Product Specification
03301 (Rev. A)
EGCP-3 MC
Multi-unit Mains Controller
Generator System Control Package
DESCRIPTION
The EGCP-3 MC is a powerful
microprocessor-based system control
and management package designed
for the most demanding power
generation applications.
Complete system
control package
Automatic loaddemand
sequencing of
multiple units
The EGCP-3 MC combines power
system, switchgear, bus and utility
monitoring, protection, and control
functions in a single, compact, and
cost-effective package.
Synchronization of
two breakers/
contactors
Perfect for medium and large-sized
generating systems, the EGCP-3 MC
is designed for use in ATS, peaking, or
utility paralleled systems.
The MC is a supervisory control system that works with EGCP-3 LS units to provide
total system control, including multiple utility tie applications.
APPLICATIONS
Real kW Load Control
True RMS power calculations
Configurable load/unload ramp rates
Load control of up to 15 EGCP-3 LS
units using percentage based load
sharing
Utility Import/Export KW control
Process control
Externally adjustable load or process
references (using Analog Inputs or
Modbus)
Reactive kVAR Control
Configurable load/unload ramp rates
PF or VAR control using percentage
based load sharing
Utility Import/Export VAR or PF
control
Externally adjustable VAR or PF
references (using Analog Inputs or
Modbus)
Manual voltage control capability
Automatic Transfer Switch (ATS)
Open or Closed transition
Configurable fast transfer time, LOM
action delay, utility and bus stable
delay
Zero power transfer across breaker
during closed transition
Emergency Power Supply (EPS)
supplying load alarm and discrete
output
LOM alarms and discrete output
Load shed on overload
Peaking Control
Automatic start/stop based on time of
day or demand level
Four time-of-day programs with two
starts and durations per program
Parallel to utility or perform
open/closed transition for time-of-day
starts
Configurable time delayed start/stop
and immediate start for demand
levels
Configurable time delay
Automatic demand monitoring of
multiple mains inputs
Comprehensive
system
protectionbus
and utility
Revenue-grade
power and energy
metering
Digital display of
bus, utility, and
system data
Real kW and
reactive kVAR
control
Advanced network
communications
with Echelon and
Modbus networks
Built-in system
diagnostics
Synchronizing
Bus Protective Features
Phase match or slip frequency synchronization
with voltage matching
Full three-phase sensing on both buses
Adjustable phase window, voltage window,
re-close attempts, re-close timing
Dead bus closing logic internal to the control
Synch check (25)
Breakers or contactors
Over/Under Voltage (59, 27)
Over/Under Frequency (81O, 81U)
Directional (Forward/Reverse) Power (32) *
Negative Sequence Phase Overcurrent (46)
Negative Sequence Phase Overvoltage (47)
Phase Overcurrent (51) *
Voltage Restrained Phase Overcurrent (51V)*
Directional VAR
Phase Current Imbalance (46) *
Communications
Utility Protective Features
Diagnostic Features
*Inverse Time Protections implemented are according to
IEEE C37.112 Very Inverse curves
*Modbus is a trademark of Modicon, Inc.
**Echelon is a trademark of Echelon Corporation
G1_52
4 Analog Inputs
4 Analog Outputs
All Configurable (*)
LOAD 1
LOAD 2
12 Relays Total
9 Configurable (**)
LOAD 3
16 Digital Inputs Total
12 Configurable (^^)
G2_52
Group52
U52
G3_52
Analog Output 4
EGCP-3 MC Interactions
Horn
Mains CTs
Mains PTs
Stop All Engines
**
EPS Supplying
Load **
DI Wetting Voltage
Meter Phase B ^^
Loss of Mains **
3-Phase or
1-Phase Sensing
Meter Phase A ^^
Audible Alarm
Enable Process ^^
Light
Load Ramp Pause ^^
Visual Alarm **
Load 3
Trip Coil
Load Lower ^^
Load Raise ^^
Load Shed 3 **
Load 2
Trip Coil
Load 1
Trip Coil
Load Shed 1 **
Voltage Raise ^^
Remote Alarm 2 ^^
Mains Breaker
Trip
Utility
Trip Coil
Utility
Close Coil
Remote Alarm 1 ^^
Mains Breaker
Close
Group
Trip Coil
Mains Breaker
Aux (52)
Battery -
Battery +
Group Breaker
Close **
Group Breaker
Aux (52) ^^
Analog Output 1
Analog Output 2
Analog Output 3
Run w/ Load
Analog Alarm *
Synchroscope *
Utility KW *
System Load *
Bus Frequency *
Analog Input 1
Analog Input 2
Analog Input 3
Analog Input 4
Test
Process Input *
Process Reference *
PF Reference *
Echelon Network
(LON) Communications
Auto
To Other
EGCP-3's
Bus PTs
3-Phase or
1-Phase Sensing
Group Breaker
Trip **
Group
Close Coil
-+
Reset Alarm ^^
Breaker/Contactor synchronization timeout and
re-close alarms
Breaker/Contactor feedback and shunt trip alarms
Phase Rotation Mismatch
Network communication error alarms
Analog input out-of-range alarms
Configuration check
Bus CTs
Over/Under Voltage (59, 27)
Over/Under Frequency (81O, 81U)
Directional (Import/Export) Power (32) *
Negative Sequence Phase Overcurrent (46)
Negative Sequence Phase Overvoltage (47)
Phase Overcurrent (51) *
Voltage Restrained Phase Overcurrent (51V) *
Directional VAR
Phase Current Imbalance (46) *
Loss of Mains/Loss of Mains with Alarm
Load Surge (islanding protection)
Load Shed 2 **
Modbus * RTU via RS-232/-422/-485 serial ports
ServLink, Watch Window via RS-232/-422/-485
serial ports
Echelon ** TP/XF-1250 network (LON)
Voltage Lower ^^
COM Port 1
Servlink or Modbus
(RS-232,485,422)
COM Port 2
Modbus
(RS-232,485,422)
COM Port 3
Servlink
(RS-232)
HARDWARE SPECIFICATIONS
Size:
Operator Interface Panel:
Power Supply Voltage:
Control Part Numbers:
282 mm (11.1) high x 358 mm (14.1) wide x 134 mm (5.275) deep
8 (20 character) lines plus membrane keypad
24 Vdc system (1832 Vdc nominal; 940 Vdc maximum)
MC: 8406-114
Installation Manual: 26122
Operation Manual: 26195
Terminal blocks are screwless CageClamp-style blocks. PT and CT
inputs are fixed screw terminals.
70300 Vac
5 Aac RMS nominal, 7 Aac RMS maximum
20 to +70 C (4 to +158 F) operating
30 to +80 C (22 to +176 F) storage
95% at 60 C non-condensing
Type 4 (NEMA) requirements from the front panel and properly installed
in an equivalent enclosure
Suitable for engine skid or control cabinet
Random Test: 102000 Hz at 0.04 G/Hz and 8.2 Grms PSD
30 G peak, 11 ms duration, non-operating
Class I, Division 2, Groups A, B, C, D for North America
Zone 2, Group IIC for Europe
Declared to the EMC; Low-Voltage, and ATEX Directives
Type Approval by ABS, DNV, and LR for marine applications
Connectors:
Voltage Measuring Input Range:
Current Measuring Inputs:
Temperature Range:
Humidity:
Enclosure Rating:
Vibration:
Mechanical Shock:
Regulatory Compliance:
CAUTION
WARNING
FIELD CONFIGURABLE GOVERNOR
WOODWARD
TM
TM
PART NO.
SERIAL NO.
REV.
CAGE 31661
MANUFACTURED IN FORT COLLINS CO U.S.A. 9606
281.94
(11.100)
EGCP-3 CONTROL
260.35
(10.250)
INSTALLATION CATEGORY III
MAXIMUM AMBIENT 70 C
10-29 VDC, 20W MAXIMUM
130.18
(5.125)
DANGER
10.8
(0.425)
10.8
(0.425)
168.28
(6.625)
336.55
(13.250)
358.14
(14.100)
15.88
(0.625)
118.14
(4.651)
336.55
(13.250)
25.65
(0.250)
TYP 8 PLACES
168.28
(6.625)
260.35
(10.250)
241.3
(9.500)
130.18
(5.125)
7.14
(0.280)
322.28
(12.688)
9.53
(0.375)
EGCP-3 Outline Drawing and Panel Layout Template
(Do not use for construction)
EGCP-3 MC Applications/Configurations
Multiple UnitUtility Parallel
PO Box 1519
Fort Collins CO, USA
80522-1519
1000 East Drake Road
Fort Collins CO 80525
Tel.: +1 (970) 482-5811
Fax: +1 (970) 498-3058
Unit 16
EGCP-3
MC
Load
Breakers
Bus A
Distributors & Service
Woodward has an
international network of
distributors and service
facilities. For your nearest
representative, call the
Fort Collins plant or see
the Worldwide Directory
on our website.
Unit 2
EGCP-3
LS
GS
Load
Unit 1
EGCP-3
LS
GS
Multiple UnitATS
Load
Breakers
Unit 16
EGCP-3
MC
www.woodward.com
Bus A
Group
Breaker
Unit 2
EGCP-3
LS
Load
Unit 1
EGCP-3
LS
GS
GS
Multiple UnitMultiple Unit Parallel
Synchronizer
Unit 16
EGCP-3
MC
Unit 15
EGCP-3
MC
SPM-D
Tie W
Load
Breakers
Load
Breakers
Bus A
Bus B
Load
Unit 2
EGCP-3
LS
Unit 1
EGCP-3
LS
GS
Load
Unit 3
EGCP-3
LS
GS
Unit 4
EGCP-3
LS
GS
GS
Other Configurations
Single UtilityMultiple Bus
Multiple UtilitySingle/Multiple Bus
For a complete set of EGCP-3 Installation/Operation manuals or Application Notes on the
above configurations, download from the Woodward website at:
www.woodward.com/publications
This document is distributed
for informational purposes
only. It is not to be construed
as creating or becoming part
of any Woodward Governor
Company contractual or
warranty obligation unless
expressly stated in a written
sales contract.
Woodward 2002
All Rights Reserved
2007/1/Fort Collins