry/cc/en/
HMI Setting:
Parameters
Recommended
Options
PLC type
SIEMENS S7-300 MPI
PLC I/F
RS-485 2W
Notes
Only HMI with a sticker MPI 187.5K on
Baud rate
187.5K
the rear cover supports MPI
communication.
Data bits
Parity
Even
Stop bits
PLC sta. no.
Online simulator
2 ~ 31
NO
Extend address mode Yes (X Series does not support)
Broadcast command NO
Device Address:
Bit/Word
Device type
Format
Range
Memo
DDDDo
0 ~ 40957
Input (I)
DDDDo
0 ~ 40957
Output (O)
DDDDo
0 ~ 40957
Bit Memory
DBnBit
DB0Bit ~
FFFFDDDDo
0 ~ 409699997
Data Register Bit
DDDDDo
0 ~ 655327
Data Register Bit
DB99Bit
IW
DDDD
0 ~ 4095
Input (I)
QW
DDDD
0 ~ 4095
Output (O)
MW
DDDD
0 ~ 4095
Bit Memory
DW
MD
DDDD
0 ~ 4094
Byte
MB
DDDD
0 ~ 4095
Bit Memory Byte
Byte
DBBn
FFFFDDDD
0 ~ 40969999
Data Register
DBn
FFFFDDDD
0 ~ 40969999
Data Register (must be even)
PLC Connection Guide
Bit/Word
Device type
Format
Range
DW
DBDn
FFFFDDDD
0 ~ 40969999
DBn_String
FFFFDDDD
0 ~ 40969999
DW
DBDn_String FFFFDDDD
0 ~ 40969999
DB0 ~ DB99
0 ~ 65532
DDDDD
Memo
Data Register Double Word
(multiple of 4)
Data Register (must be even)
Double word and floating point value must use DBDn device type.
Multi-HMIs-Multi-PLCs Communication Setting:
For SIEMENS S7-300 MPI driver in Multi-HMIs-Multi-PLCs communication, [Max. station
no. (MPI network)] parameter must be correctly set. This setting is relevant to the station
no. of the devices, as shown, two HMI (station no. 0, 1) and two PLC (station no. 2, 3) are
in MPI network, Max. Station No. should be set to 3.
PLC Connection Guide
For the effectiveness of communication, users may set PLC device in STEP 7 as shown
below. In Properties MPI / Network Settings, set Highest MPI address to the number
closest to the actual device station number.
HMI sta. no. can not be the same as PLC sta. no.
Highly recommended that the device station numbers start from 0 sequentially and
correctly set [Max. station no. (MPI network)].
Available for EasyBuilder V4.50 and later.
X Series does not support multiple-HMI-to-multiple-PLC communication, and supports
only 1-HMI-to-1-PLC communication.
How to Import Tag:
SIEMENS STEP 7 program allows building files of user-defined tag (*.dif file and *.AWL
file), and import these files in EasyBuilder8000/EasyBuilderPro -> System Parameter
Settings. The following describes how to build and import these two types of files.
PLC Connection Guide
1. Building *.dif File
a In Symbols create user-defined tag.
b Click Export to export the edited file and click Save.
PLC Connection Guide
2. Building *.AWF File
a In Blocks create items as shown below:
b Open LAD/STL, FBD Programming S7 Blocks, click File -> Generate
Source.
c Select Sources as storage path, specify the file name then click OK.
PLC Connection Guide
d Select the objects to be exported then click OK.
e Under Sources there will be names of the saved files, select Export
Source to build *.AWL file.
PLC Connection Guide
The generated *.dif and *.AWL files can be imported in EasyBuilder8000/EasyBuilderPro
System Parameter Settings, by clicking Import Tag.
Tag information successfully imported.
Pass-Through Settings:
[Designate client IP]: In Pass-through mode designate the client IP address to connect
HMI. The client usually refers to Siemens Step 7 application.
PLC Connection Guide
The following lists the system registers relevant to Siemens S7-200 PPI and
Siemens S7-300 MPI Pass-through feature.
[LW-10850: disable/enable (0 : disable, 1 : normal, 2 : IP limited) (siemens
pass-through)]
[LW-10851: destination COM port (siemens pass-through)]: Generally refers to the
COM port connected with PLC.
[LW-10852: destination PLC station no. (siemens pass-through)]
[LW-10853: communication protocol (0 : invalid, 1 : PPI, 2 : MPI) (siemens
pass-through)]
[LW-10854 to LW-10857: IP of connecting client (siemens pass-through)]: Displays
current client IP address connected with HMI.
[LW-10858 to LW-10861: IP of designated client (siemens pass-through)]: If
LW-10850 is set to 1, the system registers can be used to designate the client IP
connected with HMI.
[LW-10862: connection status (0 : ready, 1 : client connecting) (siemens
pass-through)]
[LW-10863: execution status (0 : normal, 1 : error) (siemens pass-through)]
[LW-10864: the last error (siemens pass-through)]
The following table lists the error codes, the description of each code, and the
possible reason.
Error Code
Description
Possible Reason
Successfully executed
HMI is already running pass-through
Prohibit client from connecting
and wont accept any request from
HMI
other client.
When LW-10850 is set to 1, the
Prohibit client from connecting client IP for connecting HMI is
HMI
different from the IP specified in
LW-10858 ~ LW-10861.
Invalid communication
protocol
Invalid setting in LW-10853.
Invalid PLC station number
The PLC station number specified in
LW-10852 does not exist.
Delayed communication
PLC connection failure.
Busy communication
PLC does not accept pass-through
request, please confirm PLC
settings.
Invalid pass-through request
Environment setup failure.
PLC Connection Guide
Wiring Diagram:
The following is the view from the soldering point of a cable.
S7-200 PPI , S7-300 MPI :RS485 2W
eMT3000 series
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM2 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
7 RX-
4 Data-
8 D-
6 RX+
1 Data+
3 D+
5 GND
5 GND
5 GND
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
9 GND
5 GND
cMT/mTV series
MT8000iE series
PLC Connection Guide
MT6000/8000 series except MT6050i/MT8050i
COM1 RS485 2W
9P D-Sub Male
COM3 RS485 2W
9P D-Sub Male
RS485 2W 9P D-Sub
Male
1 RX-
6 Data-
8 D-
2 RX+
9 Data+
3 D+
5 GND
5 GND
5 GND
COM1 RS485 2W
9P D-Sub Female
COM3 RS485 2W
9P D-Sub Female
RS485 2W 9P D-Sub
Male
1 RX-
7 Data-
8 D-
2 RX+
8 Data+
3 D+
5 GND
5 GND
5 GND
MT6050i/MT8050i
Driver Version:
Version
Date
Description
V1.90
May/26/2011
Added registers: MB & DBBn
V2.00
Aug/19d/2011
i Series HMI support Multi HMIs-Multi PLCs
communication.