Thermodynamics of Refrigerant Mixtures and Refrigerant-Oil Mixtures
Thermodynamics of Refrigerant Mixtures and Refrigerant-Oil Mixtures
Chapter 15
Thermodynamics of Refrigerant Mixtures
and Refrigerant-Oil Mixtures
SUMMARY: The principles of phase equilibrium of zeotropic mixtures are presented in an abbreviated
form, including the phase diagram and preparation of enthalpy profiles for describing their evaporation
(or condensation) over a temperature glide. Next the thermodynamic description of refrigerant-oil
mixtures is presented, including methods to predict the local oil mass fraction, the local bubble point
temperature rise caused by the oil, enthalpy changes for their evaporation (or condensation) and the effect
of oil on log mean temperature differences. This chapter focuses on the thermodynamics of mixtures
during their evaporation but these methods are equally applicable to condensation.
15.1 Introduction
A basic working knowledge of phase equilibria is required to understand the evaporation (and
condensation) of zeotropic mixtures and also is an important prerequisite for the design of evaporators
that properly take into account the effect of oil on thermal performance. The objective of this chapter is
to provide this necessary background. Topics covered include the phase equilibrium diagram, the dew
point temperature, the bubble point temperature, the boiling range or temperature glide, the phase
equilibria of refrigerant-oil mixtures, enthalpy curves for mixtures and a few other concepts important to
the subject. For a more detailed introduction to phase equilibria, the reader is referred to Chapter 12 in
Collier and Thome (1994, 1996). Instead, for a comprehensive treatment of prediction of phase equilibria,
numerous chemical engineering textbooks are available, such as that by Prausnitz (1969), or can be found
in the chapter by Smith, Block and Hickman (1963) appearing in the Chemical Engineer's Handbook
(available in more recent editions).
A zeotropic mixture refers to a mixture whose components have different mass fractions in the liquid
phase than in the vapor phase at equilibrium conditions. An example of such a mixture is R-407C, which
has three components. In contrast, an azeotropic mixture refers to a mixture whose components have the
same compositions in both phases. A well-known example is refrigerant R-502, which is a binary
refrigerant mixture at the azeotropic composition of its two components. An azeotropic fluid functions
just like a pure fluid and hence pure fluid design methods can be applied. Instead, a zeotropic mixture
evaporates (or condenses) over a temperature range and hence this must be taken into account in thermal
design methods.
A refrigerant-oil mixture functions as an azeotropic mixture in which the refrigerant (either a pure
refrigerant such as R-134a or a zeotropic mixture such as R-407C) is combined with a miscible,
lubricating oil. The oil for our purposes here can be considered to be one component in such a mixture,
even though normally lubricating oil is a multi-component mixture including various additives, longchain molecules, etc. In this chapter, only refrigerant-oil mixtures that are completely miscible will be
considered. These mixtures act as zeotropic mixtures and the refrigerant and oil are miscible in the liquid
phase. Some refrigerant-oil mixtures are not miscible, which means they do not mix together in
equilibrium conditions, such as is also true for water and oil. Immiscible refrigerant-oil mixtures are not
addressed here. One must be careful, however, as some refrigerant-oil mixtures are miscible only within a
certain range of temperature or up to a certain oil mass fraction, so that part of the refrigerant cycle or test
facility fluid loop may pass outside the miscible range.
15-1
15-2
Referring again to the phase diagram in Figure 15.1, the more volatile component (also referred to as the
lighter component) is defined as the fluid that has the lower boiling point temperature at the pressure of
the diagram. This is the fluid with its saturation temperature on the right vertical axis in Figure 15.1. This
fluid is more volatile in the sense that this component is always above its normal boiling point. For a
refrigerant-oil mixture, the refrigerant will always be the more volatile component since the boiling point
temperatures of lubricating oils are in the range from 300 C to 510 C (570-950F), and are thus much
larger than those of refrigerants. Hence, the oil will be the less volatile component (also referred to as the
heavier component).
For the present situation, a refrigerant-oil mixture can be considered as a zeotropic binary mixture, which
is a mixture with two components that does not form an azeotrope. One component is the pure
refrigerant, be it R-134a, R-22, or any other single-component refrigerant (R-123, R-125, ammonia, etc.)
and the second component is the oil. Even though lubricating oils are multi-component blends of oil plus
additives, for the present purposes it is more than adequate to consider them here as a single component
fluid.
Figure 15.2. Phase equilibrium diagram for a binary mixture of R-134a and oil at a
pressure of 3.43 bar (49.7 psia).
Figure 15.2 depicts an approximate phase diagram for R-134a mixed with Mobil Arctic EAL 68
lubricating oil at 3.43 bar (49.7 psia). In this case, the horizontal axis shows the oil composition in mass
%. At the left axis of the diagram, the saturation temperature of pure R-134a is 4.44C (40F). Near the
right axis, the dew and bubble point temperatures rise rapidly towards the saturation temperature of the
pure oil (not shown), which is in the neighborhood of 350C (662F). The bubble point curve is nearly
horizontal with a slightly upward slope from left to right at low oil compositions. It then begins to rise
more rapidly at intermediate compositions and then rises rapidly when above 70 mass % oil. The actual
location of the dew point curve is not known for refrigerant-oil mixtures; it was drawn assuming
negligible amounts of oil enter the vapor phase at liquid oil compositions below 70 mass %, i.e. the part
of the dew point line on the left y-axis at 0.0 mass % oil. Above this value its composition is represented
15-3
here by a simple extrapolation towards the pure oil value. The method for predicting the bubble point
curve shown here is given later in this Chapter.
Figure 15.3. Isobaric process path and enthalpy curve of a binary mixture.
To better illustrate these concepts, consider now a situation excerpted from Collier and Thome (1994,
1996). Figure 15.3 shows a piston-and-cylinder setup that contains a binary liquid mixture whose mole
fraction of the more volatile component is Xo and which is held at a fixed pressure of p and temperature
of T1. What happens to the liquid mixture as it evaporates is conveniently depicted on the temperature-
15-4
composition phase diagram at the right, where the mole fraction of the more volatile component is plotted
along the horizontal axis and the temperature of the mixture on the vertical axis. Denoting the initial
conditions in the vessel by point Q, the piston-and-cylinder is now heated under constant pressure
maintaining an isothermal temperature throughout the vessel. When the temperature T2 is reached, liquid
will begin to evaporate at point R. The vapor formed at temperature T2 has a composition Yo as shown by
point S. This vapor is richer in the more volatile component than the liquid. If this procedure is repeated
for the complete range of initial liquid compositions, then a series of points R, T and X will be found. The
locus of the curve formed by points AXTRB is known as the bubble point curve and the curve formed by
points AWVSB is the dew point curve.
If the vessel is heated above point R, the composition of the liquid will change because of the loss of
some of its more volatile component to the vapor. The boiling point temperature will rise to some new
temperature T3 and the compositions in both the liquid and vapor phases will change, both becoming
richer in the less volatile component represented by points T and V, respectively. Since no material is lost,
the relative volumes occupied by the two phases also change during this process; the volume occupied by
the liquid decreases while that of the vapor increases. On still further heating to temperature T4, all the
liquid is evaporated and the vapor in the vessel at point W has the same composition as the original liquid
Xo. The last drop of liquid in the vessel disappears at the temperature T4 with a composition of X1,
indicated by point X on the phase diagram, and is very rich in the less volatile component.
During this experiment the amount of heat added to the system could be noted. In addition, there is a clear
analogy between this isobaric evaporation process in the piston-and cylinder chamber and evaporation of
a refrigerant-oil mixture inside an evaporator tube. Similar to evaporation of the liquid mixture in the
vessel, a refrigerant-oil mixture will evaporate along its bubble point curve. However, since essentially
none of the oil enters the vapor phase because of the extremely low vapor pressure of the oil relative to
the refrigerant (on the order of one millionth that of the refrigerant), the situation is simplified. Thus, as
one moves along an evaporator tube from the inlet towards the outlet, the local oil mass percent in the
remaining liquid increases, the vapor phase composition remains pure refrigerant, and the local boiling
point temperature Tbub increases. The amount of heat necessary to evaporate the refrigerant-oil mixture is
therefore equal to the sensible heating of the liquid and vapor phases caused by the increase in the bubble
point temperature along the tube plus the latent heat for vaporizing the refrigerant from the liquid to the
vapor phase. These points will be discussed in more detail in the following sections.
15-5
perspective, it is analogous to assuming that a zeotropic refrigerant mixture, such as R-407C, may be
modeled using the vapor pressure curve of only one of its three components, say R-134a. Clearly that is
not correct thermodynamically. Thus, the "contamination" approach will not lead to a resolution of the
long-standing problem of how to model the influence of oil on flow boiling of refrigerants.
q
Tw Tbub
[15.3.1]
where q is the heat flux through the wall to the evaporating fluid, Tw is the wall temperature and Tbub is
the bubble point temperature of the fluid. Since the value of Tbub for a refrigerant-oil mixture is higher
than Tsat for the pure refrigerant, reducing raw test data in this correct manner (rather than reducing it
using Tsat as has been incorrectly but widely done in the past) results in an increase in the heat transfer
coefficient. On the other hand, use of Tbub rather than Tsat for the pure refrigerant in an incremental log
mean temperature difference (LMTD) calculation for an evaporator will decrease the value of the LMTD,
which partially compensates for the larger boiling coefficient when using Tbub in the definition of . In
any case, it should be remembered that the difference between using Tbub or Tsat typically only becomes
significant when reducing test data at vapor qualities greater than about 80%. Thome (1995) presented a
detailed discussion of the thermodynamic effects on boiling points and enthalpy caused by oil and these
are discussed below.
15-6
ln(psat ) = [A / Tbub] + B
[15.3.2]
where psat is the saturation pressure in MPa and Tbub is the bubble point temperature in K. Rearranging
[15.3.2] in order to calculate the bubble point temperature for a given saturation pressure and oil mass
fraction, it becomes:
Tbub = A /[ln(psat ) + B]
[15.3.3]
The amount of oil in the liquid-phase is given by w, i.e. in mass fraction, not mass percent. A and B are
given by the following empirical expressions:
[15.3.4]
[15.3.5]
bo = 8.0736
b1 = -0.72212
b2 = 2.3914
b3 = -13.779
b4 = 17.066
Evaluating [15.3.3] at a saturation pressure of 0.55 MPa (79.8 psia), Table 15.1 depicts the effect of oil
mass fraction on the bubble point temperature for R-22 mixed with various mass fractions of oil. The
right column shows the difference between the bubble point temperatures of the mixtures and the
saturation temperature of pure R-22 (TR-22) at this pressure.
Table 15.1. Bubble point temperatures of R22/oil mixtures at 0.55 MPa (79.8 psia).
w (mass fraction)
Tbub (C)
0.00
2.99
0.01
3.01
0.02
3.03
0.03
3.04
0.04
3.06
0.05
3.09
0.06
3.11
0.07
3.13
0.08
3.15
[] - Extrapolated value.
Tbub-TR-22 (C)
0.00
0.02
0.04
0.05
0.07
0.10
0.12
0.14
0.16
w (mass fraction)
0.09
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
Tbub (C)
3.17
3.19
3.44
3.79
4.31
5.25
7.22
11.53
[19.95]
Tbub-TR-22 (C)
0.18
0.20
0.45
0.80
1.32
2.26
4.23
8.54
[16.96]
Thome (1995) generalized the above method for application to refrigerants other than R-22 and also
temperatures outside the original experimental range. This was accomplished by replacing the original
values of ao and bo that are specifically for R-22 with new ones for the desired refrigerant, such as R-134a.
Since the vapor pressure of oil is very small compared to that of the refrigerant, it was demonstrated that
the effect of the specific type of oil on the empirical constants a1 to a4 and b1 to b4 is negligible for oil
15-7
fractions below 0.50 of oil (50% mass). Rather than using fixed values of ao and bo for a particular pure
refrigerant, an accurate equation of state for the pure refrigerant vapor pressure curve is used to determine
the values of ao and bo at the specified saturation pressure instead of the simple Antoine expression, i.e.
[15.3.2]. Using these new values of ao and bo, [15.3.2] and [15.3.3] are now accurate for predicting
saturation temperatures and bubble point temperatures over narrow temperature ranges for essentially any
miscible mixture of commonly used refrigerants and oil. Thome (1997b) [also see Zrcher, Thome and
Favrat (1998b)] has also applied this method to zeotropic refrigerant blends mixed with miscible oils (in
particular R-407C/oil mixtures) and showed that it accurately matched experimental measurements over a
wide range of oil mass fractions.
The procedure to use the expression [15.3.3] for any refrigerant is thus:
Determine the pure refrigerant saturation temperature and pressure just above and just below the
design pressure with an accurate equation-of-state of the user's choice;
Use these two sets of values for Tbub and psat to solve for ao and bo in [15.3.3] with w set to zero. The
solution is straightforward with two equations and two unknowns.
These new values of ao and bo replace those of ao = -2394.5 and bo = 8.0736 for R-22, respectively.
All the other values of a1 to a4 and b1 to b4 remain the same since they only refer to the effect of the
oil on Tbub.
Equations [15.3.3], [15.3.4] and [15.3.5] are then evaluated for the desired oil mass fraction, w, to
obtain Tbub for the desired value of psat and w; instead, psat can be obtained for specified values of Tbub
and w using [15.3.2], [15.3.4] and [15.3.5].
15-8
w = winlet /(1 x)
[15.3.6]
As an illustration, assume that 100 g of refrigerant-oil mixture enters the expansion valve with an inlet oil
mass fraction, winlet, equal to 0.05 (thus, there are 5 g of oil and 95 g of refrigerant):
1. Before the expansion valve the local vapor quality is 0.0 and w = winlet = 0.05 as indicated by [15.3.6];
2. For a local vapor quality equal to 0.20 immediately after the expansion valve, w is 0.0625 [i.e.
0.05/(1-0.20)];
3. For a local vapor quality of 0.90, w is 0.50 or 50 mass % oil, i.e. [0.05/(1-0.90)];
4. If the entire refrigerant was evaporated from the liquid mixture, the local vapor quality would be (1winlet) or 0.95 and [15.3.6] appropriately predicts that w for this situation is 1.0 [i.e. 0.05/(1-0.95)].
[15.3.7]
where x is the local vapor quality, hLG is the latent heat of vaporization of the pure refrigerant since no oil
enters the vapor-phase, cpL is the specific heat of the liquid-phase refrigerant-oil mixture and cpG is the
specific heat of the pure refrigerant vapor. The values of hLG and cpG are obtained from equations for the
pure refrigerant at the local saturation temperature while cpL is a function of the local oil composition and
bubble point temperature. Equation [15.3.7] reduces to only the latent heat for a pure refrigerant without
oil.
A heat release curve is not actually implemented as a curve. Instead, it is prepared as a table of values at
set intervals of temperature or vapor quality that gives the amount of heat absorbed by the fluid per unit
mass (i.e. dh is in J/kg or Btu/lb) relative to its inlet state together with the bubble point temperature and
vapor qualities that correspond to these points.
At a standard evaporation temperature of 4.44C (40F) in a refrigeration system, for pure R-134a this
corresponds to a saturation pressure of 3.43 bar (49.7 psia) absolute. For a mixture with 3 (% mass) oil in
R-134a at this saturation pressure, Table 15.2 lists the enthalpy curve in tabular form at this pressure
covering the vapor quality range from 0.15 to 0.95 utilizing the method of Thome (1995). The oil is
Mobil Arctic EAL 68 whose density is 971 kg/m3 (60.7 lb/ft3) at 15.56C (60F) {Note: the oil's density is
utilized to predict its liquid specific heat, cf. Thome (1995) and thus that of the refrigerant-oil mixture}.
The first column in Table 15.2 shows the local vapor quality intervals along the evaporator tube. The next
two columns list Tbub and w. The total heat absorbed relative to the inlet condition is shown in the 4th
column (in kJ/kg). The contributions of the heat absorbed as latent heat dhlatent and as sensible heating of
the liquid and vapor dhsensible are given in the last two columns (in kJ/kg), respectively. As can be seen, the
rise in the bubble point temperature and oil mass fraction in the liquid is most rapid at high vapor
15-9
qualities. The contribution of sensible heat is important at high vapor qualities since its effect is directly
dependent on the rise in Tbub.
Table 15.2. An enthalpy curve for R-134a/3 (% mass) oil mixture at 3.43 bar.
x
0.150
0.230
0.310
0.390
0.470
0.550
0.630
0.710
0.790
0.870
0.950
Tbub (C)
4.509
4.516
4.525
4.536
4.550
4.570
4.598
4.643
4.729
4.954
8.289
w
3.53
3.90
4.35
4.92
5.66
6.67
8.11
10.34
14.29
23.08
60.00
dhtotal (kJ/kg)
0.00
15.64
31.28
46.92
62.56
78.20
93.85
109.52
125.23
141.05
159.76
dhlatent (kJ/kg)
0.00
15.63
31.26
46.29
62.51
78.13
93.75
109.37
124.99
140.59
156.07
dhsensible (kJ/kg)
0.00
0.01
0.02
0.03
0.05
0.07
0.10
0.15
0.24
0.46
3.69
Table 15.2 also illustrates the influence of oil on Tbub with respect to the pure refrigerant (R-134a)
saturation temperature Tsat of 4.44C (40F). For x < 0.50, the increase in boiling point tends to be 0.1C
(0.2F) or less, for 0.50 < x < 0.80, the rise increases up to about 0.3C (0.54F), and for x > 0.80 the
elevation of the boiling point can become very significant (3.845C or 6.921F at x = 0.95 in Table
15.2!). The temperature difference between Tbub and Tsat depends on the local vapor quality and the inlet
oil mass fraction.
For refrigerant-oil mixtures, it is preferable to use set intervals of vapor quality for determining the points
on a heat release curve rather than set intervals of temperature. If an evaporator is to be designed with an
inlet vapor quality after the expansion valve of 0.20 and an outlet vapor quality of 0.90, then the heat
absorbed and bubble point temperatures might be determined at vapor qualities of 0.20, 0.30, 0.40, 0.50,
0.60, 0.70, 0.80 and 0.90. The heat absorbed at x = 0.20 would be zero and would serve as the datum for
the other values. In practice, the number of intervals to use is up to the designer and should be sufficient
to accurately represent the heat release curve and also the variation in the two-phase heat transfer
coefficient as a function of vapor quality. Normally eight to ten intervals are recommended, but more can
be used as desired.
For refrigerant-oil mixtures, the following procedure is used for preparation of a heat release curve at a
fixed, isobaric pressure:
1. Select the desired pressure psat and inlet oil mass fraction before the expansion valve, winlet.
2. Determine two sets of pure refrigerant saturation temperature and pressure just above and just below
psat with an accurate equation-of-state;
3. Use these two sets of values for Tbub and psat to solve for ao and bo with w set to zero from the two
equations and two unknowns.
4. The new values of ao and bo are used in place of ao = -2394.5 and bo = 8.0736, respectively. All the
other values of a1 to a4 and b1 to b4 remain the same.
15-10
5. Choose the inlet vapor quality, the exit vapor quality (always less than the value of 1-winlet), and the
number of design intervals desired (for example, if the evaporator is divided into ten heat transfer
zones, then 11 points are needed in the heat release curve).
6. Calculate the local oil fractions corresponding to the local vapor qualities using [15.3.6] (for example,
determine w for each of the eleven vapor quality points above).
7. Calculate the local bubble point temperatures corresponding to the local vapor qualities and local oil
mass fractions at each point.
8. Calculate the values of hLG and cpG at these bubble point temperatures using methods for pure
refrigerants. Determine the liquid specific heat of the refrigerant-oil mixture cpL for each point based
on the local values of w and Tbub using [15.4.1] and [15.4.2].
9. Determine the heat absorbed by the refrigerant-oil fluid in each interval, dh, and then add these up to
obtain the total heat absorbed per unit mass of fluid from inlet to outlet.
The heat release curve preparation is now complete and the following values required for thermal design
of the evaporator are known at each local vapor quality x: w, Tbub and dh.
[15.4.1]
where the liquid specific heat (cpL)oil is in units of kJ/kgC, the temperature of the oil, T, must be in C
(valid for -18 < T < 204C) and s is the liquid specific gravity at 15.56C (60F) and is valid for 0.75 < s
< 0.96. Literature furnished by manufacturers of lubricating oils usually provides the density or specific
gravity of the oil at a temperature of 60F (15.56C). Thus, application of [15.4.1] for general use for
lubricating oils presents no problem. In preparation of a heat release curve, the temperature, T, in [15.4.1]
is the bubble point temperature Tbub for the local vapor quality in question.
The above correlation compares well with tabular values for engine lubricating oil in Incropera and
DeWitt (1981), giving maximum deviations of -2% and +7%. This equation has also been doublechecked against numerous heavy hydrocarbons and viscous commercial heat transfer fluids with good
results over the temperature range of interest for lubricating oils. Thus it should be sufficiently accurate
since liquid sensible heat normally only contributes a small fraction of the total heat absorbed by an
evaporating refrigerant-oil mixture.
Some lubricating oils have a specific gravity as high as 1.05, i.e. not very far outside the range cited by
Liley and Gambill, and use of [15.4.1] is still recommended in the absence of values from the
15-11
manufacturer. As an example calculation, consider an oil at 4.44C (40F) with a specific gravity of 0.890
at 15.56C (60F). Equation [15.4.1] predicts the liquid specific heat to be 1.80 kJ/kgC (0.43 Btu/lbF).
In comparison, the values for R-134a and R-22 at 4.44C (40F) are 1.354 and 1.187 kJ/kgC,
respectively (0.323 and 0.283 Btu/lbF).
( )
( )
[15.4.2]
The above equation is evaluated with the refrigerant and oil properties at the local bubble point
temperature of the mixture. For example for 30 mass % oil (w = 0.30), if the specific heat at 4.44C for
the oil is 1.80 kJ/kgK while that of R-22 is 1.187 kJ/kgK, then the liquid specific heat of the mixture is
1.371 kJ/kgK [= 0.3 (1.80) + (1.0-0.3)(1.187)].
15-12
Table 15.3. R134a-oil temperature-enthalpy curve at 2.93 bar (42.5 psia) for 5 mass % oil at inlet.
dhtotal
dhlatent
(kJ/kg)
(kJ/kg)
0.000
0.076
5.00
0.00
0.00
0.093
0.084
5.51
18.53
18.52
0.186
0.094
6.14
37.06
37.04
0.279
0.106
6.93
55.60
55.56
0.372
0.123
7.96
74.14
74.08
0.465
0.146
9.35
92.68
92.59
0.558
0.180
11.31
111.23
111.10
0.651
0.236
14.33
129.80
129.63
0.744
0.346
19.53
148.42
148.11
0.837
0.663
30.67
167.22
166.59
0.846
0.729
32.47
169.14
168.44
0.856
0.819
34.72
171.08
170.29
0.865
0.922
37.04
173.03
172.14
0.874
1.056
39.68
175.00
173.98
0.883
1.240
42.74
177.02
175.82
0.893
1.541
46.73
179.15
177.66
0.902
1.974
51.02
181.41
179.50
0.911
2.726
56.18
183.93
181.33
0.921
4.435
63.29
187.43
183.15
0.930
8.015
71.43
192.70
184.95
(% errors determined assuming a heat flux of 10,000 W/m2).
x
Tbub (C)
w (%)
dhsensible
(kJ/kg)
0.00
0.01
0.02
0.04
0.06
0.06
0.13
0.16
0.31
0.63
0.70
0.79
0.89
1.02
1.20
1.49
1.91
2.63
4.28
7.75
5C
%Error
-1.5
-1.7
-1.9
-2.1
-2.5
-2.9
-3.6
-4.7
-6.9
-13.3
-14.6
-16.4
-19.4
-21.1
-24.8
-30.8
-39.5
-54.5
-
2C
%Error
-3.8
-4.2
-4.7
-5.3
-6.2
-7.3
-9.0
-11.8
-17.3
-33.2
-36.5
-41.0
-46.1
-52.8
-62.0
-
In the last two columns in Table 15.3, the effect of erroneously using Tsat in place of Tbub in converting
"raw" data to experimental heat transfer coefficients is shown for wall superheats of 5C (9F) and 2C
(3.6F). It is evident that existing published data using Tsat are always too low compared to their more
correct values. For instance, at a vapor quality of 0.837 and a wall superheat of 5C (9F), published
values would be 13.3% lower than the thermodynamically correct values.
For a plain tube the effect of the oil on flow boiling heat transfer becomes significant (> 5%) at a local oil
mass fraction greater than 15% while for a micro fin tube it becomes significant at w > 6.5%. At high
vapor qualities and oil mass fractions, the effect becomes very significant, substantially changing the
trends reported in the literature. Published test data reduced with the oil contamination method that fall
in these ranges should be used with caution or better yet, the heat transfer coefficients should be
recalculated.
15-13
(-17.2%), liquid viscosity (+9003%), liquid specific heat (+23.6%), liquid thermal conductivity (+11.7%),
critical pressure (-58.1%), critical temperature (+103%) and liquid Prandtl number (+10,021%). Also
shown is the ratio of the liquid Reynolds number relative to than for the inlet at x = 0.0, which decreases
drastically as the liquid viscosity rises. Thus, the variation is local physical properties can potentially have
a significant effect on the local heat transfer coefficients, both for nucleate pool boiling and for flow
boiling.
Table 15.4. R134a-oil properties at 2.93 bar for 5 mass % oil at inlet over a range of vapor qualities.
Local Vapor Quality
Oil Mass Fraction %
Liquid Molecular Weight
Bubble Point Temp. (C)
Heat Absorbed (kJ/kg)
Liquid Density (kg/m3)
Vapor Density (kg/m3)
Liquid Viscosity (cp)
Vapor Viscosity (cp)
Liquid Sp. Heat (kJ/kg K)
Vapor Sp. Heat (kJ/kg K)
Liquid Th. Cond. (W/m K)
Vapor Th. Cond. (W/m K)
Surface Tension (dyne/cm)
Latent Heat (kJ/kg)
Critical Pressure (bar)
Critical Temperature (K)
Liquid Prandtl Number
Relative Liquid Re Number
0.000
5.00
126.4
0.076
0.00
1276
14.5
0.398
0.011
136.3
0.889
0.094
0.012
11.7
199.1
38.9
405.7
5.75
1.000
0.279
6.93
135.9
0.106
55.6
1270
14.5
0.458
0.011
1.372
0.889
0.095
0.012
11.7
191.1
38.2
417.9
6.64
0.869
0.558
11.31
157.2
0.180
37.1
1256
14.5
0.628
0.011
1.391
0.889
0.095
0.012
11.7
1.991
36.7
445.5
9.20
0.634
0.744
19.53
197.3
0.346
148.4
1230
14.6
1.137
0.011
1.428
0.889
0.096
0.012
11.8
198.9
33.9
497.4
16.9
0.350
0.930
71.43
450.6
8.015
192.6
1057
16.8
35.83
0.011
1.684
0.906
0.105
0.013
17.2
195.5
16.3
824.7
576.2
0.011
15-14
150C (302F) to drive off the refrigerant, then weighed again with a top loading balance accurate to 0.01
g or better. The oil composition can then be calculated from the initial and final weights. While this
method is appropriate as a standard, it is not very convenient for practice. Shortcuts to the standard
method, i.e. dispensing with the heating and/or evacuation procedures, result in overstating the oil
concentration by as much as 1.5 mass % oil or more. Consequently, it is felt that an online method is
imperative in order to measure the oil compositions conveniently and accurately over the range of test
conditions to be encountered.
Various methods for determining oil compositions online have been proposed and several have been
tested. Baustian, Pate and Bergles (1988a, 1988b, 1988c) have used a Coriolis density meter, an acoustic
velocity sensor and a viscosity meter, respectively, to measure oil concentrations with accuracies in the
range of 1-2 mass % oil. The Coriolis meter used in their tests had a density measurement accuracy of 10
kg/m3 (0.6 lb/ft3) and the effect of compressibility on the subcooled liquid passing through the meter was
not accounted for; however, newer more accurate Coriolis meters are now available and may suit
industrial use. Meyer and Saiz Jabardo (1994) built an ultrasonic acoustic velocity device and accurately
calibrated it for measuring concentrations for R-12 and R-134a with various oils (95% confidence level
accuracy of 0.23-0.26 mass % oil). Suzuki, Fujisawa, Nakarazawa and Matsuoka (1993) instead have
used a light absorption method for measuring oil concentrations online.
15-15
Their calibration correlation had an average error of 0.09 mass % oil for all 246 data points measured for
the oil concentrations of 0.0, 0.5, 1.0, 2.0, 3.0, 4.0, 5.0 and 6.0 mass %, a maximum error of 0.69 mass %
oil and a 95% confidence limit of 0.21 mass % oil.
[15.6.1]
Solving this expression to obtain the oil mass fraction w (in mass fraction, not mass %) gives
[15.6.2]
The refrigerant saturation density ref in this equation is calculated from an accurate equation for the
refrigerant (such as ASHRAE methods). The lubricating oil density oil can either be measured as a
function of temperature or obtained from data supplied by the manufacturer. Otherwise, using a method
adapted from Thome (1992), it can be estimated from the following equation for lubricating oils:
0.29
[15.6.3]
where man is the oil density (kg/m3) at the temperature provided by the manufacturer Tman (normally
15C), Tcrit is the critical temperature of the oil (assume equal to 760 K for all oils as an approximation),
and T is the measured temperature (K). Subtracting the density difference due to compressibility from the
measured density and using the pure refrigerant and oil densities determined as discussed, the oil
composition is determined with [15.6.2]. This simplified method has been successfully compared to R134a/oil density test data of Bayini, Thome and Favrat (1995) with a mean error of 0.22 mass % oil.
Because of nonlinear variations in density with composition, the accuracy varies from about 0.1 mass %
mean error for the 0.5 mass % mixture up to about 0.5 mass % mean error for the 6.0 mass % mixture,
which is more than satisfactory for most applications.
To get the best results, the meter should be calibrated against the pure refrigerant first, i.e. measure the
pure refrigerant's density with the meter, correct this value for liquid compressibility and then compare it
against the calculated saturated refrigerant density.
------------------------------------------------------------------------------------------------------------------------------Example Calculation: Assume a density meter is used to measure oil mass fraction of a slightly
subcooled mixture of R-134a and oil at the conditions of 0C and 2.93 bar. R-134a has a density of 1276
kg/m3 at this temperature while the oil has a density of 900 kg/m3 at the 15C according to the
manufacturer. If the density measured is 1270 kg/m3, what is the oil mass fraction?
Solution: The density of the oil at 0C (273.15 K) is obtained with [15.6.3]:
0.29
0.29
= 908.2 kg / m3
15-16
The oil mass fraction w (in mass fraction) is obtained with [15.6.2]:
15-17