GE Energy
Power Generation Services
Oil Ingress in Medium
GE Generators
GER4618 (07/12)
Alex Lemberg
Oil Ingress in Medium GE Generators
The two major components of GE turbine generators, the armature (stator) and field (rotor), utilize
insulating materials which are impervious to turbine oil. Stator winding epoxy-mica insulation and the
field winding insulating materials are chemically neutral to the turbine oil. However, oil can trap
contaminants that could potentially contribute to eventual electrical issues if not promptly corrected.
Similarly, oil deposits inside stator slots may reduce friction between slot elements and facilitate stator
bar motion in the slot which could lead to stator bar abrasion. For reasons such as these, proper
operational and maintenance practices must be maintained to prevent oil ingress into the generators.
Turbine oil can enter inside generators in a number of ways. In hydrogen-cooled generators the oil
comes from the hydrogen seal system of the generator. In air-cooled generators, the bearing lube oil
system can be the source of oil ingress.
Hydrogen-cooled generators
Common causes of the oil ingress in hydrogen-cooled generators are:
Failure to open the float trap bypass at initial hydrogen
pressurization.
On some generators it may be necessary to operate with the
Inadequate hydrogen seal ring performance due to:
Buildup of residues from oil on the seal ring bore.
This results in reduced clearance and may lead to overheating
of the rings.
Improper hydrogen seal assembly or contaminants in the oil
float trap bypass open when operating at lower generator
causing seal rings to tilt (unbolted style) or not fully seal on the
casing gas pressures in order to avoid flooding the seal drain
lapped surface of the H2 seal casing.
enlargements. When the generator casing gas pressure is low
(approximately 5 psi [0.352 kg/cm2] or less) the gas pressure in
Excessive seal oil flow, overwhelming the float trap and backing
up into the seal oil drain enlargement tank (SDE), and eventually
the seal drain enlargement is not always sufficient to overcome
into the generator belly. Typical causes are improperly installed
the friction in the piping between the seal drain enlargement
or incorrectly sized seals (journal to seal ring gap too large).
and bearing drain enlargement. This may cause flooding of the
seal drain enlargements. As casing gas pressure builds up to
Seal oil drain piping installed incorrectly (slope, vent locations,
excess number of 90 elbows, etc). Improper installation is likely
approximately 5psi, the bypass valve must be closed so that
to reveal itself during commissioning. However, a generator may
gas will not be blown into the bearing drain enlargement.
run properly for a period of time until a minor change during
(Refer to Shaft Sealing GEKs 104016, 107241, and/or 107237
operation causes the drain system to malfunction.
for packaged and unpackaged generators).
Seal oil drain line or float trap drain line clogging.
Differential pressure regulator malfunction or sudden swings
in the seal oil pressure. Typical causes include pilot valve
mis-adjustment or inoperative pilot valves,
Misoperation or lack of operation of DC emergency pump
following an AC black out.
Air-cooled generators
With the field inside the stator, it is not possible to access the slot
The bearing lube oil drain can be a source of oil ingress in
components and stator vent ducts for thorough cleaning. Removal
air-cooled generators. Typical causes include clogged drains,
of the field is a major task, which should be undertaken giving
improper pressure balance around the bearing, demister
consideration to the severity of contamination and unit repair
malfunction, or installation errors.
schedule.
Cleaning
Once the field is out, inspect the slot ends for greasing deposits and
If oil ingestion occurs with the unit at standstill, oil mist and
contamination will not immediately circulate through the generator.
However, if oil ingestion occurs during generator operation, or the
the core cooling ducts for oil. If oil is found in vent ducts or greasing
is noted in the slots, contact GE Engineering for appropriate
cleaning recommendations.
unit is started after standstill ingestion, the oil mist will circulate
Conclusion
throughout the generator. Increased oil ingestion can lead to higher
A generator field can have long-term negative effects due to oil
levels of greasing, compounding the difficulty of generator cleaning
ingress. If oil gets into the winding, it can attract dust or other
as operating time advances.
contaminants, potentially forming a creepage path for current
Cleaning oil from generators should begin with draining the oil from
between the copper and forging.
the frame floor or generator belly. Oil deposited on the end winding
Proper practices must be maintained to prevent oil ingress and
must be cleaned with proper solvents, materials, and methods
minimize the oil mist deposits on the stator and field winding.
specified in GE Operation & Maintenance manuals.
Should oil ingress occur, generator cleaning must be performed at
If a significant amount of oil enters the generator frame and
triggers a liquid level alarm, it may contaminate the coolers in some
models. If coolers are found to be contaminated, they would have
to be removed for steam cleaning.
Inspection and cleaning must include the connections between the
line leads and the connection rings. These can generally be
accessed through the two access covers on the collector end of the
machine. It is also recommended to use a borescope to inspect the
drain lines for blockage. Further guidance can be found in the
Operation & Maintenance manual.
For leads-down units, check gas-cooled bushings for internal oil
accumulation that would inhibit cooling. If oil accumulation is
noted, drain or vacuum-extract the oil.
the earliest opportunity. For further information regarding
generator maintenance, please contact your Contract Performance
Manager or local GE Service Representative.