GEA fan coil units for suspended ceilings with HX-Factor
Energy efficient - Powerful - Hygienic - Low noise
GEA HyPower-Geko
Product Brochure
engineering for a better world
GEA Heat Exchangers
Optimal climate with HX-Factor:
Hygienic. Efficient. Sustainable.
The HX-Factor is our performance promise. It
stands for unique competence in heat exchange
(HX = HEAT EXCHANGE) and ensures you
diverse great product benefits. The GEA
HyPower-Geko fan coil units generate a whisperquiet and comfortable feel-good climate at
maximum energy efficiency and optimal air treatment.
[2]
PR-2014-0006-GB Subject to modification K1-02/2015
Economy and ecology in harmony
The signs of the times are clear
Investors, plant engineers, planners, and architects no longer ask "whether" but "how" they
can enhance the degree of sustainability of their plants and building management systems.
Buildings are unique objects. Location, size, construction quality, and increasingly,
building engineering technology determine values and returns. Energy matters substantially gain in significance since buildings absorb about 40 % of the world energy consumption and produce 21 % of world-wide greenhouse gas emissions. Energy costs will increasingly become a second rent for users and residents.
Where air conditioning is required for rooms and buildings, GEA contributes to technological advances. We offer highly efficient air treatment and supply with the greatest
We design we the most
efficient demand-controlled
solution for your
requirements
possible reduction of energy consumption over the entire service life of the plants: This
pays off in cents and euros, comfort and work productivity. In highly sensitive areas, such
as clinical and clean room applications, our solutions reliably satisfy all international
standards and achieve high rankings in the demanding classification of the Eurovent
Compliance Committee for Air Handling Units. They furthermore set new standards for
sustainability and perfect system integration in modern sport arenas, factory buildings,
airport facilities, and swimming pools, as well as in offices, museums and hotels.
Summarized with the concept "HX-Factor", this quality justifies our technological
advantage. The HX-Factor is more than just technology. It is an attitude and creates value
with a future: quality of life for residents and users. Protection of energy resources and our
climate. Certainty for investors and planners.
PR-2014-0006-GB Subject to modification K1-02/2015
[3]
Not just hot air, only full power
The new dimensions of innovative air handling
GEA HyPower-Geko
means:
GEA HyPower-Geko The innovative fan coil unit in recirculating air mode convinces in
three ways with an integral concept, that sets new standards: On maximum capacity with
High Power
maximum energy efficiency and greatest possible demand on hygiene, GEA HyPower-Geko
Hygienic Power
performs individual air-conditioning at its best.
Hydronic Power
Maximum power with precision:
Maximum cooling capacity at highest speed (25 kW)
Powerful thanks to external pressure up to 150 Pa
Modular construction system enables a flexible design, low-noise operation
Certified hygiene conformity (VDI6022)
Variable capacity stages: 2-pipe and 4-pipe
Individual installation, e.g. in a discreet position in the false ceiling
Certified according to VDI 6022
Holistic eXpertise
Comprehensive conceptmaximum use
We optimize your total operating costs continuously and
sustainably: highly-efficient fans are integrated in the unit
and precisely tailored to our GEA MATRIX control technology. Besides, our reliable software enables individual
optimized total
operating costs
configuration and layout of your system.
EC fan
Integration in unit
Compatibility of control system
Software flexibility (individual operating points)
[4]
PR-2014-0006-GB Subject to modification K1-02/2015
Power is in the air
Concentrated power, efficiency and comfort for a perfect room climate
EC fans made by quality manufacturer ebm-pabst
Maximum cooling and heating capacity with minimum electric power consumption excellently awarded: EUROVENT energy label FCEER/FCOOP (class A)
Condensate pump MaxiBlue
Harmony all along the line: powerful, energy-efficient, low-noise and reliable owing to a
new rotation-membrane principle.
GEA MATRIX control system
Diverse control options in different stages of expansion - including: "Plug and Play" function, power-optimized operation and competent service with service tool.
Compact controller CET-EC
Equipped with auto and manual mode in 3 speeds: heating and cooling/only heating or
cooling. Compatible with open/close valves. The fan is continuously controlled in auto
mode.
PR-2014-0006-GB Subject to modification K1-02/2015
[5]
Comprehensive control
possibilities:
Control functions in various
expansion stages
Bus interface to analog and
Intelligent control technology
Always the right idea for the right climate with
the GEA MATRIX
digital devices
Plug-and-play functionality
If requested as option, the proven GEA MATRIX control unit will be integrated into the
Energy-optimized equipment
GEA HyPower Geko at the factory. Thus, only completely tested equipment will be supplied
operation
to your construction site.
Equipment ready to operate
and highly competent service
The GEA MATRIX is available in the configuration levels 3000 and 4000, in accordance
Global add-on modules
with various applications. The model variants provide a 2-core GEA MATRIX.NET bus
LON connection
system that allows communication among all GEA MATRIX units. As a result, it is simple to
Service tool available
implement daytime and nighttime switching actions, or to control pumps and collect error
messages at a single point. GEA MATRIX can also be connected to higher-level bus systems.
GEA MATRIX furthermore ensures an energy-optimized operation of the GEA HyPowerGeko units. A coordinated switchover function, for example, prevents heating and cooling
circulation systems from working against each other. With summer compensation, GEA
MATRIX takes the outside temperature influence into consideration and thereby prevents
an energy-intensive climate control.
Hardware and software are developed entirely at GEA. As a result of close collaboration in
the company, GEA engineers can systematically adjust the control system to match every
component and in turn optimally exploit the possibilities of the fan coil units. Service and
support also benefit from this arrangement, and can rapidly and competently react whenever questions arise. Numerous additional global modules are available as function expansions of the standard local connections of the MATRIX control system, such as intra-group
control units and clock modules, modules for activation control of chillers, expansion of
analog or digital input and output signals, inputs and outputs for valves, and integration
into a LON bus system in accordance with the LonWorks standard.
All modules can be simply and easily integrated via the MATRIX.Net bus system. Furthermore, the service tool MATRIX.PC can be deployed for the parameterization, commissioning, maintenance and data recording of the GEA MATRIX control system.
[6]
PR-2014-0006-GB Subject to modification K1-02/2015
Control panels for MATRIX 3000
and MATRIX 4000
Compact controller
MATRIX OP 30 with key
MATRIX OP 31 with economy
mode key
MATRIX OP 44
As for the OP31 control panel, but also
Compact controller
CET.ECH
with
White casing, similar to
Casing without display, pure white
Toggle between heating/cooling/
RAL 9016
Recirculating air mode, IP 20 enclosure-
automatic mode
Recirculating air mode
protection class
All control panels without display and
Protection class IP 30
Setpoint temperature setting
optionally with protective cover
Setpoint temperature setting
Speed selector switch for continuous/
Speed selector switch for
automatic operation
continuous/automatic opera-
LED display of operation / malfunction /
tion
external control
Integrated room-temperature
Integrated room-temperature sensor
sensor
Input via volt on-site floating
contact by others
Contact for external sensor
Room frost protection
MATRIX OP 50 without clock
MATRIX OP 51 with clock
MATRIX.IR infrared remote
control unit
Casing with display, pure white
Functions like OP 44 control panel,
Recirculating air mode
however
IP 20 class
without operational / error messages
Operation with rotary navigator
without messages on ext. influence
LCD display with plain-text display
without integrated room sensor
Status report by pictograms
Black casing, similar to RAL 9004
Integrated room-temperature sensor
LCD display 45 x 30 mm
Transmission range about 20 m
PR-2014-0006-GB Subject to modification K1-02/2015
[7]
Max. dimensions and
weights
GEA HyPower-Geko
Basic unit - version A
Without chamber for fans
Basic unit - version B
With chamber for fans
Basic unit - version C
With chamber for fans
Free intake
On-site filter must be provided
without insulation of the fan chamber
With integrated flat filter
Duct and accessory connection possible
Like version B, but with
interior acoustic insulation
of the fan chamber
Size
Size
Size
Width*
mm
Depth
mm
Height
mm
803
1108
1413
1833
595
595
595
595
340
340
340
340
1
2
3
4
Weight including water charge
Width*
mm
Depth
mm
Height
mm
803
1108
1413
1833
705
705
705
705
340
340
340
340
1
2
3
4
Weight including water charge
Width*
mm
Depth
mm
Height
mm
803
1108
1413
1833
705
705
705
705
340
340
340
340
1
2
3
4
Weight including water charge
Size
Max.
Size
Max.
Size
Max.
1
2
3
4
31 kg
42 kg
55 kg
69 kg
1
2
3
4
37 kg
50 kg
66 kg
84 kg
1
2
3
4
40 kg
53 kg
69 kg
88 kg
Extended condensate pan
- optional for cooling operation -
Basic unit in hygiene configuration
- on request -
additional equipment
Only available for authorized sales
regions
Additional extended condensate pan at
mounted valves and connection fixtures
Heat exchanger cover plates on the front
and back side to provide optical covering
and protect the hydraulics and copper pipes
from damage during installation
An additional 264 mm is then added to the
entire width of the unit
Condensate pan, extended and
powder-coated
Increased distance between hydraulic
system and electric terminal box
* plus 264 mm when using the extended condensate pan
[8]
PR-2014-0006-GB Subject to modification K1-02/2015
Accessory items
GEA HyPower-Geko
Optional selectable accessories
Spare filters (G2 or G4)
Flexible connection (intake or discharge)
Air-intake plenum with round connectors DN 250
(insulated or non-insulated)
Number of round connectors:
Model size 1 = 3 pcs.
Model size 2 = 4 pcs.
Model size 3 = 5 pcs.
Model size 4 = 6 pcs
Seal cap DN 250 for round connector
Transition piece for accessories
Sound attenuator (intake/discharge)
Suspension rail for ceiling mounting
PR-2014-0006-GB Subject to modification K1-02/2015
[9]
Cooling - Recirculating air
2-pipe system - chilled water
Air volume flow V at external pressure of 50 Pa in speed 3 and capacity stage 1
Cooling capacity
PCW 6 / 12 C
Air intake 27 C / 46 %
Capacity stage
Sound power level*
at capacity stage 1
Motor data
EC motor
1 ~ 230 Volt
Size
Speed
Max.
CS1
CS2
CS3
Intake
Discharg
e
Casing
Max.
Max.
340 m3/h
1.70 kW
2.30 kW
2.60 kW
41 dB(A)
44 dB(A)
36 dB(A)
20 W
0.13 A
620 m /h
2.70 kW
3.90 kW
4.40 kW
57 dB(A)
60 dB(A)
50 dB(A)
100 W
0.72 A
920 m3/h
3.60 kW
5.50 kW
6.40 kW
67 dB(A)
71 dB(A)
59 dB(A)
213 W
1.54 A
420 m3/h
2.20 kW
2.90 kW
3.20 kW
37 dB(A)
40 dB(A)
30 dB(A)
19 W
0.18 A
970 m3/h
4.20 kW
6.00 kW
6.70 kW
56 dB(A)
59 dB(A)
46 dB(A)
136 W
0.89 A
1525 m /h
5.90 kW
8.80 kW
10.10 kW
66 dB(A)
70 dB(A)
57 dB(A)
296 W
2.09 A
630 m3/h
3.20 kW
4.30 kW
4.90 kW
45 dB(A)
48 dB(A)
36 dB(A)
36 W
0.30 A
1410 m /h
6.00 kW
8.70 kW
10.00 kW
61 dB(A)
64 dB(A)
53 dB(A)
258 W
1.84 A
2090 m3/h
8.10 kW
12.10 kW
14.20 kW
70 dB(A)
73 dB(A)
61 dB(A)
510 W
3.43 A
735 m3/h
4.00 kW
5.30 kW
6.10 kW
43 dB(A)
42 dB(A)
35 dB(A)
34 W
0.29 A
1735 m /h
7.80 kW
11.10 kW
12.70 kW
61 dB(A)
60 dB(A)
51 dB(A)
259 W
1.75 A
2800 m3/h
10.70 kW
16.70 kW
19.70 kW
71 dB(A)
72 dB(A)
61 dB(A)
591 W
3.76 A
*For an example of the conversion of the sound power level in the sound pressure level, see page 16.
[10]
PR-2014-0006-GB Subject to modification K1-02/2015
Heating - Recirculating air
2-pipe system - Warm water
Air volume flow V at external pressure of 50 Pa in speed 3 and capacity stage 1
Thermal output
PWW 70 / 50 C
Air intake 20 C
Capacity stage
Sound power level*
at capacity stage 1
Motor data
EC motor
1 ~ 230 Volt
Size
Speed
Max.
CS1
CS2
CS3
Intake
Discharg
e
Casing
Max.
Max.
340 m3/h
3.50 kW
4.50 kW
4.70 kW
41 dB(A)
44 dB(A)
36 dB(A)
20 W
0.13 A
620 m /h
5.60 kW
7.70 kW
8.20 kW
57 dB(A)
60 dB(A)
50 dB(A)
100 W
0.72 A
920 m3/h
7.70 kW
10.90 kW
12.00 kW
67 dB(A)
71 dB(A)
59 dB(A)
213 W
1.54 A
420 m3/h
4.50 kW
5.60 kW
5.70 kW
37 dB(A)
40 dB(A)
30 dB(A)
19 W
0.18 A
970 m3/h
8.80 kW
11.90 kW
12.70 kW
56 dB(A)
59 dB(A)
46 dB(A)
136 W
0.89 A
1525 m /h
12.50 kW
17.80 kW
20.00 kW
66 dB(A)
70 dB(A)
57 dB(A)
296 W
2.09 A
630 m3/h
6.70 kW
8.50 kW
9.00 kW
45 dB(A)
48 dB(A)
36 dB(A)
36 W
0.30 A
1410 m /h
12.70 kW
17.40 kW
19.30 kW
61 dB(A)
64 dB(A)
53 dB(A)
258 W
1.84 A
2090 m3/h
17.20 kW
24.60 kW
27.80 kW
70 dB(A)
73 dB(A)
61 dB(A)
510 W
3.43 A
735 m3/h
8.10 kW
10.30 kW
10.90 kW
43 dB(A)
42 dB(A)
35 dB(A)
34 W
0.29 A
1735 m /h
16.30 kW
22.20 kW
24.30 kW
61 dB(A)
60 dB(A)
51 dB(A)
259 W
1.75 A
2800 m3/h
23.60 kW
33.80 kW
38.00 kW
71 dB(A)
72 dB(A)
61 dB(A)
591 W
3.76 A
*For an example of the conversion of the sound power level in the sound pressure level, see page 16.
PR-2014-0006-GB Subject to modification K1-02/2015
[11]
Cooling or heating - Change-Over operation - Recirculating air
2-pipe system chilled or warm water
Air volume flow V at external pressure of 50 Pa in speed 3 and capacity stage 1
Cooling capacity
PCW 6 / 12 C
Air intake 27 C / 46 %
Capacity stage
Sound power level*
at capacity stage 1
Motor data
EC motor
1 ~ 230 Volt
Size
Speed
Max.
CS1
CS2
CS3
Intake
Discharg
e
Casing
Max.
Max.
340 m3/h
1.70 kW
2.30 kW
2.60 kW
41 dB(A)
44 dB(A)
36 dB(A)
20 W
0.13 A
620 m /h
2.70 kW
3.90 kW
4.40 kW
57 dB(A)
60 dB(A)
50 dB(A)
100 W
0.72 A
920 m3/h
3.60 kW
5.50 kW
6.40 kW
67 dB(A)
71 dB(A)
59 dB(A)
213 W
1.54 A
420 m3/h
2.20 kW
2.90 kW
3.20 kW
37 dB(A)
40 dB(A)
30 dB(A)
19 W
0.18 A
970 m3/h
4.20 kW
6.00 kW
6.70 kW
56 dB(A)
59 dB(A)
46 dB(A)
136 W
0.89 A
1525 m /h
5.90 kW
8.80 kW
10.10 kW
66 dB(A)
70 dB(A)
57 dB(A)
296 W
2.09 A
630 m3/h
3.20 kW
4.30 kW
4.90 kW
45 dB(A)
48 dB(A)
36 dB(A)
36 W
0.30 A
1410 m /h
6.00 kW
8.70 kW
10.00 kW
61 dB(A)
64 dB(A)
53 dB(A)
258 W
1.84 A
2090 m3/h
8.10 kW
12.10 kW
14.20 kW
70 dB(A)
73 dB(A)
61 dB(A)
510 W
3.43 A
735 m3/h
4.00 kW
5.30 kW
6.10 kW
43 dB(A)
42 dB(A)
35 dB(A)
34 W
0.29 A
1735 m /h
7.80 kW
11.10 kW
12.70 kW
61 dB(A)
60 dB(A)
51 dB(A)
259 W
1.75 A
2800 m3/h
10.70 kW
16.70 kW
19.70 kW
71 dB(A)
72 dB(A)
61 dB(A)
591 W
3.76 A
*For an example of the conversion of the sound power level in the sound pressure level, see page 16.
[12]
PR-2014-0006-GB Subject to modification K1-02/2015
Cooling or heating - Change-Over operation - Recirculating air
2-pipe system chilled or warm water
Air volume flow V at external pressure of 50 Pa in speed 3 and capacity stage 1
Thermal output
PWW 70 / 50 C
Air intake 20 C
Capacity stage
Sound power level*
at capacity stage 1
Motor data
EC motor
1 ~ 230 Volt
Size
Speed
Max.
CS1
CS2
CS3
Intake
Discharg
e
Casing
Max.
Max.
340 m3/h
3.50 kW
4.50 kW
4.70 kW
41 dB(A)
44 dB(A)
36 dB(A)
20 W
0.13 A
620 m /h
5.60 kW
7.70 kW
8.20 kW
57 dB(A)
60 dB(A)
50 dB(A)
100 W
0.72 A
920 m3/h
7.70 kW
10.90 kW
12.00 kW
67 dB(A)
71 dB(A)
59 dB(A)
213 W
1.54 A
420 m3/h
4.50 kW
5.60 kW
5.70 kW
37 dB(A)
40 dB(A)
30 dB(A)
19 W
0.18 A
970 m3/h
8.80 kW
11.90 kW
12.70 kW
56 dB(A)
59 dB(A)
46 dB(A)
136 W
0.89 A
1525 m /h
12.50 kW
17.80 kW
20.00 kW
66 dB(A)
70 dB(A)
57 dB(A)
296 W
2.09 A
630 m3/h
6.70 kW
8.50 kW
9.00 kW
45 dB(A)
48 dB(A)
36 dB(A)
36 W
0.30 A
1410 m /h
12.70 kW
17.40 kW
19.30 kW
61 dB(A)
64 dB(A)
53 dB(A)
258 W
1.84 A
2090 m3/h
17.20 kW
24.60 kW
27.80 kW
70 dB(A)
73 dB(A)
61 dB(A)
510 W
3.43 A
735 m3/h
8.10 kW
10.30 kW
10.90 kW
43 dB(A)
42 dB(A)
35 dB(A)
34 W
0.29 A
1735 m /h
16.30 kW
22.20 kW
24.30 kW
61 dB(A)
60 dB(A)
51 dB(A)
259 W
1.75 A
2800 m3/h
23.60 kW
33.80 kW
38.00 kW
71 dB(A)
72 dB(A)
61 dB(A)
591 W
3.76 A
*For an example of the conversion of the sound power level in the sound pressure level, see page 16.
PR-2014-0006-GB Subject to modification K1-02/2015
[13]
Cooling and heating - Recirculating air
4-pipe system - Chilled and warm water
Air volume flow V at external pressure of 50 Pa in speed 3 and capacity stage 1
Cooling capacity
PCW 6 / 12 C
Air intake 27 C / 46 %
Capacity stage
Sound power level*
at capacity stage 1
Motor data
EC motor
1 ~ 230 Volt
Size
Speed
Max.
CS1
CS2
Intake
Discharg
e
Casing
Max.
Max.
335 m3/h
2.10 kW
2.20 kW
41 dB(A)
44 dB(A)
36 dB(A)
20 W
0.13 A
610 m /h
3.40 kW
3.80 kW
57 dB(A)
60 dB(A)
50 dB(A)
100 W
0.72 A
910 m3/h
4.70 kW
5.30 kW
67 dB(A)
71 dB(A)
59 dB(A)
213 W
1.54 A
400 m3/h
2.50 kW
2.70 kW
37 dB(A)
40 dB(A)
30 dB(A)
19 W
0.18 A
920 m3/h
5.10 kW
5.70 kW
56 dB(A)
59 dB(A)
46 dB(A)
136 W
0.89 A
1460 m /h
7.40 kW
8.40 kW
66 dB(A)
70 dB(A)
57 dB(A)
296 W
2.09 A
600 m3/h
3.80 kW
4.20 kW
45 dB(A)
48 dB(A)
36 dB(A)
36 W
0.30 A
1340 m /h
7.50 kW
8.40 kW
61 dB(A)
64 dB(A)
53 dB(A)
258 W
1.84 A
1995 m3/h
10.20 kW
11.70 kW
70 dB(A)
73 dB(A)
61 dB(A)
510 W
3.43 A
710 m3/h
4.70 kW
5.10 kW
43 dB(A)
42 dB(A)
35 dB(A)
34 W
0.29 A
1665 m /h
9.60 kW
10.70 kW
61 dB(A)
60 dB(A)
51 dB(A)
259 W
1.75 A
2695 m3/h
14.10 kW
16.10 kW
71 dB(A)
72 dB(A)
61 dB(A)
591 W
3.76 A
*For an example of the conversion of the sound power level in the sound pressure level, see page 16.
[14]
PR-2014-0006-GB Subject to modification K1-02/2015
Cooling and heating - Recirculating air
4-pipe system - Chilled and warm water
Air volume flow V at external pressure of 50 Pa in speed 3 and capacity stage 1
Thermal output
PWW 70 / 50 C
Air intake 20 C
Capacity stage
Sound power level*
at capacity stage 1
Motor data
EC motor
1 ~ 230 Volt
Size
Speed
Max.
CS1
CS2
Intake
Discharg
e
Casing
Max.
Max.
335 m3/h
2.30 kW
3.30 kW
41 dB(A)
44 dB(A)
36 dB(A)
20 W
0.13 A
610 m /h
3.50 kW
5.30 kW
56 dB(A)
60 dB(A)
50 dB(A)
100 W
0.72 A
910 m3/h
4.60 kW
7.40 kW
67 dB(A)
71 dB(A)
59 dB(A)
213 W
1.54 A
400 m3/h
2.90 kW
4.10 kW
37 dB(A)
39 dB(A)
30 dB(A)
19 W
0.18 A
920 m3/h
5.30 kW
8.00 kW
56 dB(A)
59 dB(A)
46 dB(A)
136 W
0.89 A
1460 m /h
7.30 kW
11.60 kW
66 dB(A)
70 dB(A)
57 dB(A)
296 W
2.09 A
600 m3/h
4.20 kW
6.20 kW
45 dB(A)
47 dB(A)
36 dB(A)
36 W
0.30 A
1340 m /h
7.50 kW
11.80 kW
61 dB(A)
64 dB(A)
53 dB(A)
258 W
1.84 A
1995 m3/h
9.90 kW
16.10 kW
69 dB(A)
73 dB(A)
61 dB(A)
510 W
3.43 A
710 m3/h
5.10 kW
7.50 kW
43 dB(A)
42 dB(A)
35 dB(A)
34 W
0.29 A
1665 m /h
9.50 kW
15.00 kW
60 dB(A)
60 dB(A)
51 dB(A)
259 W
1.75 A
2695 m3/h
13.40 kW
21.80 kW
71 dB(A)
72 dB(A)
61 dB(A)
591 W
3.76 A
*For an example of the conversion of the sound power level in the sound pressure level, see page 16.
PR-2014-0006-GB Subject to modification K1-02/2015
[15]
GEA Heat Exchangers
GEA Air Treatment GmbH
Zweigniederlassung GEA Happel Klimatechnik
Sdstr. 48, 44625 Herne, Germany
Phone: +49 2325 468-00, Fax: +49 2325 468-254
[email protected], www.gea-hx.com