0% found this document useful (0 votes)
4K views24 pages

PRO Side Mount Packaged Refrigeration System: Installation and Operations Manual

Installation and Operations Manual Bulletin H-IM-PSM may 2008 Part Number 25008001 PRO3 side mount packaged refrigerator system.

Uploaded by

GuGi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4K views24 pages

PRO Side Mount Packaged Refrigeration System: Installation and Operations Manual

Installation and Operations Manual Bulletin H-IM-PSM may 2008 Part Number 25008001 PRO3 side mount packaged refrigerator system.

Uploaded by

GuGi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

Installation and

Operations Manual
Bulletin H-IM-PSM

May 2008

Part Number 25008001

PRO3 Side Mount


Packaged Refrigeration System

Installation and Operations Manual

Table of Contents
Inspection............................................................................3
Installation Requirements .................................................3
Recommended Unit Placement
FIGURE 1: System Space Requirements | Back View
FIGURE 2: System Space Requirements | Side View

Access Requirements .........................................................3


Condensing Unit Section (Exterior of box)
FIGURE 3: Access Requirements | Top View

Evaporator Section (Interior of box)


Installation Procedures................................................... 4-7
FIGURE 4: Cutout Location
FIGURE 5: Cutout Dimensions | Small Cabinet
FIGURE 6: Cutout Dimensions | Large Cabinet
FIGURE7: Plug Detail
FIGURE 8: Plug Detail | Small Cabinet
FIGURE9: Plug Detail | Large Cabinet

Rigging

FIGURE10: Rigging Holes


FIGURE 11: Rigging Holes | Front View

Mounting

FIGURE12: Mounting Holes | Side View


FIGURE 13: Mounting Holes | Front View
FIGURE 14: Mounting Holes | Top View

Electrical Connection
Refrigeration Sequence of Operation................................7
Table 1 Model PST | Default Temperature Control Settings

Cooler Temperature Control


Coolers: Air-defrost Operation
Cooler with Electric Defrost and Freezer Temperature/
Defrost Control
Cooler with Electric Defrost and Freezer Sequence of
Operation
Programming Electronic Controller............................. 8-16
Dixell Electronic Controller (XR40CX and XR60CX)
Front Panel Commands ..................................................................8
Use of LEDs...........................................................................................8
Max. & Min. Temperature Memorization: .................................9
How to See the Min. Temperature
How to See the Max. Temperature
How to Reset the Max. & Min. Temperature Recorded
Main Functions: .................................................................................9
How to see the set-point
How to change the set-point
How to start a manual defrost
How to change a parameter value

The Hidden Menu .............................................................................9


How to Enter the Hidden Parameters
How to Move a Parameter from the Hidden Menu
How to Lock the Keyboard
The Continuous Cycle
The On/Off Function
Parameters .................................................................................10-11
Regulation
Display
Defrost
Fans (XR60CX ONLY)
Alarms
How to use the Hot Key ................................................................11
How to program a Hot Key from the Instrument
Alarm Signals ...................................................................................12
Alarm Recovery
Other Messages ..............................................................................12
Technical Data .................................................................................12
Connections .....................................................................................13
Service Information..........................................................13
Maintenance
System Standard Maintenance Guidelines
Drain Pan Removal..............................................................................14
FIGURE 15: Drain Pan Removal | View A
FIGURE 16: Drain Pan Removal | View B

Wiring Diagrams..........................................................15-18
Diagram 1 High Temperature Cooler | Air Defrost | Large Cabinet
Diagram 2 High Temperature Cooler | Air Defrost | Small Cabinet
Diagram 3 Freezer and Medium Temperature Cooler | Electric Defrost | Small Cabinet
Diagram 4 Freezer and Medium Temperature Cooler | Electric Defrost | Large Cabinet

Performance, Capacities and Specifications ..................19


Table 2 Cooler Application | Air Defrost | BTUH at 95F ambient
Table 3 Cooler Application | Electric Defrost | BTUH at 95F ambient
Table 4 Freezer Application | Electric Defrost | BTUH at 95F ambient
Table 5 Specifications

Dimensions.................................................................. 20-21
Diagram 5 Dimensions | Small Cabinet: 1-fan | Top view
Diagram 6 Dimensions | Small Cabinet: 1-fan | Side view
Diagram 7 Dimensions | Small Cabinet: 1-fan | Back view
Diagram 8 Dimensions | Large Cabinet: 2-fan | Top view
Diagram 9 Dimensions | Large Cabinet: 1-fan | Side view
Diagram 10 Dimensions | Large Cabinet: 1-fan | Back view

Replacement Parts by InterLink .....................................22


Table 6 Replacement Parts List

Warranty Statement ........................................................23

2008 Heatcraft Refrigeration Products LLC

PRO3 Side Mount Packaged Refrigeration System

Inspection
1.

Each shipment should be carefully checked against the bill


of lading.

2.

The shipping receipt should not be signed until all items listed
on the bill of lading have been accounted for.

3.

Check packaging for signs of damage.

4.

Any shortage or damages should be immediately reported to


the delivering carrier.

5.

Damaged material becomes the delivering carriers


responsibility, and should not be returned to the manufacturer
unless prior approval is given to do so.

6.

All units are shipped on heavy skids and enclosed in open


crating. Generally, it is advisable to bring the unit as close to
its final location as possible before removing crating.

7.

When unpacking the system, care should be taken to


prevent damage.

8.

Avoid removing the shipping base until the unit has been
moved to the final destination.

Installation Requirements
Recommended Unit Placement
1.

Ensure that the structural integrity of the box can withstand


the weight of the side-mounted equipment.

2.

The air pattern must cover the entire room

3.

Location of aisles, racks, etc. must be known

4.

For space requirements, see FIGURES 1 and 2

Figure 2: System Space Requirements | Side View

24"

Leave these areas


unobstructed

Access Requirements
Condensing Unit Section (Exterior of box)
Provide adequate access space (minimum 36") on the right side of
the unit for electric box clearance. The front of the unit should have
a minimum of 24" clearance for compressor and fan motor service.
The left side of the unit should be a minimum of 8" clearance.
Figure 3: Access Requirements | Top View

Figure 1: System Space Requirements | Back View

18"

18"

4.00

36"
8"
24"

TOP VIEW

Evaporator Section (Interior of box)

Leave this area unobstructed

The front of the evaporator should have no obstructions since this


is the leaving airside of the evaporator. There should also be no
obstructions under the evaporator. A minimum of 8" clearance should
be held on each side of the evaporator for drain pan removal.

PRO3 Side Mount Packaged Refrigeration System Installation and Operations Manual, May 2008 

Installation and Operations Manual

Installation Procedures

NOTE: Installation and maintenance to be performed only

by qualified personnel who are familiar with local codes and


regulations and are experienced with this type of equipment.

CAUTION: Make sure all power sources are disconnected


before any service work is done on units.
A.) Inspect packaging/unit for shipping damage
B.) Review the space and location requirements provided for your
method of installation.

5.




The unit will need to be lifted to the appropriate height and


inserted into the open slots. The bottom of the unit should
be temporarily supported during the remainder of the installation
process (no portion of the unit should be supported by the
bottom of the evaporator section as this WILL cause damage to
the drain pan).

6. Set and secure the roof of the box and firmly attach the unit to

the box and carefully seal all seams and penetration points.
Figure 4: Cutout Location

C.) Follow installation instructions listed in method #1 or #2

Installation Method #1

Top Installation (See Figures 4, 5 and 6)


This installation method is the recommended installation method
in applications where it is feasible.
In order to install a unit using this method, you will need to provide
cutout slots for the arms. The unit should be placed on the wall
prior to setting and securing the roof of the box.
Please use the following guidelines when completing the installation
in this manner.
1. You will need to provide finished slots with the appropriate

dimensions in the box wall. See FIGURES 5 and 6.
2. The slots can straddle a seam but they should not be on a seam.

See Figure 4.
3. The cut-out sections should not be placed in a location where

they would interfere with any cam locks.
4. It is preferred that a cam lock be placed in between the cutouts

to give additional support

CAUTION: Do not support any portion of the unit by the


drain pan.
Figure 6: Cutout Dimensions | Large Cabinet

Figure 5: Cutout Dimensions | Small Cabinet

28.75" TYP

22.75" TYP
2.62" TYP

2.62" TYP

20.25" TYP

CUTOUTS

20.25" TYP

CUTOUTS

PRO3 Side Mount Packaged Refrigeration System

Installation Method #2

Figure 7: Plug Detail

Side Installation (See FIGURES 7, 8, and 9)


This installation method is intended for applications that have
height restrictions that do not allow the unit to be installed from
above (see method #1) and installations into pre-existing boxes
where it is impractical to remove the roof.
In order to install a unit using this method, you must provide an
additional plug section of the box to fill in the open space between
evaporator arms after installation. This section should contain cam
locks to anchor it in place.

SEE PLUG DETAIL

Please use the following guidelines when completing the installation


in this manner.
1. Provide a finished opening with the appropriate dimensions

from Figure 8 or 9.
2. The cut-out section should not be placed in a location where it

would degrade the structural integrity of the box (should not

interfere with cam locks)
3.




The unit will need to be lifted to the appropriate height and


inserted into the open slot. The bottom of the unit should be
temporarily supported during the remainder of the installation
process (no portion of the unit should be supported by the
bottom of the evaporator section as this WILL cause damage to
the drain pan).

4. You should use cam locks to re-connect the plug section after

installing the unit, firmly attach the unit to the box and carefully

seal all seams.

Figure 8: Plug Detail | Small Cabinet

Figure 9: Plug Detail | Large Cabinet

29.00

23.00

20.00
CAMLOCKS
4 PLACES

20.07

CAMLOCKS
4 PLACES

PRO3 Side Mount Packaged Refrigeration System Installation and Operations Manual, May 2008 

Installation and Operations Manual


Rigging

4.

CAUTION: Avoid contact with sharp edges and coil


surfaces. They are a potential injury hazard. Wear gloves
during moving and rigging.

Ensure that the condensing unit airflow is not obstructed after


removing the temporary support.

5.

Do not obstruct the evaporator airflow with shelving. The area


below the evaporator should be left completely open.

6.

Connect unit to power supply through knock-out provided


above electrical box using all local wiring codes.

7.

Apply power to unit. All controls are preset to factory default


settings. See Table 1 (next page).

8.

Check the unit for proper operation.

Caution should be exercised when moving these units. To prevent


damage to the unit housing during rigging, cables or chains used
must be held apart by spacer bars. Rigging holes are provided on
all models. See FIGURES 10 and 11.
Figure 10: Rigging Holes

Figure 12: Mounting Holes | Side View


Mounting holes

Figure 11: Rigging Holes | Front View

Rigging holes
FIGURE 13: Mounting Holes | Front View

Mounting holes

Front panels
removed
for clarity

Mounting
The system requires two through-bolts to be used to connect to
the roof panel. A minimum of four through-bolts should be used to
connect to the side panel of the box. The opposite side of the box
should be reinforced with wood or metal to prevent the bolts from
pulling through the panel. See FIGURES 12, 13 and 14 for locations.

Mounting
holes

FIGURE 14: Mounting Holes | Top View

Through bolts should be insulated or non-conductive to prevent


sweating. All penetrations to the box should be caulked to prevent
moisture from entering the box.
1.

Install two through bolts to secure the unit to the wall. The inside
of the box should be reinforced with wood or metal for proper
when mounting of the unit to the box with through bolts.

2.

Install and secure the roof of the box. Inside the box,
provisions have been made to secure the evaporator section
to the roof panel with through bolts.

3.

The area between the evaporator section and the roof


panel should be caulked to meet NSF codes. In addition, the
openings where the unit was lowered into the box panel
should be caulked to prevent any infiltration from the outside
area into the box.

Top not shown


for clarity

Mounting holes

PRO3 Side Mount Packaged Refrigeration System


Electrical Connection

Cooler with Electric Defrost and Freezer


Sequence of Operation

1.

Refer to all local codes for proper connection.

2.

A knock-out is provided for 1" conduit on the side of the


condensing unit section above the electrical box. See FIGURE 12.

3.

Wire will be brought into the electrical box through the


bottom of the electrical box and connected to the top of the
contactor.

Refrigeration Sequence of Operation


1.

Power is provided to the temperature control, compressor


contactor and cooler evaporator fans.

2.

The temperature controller closes and energizes the


compressor contactor, starting the compressor, evaporator
and condenser fan(s).

3.

When the system reaches the desired box temperature, the


temperature control will de-energize the compressor contactor.
Evaporator fans will continue to operate at this point.

4.

When the fixture temperature rises above the set point


and minimum off-time has elapsed, the temperature control
will close and re-energize the compressor contactor.

Power is provided to the temperature control and compressor


contactor. The drain line heater as well as the crankcase heaters will
also have continuous power supplied to them.
The temperature controller energizes the compressor contactor,
starting the compressor and condenser fan(s). The evaporator fans
will be energized by the electronic controller.
When the system reaches the desired box temperature, the
temperature control will de-energize the compressor contactor and
the evaporator fans.
When the temperature rises above the set point and minimum offtime (4 minutes) has elapsed, the temperature control will close and
re-energize the compressor contactor.
1.

During normal operation, at the preset times of day, the


temperature/defrost control will de-energize the compressor
contactor and evaporator fans and energize the defrost
heaters. These functions are controlled through relays on the
controller.

2.

When the coil has defrosted fully and has reached thepreset
coil temperature (as sensed by the coil temperature sensor)
the defrost heater de-energizes and the fan delay and drip
sequences begin.

3.

The temperature/defrost control energizes the compressor


contactor, starting the compressor and condenser fan(s).

4.

Freezer evaporator fans will be energized by the temperature/


defrost control when the coil temperaturereaches 35F or fan
delay time has elapsed.

Coolers: Air-defrost Operation


Air defrost units are pre-programmed for 4 defrost per day. These
periods are reprogrammable. When the coil temperature reaches
38F, the control will terminate the defrost cycle.
For programming information see pages 7-16.

Cooler with Electric Defrost and Freezer


Temperature/Defrost Control
PRO3 packaged refrigeration system cooler with electric defrost and
freezer units come factory equipped with an electronic temperature/
defrost control.
For programming information see pages 7-16.

Table 1 Model PST | Default Temperature Control Settings


Application:
Temperature set
points

Defrost start times

Cooler: 35 F

Every 3 hours of
compressor run time

Cooler w/ Electric
Defrost: 34 F
Freezer: -10 F

4 times / day

Defrost
Duration

Drip Time

Fan Delay

Defrost
Termination
Set Point

Minutes
60

38 F

40

65 F

40

65 F

PRO3 Side Mount Packaged Refrigeration System Installation and Operations Manual, May 2008 

Installation and Operations Manual

Programming XR-40CX or XR-60CX


Dixell Electronic Controller

Front Panel Commands


Button

Reprinted with permission from Dixell.

The Dixell XR-40CX (High Temperature) and XR-60CX (Medium


and Low Temperature) are fully configurable electronic
refrigeration controllers. These controls are used on PRO3 Side
Mount units. All parameter values are reprogrammable and are
stored in the non-volatile memory.

(DEF) To start a manual defrost


(UP): To see the max. stored temperature;
in programming mode it browses
the parameter codes or increases the
displayed value
(DOWN) To see the min stored
temperature; in programming mode it
browses the parameter codes or decreases
the displayed value

The controller uses two levels of programming that can be


accessed through the keypad. The first level is the user level. It
gives access to six settings temperature differential, defrost
cycle intervals, defrost termination temperature, draining time,
defrost fan delay and fan stop temperature.
The second level is the service level. It allows access to all other
parameters. It is recommended that changes in this level be
made only by a qualified technician.

Command
To display target set point; in
programming mode it selects a parameter
or confirm an operation

To switch the instrument off, if onF = oFF


Not enabled
KEY COMBINATIONS
To lock & unlock the keyboard
+
To enter in programming mode
+
To return to the room temperature display
+

Use of LEDs
LED

LED MODE

FUNCTION

ON

Compressor enabled

Flashing

Anti-short cycle delay


enabled

ON

Defrost enabled

Flashing

Drip time in progress

ON

Fans enabled (XR60CX only)

Flashing

Fans delay after defrost in


progress (XR60CX only)

ON

An alarm is occurring

ON

Continuous cycle is running

ON

Energy saving enabled

C/F

ON

Measurement unit

C/F

Flashing

Programming phase

PRO3 Side Mount Packaged Refrigeration System

Max. & Min. Temperature Memorization

The Hidden Menu

How to see the min. temperature

The hidden menu Includes all the parameters of the instrument.

1.

Press and release the DOWN key.

How to enter the hidden parameters

2.

The Lo message will be displayed followed by the minimum


temperature recorded.

1.

Enter the Programming mode by pressing the Set + DOWN


keys for 3 seconds (the C or F LED starts blinking).

3.

By pressing the DOWN key again or by waiting 5 seconds the


normal display will be restored.

2.

Release the keys, then push again the Set+DOWN keys


for more than 7 seconds. The Pr2 label will be displayed
immediately followed from the HY parameter.
NOW YOU ARE IN THE HIDDEN MENU

How to see the max. temperature


1.

Press and release the UP key.

3.

Select the required parameter.

2.

The Hi message will be displayed followed by the maximum


temperature recorded.

4.

Press the SET key to display its value

3.

By pressing the UP key again or by waiting 5 seconds the


normal display will be restored.

5.

Use UP or DOWN to change its value.

6.

Press SET to store the new value and move to the following
parameter.

How to reset the max and min temperature recorded


1.

Hold press the SET key for more than 3 seconds, while the
max. or min temperature is displayed. (rSt message will
be displayed)

2.

To confirm the operation the rSt message starts blinking and


the normal temperature will be displayed

Main Functions
How to see the set-point
1. Push and immediately release SET key: the
display will show the set point value
2.

Push and immediately release the SET key or wait 5 seconds to


display the probe value again

How to change the set-point

To exit: Press SET + UP or wait 15 seconds without pressing a key.

NOTE 1: If no parameter is present in Pr1, after 3 seconds the noP


message is displayed. Keep the keys pushed until the Pr2 message
is displayed.
NOTE 2: The set value is stored even when the procedure is exited
by waiting the time-out to expire.
How to move a parameter from the hidden menu to
the first level and vice versa
Each parameter present in the HIDDEN MENU can be removed or
put into THE FIRST LEVEL (user level) by pressing SET + Down.
In HIDDEN MENU when a parameter is present in First Level the
decimal point is on.
How to lock the keyboard
1.

Keep the UP + DOWN keys pressed for more than 3 seconds.

2.

To change the set value push UP or DOWN arrows within 10


seconds

The POF message will be displayed and the keyboard will be


locked. At this point it will be possible only to see the set point
or the MAX o Min temperature stored

3.

To memorize the new set point value push SET key again or
wait 10 seconds

If a key is pressed more than 3 seconds the POF message will


be displayed.

To unlock the keyboard

1.

Push SET for more than 2 seconds to change the set-point value

2.

The value of the set-point will be displayed and the C or F


LED starts blinking

3.
4.

How to start a manual defrost


Push DEF key for more than 2 seconds and a manual
defrost will start.

Keep the UP + DOWN keys pressed for more than 3 seconds, until
the Pon message is displayed.

The continuous cycle

1.

Enter the Programming mode by pressing the SET + DOWN


keys for 3 seconds (the C or F LED starts blinking)

When defrost is not in progress, it can be activated by holding the


UP key pressed for about 3 seconds. The compressor operates to
maintain the ccS set point for the time set through the CCt parameter.
The cycle can be terminated before the end of the set time using the
same activation key UP for 3 seconds.

.

Select the required parameter. Press SET to display its value.

The on/off function

3.

Use UP or DOWN to change its value

4.

Press SET to store the new value and move to the following
parameter

With onF = oFF, pushing the ON/OFF key, the instrument is


switched off. The OFF message is displayed. In this configuration,

How to change a parameter value


To change a parameter value:

To exit: Press SET + UP or wait 15 seconds without pressing a key

NOTE: The set value is stored even when the procedure is exited by
waiting the time-out to expire.

To switch the instrument on, push again the ON/OFF key.


WARNING: Loads connected to the normally closed contacts of
the relays are always supplied and under voltage, even if the
instrument is in stand by mode.

PRO3 Side Mount Packaged Refrigeration System Installation and Operations Manual, May 2008 

Installation and Operations Manual

Parameters
Label

Characteristic

Description

Menu/User
Level

tdF

dtE

IdF

MdF

Fdt

10

Defrost type

EL = electrical heater; in = hot gas

(-5050 C/ -58122F) (Enabled only


Defrost termination when EdF=Pb) sets the temperature
temperature
measured by the evaporator probe,
which causes the end of defrost
(0120h) Determines the time
Interval between
interval between the beginning of
defrost cycles
two defrost cycles
(0255min) When P2P = n, (not
evaporator probe: timed defrost) it
(Maximum) length
sets the defrost duration, when P2P =
for defrost
y (defrost end based on temperature)
it sets the maximum length for defrost
(0120 min) time interval between
reaching defrost termination
temperature and the restoring of the
Drip time
controls normal operation. This time
allows the evaporator to eliminate
water drops that might have formed
due to defrost

Default Settings
Low
Temp.

Medium
Temp.

High
Temp.

LS ~ US

-10

34

38

Pr1

1~ 45

Pr2

-67 ~ SET

-23

25

33

Pr2

SET ~ 302F

37

40

45

Pr2

-21~21

Pr2

0 ~ 255
minutes

Pr2

0 ~ 50 minutes

Pr2

0 ~ 255
minutes

Regulation
SEt
Set Point
(0,1 25,5C / 1255 F) Intervention
differential for set point. Compressor
Hy
Differential
Cut IN is Set Point + differential (Hy).
Compressor Cut OUT is when the
temperature reaches the set point
(- 50CSET/-58FSET): Sets the
LS
Minimum set point
minimum value for the set point..
(SET110C/ SET230F). Set the
US
Maximum set point
maximum value for set point.
(-12.012.0C; -120120F) allows
Thermostat probe
Ot
to adjust possible offset of the
calibration
thermostat probe
(0255min) This function is
enabled at the initial start up of the
Outputs activation
OdS
instrument and inhibits any output
delay at start up
activation for the period of time set in
the parameter
(050 min) minimum interval
Anti-short cycle
AC
between the compressor stop and
delay
the following restart
(0255 min) time during which the
Compressor OFF
compressor is OFF in case of faulty
COF time with faulty
thermostat probe. With COF=0
probe
compressor is always active
Display
C=Celsius; F=Fahrenheit. WARNING:
When the measurement unit is
Temperature
changed the SET point and the values
CF
measurement unit of the parameters Hy, LS, US, Ot, ALU
and ALL have to be checked and
modified if necessary
Defrost

Possible
Settings

Pr2

C = Celsius
F =Fahrenheit

Pr2

EL = electric
defrost / in =
hot gas defrost

EL

EL

EL

Pr1

-58~122

65

65

38

Pr1

0 ~ 120 hours

Pr2

0 ~ 255
minutes

40

40

60

Pr1

0 ~ 255
minutes

PRO3 Side Mount Packaged Refrigeration System

Label

Characteristic

Fans (XR60CX only)


Fans delay after
Fnd
defrost

Fct

Temperature
differential
avoiding short
cycles of fans

FSt

Fans stop
temperature

Description

(0255min) Interval between end of


defrost and evaporator fans start
(059C; Fct=0 function disabled).
If the difference of temperature
between the evaporator and the
room probes is more than the value
of the Fct parameter, the fans are
switched on
(-5050C/122F) setting of
temperature, detected by
evaporator probe, above which fans
are always OFF

Menu/User
Level

Possible
Settings

Pr1

Default Settings
Low
Temp.

Medium
Temp.

High
Temp.

0 ~ 255
minutes

Not
Applicable

Pr2

0~90

10

10

Not
Applicable

Pr1

-58~122

35

35

Not
Applicable

Pr2

rE = relative to
set point
Ab = absolute

Ab

Ab

Ab

Pr2

ALL~ 302

38

50

50

Pr2

-58~ ALu

-25

15

30

Alarms

ALC

ALU
ALL

(Ab; rE) Ab= absolute temperature:


alarm temperature is given by the
ALL or ALU values. rE = temperature
Temperature alarms
alarms are referred to the set point.
configuration
Temperature alarm is enabled
when the temperature exceeds the
SET+ALU or SET-ALL values
(SET110C; SET230F) when this
MAXIMUM
temperature is reached the alarm is
temperature alarm
enabled, after the ALd delay time
-50.0 SETC; -58230F when this
Minimum
temperature is reached the alarm is
temperature alarm
enabled, after the ALd delay time

How to Use the Hot Key


How to program a hot key from the instrument
(upload)
1.

Program one controller with the front keypad.

2.

When the controller is ON, insert the Hot key and push UP;
the uPL message appears followed a by flashing End

1.

Push SET key and the End will stop flashing.

2.

Turn OFF the instrument remove the Hot Key, then turn it
ON again.

NOTE: The Err message is displayed for failed programming. In


this case push again o key if you want to restart the upload again
or remove the Hot key to abort the operation.
How to program a hot key from the instrument
(download)
1.

Turn OFF the instrument.

2.

Insert a programmed Hot Key into the 5 PIN receptacle and


then turn the Controller ON.

3.

Automatically the parameter list of the Hot Key is


downloaded into the Controller memory, the doL message is
blinking followed a by flashing End.

4.

After 10 seconds the instrument will restart working with the


new parameters.

5.

Remove the Hot Key.

NOTE: The message Err is displayed for failed programming. In


this case turn the unit off and then on if you want to restart the
download again or remove the Hot key to abort the operation.
PRO3 Side Mount Packaged Refrigeration System Installation and Operations Manual, May 2008 11

Installation and Operations Manual


Alarm Signals

Technical Data

Message

Cause

Outputs

P1

Room probe failure

Compressor output according


to parameters Con and COF

P2

Evaporator probe
failure

Defrost end is timed

P3

Third probe failure

Outputs unchanged

P4

Fourth probe
failure

Outputs unchanged

HA

Maximum
temperature alarm

Outputs unchanged

LA

Minimum
temperature alarm

Outputs unchanged

HA2

Condenser high
temperature

It depends on the Ac2


parameter

LA2

Condenser low
temperature

It depends on the bLL


parameter

dA

Door open

Compressor and fans restarts

EA

External alarm

Output unchanged

Alarm Recovery

Characteristic

Description

Housing

self extinguishing ABS

Case

XR40CX/XR60CX frontal 32x74 mm;


depth 60mm

Mounting

XR40CX/XR60CX panel mounting in a


71x29mm panel cut-out

Protection

IP20

Frontal protection

XR40CX/XR60CX IP65

Connections

Screw terminal block 2,5 mm2 wiring

Power supply

according to the model: 12Vac/dc,


10%; 24Vac/dc, 10%; 230Vac 10%,
50/60Hz, 110Vac 10%, 50/60Hz

Power absorption

3VA max

Display

3 digits, red LED, 14,2 mm high;

Inputs

Up to 4 NTC or PTC probes

Digital input

free voltage contact

Relay outputs

compressor: SPST 8(3) A, 250Vac; SPST


16(6)A 250Vac or 20(8)A 250Vac
defrost: SPDT 8(3) A, 250Vac
fan (XR60CX only): SPST 8(3) A, 250Vac
or SPST 5(2) A

Data storing

on the non-volatile memory (EEPROM)

Kind of action

1B

Pollution grade

Software class

Probe alarms P1, P2, P3 and P4 start some seconds after the fault
in the related probe; they automatically stop some seconds after
the probe restarts normal operation. Check connections before
replacing the probe.

Rated impulsive voltage 2500V

Temperature alarms HA, LA, HA2 and LA2 automatically stop as soon
as the temperature returns to normal values.

Other Messages
Message Meaning
Pon
Keyboard unlocked
PoF
Keyboard locked
In programming mode: none parameter is present in Pr1
noP
On the display the selected probe is not enabled
noA
None alarm is recorded

12

Overvoltage Category

II

Operating temperature

060 C

Storage temperature

-3085 C

Relative humidity

2085% (no condensing)

Measuring and
regulation range

NTC probe: -40110C (-40230F)

Resolution

0,1 C or 1C or 1 F (selectable)

Accuracy (ambient
temp. 25C)

0,7 C 1 digit

PTC probe: -50150C (-58302F)

PRO3 Side Mount Packaged Refrigeration System

Service Information

Connections
XR40CX
The X-REP output excludes the TTL output. Its present in the
following codes: XR40CX- xx2xx, XR40CX xx3xx; XR40CX xx6xx;
XR40CX xx7xx;
The digital input configurable as third probe is present in the
following codes: XR40CX- xx4xx, XR40CX xx5xx; XR40CX xx6xx;
XR40CX xx7xx;
8A compressor

.p
va
E

m
o
o
R

9 10 11 1
8(3)A250V


Def

8(3)A250V

N.C.

8
Hot Key/IV Probe
TTL or X-REPoutput

Comp

All PRO3 packaged refrigeration system units are designed for


maximum durability, reliability and simplicity. The PRO3 packaged
refrigeration system comes to you ready for operation, fully charged
and with all controls preset at the factory. The following information
is provided as an aid in the event that service is required.

Maintenance
The evaporator section of a PRO3 packaged refrigeration system
should be checked at least once for proper defrosting because the
amount and pattern of frosting can vary greatly.
The frost build-up is dependent on the temperature of the room,
the type of product being stored, how often new product is brought
into the room and percentage of time the door to the room is open.
It may be necessary to periodically change the number of defrost
cycles or adjust the duration of defrost.

System Standard Maintenance Guidelines


After first year of operation and under normal usage, maintenance
should cover the following items at least once every six months:

Line

20A compressor

.p
av
E

m
oo
R

1.

Check and tighten ALL electrical connections.

2.

Check all wiring and insulators.

3.

Check contactors for proper operation and for worn contact


points.

4.

Check all fan motors. Tighten motor mount bolts/ nuts and
tighten fan set screws.

5.

Clean the condenser coil surface.

6.

Check the operation of the control system. Make certain all


safety controls are operating properly.

9 10 11 1
8(3)A250V


Def

20(8)A250V

N.C.

8
Hot Key/IV probe
TTL or X-REP output

Comp

Line

7.

Check all defrost controls for proper function.

XR60CX

8.

Clean the evaporator coil surface.

The X-REP output excludes the TTL output. Its present in the
following codes: XR60CX- xx2xx, XR60CX xx3xx; XR60CX xx6xx;
XR60CX xx7xx;

9.

Clean the drain pan and check the drain pan and drain line for
proper drainage.

The digital input configurable as third probe is present in the


following codes: XR60CX- xx4xx, XR60CX xx5xx; XR60CX xx6xx;
XR60CX xx7xx;

Evap.

Room

8A or 16A comp. relay - 230 VAC

CAUTION: Unit is critically charged, care must be taken


not to reduce the system refrigerant charge while
taking pressure readings. Technician must compensate
for any refrigerant that might escape the unit into the
gauge tubing.

9 10 11 12

8(3)A
Max 8(3)A250V~
16A

1 2
Def

Line

3
N.C.

7
Hot Key/IV probe/
TTL or X-REP output

Fan Comp

NOTE: The compressor relay is 8(3)A or 16(6)A according to the model.

9 10 11 12

20(8)A250V~
8(3)A250V~

5(1)A

Max
20A

1 2

Room

Evap.

20A comp. relay - 230 VAC

7 8
Hot Key/IV probe

Line

Fan Comp

Def

N.C.TTL or. X-REP output

PRO3 Side Mount Packaged Refrigeration System Installation and Operations Manual, May 2008 13

Installation and Operations Manual


Drain Pan Removal
1.

Remove screws from evaporator side panels

2.

Remove evaporator side panels

3.

Remove screws connecting drain pan to evaporator supports (2)

4.

Remove screws attaching the drain pan bracket to evaporator


supports (2)

5.

Remove the screws attaching the drain pan bracket to the


coil endplates (4)

6.

Lower the drain pan/heater/bracket assembly

7.

Remove nuts and retainers attaching heater.

Reverse process to replace drain pan


FIGURE 15: Drain Pan Removal | View A
HEATER COVER

HEATERS
HEATER COVER SCREWS

DRAIN PAN

DRAIN PAN BRACKET SCREWS


HEATER IN DRAIN PAN
DRAIN PAN TO EVAP
SUPPORT SCREW

DRAIN PAN BRACKET


DRAIN PAN BRACKET SCREW

ECN NO.

REV

DATE

BY

DESCRIPTION

TITLE

SOLID-EDGE
TOLERANCES (UNLESS OTHERWISE SPECIFIED)
COIL ASSEMBLY
SHEET METAL
FINNED LENGTH
CUT SIZE--------------.03
0 TO 24--------------.06
HOLE DIAMETER--------.005
24 TO 75-------------.13
ENDPLATE TUBE HOLE---.001
OVER 75--------------.19
C/L OF HOLES----------.02
CONNECTIONS-----------.13
ANGLES-----------------2
FIN QTY.---------------3%
FORMED DIMENSIONS
BOW (ANY DIRECTION)
0 TO 36--------------.03
12 TO 36-------------.13
36 TO 120------------.06
36 T0 96-------------.19
OVER 120-------------.13
OVER 96--------------.25

FIGURE 16: Drain Pan Removal | View B

WIRE AND CONDUIT


WIRE CUT SIZE----+.50/-.00
CONDUIT CUT SIZE
(NOT UNDER TENSION)
0 TO 12---------+.13/-.00
12 TO 36--------+.38/-.00
OVER 36---------+.75/-.00

TUBING
FRACTIONAL------------.03
1 TO 36---------------.06
OVER 36---------------.13
ANGLES-----------------5

TOLERANCE BLOCK
ISSUED 02/25/94

REV.

DRAIN PAN REMOVAL


Side Mount Package Unit - USA
B
PRODUCT

THIS DOCUMENT CONTAINS MATERIAL AND/OR


INFORMATION WHICH IS THE PROPERTY OF
HEATCRAFT REFRIGERATION PRODUCTS AND IS
SUPPLIED ONLY ON A PROPRIETY BASIS. NO
TRANSMITTAL SHALL BE MADE TO ANY PERSON,
FIRM, OR CORPORATION WITHOUT PRIOR
WRITTEN APPROVAL.

DRAWN

mss5

DATE

APPROVED

ess

SHT.

01-17-08
DATE

01-17-08
1 OF 2

PART NO.

DWG. NO.

REV.

EVAP SIDE PANEL

EVAP SIDE PANEL


DEFROST HEATER
DRAIN PAN

DRAIN PAN BRACKETS

14

SC

DLT -- DRAIN LINE THERMOSTAT


EFM -- EVAPORATOR FAN MOTOR
GND -- GROUND

RC

SR

CCH -- CRANKCASE HEATER


CFM -- CONDENSER FAN MOTOR
DH -- DEFROST HEATER

DLH -- DRAIN LINE HEATER

RIGHT

CFM 3

TOP VIEW OF CONDENSING UNIT

CENTER

LEFT

WN

CFM 2

T1

L2

T2

CFM 1

PFC

WN

L1

T1

CC -- COMPRESSOR CONTACTOR

COMPRESSOR

L1

TFC

BLACK

BLACK

CC

LEGEND

BLUE

BLUE

BLUE

GRAY

SW

BLACK

WN

CCH

DLH
GRAY

T1

HPS -- HIGH PRESSURE SWITCH


PFC -- PRESSURE FAN CYCLE SWITCH
RC -- RUN CAPACITOR

HL -- HEATER LIMIT THERMOSTAT

GND

WN

T2

EFM

EFM

CC

YELLOW
BLACK

DLT

WN

YELLOW

SW -- SWITCH

SC -- START CAPACITOR
SR -- START RELAY

RT -- ROOM THERMOSTAT

HPS

WHITE

T3

208-230V/1phase/60HZ

YELLOW

WN -- WIRE NUT

9 10 11 12

BLUE

1
2

4 5

6 7

REFRIGERATION CONTROLLER

TFC -- TEMPERATURE FAN CYCLE SWITCH

ORANGE

YELLOW

USE COPPER CONDUCTORS ONLY

PRIMARY SINGLE PHASE PROTECTION PROVIDED

ROOM TEMP

FIELD WIRING

FACTORY WIRING

YELLOW

EVAP TEMP

PRO3 Side Mount Packaged Refrigeration System

Wiring Diagrams
Diagram 1 Wiring Diagram | High Temperature Cooler | Air Defrost | Large Cabinet

PRO3 Side Mount Packaged Refrigeration System Installation and Operations Manual, May 2008 15

DLT -- DRAIN LINE THERMOSTAT


EFM -- EVAPORATOR FAN MOTOR
GND -- GROUND

RC

SC

CCH -- CRANKCASE HEATER


CFM -- CONDENSER FAN MOTOR
DH -- DEFROST HEATER

SR

DLH -- DRAIN LINE HEATER

CC -- COMPRESSOR CONTACTOR

COMPRESSOR

RIGHT

LEFT

WN

CFM 2

T1

L2

T2

CFM 1

PFC

L1

T1

TOP VIEW OF CONDENSING UNIT

L1

BLACK

BLACK

CC

LEGEND

BLUE

BLUE

BLUE

GRAY

SW

BLACK

WN

CCH

DLH
GRAY

T1

HPS -- HIGH PRESSURE SWITCH


PFC -- PRESSURE FAN CYCLE SWITCH
RC -- RUN CAPACITOR

HL -- HEATER LIMIT THERMOSTAT

GND

WN

T2

EFM

CC

YELLOW
BLACK

DLT

WN

YELLOW

SW -- SWITCH

SC -- START CAPACITOR
SR -- START RELAY

RT -- ROOM THERMOSTAT

HPS

WHITE

T3

208-230V/1phase/60HZ

YELLOW

1
2

4 5

WN -- WIRE NUT

6 7

REFRIGERATION
CONTROLLER

TFC -- TEMPERATURE FAN CYCLE SWITCH

ORANGE

YELLOW

16
USE COPPER CONDUCTORS ONLY

PRIMARY SINGLE PHASE PROTECTION PROVIDED

9 10 11 12

BLUE
ROOM TEMP

FIELD WIRING

FACTORY WIRING

YELLOW

EVAP TEMP

Installation and Operations Manual

Diagram 2 Wiring Diagram | High Temperature Cooler | Air Defrost | Small Cabinet

RIGHT

LEFT

DLT -- DRAIN LINE THERMOSTAT


EFM -- EVAPORATOR FAN MOTOR
GND -- GROUND

SC

CCH -- CRANKCASE HEATER


CFM -- CONDENSER FAN MOTOR
DH -- DEFROST HEATER

RC

SR

DLH -- DRAIN LINE HEATER

TOP VIEW OF CONDENSING UNIT

CFM 2

L2

T2

CFM 1

T1

WN

L1

T1

CC -- COMPRESSOR CONTACTOR

COMPRESSOR

L1

PFC

BLACK

BLACK

CC

LEGEND

BLUE

BLUE

BLUE

GRAY

SW

BLACK

WN

CCH

DLH
GRAY

HPS -- HIGH PRESSURE SWITCH


PFC -- PRESSURE FAN CYCLE SWITCH
RC -- RUN CAPACITOR

HL -- HEATER LIMIT THERMOSTAT

GND

YELLOW

DH

HL

EFM

F1 F2

BLUE

WHITE

CC

3
X

YELLOW
BLACK

DLT

WN

SW -- SWITCH

SC -- START CAPACITOR
SR -- START RELAY

RT -- ROOM THERMOSTAT

HPS

WHITE

H1 H2

WN
YELLOW

RED

1
2

BLACK

4 5

WN -- WIRE NUT

6 7

10 11 12

REFRIGERATION CONTROLLER

TFC -- TEMPERATURE FAN CYCLE SWITCH

ORANGE

YELLOW

YELLOW

PRIMARY SINGLE PHASE PROTECTION PROVIDED


USE COPPER CONDUCTORS ONLY
208-230V/1 phase/60HZ

BLUE

YELLOW

FIELD WIRING

FACTORY WIRING

DEFROST TEMP

ROOM TEMP

PRO3 Side Mount Packaged Refrigeration System

Diagram 3 Wiring Diagram | Freezer and Medium Temperature Cooler | Electric Defrost | Small Cabinet

PRO3 Side Mount Packaged Refrigeration System Installation and Operations Manual, May 2008 17

18

SR

SC

DLT -- DRAIN LINE THERMOSTAT


EFM -- EVAPORATOR FAN MOTOR
GND -- GROUND

RC

CCH -- CRANKCASE HEATER


CFM -- CONDENSER FAN MOTOR
DH -- DEFROST HEATER

RIGHT

CFM 3

TOP VIEW OF CONDENSING UNIT

CENTER

CFM 2

L2

T2

DLH -- DRAIN LINE HEATER

LEFT

CFM 1

T1

WN

WN

L1

T1

CC -- COMPRESSOR CONTACTOR

COMPRESSOR

L1

PFC

TFC

BLACK

BLACK

CC

LEGEND

BLUE

BLUE

BLUE

GRAY

SW

BLACK

WN

CCH

DLH
GRAY

HPS -- HIGH PRESSURE SWITCH


PFC -- PRESSURE FAN CYCLE SWITCH
RC -- RUN CAPACITOR

HL -- HEATER LIMIT THERMOSTAT

GND

YELLOW

DH

HL

EFM

EFM

F1 F2

BLUE

WHITE

CC

3
X

YELLOW
BLACK

DLT

WN

SW -- SWITCH

SC -- START CAPACITOR
SR -- START RELAY

RT -- ROOM THERMOSTAT

HPS

WHITE

H1 H2

WN

208-230V/1 PHASE/60HZ

USE COPPER CONDUCTORS ONLY

PRIMARY SINGLE PHASE PROTECTION PROVIDED

YELLOW

RED

BLACK

4 5

WN -- WIRE NUT

TFC -- TEMPERATURE FAN CYCLE SWITCH

ORANGE

YELLOW

YELLOW

6 7

10 11 12

REFRIGERATION CONTROLLER

BLUE

YELLOW

FIELD WIRING

FACTORY WIRING

DEFROST TEMP

ROOM TEMP

Installation and Operations Manual

Diagram 4 Wiring Diagram | Freezer and Medium Temperature Cooler | Electric Defrost | Large Cabinet

PRO3 Side Mount Packaged Refrigeration System

Performance, Capacities and Specifications


Table 2 Model PST | Cooler Application | Air Defrost | BTUH at 95F Ambient Temperature
Model
PST070H6B*
PST090H6B*
PST131H6B*
PST147H6B*

Box Temperature
35F
38F
6,641
6,968
8,643
9,064
12,448
13,107
14,081
14,758

Voltage

MCA

208-230/1/60
208-230/1/60
208-230/1/60
208-230/1/60

15
15
15
15

MOPD Evaporator CFM


20
20
20
20

625
625
1,350
1,350

Dimensions
Figure
A
A
B
B

Table 3 Model PST | Cooler Application | Electric Defrost | BTUH at 95F ambient temperature
Model

35F Box Temperature

Voltage

MCA

MOPD

PST066M6B*
PST086M6B*
PST124M6B*
PST141M6B*

6,641
8,643
12,448
14,081

208-230/1/60
208-230/1/60
208-230/1/60
208-230/1/60

15
15
15
15

20
20
20
20

Evaporator
CFM
625
625
1,350
1,350

Dimensions
Figure
A
A
B
B

Table 4 Model PST | Freezer Application | Electric Defrost | BTUH at 95F ambient temperature
Model
PST034L6B*
PST051L6B*
PST057L6B*
PST077L6B*

Box Temperature
0F
-10F
-20F
4,746
3,444
2,260
6,530
5,121
3,720
7,541
5,735
3,918
10,002
7,716
5,689

Voltage

MCA

MOPD

208-230/1/60
208-230/1/60
208-230/1/60
208-230/1/60

15.0
15.0
15.0
20.7

20
20
20
35

Evaporator
CFM
625
625
1,350
1,350

Dimensions
Figure
A
A
B
B

Table 5 Model PST | Specifications


Model

Refrigerant

Coolers
PST070H6B*
R-404A
PST090H6B*
R-404A
PST131H6B*
R-404A
PST147H6B*
R-404A
Coolers with electric defrost
PST066M6B*
R-404A
PST086M6B*
R-404A
PST124M6B*
R-404A
PST141M6B*
R-404A
Freezers
PST034L6B*
R-404A
PST051L6B*
R-404A
PST057L6B*
R-404A
PST077L6B*
R-404A

Refrigerant
Charge (oz.)

Approximate Net Weight


lbs.

kg

36
36
40
40

260
265
320
325

118
120
145
148

36
36
40
40

260
265
320
325

118
120
145
148

36
36
40
40

260
265
320
325

118
120
145
148

* H for PSC, E for EC motor on evaporator section only.

WARNING: This equipment may contain a substance that harms public health and the environment by destroying ozone
in the upper atmosphere. Venting of certain refrigerants to the atmosphere may be illegal in your location. Refrigerant
recovery devices should be used when installing or servicing this product. Consult your local codes for requirements in
your location.
WARNING: Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly. Failure to
follow this warning may result in personal injury or death.
PRO3 Side Mount Packaged Refrigeration System Installation and Operations Manual, May 2008 19

Installation and Operations Manual

Dimensions
Diagram 5 Dimensions | Small Cabinet: 1-fan | Top View

49-1/8"
1248 mm
13-3/8"
340 mm

30-1/2"
775 mm

1-3/4"
44 mm

16-1/4"
413 mm

31-3/4"
806 mm

27-7/8"
708 mm

23"
584 mm

28"
711 mm

Diagram 6 Dimensions | Small Cabinet: 1-fan | Side View

30"
762 mm

Diagram 7 Dimensions | Small Cabinet: 1-fan | Back View

1-3/4"
44 mm

49-1/8"
1248 mm
46-1/4"
1175 mm
29-5/8"
752 mm
20-1/4"
514 mm

1-3/4"
44 mm

35-5/8"
905 mm
34"
864 mm

17-1/4"
438 mm

12-1/4"
311 mm
32-5/8"
905 mm

20

16-5/8"
422 mm

1-5/8"
41 mm

30"
762 mm

PRO3 Side Mount Packaged Refrigeration System

Diagram 8 Dimensions | Large Cabinet: 2-fan | Top View

49-1/8"
1248 mm
13-3/8"
340 mm

36-1/2"
927 mm

1-3/4"
45 mm

16-1/4"
413 mm

37-3/4"
959 mm

33-7/8"
860 mm
29"
737 mm

34"
864 mm

Diagram 9 Dimensions | Large Cabinet: 1-fan | Side View

36"
914 mm

Diagram 10 Dimensions | Large Cabinet: 1-fan | Back View

1-3/4"
44 mm

49-1/8"
1248 mm
46-1/4"
1175 mm
29-5/8"
752 mm
20-1/4"
514 mm

1-5/8"
41 mm

1-3/4"
44 mm

38-1/2"
978 mm

17-1/4"
438 mm

40-1/8"
1019 mm

12-1/4"
311 mm
32-5/8"
905 mm

16-5/8"
422 mm

36"
914 mm

PRO3 Side Mount Packaged Refrigeration System Installation and Operations Manual, May 2008 21

Installation and Operations Manual

Replacement Parts by
Commercial Refrigeration Parts

When contacting the factory for service or replacement parts, refer to the model number and serial number of the unit as stamped on the
serial plate attached to the unit. If replacement parts are required, mention the date of installation of unit and date of failure, along with an
explanation of the malfunctions and a description of the replacement parts required.

Table 6 Model PST | Replacement Parts List


Coolers with
electric defrost

PST090H6B*

PST131H6B*

PST147H6B*

PST066M6B*

PST086M6B*

PST124M6B*

PST141M6B*

PST034L6B*

PST051L6B*

PST057L6B*

PST077L6B*

Part Description

Freezers

PST070H6B*

Coolers

5140C
22901901

1
2

1
2

2
3

2
3

1
2

1
2

2
3

2
3

1
2

1
2

2
3

2
3

25308601
25317701
25308301
23103301
4000104

1
1
2
1
2

1
1
2
1
2

2
2
3
2
3

2
2
3
2
3

1
1
2
1
2

1
1
2
1
2

2
2
3
2
3

2
2
3
2
3

1
1
2
1
2

1
1
2
1
2

2
2
3
2
3

2
2
3
2
3

34915200

21300701
21300801
21300901
5708L

1
1
1

1
1
1

1
1
1

1
1
1

1
1
1
1

1
1
1
1

1
1
1
1

1
1
1
1

1
1
1
1

1
1
1
1

1
1
1
1

1
1
1
1

3
3

1
1
1
1

1
1
1
1

Part Number

Fan Blades
Evaporator
Condenser
Fan Motors
Evaporator, PSC - 208/230 volt
Evaporator, EC - 208/230 volt
Condenser - 208/230
Evaporator fan motor bracket
Condenser fan motor bracket
Contactors
20A, 230-volt
Temperature Control
Freezer control kit -208/230 volt
Cooler with electric defrost-208/230 volt
Cooler control kit - 208/240 volt
Heater limit thermostat
Defrost Heaters
Defrost heaters - 230 volt
Defrost heaters - 230 volt

4312F
4342L

1
1
1
1

1
1
1
1

Outdoor Parts
Fan pressure control
Fan temperature control
Drain line heater
Drain line heater thermostat

28917301
5521R
24753401
28917401

1
1
1
1

1
1
1
1

1
1
1
1

1
1
1
1

1
1
1
1

1
1
1
1

1
1
1
1

1
1
1
1

* H for PSC, E for EC motor on evaporator section only.

Right source. Right parts. Right now.


InterLink is your link to a complete line of dependable and certified commercial refrigeration
parts, accessories and innovative electronic controls for all Heatcraft Refrigeration Products (HRP)
equipment. At InterLink, we provide our wholesalers with a comprehensive selection of product
solutions and innovative technologies for the installed customer base. And every product is built
to ensure the same high performance standards with which all HRP brands are built backed by
a dedicated team to serve every customer need, delivering at the best lead times in the industry.

Dependable. Versatile. Courteous.


Finally, one simple source for all your replacement needs from a name you can trust.
22

For parts, please contact:


Commercial Refrigeration Parts

www.interlinkparts.com or
(800) 686-7278

PRO3 Side Mount Packaged Refrigeration System

Warranty Statement
Heatcraft Refrigeration Products LLC warrants to its direct purchasers
that the PRO3 product, except Service Parts, manufactured by Heatcraft
Refrigeration Products LLC shall be of a merchantable quality, free of
defects in material or workmanship, under normal use and service for
a period of two (2) years from date of original installation, or thirty (30)
months from date of shipment by Heatcraft Refrigeration Products
LLC, whichever first occurs. Service Parts, for product out of original
warranty, should be so warranted for a period of twelve (12) months
from date of shipment. Any product covered by this order found to
Heatcraft Refrigeration Products LLCs satisfaction to be defective
upon examination at Heatcraft Refrigeration Products LLCs factory
will, at Heatcraft Refrigeration Products LLCs option, be repaired
or replaced and returned to Buyer via lowest common carrier, or
Heatcraft Refrigeration Products LLC may at its option grant Buyer
a credit for the purchase price of the defective article. Upon return
of a defective product to Heatcraft Refrigeration Products LLCs
plant, freight prepaid, by Buyer, correction of such defect by repair
or replacement, and return freight via lowest common carrier, shall
constitute full performance by Heatcraft Refrigeration Products LLC
of its obligations hereunder.
Hermetic compressors furnished by Heatcraft Refrigeration Products
LLC are subject to the standard warranty terms set forth above, except
that motor compressor replacements or exchanges shall be made
through the nearest authorized wholesaler of the motor compressor
manufacturer (not at Heatcraft Refrigeration Products LLCs factory)
and no freight shall be allowed for transportation of the motor
compressor to and from the wholesaler. The replacement motor
compressor shall be identical to the model of the motor compressor
being replaced. Additional charges which may be incurred throughout
the substitution of other than identical replacements are not covered
by this warranty.
The foregoing is in lieu of all other warranties, express or implied,
notwithstanding the provisions of the uniform commercial code, the
Magnuson-Moss Warranty-Federal Trade Commission Improvement
Act, or any other statutory or common law, federal or state.
Heatcraft Refrigeration Products LLC makes no warranty expressed or
implied, of fitness for any particular purpose, or of any other nature
whatsoever, with respect to products manufactured or sold by
Heatcraft Refrigeration Products LLC hereunder, except as specifically
set forth above and on the face hereof. It is expressly understood and
agreed that Heatcraft Refrigeration Products LLC shall not be liable to
buyer, or any customer of Buyer, for direct or indirect, special, incidental,
consequential or penal damages, or for any expenses incurred by
reason of the use or misuse by Buyer or third parties of said products.
To the extent said products may be considered Consumer Products,
as defined in Section 101 of the Magnuson-Moss warranty-Federal
Trade Commission Improvement Act, Heatcraft Refrigeration Products
LLC makes no warranty of any kind, express or implied, toConsumers,
except as specifically set forth above and on the face hereof.

This equipment is designed to operate properly and produce the


rated capacity when installed in accordance with good refrigeration
industry practices.
The following conditions should be adhered to when installing this
unit to maintain the manufacturers warranty:
(a) The power supply to the unit must meet the following
conditions:
A. Three phase voltages must be +/- 10% of nameplate
ratings. Single phase must be within +10% or -5%
of nameplate ratings.
B. Phase imbalance cannot exceed 2%.
(b) All control and safety switch circuits must be properly
connected according to the wiring diagram.
(c) The factory installed wiring must not be changed without
written factory approval.

Optional Three-Year Extended Compressor Warranty


The Equipment Dealer may purchase for the Owner at the time of the
original invoice of the equipment a Three-Year Limited Replacement
Compressor Warranty. This entitles the owner to be reimbursed for
the cost of a replacement compressor, during the third through fifth
year of the life of the compressor.
The warranty program functions similarly to the standard warranty
offered. When a compressor failure occurs and the unit is exchanged
over the counter at the authorized wholesaler outlet a salvage credit
is issued along with the invoice for the new compressor. Return copies
of both the credit and invoice to the Equipment Dealer along with
the model and serial number of the condensing unit. The Equipment
Dealer will process this claim with the Manufacturer and subsequently
reimburse the Owner for the cost of the new compressor.
This warranty covers the actual compressor only and does not extend
to any labor, trip charges, crane rental, taxes or additional parts,
refrigerant or processing/handling charges required to make the
unit operational.

PRO3 Side Mount Packaged Refrigeration System Installation and Operations Manual, May 2008 23

Heatcraft Refrigeration Products LLC

2175 West Park Place Blvd., Stone Mountain, GA 30087


P: (800) 321-1881 F: (770) 465-5990 www.heatcraftrpd.com

Since product improvement is a continuing effort, we reserve the right to make changes in specifications without notice.

The name behind the brands you trust.

CLIMATE

CONTROL

Commercial Refrigeration Parts

H-IM-PSM-0508 | Version 000

You might also like