Omnigrad S TR88, TC88
Modular Thermometer
Analog output 4 to 20 mA
HART
PROFIBUS PA
FOUNDATION Fieldbus
Your benefits
High degree of flexibility thanks to modular design with standard terminal heads
as per DIN EN 50446 and customer-specific immersion lengths
Variable total length in suitable thermowells thanks to compression fitting on
extension neck
Types of protection for use in hazardous locations:
Intrinsic Safety (Ex ia)
Non-sparking (Ex nA)
Endress+Hauser
Measuring system
24V DC / 30 mA
4...20 mA
A
20-250V DC/AC
A0012641
1
A
B
Application example
Thermometer with fitted head transmitter mounted in an existing onsite thermowell
RIA16 field display unit - The display unit records the analog measuring signal from the head transmitter and
shows this on the display. The LC display shows the current measured value in digital form and as a bar graph
indicating a limit value violation. The display unit is looped into the 4 to 20 mA circuit and gets the required
energy from there. More information on this can be found in the Technical Information (see "Documentation").
Active barrier RN221N - The RN221N (24 V DC, 30 mA) active barrier has a galvanically isolated output for
supplying voltage to loop-powered transmitters. The universal power supply works with an input supply
voltage of 20 to 250 V DC/AC, 50/60 Hz, which means that it can be used in all international power grids.
More information on this can be found in the Technical Information (see "Documentation").
Equipment architecture
2
8
ML
ML
IL
A0012672
Thermometer design
1
2
3
4
5
Endress+Hauser
Thermometers from the Omnigrad S TR88 and TC88 series have a modular design. The terminal
head is used as a connection module for the mechanical and electrical connection of the insert. The
position of the actual thermometer sensor in the insert ensures that it is mechanically protected. If
installed in a thermowell the insert can be exchanged and calibrated without interrupting the
process. The insert has flying leads, a ceramic connection socket or mounted temperature
transmitter. The thermometers are designed for installation in an existing onsite thermowell.
Different threaded connections are available on the bottom of the extension neck for installation in
the thermowell. Insofar as the thermowell is suited to this purpose, the thermometer may also be
mounted using a suitable compression fitting on the extension neck. This means that thermometers
with a fixed insertion length (ML) can be used variably, even in thermowells of varying length, and
can be installed in such a way that an optimum thermal contact is guaranteed between the tip of the
insert and the bottom of the thermowell.
Measurement range
Performance characteristics
Operating conditions
Temperature in C (F)
Depends on the terminal head used and the cable gland or fieldbus
connector, see 'Terminal heads' section
40 to 85 C (40 to 185 F)
Process pressure
The maximum process pressure depends on the thermowell into which the thermometer is screwed.
For an overview of the Endress+Hauser thermowells which may be used, see 22.
Permitted flow rate as a function of immersion length
The maximum permitted flow rate to which the thermometer can be subjected, reduces the greater
the immersion depth of the thermowell in the flowing medium. In addition, it is dependent on the
diameter of the tip of the thermowell, the medium type, process temperature and process pressure.
For an overview of the Endress+Hauser thermowells which may be used, see 22 .
Shock and vibration resistance
The Endress+Hauser inserts meet the requirements of IEC 60751 which specify shock and vibration
resistance of 3g in the range from 10 to 500 Hz. The vibration resistance at the measuring point
depends on the sensor type and design, see the following table:
Version
30 m/s (3g)
Endress+Hauser
Accuracy
Class
Characteristics
1)
3.0
Cl. A
2.5
Cl. B
2.0
Thin-film version
(TF):
Standard
iTHERM
StrongSens
B
1.5
Cl. A
Cl. AA
100 to
+450 C
50 to +250 C
Cl. A
Cl. AA
30 to +300 C
0 to +150 C
30 to +300 C
0 to +200 C
1.0
A
AA
0.5
-200
-100
100
200
300
400
500
600C
AA
- 0.5
A
- 1.0
- 1.5
- 2.0
- 2.5
1)
In order to obtain the maximum tolerances in F, the results in C must be multiplied by a factor
of 1.8.
Permissible deviation limits of thermoelectric voltages from the standard characteristic for
thermocouples as per IEC 60584 or ASTM E230/ANSI MC96.1:
Standard
Type
Standard tolerance
Special tolerance
Class Deviation
Class Deviation
J (Fe-CuNi)
K (NiCr-NiAl)
IEC 60584
1)
Standard
ASTM E230/ANSI
MC96.1
1)
Endress+Hauser
Type
Standard tolerance
Special tolerance
J (Fe-CuNi)
K (NiCrNiAl)
Response time
Tested in accordance with IEC 60751 in flowing water (0.4 m/s at 30 C):
Insert:
Sensor type
Diameter ID
Response time
iTHERM StrongSens
6 mm (0.24 in)
t50
< 3.5 s
t90
< 10 s
t50
2.5 s
t90
5.5 s
t50
5s
t90
13 s
t50
2s
t90
6s
t50
4s
t90
12 s
t50
0.8 s
t90
2s
t50
2s
t90
5s
t50
1s
t90
2.5 s
t50
2.5 s
t90
7s
3 mm (0.12 in)
TF Sensor
6 mm (0.24 in)
3 mm (0.12 in)
WW Sensor
6 mm (0.24 in)
3 mm (0.12 in)
Thermocouple (TPC100)
grounded
6 mm (0.24 in)
3 mm (0.12 in)
Thermocouple (TPC100)
ungrounded
6 mm (0.24 in)
Insulation resistance
RTD:
Insulation resistance according to IEC 60751 > 100 M at 25 C between terminals and sheath
material measured with a minimum test voltage of 100 V DC
TC:
Insulation resistance according to IEC 1515 between terminals and sheath material with a test
voltage of 500 V DC:
> 1 G at 20 C
> 5 M at 500 C
Dielectric strength
Self heating
RTD elements are passive resistances that are measured using an external current. This
measurement current causes a self-heating effect in the RTD element itself which in turn creates an
additional measurement error. In addition to the measurement current, the size of the measurement
error is also affected by the temperature conductivity and flow velocity of the process. This selfheating error is negligible when an Endress+Hauser iTEMP temperature transmitter (very small
measurement current) is connected.
Calibration
Endress+Hauser
Calibrations are traceable to national and international standards. The calibration certificate is
referenced to the serial number of the thermometer. Only the insert is calibrated.
Insert:
6 mm (0.24 in) and 3 mm (0.12 in)
Temperature range
80 to 40 C (110 to 40 F)
200 (7.87)
40 to 0 C (40 to 32 F)
160 (6.3)
Material
120 (4.72)
150 (5.91)
300 (11.81)
450 (17.72)
Short form
Recommended
Properties
max. temp. for
continuous use in
air
AISI 316L/
1.4404
1.4435
X2CrNiMo17-12-2
X2CrNiMo18-14-3
Alloy 600/
2.4816
1)
NiCr15Fe
Can be used to a limited extent up to 800 C (1472 F) for low compressive loads and in non-corrosive
media. Please contact your Endress+Hauser sales team for further information.
Components
Family of temperature
transmitters
Endress+Hauser
Endress+Hauser
Terminal heads
All terminal heads have an internal shape and size in accordance with DIN EN 50446 flat face and a
thermometer connection of M24x1.5, G1/2" or 1/2" NPT thread. All dimensions in mm (in). The
cable glands in the diagrams correspond to M20x1.5 connections. Specifications without head
transmitter installed. For ambient temperatures with head transmitter installed, see "Operating
conditions" section.
TA30A
Specification
15.5 (0.6)
68.5 (2.7)
107.5 (4.23)
28
(1.1)
78 (3.1)
A0009820
Specification
Available with one or two cable entries
Protection class: IP66/68 (NEMA Type 4x encl.)
Temperature: 50 to +150 C (58 to +302 F) without cable
gland
Material: aluminum, polyester powder coated
Seals: silicone
Threaded cable entry: G ", " NPT and M20x1.5
Protection armature connection: M24x1.5
Head color: blue, RAL 5012
Cap color: gray, RAL 7035
Weight: 420 g (14.81 oz)
with TID10 display
Ground terminal, internal and external
3-A marked
15.5 (0.6)
107.5 (4.23)
91.6 (3.61)
28
(1.1)78 (3.1)
A0009821
TA30D
Specification
15.5 (0.6)
110 (4.3)
107.5 (4.23)
28
(1.1) 78 (3.1)
A0009822
Endress+Hauser
TA30P
Spezifikation
114 (4.5)
41.5 (1.63)
!83
(3.3
)
11
(0.43)
68 (2.7)
A0012930
TA20B
Specification
116 (6.54)
73 (2.87)
25 (1)
84 (3.3)
A0008663
TA21E
Specification
Protection class: IP65 (NEMA Type 4x encl.)
Temperature: 40 to 130 C (40 to 266 F) silicone, up to
100 C (212 F) rubber seal without cable gland (observe
max. permitted temperature of the cable gland!)
Material: aluminum alloy with polyester or epoxy coating,
rubber or silicone seal under the cover
Cable entry: M20x1.5 or plug M12x1 PA
Protection armature connection: M24x1.5, G 1/2" or NPT
1/2"
Head color: blue, RAL 5012
Cap color: gray, RAL 7035
Weight: 300 g (10.58 oz)
3-A marked
57 (2.2)
95 (3.9)
122 (4.8)
28 (1.1)
84 (3.3)
A0008669
10
Endress+Hauser
TA20J
Specification
Protection class: IP66/IP67 (NEMA Type 4x encl.)
Temperature: 40 to 70 C (40 to 158 F) without cable
gland
Material: 316L (1.4404) stainless steel, rubber seal under the
cover (hygienic design)
4 digits 7-segments LC display (loop powered with optional4
to 20 mA transmitter)
Cable entry: 1/2" NPT, M20x1.5 o plug M12x1 PA
Protection armature connection: M24x1.5 or 1/2" NPT
Head and cap color: stainless steel, polished
Weight: 650 g (22.93 oz) with display
Humidity: 25 to 95 %, no condensation
3-A marked
41 (1.61)
119 (4.7)*
89 (3.5)
114 (4.49)
28 (1.1)
64 (2.52)
A0008866
TA20R
Specification
81 (3.2)
54 (2.13)
79 (3.11)
53 (2.1)
28 (1.1)
!55 (2.17)
A0008667
Endress+Hauser
Type
Temperature range
20 to +95 C (4 to +203 F)
11
!42 (1.65)
!33 (1.3)
!44 (1.73)
33 (1.3)
10 (0.4)
10 (0.4)
M4x1
!6
(0.24)
!33 (1.3)
!42 (1.65)
ML
IL
ML
!11 (0.43) /
!12 (0.47)
D
180 (7.1) "
2x Pt100
90 (3.54) "
1x Pt100
Design
!ID
!ID
!ID
!ID
A0012662
3
A
B
C
D
E
IL
ML
ID
The insertion length (ML) must be selected on the basis of the total length and the type of
thermowell used.
12
Endress+Hauser
Depending on the application different inserts are available for the assembly:
Insert
Sensor
Sensor design;
connection method
Vibration resistance of
the insert tip
Measuring range;
accuracy class
Standard thin-film
iTHERM StrongSens
Wire wound
1x Pt100, 3- or 4-wire,
mineral insulated
50 to +500 C
50 to +400 C
(58 to +752 F), Class A or AA (58 to +932 F), Class A or AA
Up to 3g
200 to +600 C (328 to +1 112 F), Class A or AA
Diameter
3 mm ( in), 6 mm ( in)
6 mm ( in)
3 mm ( in), 6 mm ( in)
Insert type
TPR100
iTHERM TS111
TPR100
TC
Selection in order code
1x K; Alloy 600
2x K; Alloy 600
1x J; 316L
2x J; 316L
40 to 1 200 C
40 to 750 C
ANSI MC 96.1
0 to 1 250 C
0 to 750 C
TC Standard, accuracy
Insert type
Diameter
Weight
Endress+Hauser
TPC100
3 mm (0.12 in) or 6 mm (0.24 in), depending on the selected tip shape
13
Process connection
Cylindrical
Conical
Version
Thread length TL
Width
across flats
AF
12 mm (0.47 in)
17
M14x1.5
M18x1.5
SW/AF
M20x1.5
15 mm (0.6 in)
24
G 1/2"
15 mm (0.6 in)
27
NPT
NPT 1/2"
8 mm (0.32 in)
22
R 3/4"
27
TL
TL
24
ML,
L
R 1/2"
22
A0019445
Threaded compression
fitting (TA50)
G1/2" 47 mm
(1.85 in)
Clamping
ring
material
Max. process
temperature
Max. process
pressure
15 mm
(0.6 in)
SS316 1)
500 C (932 F)
40 bar at 20 C
(580 psi at 68
F)
F
A0016971
1)
SS316 compression ferrule: Can only be used once, the compression fitting cannot be repositioned on the
protection tube after loosening. Fully adjustable immersion length on initial installation.
When using a compression fitting the thermometer is pushed through a gland and fixed using a
metal ferrule (cannot be loosened).
Spare parts
14
Endress+Hauser
Wiring
Wiring diagrams for RTD
mA
1
3-wire
4-wire
RTD
RTD
6 (red)
5 (red)
6 (red)
5 (red)
4 (white)
3 (white)
3 (white)
A0016433-EN
Sensor input 1
RTD: 3-wire
Bus connection
and supply voltage
red
(black)
red
(black)
7
red
6
6
red
5
5
white
(yellow)
white
white
1
+
2
-
-2
Display connection
A0008848-EN
2 x Pt100
1 x Pt100
red
red
red
red
white
white
4 wires
white
white
black
red
black
red
yellow
3 wires
3 wires
A0008591-EN
Endress+Hauser
15
Sensor
input 1
TC
7
Sensor
input 2
TC
Power supply
head transmitter and
analog output 4...20 mA
or bus connection
Bus connection
and supply voltage
1
+
5
5
1 +
2 -
1
+
-2
Display connection
A0012698-EN
A0012699-EN
2 x TC
1 x TC
-
+
A0012700
16
Endress+Hauser
Installation conditions
Orientation
No restrictions.
Installation constructions
ML
A
A0012639
Thermometer installation
The thermometer is designed for installation in an existing thermowell or in a thermowell which can
be ordered separately. Different threaded connections to suit the thermowell are available on the
thermometer's extension neck 14. The necessary insertion length (ML) of the insert depends
on the total length of the thermowell (A) and the type of thermowell used. It can be freely selected
within the range of 100 to 5 000 mm (3.94 to 197 in). Longer insertion lengths are available on
request. This also applies when ordering the insert as a spare part. More detailed information on
determining the insertion length (ML) required in each case can be found in the following table
(applies to Endress+Hauser thermowells with standard base thicknesses (D)).
Type of thermowell
ML in mm (in)
Type of thermowell
ML in mm (in)
TA535
ML = A
TA565
ML = A - 3 (0.12)
TA540
ML = A - 2 (0.08)
TA566
ML = A - 3 (0.12)
TA550
ML = A - 3 (0.12)
TA570
ML = A - 3 (0.12)
TA555
ML = A - 2 (0.08)
TA571
ML = A - 3 (0.12)
TA557
ML = A - 2 (0.08)
TA572
ML = A - 3 (0.12)
TW15
ML = A
TA575
ML = A - 3 (0.12)
TA560
ML = A - 3 (0.12)
TA562
ML = A - 3 (0.12)
TA576
ML = A - 2 (0.08)
In the case of thermowells with a noncompliant standard base thickness (D), the following formula
must be used: ML = A - D + 3 (0.12) in mm (in).
Endress+Hauser
17
The extension neck is the part between the process connection and the terminal head. As illustrated
in the following diagram, the extension neck length influences the temperature in the terminal
head. This temperature must remain within the limit values defined in the "Operating conditions"
section.
180
T in K
160
140
120
100
80
60
40
20
50
2
100
4
150
6
200
8
250
10
Process temperature
1000 C (1832 F)
800 C (1472 F)
600 C (1112 F)
400 C (752 F)
250 C (482 F)
300 mm
12 in
Heating of the terminal head as a function of the process temperature. Temperature in terminal head =
ambient temperature 20 C (68 F) + T
The device meets the legal requirements of the EC directives if applicable. Endress+Hauser confirms
that the device has been successfully tested by applying the CE mark.
For further details on the available Ex versions (ATEX, CSA, FM etc.), please contact your nearest
Endress +Hauser sales organization. All relevant data for hazardous areas can be found in separate
Ex documentation.
PED approval
The thermometer complies with paragraph 3.3 of the Pressure Equipment Directive 97/23/EC and is
not marked separately.
The "Factory calibration" is carried out according to an internal procedure in a laboratory of Endress
+Hauser accredited by the European Accreditation Organization (EA) according to ISO/IEC 17025. A
calibration which is performed according to EA guidelines (SIT/Accredia or DKD/DAkks calibration)
may be requested separately. The calibration is performed on the replaceable insert of the
thermometer. In the case of thermometers without a replaceable insert, the entire thermometer from the process connection to the tip of the thermometer - is calibrated.
18
Endress+Hauser
Ordering information
Detailed ordering information is available from the following sources:
In the Product Configurator on the Endress+Hauser web site: www.endress.com Choose your
country Products Select measuring technology, software or components Select product
(picklists: measurement method, product family etc.) Device support (right-hand column):
Configure the selected product The Product Configurator for the selected product is opened.
From your Endress+Hauser Sales Center: www.addresses.endress.com
Product Configurator - the tool for individual product configuration
Up-to-the-minute configuration data
Depending on the device: Direct input of measuring point-specific information such as
measuring range or operating language
Automatic verification of exclusion criteria
Automatic creation of the order code and its breakdown in PDF or Excel output format
Ability to order directly in the Endress+Hauser Online Shop
Endress+Hauser
19
Accessories
Various accessories, which can be ordered with the device or subsequently from Endress+Hauser, are
available for the device. Detailed information on the order code in question is available from your
local Endress+Hauser sales center or on the product page of the Endress+Hauser website:
www.endress.com.
Communication-specific
accessories
Commubox FXA195
HART
For intrinsically safe HART communication with FieldCare via the USB interface.
Commubox FXA291
Is used to evaluate and convert dynamic HART process variables to analog current
signals or limit values.
details, see "Technical Information" TI00429F and Operating Instructions
For
BA00371F
Gateway for the remote monitoring of connected 4-20 mA measuring devices via a
Web browser.
details, see "Technical Information" TI00025S and Operating Instructions
For
BA00053S
Fieldgate FXA520
Gateway for the remote diagnostics and remote configuration of connected HART
measuring devices via a Web browser.
details, see "Technical Information" TI00025S and Operating Instructions
For
BA00051S
Compact, flexible and robust industry handheld terminal for remote configuration
and for obtaining measured values via the HART current output (4-20 mA).
Accessories
Description
Applicator
20
Endress+Hauser
Konfigurator+temperature
Software for selecting and configuring the product depending on the measuring
task, supported by graphics. Includes a comprehensive knowledge database and
calculation tools:
For temperature competence
Quick and easy design and sizing of temperature measuring points
Ideal measuring point design and sizing to suit the processes and needs of a wide
range of industries
The Konfigurator is available:
On request from your Endress+Hauser sales office on a CD-ROM for local PC
installation.
W@M
FieldCare
Accessories
Description
The display unit records the analog measuring signal from the head transmitter
and shows this on the display. The LC display shows the current measured value in
digital form and as a bar graph indicating a limit value violation. The display unit is
looped into the 4 to 20 mA circuit and gets the required energy from there.
Active barrier with power supply for safe separation of 4-20 mA standard signal
circuits. Offers bidirectional HART transmission.
details, see "Technical Information" TI00073R and Operating Instructions
For
BA00202R
RNS221
Supply unit for powering two 2-wire measuring devices solely in the non-Ex area.
Bidirectional communication is possible via the HART communication jacks.
details, see "Technical Information" TI00081R and Brief Operating
For
Instructions KA00110R
Endress+Hauser
21
Documentation
Technical Information:
iTEMP Temperature head transmitter:
TMT180, PC-programmable, single-channel, Pt100 (TI088R/09/en)
PCP TMT181, PC-programmable, single-channel, RTD, TC, , mV (TI00070R/09/en)
HART TMT182, single-channel, RTD, TC, , mV (TI078R/09/en)
HART TMT82, two-channel, RTD, TC, , mV (TI01010T/09/en)
PROFIBUS PA TMT84, two-channel, RTD, TC, , mV (TI138R/09/en)
FOUNDATION FieldbusTM TMT85, two-channel, RTD, TC, , mV (TI134R/09/en)
Inserts:
Resistance thermometer insert Omniset TPR100 (TI268t/02/en)
Thermocouple insert Omniset TPC100 (TI278t/02/en)
iTHERM TS111 Insert for installation in thermometers (TI01014T/09/en)
Application example:
RN221N Active barrier, for supplying loop-powered transmitters (TI073R/09/en)
RIA16 Field display unit, loop-powered (TI00144R/09/en)
Technical information thermowells:
Type of thermowell
TA535
TI250T/02/en
TA565
TI160T/02/en
TA540
TI00166T/09/en
TA566
TI177T/02/en
TA550
TI153T/02/en
TA570
TI161T/02/en
TA555
TI154T/02/en
TA571
TI178T/02/en
TA557
TI156T/02/en
TA572
TI179T/02/en
TW15
TI00265T/02/en
TA575
TI162T/02/en
TA560
TI159T/02/en
TA576
TI163T/02/en
TA562
TI00230T/09/en
22