MPR300 Relay

The MPR300 is a microcontroller-based motor protection relay for motors up to 50KW. It provides protection against thermal overload, single phasing, earth fault, locked rotor, and under current. Settings include the motor current and earth fault pickup level. Protections include four thermal overload trip curves, and indications are provided for each fault. It has compact DIN rail or back panel mounting and integrates current transformers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
10K views

MPR300 Relay

The MPR300 is a microcontroller-based motor protection relay for motors up to 50KW. It provides protection against thermal overload, single phasing, earth fault, locked rotor, and under current. Settings include the motor current and earth fault pickup level. Protections include four thermal overload trip curves, and indications are provided for each fault. It has compact DIN rail or back panel mounting and integrates current transformers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

MOTOR PROTECTION RELAY

FOR SMALL MOTORS


TYPE MPR300
Relay MPR300 is a three phase LT motor protection relay for motor sizes up to 50KW (max.
88 A current). It is a low cost solution , offering five major protections for motors widely
used in fans, pumps, crushers, mills, compressors, belt
conveyors,centrifuges, mixers,
ventilators, escalators, motorized valves etc. Major advantage is that it provides E/F coordination in contactor started motors, thus offering greater security, operator safety and
economy. The relay is microcontroller based , highly user friendly and compact with inbuilt
CTs. The relay can also be used for protection of larger motors by using external CTs.
medium voltage and high voltage sub-stations.

49, 51LR, 32, 51N, 46


DIN rail / Back panel mounting
Integral CTs
Wide range of motor currents ( 1 A to 88A)
5 major protections
(Thermal O/L, Single phasing, E/F,
Locked rotor & Under current)
4 trip time cureves for O/L (selectable)
Trip Indications
Test facility

MPR300 has very few controls / settings on the front


panel. There are two potentiometers one for setting
the motor rated current and the other for setting the
E/F pick up level. A DIP switch is provided for
selection of thermal overload trip class and enable /
disable of Locked rotor protection and Under
current protection. Other settings are prefixed in the
relay ( some of them related to the trip class selected).
Six LEDs are provided five to indicate the faults and
one to indicate power on condition. There are two
push buttons- one to reset the LEDs on clearance of
fault and the other to test the relay . The test PB
operation runs a small software routine which
performas check on all software & hardware blocks
internal to relay .
2

-2SIDE LABELS : All data pertaining to pick up level and applicable time delays are
indicated on a label on right hand side of the unit. The wiring diagram label is provided on
the left hand side of the unit.
SETTINGS :
*
*
*

Motor Full load current Im


Trip time characteristic
(class 10A, 10, 20, 30)
Enable / Disable Under Current

E/F pick up level Io

Enable / Disable Locked Rotor

The pick up levels and time delays for negative sequence , locked rotor and under current
protections are preset in the relay.
RELAY CONNECTIONS :

R-Y-B phase wires pass through relay.


Trip contacts to be wired to starter

TECHNICAL SPECIFICATIONS
1.0

Protections offered :

Thermal over load, Negative Sequence,


Earth fault, Locked rotor, Under current

2.0

Thermal Over Load Protection

a)

Current setting 1 to 88 A
in 6 different models
1A to 2.75 A
2A to 5.50 A
4A to 11 A
8A to 22 A
16A to 44 A
32A to 88 A
Continuously adjustable

b)

Trip Time Characteristics


Class 10A, 10 , 20 and 30 as per
IEC 947-4-1. Field selectable through
front DIP switches.

c)

Pre alarm - at 1.05 Im by flashing


LED ( Im = Motor rated current)

d)

Thermal Memory - Provided.

a)

Current setting 10 to 50% of Im


(Field selectable by front panel control)

3.0

Earth fault Protection

b) Trip time delay - 200 msec (Factory set)


c)

Disable feature - Available

-3-

4.0

Phase Unbalance Protection

a)
Unbalance current 50% of Im
b)
Trip time delay - 3 sec
(Both factory set)

5.0

Locked rotor protection

a)
Locked rotor current - 3 Im
b)
Trip time delay - 1 sec
(Both factory set)
c)
Disable feature - Available

6.0

Under Current protection

a)
Under current threshold - 50% of Im
b)
Trip time delay - 3 sec
(Both factory set)
c)
Disable feature
- Available

7.0

Operational Indicators

a)
Indications for Power On
LED
b)
Indications for trip on each of the 5 faults
LED starts flashing when fault is detected.
Become steady on when the relay trips after the
preset time delay. LEDs are manual reset.

8.0

Contacts

1 N/O + 1 N/C manual reset


Rated Voltage
250 V AC / 30 V DC
Rated Current
5A
Rated breaking capacity 2000 VA / 240 W
( resistive)

9.0
10.0
11.0
12.0

Auxiliary power supply


Operating Temperature
Accuracy
Reference Standards

240 V AC +/- 20%


0 to 60 deg. C
As per IEC 947-4-1
IEC 60255, IEC 61000 and IEC 60068
Please refer separate document
General Electrical Characteristics

13.0
14.0

Over all dimensions


Weight

70mm W x 85 mm H x 106 mm D
Less than 400 gms

CATALOG Nos.
MPR300BE010
MPR301BE020
MPR302BE040
MPR303BE080
MPR304BE160
MPR305BE320

Motor Protection Relay , 1 to 2.75A


Motor Protection Relay , 2 to 5.5A
Motor Protection Relay , 4 to 11A
Motor Protection Relay , 8 to 22A
Motor Pro tection Relay , 16 to 44A
Motor Protection Relay , 32 to 88A
4

-4-