Product data sheet
Characteristics
ATS48C14Q
soft starter for asynchronous motor - ATS48 131 A - 230..415 V - 30..110 KW
Range of product
Altistart 48
Product or component
type
Soft starter
Product destination
Asynchronous motors
Product specific application
Pumping and ventilation machine
Severe and standard applications
Component name
ATS48
Power supply voltage
230...415 V (- 15...10 %)
Motor power kW
37 kW at 230 V (connection in the motor supply line)
for standard applications
30 kW at 230 V (connection in the motor supply line)
for severe applications
110 kW at 400 V (connection to the motor delta terminals) for standard applications
90 kW at 400 V (connection to the motor delta terminals) for severe applications
75 kW at 400 V (connection in the motor supply line)
for standard applications
75 kW at 230 V (connection to the motor delta terminals) for standard applications
55 kW at 400 V (connection in the motor supply line)
for severe applications
55 kW at 230 V (connection to the motor delta terminals) for severe applications
Power dissipation in W
391 W for standard applications
306 W for severe applications
Utilisation category
AC-53A
Type of start
Start with torque control (current limited to 5 In)
Icl nominal current
242 A (connection to the motor delta terminals)for
standard applications
191 A (connection to the motor delta terminals)for
severe applications
140 A (connection in the motor supply line)for standard applications
110 A (connection in the motor supply line)for severe applications
IP degree of protection
IP00
Complementary
Assembly style
With heat sink
Function available
External bypass (optional)
Power supply voltage limits
195...456 V
Power supply frequency
50...60 Hz (- 5...5 %)
Power supply frequency limits
47.5...63 Hz
Device connection
In the motor supply line
To the motor delta terminals
Factory setting current
131 A
Control circuit voltage
220 - 15 % to 415 + 10 %, 50/60 Hz
Control circuit consumption
30 W
Discrete output number
Discrete output type
(R3) relay outputs motor powered NO
(R2) relay outputs end of starting relay NO
(R1) relay outputs fault relay NO
(LO2) logic output 0 V common configurable
(LO1) logic output 0 V common configurable
Output absolute accuracy precision
+/- 5 %
Apr 2, 2015
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Minimum switching current
Relay outputs 10 mA at 6 V DC
Maximum switching current
Relay outputs 1.8 A at 30 V DC inductive load, cos phi = 0.5, L/R = 20 ms
Relay outputs 1.8 A at 230 V AC inductive load, cos phi = 0.5, L/R = 20 ms
Logic output 0.2 A at 30 V DC
Discrete input number
Discrete input type
(Stop, Run, LI3, LI4) logic <= 8 mA 4300 Ohm
PTC 750 Ohm at 25 C
Discrete input voltage
24 V (<= 30 V)
Discrete input logic
(Stop, Run, LI3, LI4) positive logic state 0 < 5 V and < 2 mA state 1 > 11 V and >
5 mA
Starting current
Adjustable 0.4...1.3 Icl
Analogue output type
(AO) current output 0-20 mA or 4-20 mA <= 500 Ohm
Communication port protocol
Modbus
Connector type
1 RJ45
Communication data link
Serial
Physical interface
RS485 multidrop
Transmission rate
4800, 9600 or 19200 bps
Max nodes number
31
Protection type
Thermal protection (starter)
Thermal protection (motor)
Phase failure (line)
Marking
CE
Type of cooling
Forced convection
Operating position
Vertical +/- 10 degree
Height
340 mm
Width
200 mm
Depth
265 mm
Product weight
12.4 kg
Environment
Electromagnetic compatibility
Voltage/Current impulse conforming to IEC 61000-4-5 level 3
Immunity to radiated radio-electrical interference conforming to IEC 61000-4-3
level 3
Immunity to electrical transients conforming to IEC 61000-4-4 level 4
Electrostatic discharge conforming to IEC 61000-4-2 level 3
Damped oscillating waves conforming to IEC 61000-4-12 level 3
Conducted and radiated emissions conforming to IEC 60947-4-2 level B
Conducted and radiated emissions conforming to IEC 60947-4-2 level A
Standards
EN/IEC 60947-4-2
Product certifications
CCC
CSA
C-Tick
DNV
GOST
NOM 117
SEPRO
TCF
UL
Vibration resistance
1.5 mm (f = 2...13 Hz) conforming to EN/IEC 60068-2-6
1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to EN/IEC 60068-2-27
Noise level
50 dB
Pollution degree
Level 3 conforming to IEC 60664-1
Relative humidity
<= 95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
Ambient air temperature for operation
-10...40 C without derating
> 40...60 C with current derating of 2 % per C
Ambient air temperature for storage
-25...70 C
Operating altitude
> 1000...2000 m with current derating of 2.2 % per additional 100 m
<= 1000 m without derating