Bca90 Housing-Extracts Amdt07
Bca90 Housing-Extracts Amdt07
ED
SU
PE
PURPOSE OF AMENDMENT
The main purpose of this amendment is to:
(a) Partially revise Part E1.
(b) Incorporate editorial changes to clarify the intent of certain provisions.
(f) Incorporate State/Territory variations, where appropriate, into the main
document.
(g) Delete those State/Territory variations deemed to be no longer appropriate.
(h) Reference the Australian Building Codes Board (ABCB).
Provisions affected by this amendment are:
Preface
About the Housing Extract, Comments, ABCB
Part A1 definitions
ED
carport (deleted)
Part A2
A2.2(e), A2.2(f)
ED
Specification C1.8
Specification C1.9
E1.7
SU
Part E1
PE
Part B1
Specification E1.7
Part F1
F1.7
Part F3
Rewritten
Part F4
F4.4, F4.6
Part F5
F5.5
Part G1
Additions/Amendment:
ACT A2.101, ACT B1.3, ACT D2.13(b)(v), ACT E1.7, ACT Spec E1.7, ACT F6.2(e), ACT G1.1(b), ACT
G1.1(c)(v) (deleted)
Amendment ACT Spec A1.3
deletions: AS 1141 Part 41, AS 1940, AS 2890 Part 1
additions: AS 3660, AS 3661 Part 1,
NSW Appendix
NSW C1.9, NSW Spec C1.9, NSW D2.1, NSW Table D3.2, NSW E1.1, NSW Table E 2.2, NSW Spec
E1.5, NSW F4.5
Amendments:
NSW Specification A1.3 Table 1 (Ministerial Specification No 10 deleted), NSW E1.7, NSW Spec E1.7,
NSW F1.7, NSW F5.1(a)
NT Appendix
NT B1.3 (added), NT B1.2
QLD Appendix
ED
ED
Amendments:
SA D3.1, SA D3.2, SA G1.1(b)(ii)
TAS Appendix
PE
Additions:
SU
************************************************************************************************
ED
This publication contains extracts from the Building Code of Australia 1990 (BCA) and is
referred to as the Building Code of Australia 1990 Housing Extract. Being an extract only,
the publication is not suitable for legal reference.
The Housing Extract includes those provisions applicable to the design and construction
of most Class 1 and 10 buildings. In some special situations it may be necessary to refer
directly to the BCA to identify all relevant requirements. Provisions in the Extract have
been modified as necessary to delete reference to other building classifications. Those
parts shown as having "No BCA provisions" have been included to allow reference of
additional provisions in State and Territory Appendices.
The Housing Extract is published by the Australian Building Codes Committee (ABCB) for
use by designers, engineers, builders, owners and other interested persons in the building
industry.
The BCA has been adopted by all mainland States and Territories.
PE
AMENDMENTS
ED
The Housing Extract includes individual State and Territory Appendices setting out
variations to the provisions for Class 1 and Class10 buildings which are considered
necessary for the application of the Extract in those States and Territories.
State and Territory variations to Clauses and Tables in the Housing Extract are identified
in the margin. Additional Clauses and Specifications to a Part of the Housing Extract are
included at the end of that Part and identified in the Section Content of each Appendix.
SU
The Housing Extract will be updated as amendments to the BCA are issued. This edition
of the Housing Extract includes the relevant provisions of Amendments No 1, 2, 3, 4 and
5.
Users of the Housing Extract should be aware that amendment No 5 may not necessarily
be in operation in each State or Territory at the time of issue.
OBJECTIVES
These are broad statements of intent included at the beginning of each Section and deal
with the basic concepts applying to all buildings and structures. They provide an
indication of what the clauses in the relevant Parts are meant to achieve. Objectives are
not intended to be used as controls in their own right. Their role is simply to assist in the
interpretation or application of the Parts to which they refer.
PERFORMANCE REQUIREMENTS
Some of the requirements of the BCA are expressed in performance terms. As an
alternative to any deemed-to-satisfy provisions, Accreditation Certificates, test reports or
other documentary evidence may be used as evidence to prove that a proposed
alternative or innovative material, component, design or construction method meets the
performance requirements of the BCA.
ED
DEEMED-TO-SATISFY PROVISIONS
PE
ED
PRESCRIPTIVE PROVISIONS
SU
In some instances the provisions of the BCA are expressed as prescriptive requirements
and there is no performance requirement against which a proposed material, component,
design or construction method can be assessed. If it is proposed to vary from a
prescriptive requirement the matter may then be resolved by an appropriate resolution
process.
PROFESSIONAL CERTIFICATION
The BCA allows for certificates from professional consultants to be used as evidence of
compliance with particular requirements or standards.
The enabling legislation will determine the extent of the use of professional certification
and the procedures for the submission of certificates, reports or other documentation to
Approval Authorities as evidence of compliance.
ACCREDITATION
The BCA provides for certificates of accreditation as evidence that the properties and
performance of a material, product, method of construction or design meets a particular
requirement.
DEFINITIONS
The words printed in italics have special meanings and are defined in clause A1.1.
Definitions and terminology used in the BCA are as far as possible consistent with that
used in State and Territory legislation, however where there is any conflict, the
requirements of the legislation take precedence.
ADMINISTRATIVE ARRANGEMENTS
ED
The BCA is brought into effect by building control legislation in each State and Territory
which adopts the BCA as the technical requirements which have to be satisfied in order to
gain building approval. The Housing Extract does not alter or supersede the provisions
of the BCA. In the event of any discrepancy between the Housing Extract and the BCA,
the BCA in effect at the time in accordance with the relevant State or Territory legislation
will take precedence.
ED
COMMENTS
PE
SU
SU
PE
ED
ED
The BBC comprises the Executive Director, one nominee each of the Commonwealth,
State, Territory and ALGA members of the ABCB and three industry members appointed
by the ABCB. Observers representing CSIRO, Standards Australia and the Australian
Fire Authorities Council also attend BCC meetings.
******************************************************************************************************
Definitions
Adoption of Standards and other references
Referenced Standards, etc
Differences between referenced documents and the BCA
Application of the BCA to a particular State or Territory
ED
ED
Suitability of materials
Evidence of suitability
Fire-resistance of building elements
Classification of Buildings and Structures
Principles of classification
Classifications
Multiple classification
A2.1
A2.2
A2.3
A3
A3.1
A3.2
A3.3
Specifications
PE
Specification A1.3
Specification A2.3
INTERPRETATION
A1.1
Definitions
SU
PART A1
Designated bushfire prone area means land which has been declared by
appropriate legislation to be likely to be subject to bushfires.
Exit means(a) Any, or any combination of the following if they provide egress to a road or
open space:
(i) An internal or external stairway.
(ii) A ramp complying with Section D.
(iii) A fire-isolated passageway.
(iv) A doorway opening to a road or open space.
(b) *
*
*
ED
External wall means an outer wall of a building which is not a common wall.
ED
Note: A dash, for examples 90/-/- or -/-/-, means there is no requirement for an FRL for that
criterion.
PE
SU
Floor area means(a) in relation to a storey - the area of that storey measured over the
enclosing walls (if any) and that part of any common wall located within
the allotment; and
(b) in relation to a room - the area of the room measured within the finished
surfaces of the walls, and includes the area occupied by any cupboard or
other built-in furniture, fixture or fitting.
Foundation means the ground which supports the building.
Habitable room means a room used for normal domestic activities, and(a) includes a bedroom, living room, lounge room, music room, television
room, kitchen, dining room, sewing room, study, playroom, family room
and sunroom; but
(b) excludes a bathroom, laundry, water closet, pantry, walk-in wardrobe,
corridor, hallway, lobby, photographic darkroom, clothes-drying room, and
other spaces of a specialised nature occupied neither frequently nor for
extended periods.
Insulation, in relation to an FRL, means the ability to maintain a temperature on the
surface not exposed to the furnace below the limits specified in AS 1530.4.
Integrity, in relation to an FRL, means the ability to resist the passage of flames and
hot gases specified in AS 1530.4.
SA A1.1 Ministers Specification
Lightweight construction means construction which incorporates or comprises(a) sheet or board material, plaster, render, sprayed application, or other
material similarly susceptible to damage by impact, pressure or abrasion;
or
(b) concrete and concrete products containing pumice, perlite, vermiculite, or
other soft material similarly susceptible to damage by impact, pressure or
abrasion; or
(c) masonry having a thickness less than 70 mm.
ED
Non-combustible (a) applied to a material - means not deemed combustible under AS1530.1 Combustibility Tests for Materials; and
(b) applied to construction or part of a building - means constructed wholly of
materials that are not deemed combustible.
ED
SU
PE
Professional engineer means a person who is(a) if legislation is applicable - a registered professional engineer in the
relevant discipline who has appropriate experience and competence in the
relevant field; or
(b) if legislation is not applicable(i) a Corporate Member of the Institution of Engineers, Australia; or
(ii) eligible to become a Corporate Member of the Institution of
Engineers, Australia, and has appropriate experience and
competence in the relevant field.
Registered Testing Authority means (a) the National Building Technology Centre (NBTC);
(b) the CSIRO Division of Building, Construction and Engineering (CSIRODBC&E);
(c) an authority registered by the National Association of Testing Authorities
(NATA) to test in the relevant field; or
(d) an organisation outside Australia recognised by NATA through a mutual
recognition agreement.
Required means required by the BCA.
Sanitary compartment means a room or space containing a toilet fixture, closet
pan, soil pan, chemical toilet, or the like.
Smoke-Developed Index means the index number for smoke developed under
AS 1530.3.
Sole-occupancy unit means a room or other part of a building for occupation by
one owner, lessee, tenant, or other occupier to the exclusion of any other
owner, lessee, tenant, or other occupier.
Spread-of-Flame Index means the index number for spread of flame under AS
1530.3
Standard Fire Test means the Fire-resistance Tests of Elements of Building
Construction as described in AS1530.4.
ED
Structural adequacy, in relation to an FRL means the ability to maintain stability and
adequate loadbearing capacity under AS 1530.4.
Structural member means a component or part of an assembly which provides
vertical or lateral support to a building or structure.
ED
QLD A1.1
SA A1.1
Swimming pool means any excavation or structure containing water and used for
swimming, wading, paddling, or the like, including a bathing or wading pool, or
spa.
PE
Window includes a roof light, glass panel, glass brick, glass louvre, glazed sash,
glazed door, or other device which transmits natural light directly from outside a
building to the room concerned when in the closed position.
A1.2
SU
(e) permitting a departure from the code, rule, specification or provision at the sole
discretion of the manufacturer or purchaser, or by arrangement or agreement
between the manufacturer and purchaser.
A1.3
A reference to a document under A1.2 refers to the edition or issue together with any
amendment listed in Specification A1.3 and only so much as is relevant in the
context in which the document is quoted.
A1.4
The BCA overrules in any difference arising between it and any Standard, rule,
specification or provision in a document listed in Specification A1.3.
A1.5
ED
ED
For application within a particular State or Territory, the BCA comprises(a) Sections A to H; and
(b) the variations, deletions and additions to Sections A to H applicable to that
State or Territory specified in the relevant Appendix.
Suitability of materials
A2.1
Evidence of suitability
SU
A2.2
PE
(e) a current SSL Product Listing Data Sheet and listing in the latest issue of the
Scientific Services Laboratory Register of Accredited Products - Fire Protection
Equipment; or
(f) any other form of documentary evidence that correctly describes the properties
and performance of the material or form of construction and adequately
demonstrates its suitability for use in the building,
and any copy of documentary evidence submitted under the BCA must be a
complete copy of the original report or document.
A2.3
A3.1
ED
ED
Classifications
A3.2
NSW A3.2
PE
SU
A3.3
Multiple classification
(a)
(b)
(c)
*
*
*
Classes 1a, 1b, 10a and 10b are separate classifications; and
a reference to(i) Class 1 - is to Class 1a and 1b; and
(ii) *
*
* ; and
(iii) Class 10 - is to Class 10a or 10b.
ED
1.
The Standards and other documents listed in Table 1 are referred to in the BCA.
Date
ED
No.
AS 1170
BCA
Clause(s)
B1.2
Table 1
1989
Part 2
1989
Wind loads
Amdt 1, Jan 1991
Amdt 2, Jan 1993
Part 3
1990
Snow loads
Part 4
1993
Earthquake loads
1981
1994
B1.3
A1.1
AS 1288
PE
SU
AS 1250
Part 1
AS 1530
Part 1
1984
Part 2
1993
Part 4
1990
AS 1538
1988
AS 1562
1980
Part 1
1992
Metal
B1.3
B1.3, F1.5
AS 1603
Spec E1.7
Part 1
1990
Heat detectors
Part 4
1987
Part 6
1987
AS 1639
1990
The design and installation of corrugated fibrereinforced cement roofing and wall cladding
Amdt 1, May 1991
F1.5
AS 1664
1979
B1.3
AS 1668
1991
Spec E1.7
Part 2
1991
F4.5
AS 1670
1986
Automatic fire detection and alarm systems system design, installation and commissioning
Amdt 1, Jan 1987
Amdt 2, March1988
Amdt 3, June 1988
Spec E1.7
Interior lighting
F4.4
AS 1680
ED
Part 1
1990
Part 2
1990
AS 1684
1992
B1.3
AS 1691
1985
G2.2
AS 1694
1974
B1.3
Part 1
Timber structures
(SAA Timber Structures Code)
SU
AS 1720
PE
ED
Part 1
1988
Design methods
Amdt 1, March 1993
B1.3
Part 4
1990
Spec A2.3
AS 1860
1991
B1.3
AS 1926
Part 1
1993
G1.1
AS 2049
1992
Roof tiles
B1.3, F1.5
AS 2050
1989
B1.3, F1.5
AS 2057
1986
B1.3
AS 2159
1978
AS 2327
Part 1
1980
AS 2376
B1.3, F1.5
Part 1
1980
Extruded PVC
Part 2
1981
Glass fibre reinforced polyester (GRP)
AS 2424
1981
Plastics building sheets- General installation
requirements and design of roofing systems
B1.3, F1.5
AS 2818
1986
Guide to swimming pool safety
G1.1
AS 2867
1986
Farm structures - General requirements for
structural design
B1.3
AS 2870
1988
Construction
B1.3, F1.10
AS 2904
1986
Damp-proof courses and flashings
F1.9
AS 2908
Part 1
Part 1
1992
Corrugated sheets
Part 2
1992
Flat sheets
B1.3, F1.5
1990
Domestic solid-fuel burning appliancesInstallation
G2.2
AS 3600
1994
Concrete Structures
AS 3623
1993
Domestic metal framing
AS 3666
1989
Air-handling and water systems in buildings Microbial control
F4.5
AS 3700
1988
Masonry in Buildings
(SAA Masonry Code)
Amdt 1, Jan 1989
Amdt 2, March 1991
Amdt 3, April 1992
AS 3740
1994
waterproofing of wet areas in residential buildings F1.7
AS 3786
1993
Smoke alarms
AS 3959
1991
Construction of buildings in bushfire prone areas
G5.2
AS 4055
1992
Wind loads for housing
B1.2
AS 4100
1990
Steel structures
Amdt 1, Aug 1992
Amdt 2, June 1993
Part 1
Part 2
PE
ED
B1.3
SU
AS 4200
ED
AS 2918
Spec E1.7
F1.6
1994
Materials
1994
installation requirements
Guidelines for assessment of fire resistance of
structural steel members
Spec A2.3
ASTM
D3018-90
B1.3
CSIRODBC&E
B1.3
CSIRONBTC
B1.3
ISO 140
AISC
Part VI
SSL
1978(E)
Spec F5.5
Spec E1.7
SPECIFICATION A2.3
1.
FIRE-RESISTANCE OF BUILDING
ELEMENTS
Scope
This specification sets out the procedures for determining the FRL of building
elements.
2.
Rating
SU
PE
ED
ED
3.
SU
PE
ED
ED
(b) the report must demonstrate by calculation that the building element would
achieve the FRL if it is subjected to the regime of the Standard Fire Test in
relation to(i) structural adequacy (including deflection); and
(ii) integrity; and
(iii) insulation; and
(c) the calculations must take into account(i) the temperature reached by the components of the prototype and their
effects on strength and modulus of elasticity; and
(ii) appropriate features of the building element such as support, restraint,
cross-sectional shape, length, height, span, slenderness ratio,
reinforcement, ratio of surface area to mass per unit length, and fire
protection; and
(iii) features of the prototype that influenced its performance in the Standard
Fire Test although these features may not have been taken into account in
the design for dead and live load; and
(iv) features of the conditions of test, the manner of support and the position
of the prototype during the test, that might not be reproduced in the
building element if it is exposed to fire; and
(v) the design load of the building element in comparison with the tested
prototype.
************************************************************************************************
SECTION B STRUCTURE
CONTENTS
Objectives
B1
B1.1
B1.2
B1.3
Structural Provisions
General requirements
Loads
Construction deemed-to-satisfy
OBJECTIVES
Structural Provisions
ED
Part B1
ED
All loads, internal actions, material properties and foundation conditions that
significantly affect structural sufficiency or serviceability must be taken into account
in the construction of a building or other structure.
STRUCTURAL PROVISIONS
B1.1
General Requirements
PE
PART B1
SU
B1.2
Loads
NT B1.2
The loading requirements of B1.1 are satisfied if the building or structure can resist
loads determined in accordance with the following:
(a) Dead and live loads and load combinations: AS 1170.1.
(b) Wind loads: AS 1170.2.
(c) Snow loads: AS 1170.3.
(d) Earthquake loads: AS 1170.4.
(e) Wind loads for housing: AS 4055.
B1.3
Construction deemed-to-satisfy
ED
ED
The requirements of B1.1 for materials and forms of construction are satisfied if they
comply with the following:
(a) Masonry (including masonry-veneer, unreinforced masonry and reinforced
masonry): AS 3700.
(b) Concrete construction (including reinforced and prestressed concrete):
AS 3600.
(c) Steel construction(i) Steel structures: AS4100 or AS1250 except that where AS1250 is used
the following limitations apply:
(A) Steels must have a specified yield stress not greater than 350MPa.
(B) Hot rolled steel sections and flat plate must not be more than 40 mm
thick.
(C) *
*
*
(D) Beam elements must not be greater than 20 m in length.
(ii) Cold formed steel structures: AS 1538.
(d) Composite steel and concrete: AS 2327.1
(e) Aluminium construction: AS 1664.
QLD B1.3(f)
SA B1.3(f)
VIC B1.3(f)
SU
PE
(i)
(iii) Cellulose fibre reinforced corrugated cement sheets: AS2908.1 with safety
mesh installed in accordance with AS2424 Clause 2.3.3. for PVC and
GRP sheeting.
(iv) Metal roofing: AS1562.1
(v) Asphalt shingles: ASTM D3018-90, Type A
(l) Particleboard structural flooring: AS1860 (except for Clauses 5 and 6 and
Table 1).
WA B1.3(m)
(m) Earthwall construction: NBTC Bulletin 5, edition 4, Tables 3.1 and 3.7 and
associated Table.
(n) Structures for primary production purposes in rural areas: AS 2867
(o) Domestic metal framing: As 3623
VIC B1.3(p),(q),(r)
WA B1.3(p)
SU
PE
ED
ED
Specifications
Fire-resisting Construction.
Fire-Resistance of Class 1 and 10 Buildings.
ED
Specification C1.1
Specification C1.9
OBJECTIVES
ED
A building must be so designed and constructed that the following objectives are
fulfilled:
Part C1
SU
PE
(a) A building must be constructed so that it is protected from fire in any other
building.
(b) Materials used in the construction must be such that if there is a fire in the
building(i) the spread of fire and the generation of smoke and toxic gases will be
minimised;
(ii) stability will be maintained for a period at least sufficient for the occupants
to escape and to ensure the safety of fire-fighters; and
(iii) there will be little risk of collapse onto adjoining property.
PART C1
NSW C1.9
C1.9
(a) Class 1 buildings must be protected from the spread of fire from(i) another building other than an appurtenant Class 10 building; and
(ii) the allotment boundary.
(b) Class 10a buildings must not significantly increase the risk of spread of fire
between Class 2 to 9 buildings.
(c) For Class 1 buildings and Class 10a buildings appurtenant to Class 1 buildings,
construction in accordance with Specification C1.9 satisfies (a).
Specification C1.1
2.5
(a)
(b)
(c)
(d)
*
*
*
*
FIRE-RESISTING CONSTRUCTION
General concessions
*
*
*
*
*
*
*
*
PE
ED
ED
1.
SU
SPECIFICATION C1.8
Scope
2.
Application
A wall system need not be tested in accordance with this specification for static
pressure or impact if it is designed and constructed in accordance with Section B to
resist the appropriate pressures and impacts defined in this specification.
3.
Tests
3.4
Walls generally
An external and internal wall of lightweight construction that is required to be fireresisting, must be subjected to the following tests and must fulfil the following criteria:
(a) The materials tests of Clause 5(a) and the criteria of Clause 6(a).
(b) A static test by the imposition of a uniformly distributed load of 0.25 kPa (or its
equivalent) in accordance with Clause 5(b) and the damage and deflection
criteria of Clauses 6(b) and (c) respectively.
(c) A dynamic test by fall of the impact bag through a height of 100 mm in
accordance with Clause 5(c) and the damage and deflection criteria of Clauses
6(b) and (d) respectively.
(d) The surface indentation test of Clause 5(d) and the surface indentation criterion
of Clause 6(e).
4.
Test specimens
4.1
General
Testing must be carried out on either(a) construction in situ; or
(b) a laboratory specimen of the construction.
ED
ED
4.2
Testing in situ
If testing is carried out in situ, it must be done on that part of the construction least
likely, because of the particular combination of the height of the walls, the support
conditions and other aspects of the construction, to resist the loads.
SU
PE
4.3
Testing of specimens
If a laboratory specimen is tested, the specimen must span only in the direction
corresponding to the height of the wall and testing must be done in accordance with
either (a) or (b) below:
(a) (i) the height of the test specimen (or length, if the specimen is tested
horizontally) must be identical with the height between supports in the
actual construction; and
(ii) the specimen must be supported at the top and bottom (or at each end if
tested horizontally) by components identical with, and in a manner
identical with, the actual construction.
(b) If the distance between supports of the actual construction is more than 3 m,
then a smaller specimen may be tested but(i) the distance between supports must be not less than 3 m; and
(ii) forces, reactions and support conditions must be modelled so as to
reproduce the behaviour of the actual construction if it were tested in-situ.
5.
Test methods
(c) For resistance to impact - The provisions for testing wall systems in
ASTM E695-79 (1985), except that(i) the point of impact must be set 1.5 m above finished floor level or 1.5 m
above the part of the specimen that corresponds to finished floor level;
and
(ii) the impact bag must be not less than 225 mm in diameter and not more
than 260 mm in diameter and have a mass of 27.2 kg (+ 0.1 kg, -0); and
(iii) the mass must be achieved by putting loose, dry sand into the bag and
must be adjusted before each series of impact tests; and
(iv) where the impact bag and suspension cannot be vertical at the instant of
impact on a curved surface or an inclined surface, the height of drop is the
net height at the point of impact.
(d) For resistance to surface indentation - For all materials irrespective of
composition the test for surface hardness of Clause A2 of Appendix A of
AS 2185.
Criteria of compliance
6.
ED
ED
(e) For resistance of lift shaft construction to repetitive load - As for 5(b)
except that(i) it is sufficient to test one specimen with the pressure applied from the side
of the construction on which the lift will operate; and
(ii) the load must be applied dynamically at a frequency not less than 1 Hz
and not more than 3 Hz; and
(iii) equivalent load shall mean the quarter-point load that produces the same
central moment as the distributed load.
PE
The wall system or the specimen of it must fulfil the following criteria:
(a) Materials - Materials must comply with the applicable standard adopted by
reference in the BCA.
SU
ED
ED
3.
Measurement of distances
(a) The distance from any point on an external wall of a building to an allotment
boundary or another building is the distance to that point measured along a line
at right angles from the allotment boundary or external wall of the other building
which intersects that point without being obstructed by a wall complying with
Clause 4.
(b) Where a wall within a specified distance is required to be constructed in a
certain manner, only that part of the wall (including any openings) within the
specified distance need be constructed in that manner.
SU
PE
4.
Construction of external walls
(a) External walls (including gables) referred to in Clause 2 or 5 must extend to the
underside of a non-combustible roof covering or non-combustible eaves lining
and must(i) have an FRL of not less than 60/60/60 when tested from the outside; or
(iii) be of masonry-veneer construction in which the external masonry veneer
is not less than 90mm thick; or
(iii) be of masonry construction not less than 90 mm thick.
(b) Openings in external walls referred to in Clause 2 or 5 must be protected by(i) non-openable fire windows or other construction with an FRL of not less
than 60/60/- ; or
(ii) self-closing solid core doors not less than 35 mm thick.
(c) Sub-floor vents, roof vents, weepholes and penetrations for pipes, conduits and
the like need not comply with (b).
5.
Class 10a buildings
(a) Where a Class 10a building is located between a Class 1 building and the
allotment boundary, other than the boundary adjoining a road alignment or
other public space, the Class 1 building must be protected in one of the
following ways:
(i) The Class 10a building is not less than 900 mm from the allotment
boundary, other than the boundary adjoining a road alignment or other
public space,.
SU
PE
ED
ED
(ii) An external wall of the Class 10a building which is less than 900 mm from
an allotment boundary, other than the boundary adjoining a road
alignment or other public space, complies with Clause 4.
(iii) An external wall of the Class 10a building which is less than 900 mm from
the Class 1 building complies with Clause 4.
(iv) The Class 1 building is not less than 900 mm from the Class 10a building.
(v) An external wall of the Class 1 building which is less than 900 mm from
the Class 10a building complies with Clause 4.
(b) Where a Class 10a building is located between a Class 1 building to which it is
appurtenant and another building on the same allotment, the Class 1 building
must be protected in one of the following ways:
(i) The Class 10a building is not less than 1.8 m from the other building.
(ii) An external wall of the Class 10a building which is less than 1.8 m from
the other building complies with Clause 4.
(iii) An external wall of the Class 10a building which is less than 1.8 m from
the Class 1 building complies with Clause 4.
(iv) The Class 1 building is not less than 1.8 m from the Class 10a building.
(v) An external wall of the Class 1 building which is less than 1.8m from the
Class 10a building complies with Clause 4.
(c) Where two or more Class 10a buildings on the same allotment are appurtenant
to different Class 1 buildings, the Class 10a buildings must be separated(i) from each other by a distance of not less than 1.8 m; or
(ii) from each other by external walls complying with Clause 4; or
(iii) from each Class 1 building by a distance of not less than 900 mm; or
(iv) from each Class 1 building by external walls complying with Clause 4; or
(v) by a wall complying with Clause 7.
(d) A carport is exempt from (a), (b) and (c) if(i) it has two or more sides open and at least one third of its perimeter open
and, for the purposes of this clause, a side is considered to be open if the
roof covering adjacent to that side is at least 500 mm from another
building or allotment boundary; and
(ii) it has a non-combustible roof covering and any ceiling lining and wall
cladding, including gables, is also non-combustible ; and
(iii) it does not provide direct vertical support to any part of the Class 1
building; and
(iv) in the case where it has a common roof structure with the Class 1 building
and the carport does not have a ceiling, the opening between the top of
the wall of the Class 1 building and the underside of the roof covering is
infilled with(A) a non-combustible material; or
(B) construction clad with non-combustible material on the carport side.
6.
Allowable encroachments
(a) An encroachment in relation to any external wall of a Class 10a building
required to comply with Clause 4 or any external wall of a Class 1 building is
ED
any construction between the external wall of the building and the allotment
boundary, or the external walls of two buildings on the same allotment.
(b) The encroachments allowed within 900 mm of an allotment boundary or within
1.8m of another building on the same allotment are(i) fascias, gutters, downpipes and the like; and
(ii) eaves with non-combustible roof cladding and non-combustible lining; and
(iii) flues, pipes, domestic fuel tanks, cooling or heating appliances or other
services; and
(iv) light fittings, electricity or gas meters, aerials or antennas; and
(v) pergolas or sun blinds; and
(vi) unroofed terraces, landings, steps and ramps, not more than 1 m in
height.
(c) Encroachments listed in (b)(i), if combustible, b(ii) and b(iii) must not be built
within 450 mm of an allotment boundary nor be built within 900 mm of the
external wall or associated encroachments of another building on the same
allotment.
SU
PE
ED
7.
Separating walls
(a) A wall that separates Class 1 dwellings, or separates a Class 1 building from a
Class 10a building which is not appurtenant to that Class 1 building must have
an FRL of not less than 60/60/60 and(i) commence at the footings or ground slab; and
(ii) extend(A) if the building has a non-combustible roof covering, to the underside
of the roof covering; or
(B) if the building has a combustible roof covering, to not less than
450 mm above the roof covering.
(b) A separating wall of lightweight construction must comply with Specification
C1.8.
(c) A separating wall complying with (a)(ii)(A)(i) must not be crossed by timber or other combustible building elements
except for roof battens with dimensions of 75 mm x 50 mm or less; and
(ii) must have any gap between the top of the wall and the underside of the
roof covering packed with mineral fibre or other suitable fire-resisting
material.
(d) Where a building has a masonry veneer external wall, any gap between the
separating wall and the external masonry veneer must be(i) not greater than 50 mm; and
(ii) packed with a mineral fibre or other suitable fire-resisting material with the
packing arranged to maintain any waterproofing requirements of F1.4.
8.
Sarking-type materials
WA Spec C1.8 8
Any sarking-type material used in the roof of a Class 1 building must have a
Flammability Index of not more than 5
9.
Rooflights
Combustible rooflights or the like installed in a roof or part of a roof required to have
a non-combustible covering must(a) have an aggregate area not more than 20 % of the roof or part of the roof; and
(b) be not less than(i) 900 mm from(A) the allotment boundary other than the boundary adjoining a road
alignment or other public space; and
(B) the vertical projection of a separating wall extending to the underside
of the roof covering; and
(ii) 1.8 m from any rooflight or the like in another building on the allotment
other than an appurtenant building or a detached part of the same
building.
SU
PE
ED
ED
Construction of Exits
Application of Part
Treads and risers
Balustrades
D3
ED
No BCA Provisions.
OBJECTIVES
ED
A building must be so designed and constructed that the following objectives are
fulfilled:
Construction of Exits
Part D2
PE
(a) Stairways, ramps and passageways must be such as to provide safe passage
for the users of the building.
(b) Stairways, ramps, floors and balconies, and any roof to which people normally
have access, must have bounding walls, balustrades or other barriers where
necessary to protect users from the risk of falling.
CONSTRUCTION OF EXITS
D2.1
Application of Part
SU
PART D2
WA D2.1
Except for D2.13 and D2.16, this Part does not apply to(a) a Class 1 or Class 10 building.
D2.13
(a) A stairway must be suitable to provide safe passage in relation to the nature,
volume and frequency of likely usage.
(b) A stairway satisfies (a) if it has(i) not more than 18 or less than 2 risers in each flight; and
(ii) going (G), riser (R) and quantity (2R+G) in with Table D2.13; and
(iii) goings and risers that are constant throughout in flight; and
(iv) risers which do not have any openings that would allow 125 mm sphere to
pass through between the treads; and
ACT D2.13(b)(v)
(v) treads which have a non-slip finish or a suitable non-skid strip near the
edge of the nosings; and
(vi) treads of solid construction (not mesh or other perforated material) if the
stairway is more than 10 m high or connects more than 3 storeys; and
(vii) *
*
*
(viii) *
*
*
(ix) in the case of a non-required stairway, not more than 4 winders in a
quarter landing.
Table D2.13 RISER AND GOING DIMENSIONS (mm)
RISER (R)
QUANTITY (2R+G)
Max
Min
Max
Min
Max
Min
190
115
355
240
700
550
ED
ED
Private stairs(a)
GOING (G)(b)
(iii) in any building, stairs which are not part of a required exit and to which the public do
not normally have access.
PE
(b) The going in tapered treads (except winders in a quarter landing) in a curved or spiral stair
is measured-
SU
(i) 270 mm in from the outer side of the unobstructed width of the stairway if the
stairway is less than 1 m wide (applicable to a non-required stairway only); and
(ii) 270 mm from each side of the unobstructed width of the stairway if the stairway is
1 m wide or more.
D2.16
Balustrades
(a) A continuous balustrade must be provided along the side of any roof to which
public access is provided, any stairway or ramp, any floor, corridor, hallway,
balcony, verandah, access bridge or the like and along the side of any path of
access to a building, if(i) it is not bounded by a wall; and
(ii) its level is more than 1 m above the floor or ground surface beneath.
(b) A required balustrade must restrict persons accidentally falling from the floor.
(c) *
*
*
(d) A balustrade in stairways and ramps satisfies (b) if it complies with (g) and
(h)(ii).
(e) A balustrade along the side of a horizontal or near horizontal surface such as a(i) roof to which public access is provided and any path of access to a
building; and
ED
ED
(ii) floor, corridor, hallway, balcony, verandah, access bridge or the like,
satisfies (b) if it complies with (g) and (h)(ii).
(f) *
*
*
(g) The height of a balustrade satisfies (b) if it is constructed in accordance with the
following:
(i) The height is not less than 865 mm above the nosings of the stair treads
or the floor of a ramp.
(ii) The height is not less than(A) 1 m above the floor of any access path, balcony, landing or the like;
or
(B) 865 mm above the floor of a landing to a stair or ramp where the
balustrade is provided along the inside edge of the landing and does
not exceed a length of 500 mm.
(iii) A transition zone may be incorporated where the balustrade height
changes from 865 mm on the stair flight or ramp to 1 m at the landing.
(h) Openings in a balustrade satisfy (b) if the balustrade is constructed in
accordance with the following:
(i) *
*
*
(ii) Any opening does not permit a 125 mm sphere to pass through it and for
stairs, the space is tested above the nosings.
WA D2.16(i)
D3.1
Application of Part
PART D3
PE
SU
E5
Maintenance
No BCA provisions
Specification
Fire Detection and Alarm Systems
ED
Specification E1.7
E1.1
Application of Part
ACT E1.1
NSW E1.1
ED
PART E1
TAS E1.1
VIC E1.1
SU
E1.7
PE
This Part does not apply to(a) a Class 1a or Class 10 building; and
(b) except for E1.7, a Class 1b building.
ACT E1.7
NSW E1.7
SA E1.7
TAS E1.7
VIC E1.7
(a) An automatic fire detection and alarm system, designed to ensure the
occupants are given adequate warning so they can evacuate the building in an
emergency, must be installed in(i) a Class 1b building.
(b) An automatic fire detection and alarm system satisfies (a) if it complies with
Specification E1.7.
PART E5
MAINTENANCE
NSW Part E5
Maintenance
Scope
This Specification describes the installation and operation of fire detection and alarm
systems, which may also be utilised to operate a smoke control system within a
building.
2.
Type of system
ACT Spec E1.7 2
NSW Spec E1.7 2
SA Spec E1.7 2
TAS Spec E1.7 2
ED
3.
4.
ED
An automatic fire detection and alarm system must comply with(b) for a Class 1b, 2 or 3 building or Class 4 part of a building, Clause 9 as
permitted by Clause 8.
6.
SU
5.
PE
An automatic fire detection and alarm system must be connected to and activate(b) where an emergency warning and communication system is not required by
Part E4, a system of loud speakers, smoke alarms or other audible warning
devices complying with Clause 2.2.3 of AS 2220.2 and located on each storey.
(a) wherever possible, surface mounted and outside air-handling ducts, unless a
point sampling system with maximum sensitivity level of 0.5% smoke
obscuration per metre is used; and
(b) located at natural collection points for hot smoke having regard to the ceiling
geometry and its effects on the migratory path; and
(c) situated not more than 1.5 m horizontal distance from smoke doors or fire
doors; and
(d) of the photo-electric type if installed within ducts or atmospheres contaminated
with dust particles less than 1 m in size and other particles likely to operate an
ionization type detector.
7.
Threshold Levels
(a) Sampling systems must comply with AS 1670, with response times and alarm
thresholds maintained at minimum levels and no alarm delay permitted on the
highest alarm threshold utilised.
(b) The setting of alarm threshold levels for addressable detectors used within
intelligent systems must not exceed the sensitivity levels nominated in(i) AS 1668.1; and
(ii) AS 1603 Parts 1, 4 and 6.
8.
ED
PE
9.
ED
SU
A system consisting of self-contained smoke alarms must comply with the following:
(a) In a Class 1b building, self-contained smoke alarms must be installed in
suitable locations on or near the ceiling(i) in every bedroom and associated hallway; and
(ii) on each storey.
(e) (i) Self-contained smoke alarms must(A) comply with AS 3786; or
(B) be listed in the SSL Register of Accredited Products; and
(ii) be connected to the consumer mains power.
Additional provisions in State/Territory Appendices:
Vic E1.7. Self contained smoke alarms
************************************************************************************************
F2.1
F3
ED
ED
Sanitary Facilities
F2
Drainage
Sarking
F1.1
F1.2
F1.3
F1.4
F1.5
F1.6
F1.7
F1.8
F1.9
F1.10
PE
F1
F4
F4.1
F4.2
F4.3
F4.4
F4.5
F4.6
F4.7
F4.8
F4.9
F4.10
F5
F5.1
F5.2
SU
Artificial lighting
Ventilation of rooms
Natural ventilation
Airlocks
Sub-floor ventilation
F5.3
F5.5
Specifications
Specification F5.2
Specification F5.5
OBJECTIVES
A building must be so designed and constructed that the following objectives are
fulfilled:
Part F1
Part F2
Sanitary Facilities
ED
ED
Part F3
Adequate toilet and washing facilities must be provided for the occupants of a
building, having regard to its use and size.
Room Sizes
SU
Part F4
PE
The ceiling height of rooms and other spaces within a building must be adequate for
their use or purpose.
Light and ventilation within a building must be adequate for the occupants, having
regard to the use or purpose of the building.
Part F5
Noise Transmission
VIC Part F5
PART F1
F1.1
Drainage
ACT F1.1
The construction of a drainage system and the position and manner of discharge of a
stormwater drain must not(a) result in the entry of water into a building; or
(b) affect the stability of a building; or
(c) create any unhealthy or dangerous condition on the site or within the building.
F1.2
F1.3
ED
ED
One or more of the following measures must be carried out if it is warranted by the
dampness of the building site:
(a) The subsoil must be adequately drained.
(b) The ground under the building must be regraded or filled and provided with
outlets to prevent accumulation of water.
(c) The surface of the ground under the building must be covered with a suitable
damp-resisting material.
F1.4
PE
SU
Roofs and external walls (including openings around windows and doors) must be so
constructed as to prevent rain or dampness penetrating to the inner parts of a
building, unless it is(a) a Class 10 building and in the particular case there is no necessity for
compliance; or
(b) a garage, tool shed, sanitary compartment, or the like, forming part of a building
used for other purposes.
F1.5
A roof complies with F1.4 if it is covered with(a) concrete roofing tiles that comply with AS 2049 and are fixed, except in cyclonic
areas, in accordance with AS 2050, as appropriate; or
(b) terracotta roofing tiles that comply with AS 2049 and are fixed, except in
cyclonic areas, in accordance with AS 2050; or
(c) corrugated cellulose fibre reinforced cement sheeting that complies with
AS2908.1 and installed in accordance with AS 1639; or
(d) metal sheet roofing that complies with AS 1562.1; or
(e) plastic sheet roofing designed and installed in accordance with AS 2376 and
AS 2424; or
(f)
F1.6
(a)
(b)
F1.7
Sarking
Sarking-type materials used for weatherproofing of roofs and walls, as required
by F1.4, must be suitable for the purpose.
Compliance with AS 4200 satisfies (a).
SA F1.7
NSW F1.7(c)
SU
F1.8
PE
ED
ED
SA F1.8
Except in a building that is exempt from weatherproofing under F1.4, moisture from
the ground must be prevented from reaching(a) the lowest floor timbers and the walls above the lowest floor joists; and
(b) the walls above the damp-proof course; and
(c) the underside of a suspended floor constructed of a material other than timber,
and the supporting beams or girders.
F1.9
A damp-proof course must consist of(a) a material that complies with AS2904; or
(b) suitable termite shields; or
(c) other suitable material.
F1.10
If a floor of a room is laid on the ground or on fill(a) moisture from the ground must be prevented from reaching the upper surface
of the floor and adjacent walls bySA F1.10(a)(i)
ED
F2.1
ED
PART F2
Sanitary and other facilities for Class 1 buildings must be provided in accordance
with Table F2.1.
CLASS OF BUILDING
SU
Class 1
PE
Table F2.1
(a)
(b)
a bath or shower;
(c)
(d)
If any of these facilities are detached from the main building, they must
be set aside for the exclusive use of the occupants of the Class 1
building.
PART F3
ROOM SIZES
F3.1
Height of rooms
ED
ED
(a) A room or space within a building must have sufficient height suitable for the
intended function of that room or space.
(b) The requirement of (a) is satisfied if the ceiling height is not less than(i) in a Class 1, 2 or 3 building or Class 4 part(B) a kitchen, laundry, or the like - 2.1 m; and
(C) a corridor, passageway or the like - 2.1 m; and
(A) a habitable room excluding a kitchen - 2.4 m; and
(ii) *
*
*
(iii) *
*
*
(iv) *
*
*
(v) in any building(A) a bathroom, shower room, sanitary compartment, airlock, tea
preparation room, pantry, store room, garage, car parking area, or
the like - 2.1 m; and
(B) *
*
*
(C) an attic room, room with a sloping ceiling or projection below ceiling
line or a non-habitable room or similar space - a height that does not
unduly interfere with the proper functioning of the room or space.
F4.1
SU
PART F4
PE
F4.2
(a) Required natural lighting must be provided by windows that(i) have an aggregate light transmitting area measured exclusive of framing
members, glazing bars or other obstructions of not less than 10% of the
floor area of the room; and
(ii) are open to the sky or face a court or other space open to the sky or an
open verandah, carport or the like.
(b) in a Class 1 building, a required window that faces a boundary of an adjoining
allotment must not be less than a horizontal distance of 900 mm from that
boundary.
F4.3
Natural lighting to a room in a Class 1 building may come through a glazed panel or
opening from an adjoining room (including an enclosed verandah) if(a) *
*
*
(b) the glazed panel or opening has an area of not less than 10% of the floor area
of the room to which it provides light; and
(c) the adjoining room has windows with an aggregate light transmitting area of not
less than 10% of the combined floor areas of both rooms,
and the areas specified in (b) and (c) may be reduced as appropriate if direct natural
light is provided from another source.
F4.4
Artificial lighting
Ventilation of rooms
F4.5
ED
ED
SU
PE
F4.6
Natural ventilation
F4.7
Natural ventilation to a room may come through a window, opening, ventilating door
or other device from an adjoining room (including an enclosed verandah) if both
rooms are within the same sole-occupancy unit or the enclosed verandah is common
property, and(a) in a Class 1 building(i) the room to be ventilated is not a sanitary compartment; and
(ii) the window, opening, door or other device has a ventilating area of not
less than 5% of the floor area of the room to be ventilated; and
(iii) the adjoining room has a window, opening, door or other device with a
ventilating area of not less than 5% of the combined floor areas of both
rooms; and
(b) *
*
*
(c) the ventilating areas specified in (a) may be reduced as appropriate if direct
natural ventilation is provided from another source.
F4.8
F4.9
ED
A room containing a closet pan must not open directly into(a) a kitchen or pantry.
Airlocks
PE
ED
If a room containing a closet pan or urinal is prohibited under F4.8 from opening
directly to another room(a) in a Class 1 building(i) access must be by an airlock, hallway or other room; or
(ii) the room containing the closet pan or urinal must be provided with
mechanical exhaust ventilation.
F4.10
Sub-floor ventilation
SU
(a) Suitable provision must be made to prevent undue deterioration of the lowest
floor of a building because of dampness, other conditions on the allotment or
the design of the building.
(b) The requirements of (a) are satisfied if(i) an adequately cross-ventilated space is provided between the underside
of the floor, if it is suspended, and the ground surface; or
(ii) an impervious cover is provided over the ground surface beneath the
building; or
(iii) the floor members are suitably treated.
PART F5
F5.1
Application of Part
NSW F5.1
VIC F5.1
This Part applies to(a) Class 1 buildings joined by a separating wall as required by Clause 7 of
Specification C1.9.
F5.2
F5.4
A wall must have an STC not less than 45 if it separates(a) sole-occupancy units.
F5.5
SU
PE
ED
ED
CAVITY BRICKWORK-
Two leaves 90 mm brick masonry with(i) all joints filled solid with mortar; and
(ii) an air space not less than 40 mm between the leaves; and
(iii) the leaves connected only by ties in accordance with AS 3700.
SINGLE LEAF BRICKWORK
110 mm thick brick masonry with(i) each face rendered 13 mm thick; and
(ii) 50 mm x 12 mm thick timber battens at not more than 610 mm centres fixed to each face but not
recessed into the render; and
(iii) one layer of 12 mm thick softboard nailed to the battens; and
(iv) 6 mm thick medium density hardboard adhesive-fixed to the softboard.
CONCRETE BLOCKWORK190 mm thick concrete block masonry with(i) each face of the blocks fitted with 50 mm x 50 mm timber battens, spaced at not more than 610
mm centres, screw-fixed into resilient plugs with rubber inserts;
(ii) the space between the battens completely filled with mineral or glass wool blanket or batts not less
F5.7
Isolation of pumps
A flexible coupling must be used at the point of connection between the service
pipes in a building and any circulating or other pump.
Scope
This Specification lists the Sound Transmission Class ratings for some common
forms of construction.
Construction deemed-to-satisfy
ED
2.
The forms of construction listed in Table 2 are considered to have the STC stated in
that Table if installed as follows:
ED
(a) Masonry - Units must be laid with all joints filled solid, including those between
the masonry and any adjoining construction.
(b) Concrete slabs - Joints between concrete slabs and any adjoining construction
must be filled solid.
SU
PE
(c) Plasterboard (i) if one layer is required under this Specification, it must be screw-fixed to
the studs with joints staggered on opposite faces; and
(ii) if 2 layers are required, the first layer must be fixed according to (i) and
the second layer must be fixed to the first layer with nails, screws or
adhesive so that the joints do not coincide with those of the first layer; and
(iii) joints between sheets or between sheets and any adjoining construction
must be taped and filled solid; and
(iv) fire-protective grade plasterboard must be the special grade manufactured
for use in fire-resisting construction.
(d) Steel studs and perimeter members (i) the section of steel must be not less than 0.6mm thick;
(ii) studs must be not less than 63mm in depth unless another depth is listed
in the Table; and
(iii) studs must be fixed to steel top and bottom plates of sufficient depth to
permit secure fixing of the plasterboard; and
(iv) all steel members at the perimeter of the wall must be securely fixed to the
adjoining structure and bedded in resilient compound or the joints must be
caulked so that there are no voids between the steel members and the
wall.
Table 2
CONSTRUCTION
STC
(not less than)
WALLS
Clay brickwork(a) 230 mm thick in one or more leaves and with a mass per unit area of not less
2
than 290 kg/m
45
(b) 110 mm thick rendered 13 mm thick on both sides with a mass per unit area of
2
the unrendered wall being not less than 190 kg/m
45
(c) 110 mm thick, of semi-dry-pressed bricks and rendered 13 mm on one side, the
2
mass per unit area of the unrendered wall being not less than 215 kg/m
45
(d) 110 mm thick, of extruded brick and rendered 13 mm on one side, the mass per
2
unit area of the unrendered wall being not less than 180 kg/m
45
Concrete brickwork- 110 mm thick with a mass per unit area of not less than
2
195 kg/m
45
Concrete blockwork (a) 190 mm thick with a mass per unit area of not less than 215 kg/m
45
(b) 140 mm thick, the wall thickness of the blocks being not less than 44 mm and
with 50 mm x 50 mm timber battens spaced at not more than 610 mm centres
screw-fixed on one face of the blocks into resilient plugs with rubber inserts
between battens and the wall; and
(ii)
the face of the battens clad with 13 mm thick standard plasterboard; and
ED
(i)
(iii) a mass per unit area of the whole system of not less than 220 kg/m
ED
Concrete-
45
(a) In-situ concrete- 125 mm thick and with a density of not less than 2200 kg/m
45
(b) In-situ concrete- 100 mm thick and with a density of not less than 2500 kg/m
45
(a) with 2 layers of 16 mm thick fire-protective grade plasterboard fixed to each face
(b) with-
(ii)
SU
(c) with-
PE
(i)
(i)
(ii)
(iii) 2 layers of fire-protective grade plasterboard fixed to the other face, the
inner layer being 16 mm thick and the outer layer being 13 mm
(d) with 2 layers of 13 mm plasterboard on both sides of 75 mm studs
SPECIFICATION F5.5
1.
Scope
45
45
45
45
45
2.
Construction to be tested
3.
Method
ED
ED
SU
PE
G1.1
Swimming pools
G2.1
G2.2
G2.3
General requirements
Installation of appliances
Open fireplaces deemed-to-satisfy
G4.1
G4.3
G4.5
G4.6
G4.7
ED
G4
ED
G2
PE
G5
Protection required
Protection deemed-to-satisfy
SU
G5.1
G5.2
OBJECTIVES
This Section contains more specific requirements for particular parts of buildings or
structures.
Parts of buildings and structures must be so designed and constructed that the
Part G1
G1.1 Swimming pools(a) Suitable means for the disposal of waste and drainage must be provided to a
swimming pool.
QLD G1.1(b)
(b)
TAS G1.1(c)
Part G2
Part G4
Additional safety measures must be provided in alpine areas in view of the increased
difficulties in fighting fire and maintaining access and means of egress in snow or
iced conditions.
Part G5
ED
ED
G1.1
Swimming pools
NT G1.1
(a)
SU
WA G1.1
PE
PART G1
(b) Safety fencing : A swimming pool associated with a Class 1 building, with a
depth of water more than 300 mm must have suitable barriers to restrict access
by young children to the immediate pool surrounds or safety fencing in
accordance with AS2818 and AS1926.1.
ACT G1.1(c), (e)
QLD G1.1(c)
SA G1.1(c)
TAS G1.1(e)
General requirements
Installation of appliances
ED
G2.2
ED
A chimney or flue must be constructed(a) to withstand the temperatures likely to be generated by the appliance to which it
is connected; and
(b) so that the temperature of the exposed faces will not reach a level that would
cause damage to nearby parts of the building; and
(c) so that hot products of combustion will not(i) escape through the walls of the chimney or flue; or
(ii) discharge in a position that will cause fire to spread nearby combustible
materials or allow smoke to penetrate through nearby windows, ventilation
inlets, or the like; and
(d) in such a manner as to prevent rainwater penetrating to any part of the interior
of the building.
The installation of a stove, heater or similar appliance in a building must comply with:
(a) Domestic oil-fired appliances - Installation: AS1691.
(b) Domestic solid-fuel burning appliances - Installation: AS2918.
PE
G2.3
ACT G2.2(e)
SU
(i)
G4.1
Application of Part
ED
PART G4
G4.3
External doorways
ED
This Part applies to any building constructed in an alpine area and overrules other
provisions of the BCA.
SU
PE
(a) A door fitted to an external doorway which may be subject to the build-up of
snow must(i) only be capable of opening inwards; and
(ii) be marked "OPEN INWARDS" on the inside face of the door in letters not
less than 75mm high and in a colour contrasting with that of the
background; and
(iii) if it serves a corridor or stairway, be positioned in an alcove or recess so
that it does not hinder egress.
(b) An alcove or recess with(i) no horizontal dimension less than twice the width of the door; and
(ii) the door positioned to open against a wall such that the distance from any
part of its swing to the nearest point of entry of the stairway or corridor is
not less than the width of the door,
is deemed to satisfy Clause (a)(iii).
G4.5
External ramps
An external ramp serving as an exit must have a gradient not steeper than 1 in 12.
G4.6
Discharge of exits
(a) Buildings must be constructed so that snow or ice is not deposited on the
allotment, any adjoining allotment, road or public space in a location or manner
that will(i) significantly obstruct a means of egress from any building to the road or
open space; or
(ii) otherwise endanger people.
(b) Construction satisfies (a) when(i) if any part of an external wall is more than 3.6 m above the natural ground
level - the distance of that part from a boundary other than a road
alignment is not less than 2.5 m plus 100 mm for each 300 mm or part by
which that part of the wall exceeds a height of 3.6 m; and
(ii) if an exit doorway discharges into a court between wings of a building - the
wings are not less than 6m apart; and
(iii) if an exit doorway is opposite a barrier which is more than 900 mm above
the threshold of the doorway - the threshold is at a distance from that
barrier of not less than twice the height of the barrier or 6 m, whichever is
the lesser.
G4.7
Protection required
G5.1
ED
PART G5
ED
External stairways, ramps, access bridges or other trafficable structures must have(a) a floor surface that consists of steel mesh or other suitable material if it is used
as a means of egress; and
(b) any required balustrade constructed so that its sides are not less than 75%
open.
SA G5.2
Protection deemed-to-satisfy
SU
G5.2
PE
CONTENTS
This Appendix contains the BCA provisions that have been varied and additional
provisions for application to Class 1 or Class 10 buildings in the ACT.
A - GENERAL PROVISIONS
ACT Specification A1.3
ACT A2.101
B - STRUCTURE
ACT B1.3
Construction deemed-to-satisfy
ACT D2.13
ACT E1.7
ACT Specification E1.7
ED
ED
Thermal Insulation
Application
Provision of thermal insulation
SU
ACT F6.1
ACT F6.2
Drainage
PE
ACT F1.1
G - ANCILLARY PROVISIONS
ACT G1.1
ACT G2.2
ACT G2.3
ACT G2.102
Swimming pools
Installation of appliances
Open fireplaces deemed-to-comply
Chimneys and flues
INTERPRETATION
No.
Date
Title
Clause(s)
AS 1691
1985
ACT G2.3
ACT G2.102
AS 1692
1989
ACT G2.2
AS 3500
1990
Stormwater drainage
ACT F1.1
AS 3660
1993
ACT B1.3
ED
Part 3
AS 3661
Part 1
1993
Requirements
ACT D2.13
ED
ACT A2.101
Hazardous Materials
PE
ACT A2.101
SU
SECTION B STRUCTURE
PART B1 STRUCTURAL PROVISIONS
Delete B1.3(j) and insert ACT B1.3(j) as follows:
ACT B1.3
Construction deemed-to-satisfy
SECTION D
PART D2
CONSTRUCTION OF EXITS
ACT D2.13
(b) (v)
treads which have a non-slip finish or a suitable non-slip strip near the
edge of the nosings that meet the requirements of AS 3661.1.
FIRE-FIGHTING EQUIPMENT
ACT E1.7
ED
(a)
ED
PE
2.
Type of system
(b) for a Class 1, 2 or 3 building or Class 4 part of a building, Clause 9 as permitted
by Clause 8.
8.
SU
Delete the title of Clause 8 and the lead-in phrase of Clause 8(a) and insert the
following:
Class 1, 2 and 3 buildings and Class 4 part of a building - alternative
system
(a) In a Class 1, 2 or 3 building or a Class 4 part of a building, an automatic smoke
detection and alarm system mustDelete Clause 9(b) and insert the following:
9.
Self-contained smoke alarms
(b) In a Class 1a, 2 or 3 building, self-contained smoke alarms must be installed in
each sole-occupancy unit or building in suitable locations on or near the ceiling in
any storey-
ACT Part F6
Thermal Insulation
PART F1
ACT F1.1
Drainage
ED
ED
(a) The construction of a drainage system and the position and manner of
discharge of a stormwater drain must not(i) result in the entry of water into a building; or
(ii) affect the stability of a building; or
(iii) create any unhealthy or dangerous condition on the site or within a
building.
(b) Stormwater drainage satisfies (a) if it complies with AS3500.3.
THERMAL INSULATION
PE
ACT Part F6
F6.2
SU
F6.1
Application of Part
This part applies to Class 1 buildings.
Provision of thermal insulation
(a) R values - In this Part "R" or "R value" means the thermal resistance of an
element if the building measured in m2.K/W.
(b) Performance requirements - Residential buildings must have a reasonable
level of thermal insulation to conserve energy used for internal heating and
cooling.
(c) Deemed-to-comply provisions - Compliance with Table F6 satisfies (b).
Table F6 MINIMUM OVERALL R VALUE
ELEMENT
MINIMUM R VALUE
Roof or Ceiling
R3.4
External walls
R1.7
Ground floor
R1.0
(d)
Exemptions - The requirements of this Part do not apply to the following types
of construction:
(i) a ceiling space or underfloor space where unrestricted access for the
installation of insulation will be available after the completion of
construction;
(ii) cavity brick, earthwall construction, ashlar stone or other masonry walls
which have a thickness (excluding any cavity) of not less than 180 mm;
(iii) windows, vents and other similar openings in walls, roofs and ceilings; or
(iv) a garage forming part of a Class 1 building which is separated from the
habitable rooms of the building by a wall complying with the requirements
for an external wall in Table F6.
(e) Fire resistance - When tested in accordance with AS1530.3 a thermal
insulation material must have a Spread-of-Flame Index of 0 and a SmokeDeveloped Index not greater than 4.
PART G1
ED
ACT G1.1
Swimming Pools
A swimming pool with a depth of water more than 300 mm must have
suitable barriers or safety fencing to restrict access by young children to
the immediate pool surrounds.
(ii) For a swimming pool associated with a Class 1, 2 or 3 building, safety
fencing located in accordance with AS 2818 Clauses 9.2.2 or 9.2.3 or
9.2.4 and constructed in accordance with AS 1926 satisfies (i)
(c) Indoor or outdoor permanent bathing, wading and swimming pools must(i) where the capacity of the pool exceeds 10 m3(A) be of the recirculation type in which the water circulation is
maintained through the pool by pumps, the water drawn from the
pool being clarified and disinfected before being returned to the pool;
(B) have an outlet sump with antivortex cover or grating and have a
skimming weir or overflow gutter or channel at high water level; and
(C) have means of egress provided in the form of ladders, steps in the
floor of the pool or a ramp;
(ii) pools must be capable of being completely emptied and any discharge or
overflow and pool backwash filter must be connected to the sewer
drainage system;
(iii) pools must be watertight with smooth surfaces of non-absorbent, non-slip
material, light in colour and with rounded corners to facilitate cleaning;
(iv) any surrounding concourses must be graded away from the pool.
(e) Luminaires and fixed electrical appliances such as filter pumps located in the
pool area must be permanently connected except where it is necessary to
remove such equipment for servicing, connection may be made with a water
resistant plug socket located-
SU
PE
(b) (i)
ED
Delete G1.1(b) and insert ACT G1.1(b), (c) and (e) as follows:
(i) at a height of not less than 450 mm above the maximum water level or
above the coping of the pool; or
(ii) for an above-ground pool, at a height of not less than 450 mm above
ground level, at a distance not less than 1 m from the water's edge.
ACT G2.2
Installation of appliances
(e) storage tanks and other associated fittings: AS 1692, as applicable for tanks in
category 1 only.
Add ACT G2.3(e) as follows:
ED
ACT G2.3
SU
PE
ED
(e) in the case of a solid-fuel burning appliance in which the fuel burning
compartment is not enclosed(i) a flue constructed of cast iron, cellulose fibre reinforced cement not less
than 9.5 mm thick, galvanised steel not less than 1.2 mm thick or such
other material of at least equivalent strength and durability, installed in
accordance with Section 6 of AS 1691, as though it is a flue connected to
an oil heating appliance; and
(ii) the heat producing appliance installed to allow ample air circulation and
ventilation; and
(iii) footings and floor structures strengthened as necessary for the imposed
load of the fireplace so as to maintain structural adequacy; and
(iv) roof penetrations for flues treated in such a manner so as to not impair the
structural adequacy of the roof and to be weatherproof.
Add ACT G2.102 as follows:
ACT G2.102
(a) A flue must not be used to convey the hot products of combustion from more
than one appliance or fireplace except in the case of(ii) oil-fired appliances referred to in ACT G2.2, where AS 1691 or AS 1940
permits otherwise; or
(iii) open fireplaces and solid-fuel burning appliances referred to in ACT G2.2
where AS 2918 permits otherwise.
************************************************************************************************
CONTENTS
This Appendix contains the BCA provisions that have been varied and additional
provisions for application to Class 1 or Class 10 buildings in NSW.
A - GENERAL PROVISIONS
NSW A1.1
NSW A3.2
Definitions
Classifications
C - FIRE RESISTANCE
Class 1 and 10 buildings
Fire-resistance of Class 1 and 10 buildings
PE
NSW F4.5
NSW F5.1
NSW F1.7
NSW Table F2.1
ED
ED
NSW C1.9
NSW Specification C1.9
G - ANCILLARY PROVISIONS
Swimming pools
Provision for cleaning of windows
Construction in bushfire prone areas
SU
NSW G1.1
NSW G1.101
NSW G5
INTERPRETATION
Definitions
NSW A3.2
Classifications
Class 1: One or more buildings which in association constitute(a) Class 1a (i) a single dwelling; or
(ii) two attached dwellings, neither of which is located above the other or
above or below another Class of building other than its appurtenant
private garage; or
ED
(b) Class 1b - a boarding house, guest house, hostel or the like with a total
floor area not exceeding 300 m2 in which not more than 12 persons would
ordinarily be resident, which is not located above or below another Class
of building other than a private garage.
ED
NSW C1.9
SU
PE
(a) Class 1 buildings or dwellings must be protected from the spread of fire from(i) another building or dwelling other than an appurtenant Class 10 building;
and
(ii) the allotment boundary.
(b) Class 10a buildings must not significantly increase the risk of spread of fire
between Class 2 to 9 buildings.
(c) For Class 1 buildings or dwellings and Class 10a buildings appurtenant to Class
1 buildings or dwellings, construction in accordance with Specification C1.9
satisfies (a).
9.
(b) (ii)
Rooflights
1.8 m from any rooflights or the like in another building or dwelling on the
allotment other than an appurtenant building or a detached part of the
same building or dwelling.
NSW E1.1
Application of Part
NSW E1.7
ED
(a) An automatic fire detection and alarm system, designed to ensure the
occupants are given adequate warning so they can evacuate the building in an
emergency, must be installed in(i) a Class 1 building or dwelling.
(b) An automatic fire detection and alarm system satisfies (a) if it complies with
Specification E1.7.
ED
2.
SU
PE
6.
(a) wherever possible, surface mounted at the return air inlet and spill air or relief
air path outside the air handling system ducts, unless a point sampling system
with maximum sensitivity level of 0.5% smoke obscuration is used; and
Delete Clause 8 and insert new clause as follows:
8.
(a) An automatic fire detection and alarm system in(i) a Class 1 building or dwelling and a Class 2 building, where required by
NSW E1.7; and
(ii) *
*
*
must-
9.
(ii)
(iii)
ED
(e)
ED
(b) In a Class 1a building or dwelling and within sole- occupancy units in a Class 2
building and a Class 4 part of a building must have self-contained smoke
alarms installed in each building, dwelling or sole-occupancy unit in suitable
locations on or near the ceiling in any storey(i) containing bedrooms(A) between each area containing bedrooms and the remainder of the
building, dwelling or sole-occupancy unit, including any hallway
associated with the bedrooms; or
(B) in each bedroom; and
(ii) not containing bedrooms.
PE
PART F1
SU
NSW F1.7
(c) Where a bath is enclosed, the enclosure must be constructed so as to(i) prevent the creation of an unhealthy condition within the enclosure; and
(ii) prevent the entry of rodents; and
(iii) prevent the degrading of any supporting members or covering, by
moisture within the bath enclosure; and
(iv) be structurally adequate.
PART F2
Insert the following lead-in to requirements for Class 1 buildings in Table F2.1:
Class 1
PART F4
NSW F4.5
(b) (ii)
Ventilation of rooms
PART F5
NSW F5.1
Application of Part
Delete G1.1(b):
Swimming pools
NSW G1.1
ED
PART G1
ED
PE
(b) (deleted).
Note: Restriction of access to swimming pools is regulated under the Swimming
Pools Act 1992.
Add NSW G1.101 as follows:
SU
NSW G1.101
(a) A building must provide for a safe manner of cleaning any windows located 3 or
more storeys above ground level.
(b) A building satisfies (a) where(i) the windows can be cleaned wholly from within the building; or
(ii) provision is made for the cleaning of the windows by a method complying
with the Construction Safety Act 1912 and regulations made under that
Act.
NSW PART G5
CONTENTS
This Appendix contains the BCA provisions that have been varied and additional
provisions for application to Class 1 or Class 10 buildings in the Northern Territory-
A - GENERAL PROVISIONS
NT Specification A1.3 Standards Adopted by Reference.
B - STRUCTURE
G - ANCILLARY PROVISIONS
Swimming pools
ED
NT G1.1
ED
NT B1.2
Loads
NT B1.3
Construction deemed-to-satisfy
NT Specification B1.2 Loads in Cyclonic Areas.
NT Specification A1.3
INTERPRETATION
PART A1
NT Table 1
AS 1170
Part 2
Title
SU
No
PE
1989
Wind forces
SECTION B STRUCTURE
PART B1
STRUCTURAL PROVISIONS
NT B1.2
(b)
(c)
(e)
Clause
Loads
NT Spec B1.2
NT B1.3
Construction deemed-to-satisfy
(n) (deleted)
NT Specification B1.2
1.
Scope
This specification contains requirements for the design of buildings in cyclonic areas.
PE
ED
ED
2.
Design
The design of a building must, where required, comply with the provision of
AS 1170.2 so that:
(a) As a minimum requirement for residential building design in Region C, terrain
category 2 with velocity multipliers equal to the average of those given in
Table 3.2.5.2 of AS 1170.2 for categories 2 and 3 are used where a terrain
roughness normally in category 3 may be subject to deterioration in extreme
winds.
(b) For the purpose of determining internal pressures in accordance with
AS 1170.2, all window openings whether glazed or not, are regarded as
potential dominant openings unless suitable protection against debris
penetration is provided.
(c) External doors are regarded as potential dominant openings unless the doors
and their fixings are shown to be adequate to resist wind loading.
(d) Protection of an opening is adequate for the purposes of this requirement
where it can be shown capable of resisting a 4 kg mass having 100 mm x
50 mm impacting cross-section striking at any angle at a velocity of 15 m/s
without affecting internal design pressures.
SU
3.
Roof Construction
(a) Roof cladding- For the purpose of this specification, roof cladding shall not be
considered to be bracing for a roof unless it is fixed in such a manner as to act
as a braced diaphragm under the combined effects of uplift, repeated loadings
and diaphragm action.
(b) Test for strength- Metal roofing and its fitments should be capable of
withstanding without failure, the test application of 10 000 cycles of working
load from zero to that maximum at a rate of 3 Hz, followed by a static load test
of 1.8 times the working load.
4.
Masonry Veneer Construction
Masonry veneer construction must be designed so that the structural framing, to
which a masonry veneer wall is tied, will ensure the stability of the masonry veneer.
NT G1.1
Swimming pools
SU
PE
ED
ED
Delete G1.1.
************************************************************************************************
CONTENTS
This Appendix contains the BCA provisions that have been varied and additional
provisions for application to Class 1 or Class 10 buildings in Queensland.
A - GENERAL PROVISIONS
Qld A1.1
Definitions
Qld Specification A1.3 Standards Adopted by Reference.
B - STRUCTURE
Qld B1.3
Construction deemed-to-satisfy
ED
ED
Qld F1.101
Qld F2.5
G - ANCILLARY PROVISIONS
Swimming pools
Qld G1.1
PE
SU
PART A1
Qld A1.1
Definitions
Date
Clause
Qld B1.3
Qld F101.1
SECTION B STRUCTURE
PART B1
STRUCTURAL PROVISIONS
Qld B1.3
Construction deemed-to-satisfy
ED
PART F1
ED
SU
PART F2
PE
Spaces between buildings on adjoining sites which are narrower than 600 mm must
be sealed off and flashed over to prevent the entrance of weather and vermin.
Qld F2.5
VERMIN CONTROL
Qld F101.1
Control of vermin
Buildings must be constructed to prevent the entry of vermin in accordance with the
Vermin Control Regulations.
PART G1
ED
Qld G1.1
ED
SU
PE
CONTENTS
This Appendix contains the BCA provisions that have been varied and additional
provisions for application to Class 1 or Class 10 buildings in South Australia.
A - GENERAL PROVISIONS
SA A1.1
Definitions
SA Specification A1.3 Standards Adopted by Reference.
B - STRUCTURE
SA B1.3
Construction deemed-to-satisfy
SA D3.1
SA D3.2
Application of Part
Access to buildings
ED
ED
SA E1.7
Fire and smoke alarms
SA Specification E1.7 Fire Detection and Alarm Systems
SA Part F6
SA F6.101
PE
SU
SA F1.7
SA F1.8
SA F1.9
SA F1.10
RODENT PROTECTION
Minimum separation between buildings
G - ANCILLARY PROVISIONS
SA G1.1
SA G5.2
SA Part G8
SA G8.106
INTERPRETATION
SA A1.1
Definitions
ED
SA Specification A1.3
No.
Date
ED
Table 1
Title
Clause(s)
AS 1157
Part 11
SA F1.10
SA F1.10
SA F1.10
SA F1.10
SA F1.10
SU
PE
SECTION B STRUCTURES
PART B1
SA B1.3
STRUCTURAL PROVISIONS
Construction deemed-to-satisfy
SA D3.1
Application of Part
This Part applies to certain Class 1 buildings where expressly referred to.
Delete Table D3.2 and insert SA Table D3.2 as follows:
REQUIREMENTS FOR ACCESS FOR PEOPLE WITH
DISABILITIES
ED
SA TableD3.2
ACCESS REQUIREMENTS
Class 1
Whenever 20 or more sole-occupancy units of
Class 1 are constructed on a site-
ED
CLASS OF BUILDING
Note: For the purposes of this Table, the term "to and within" a building includes those parts,
elements, equipment and facilities such as ramps, handrails, grabrails, doorways, circulation
spaces, glazing, door controls, lifts, sanitary facilities, controls and floor surfaces as embraced
by AS 1428.1, excluding any references within that Standard to AS 1735.12.
SU
PART E1
PE
SA E1.7
(a)
(i)
2.
(b)
Type of system
for a Class 1 building, Clause 9 as permitted by Clause 8.
Substitute the title of Clause 8 and lead-in phrase of Clause 8(a) of Specification
E1.7 as follows:
8.
(a)
9.
SA Part F6
Rodent Protection
The formation of narrow spaces between buildings, or a building and the boundary,
must be avoided to limit the possibility of litter buildup and subsequent rodent
infestation.
ED
SA F1.7
ED
PART F1
SU
PE
(a) A laundry, bathroom, shower facility, water closet or room containing a shower
facility or a sanitary fixture such as a handbasin, vanity bowl, urinal, bidet,
cleaner's sink, slop sink, pan sink, sterilizer, potato peeler or any other similar
fixture must have(i) a floor surface that is impervious and drained to prevent the accumulation
of water on it; and
(ii) a wall surface that is impervious; and
(iii) impervious joints between the floor and wall surfaces; and
(iv) in the case of a shower facility, impervious joints between adjacent walls.
(c) The enclosure under every built-in bath must be ventilated and have an
impervious floor graded to an outlet discharging over an adjacent floor, except
where the bath is
(i) situated on the ground floor of a building and is suspended in accordance
with E&WS Sanitary Plumbing and Drainage Directions; and
(ii) that floor of the building is provided with underfloor ventilation in
accordance with clause F4.10.
(d) Every in-situ bath must have impervious surfaces and construction.
(e) Where a bench top containing an inset sanitary fixture or any sanitary fixture
abuts a wall surface (i) the wall surface must be impervious; and
(ii) the joint between the sanitary fixture or bench top and the wall surface
must be impervious.
(f) Compliance with Minister's Specification SA F1.7 is compliance with this clause.
Delete F1.8 and F1.9 and insert SA F1.8 and SA F1.9, as follows:
SA F1.8
Damp-proof courses
Except in a building that is exempt from weatherproofing under F1.4, moisture from
the ground must be prevented from reaching (a) the lowest floor timbers and the walls above the lowest floor joists; and
(b) any part of a masonry wall; and,
(c) the underside of a suspended floor constructed of a material other than timber,
and the supporting beams or girders.
SA F1.9
PE
ED
ED
(a) Every damp-proof course required must(i) be impervious to the passage of water; and
(ii) exhibit long term resistance to degradation by dissolved salts in
groundwater.
(b) The following damp-proof courses are deemed-to-satisfy the requirements of
(a):
(i) embossed black polyethylene film of high impact resistance and low slip,
with a nominal thickness of 0.5 mm prior to embossing, and meeting the
requirements of clause 7.6 of AS 2904; or
(ii) polyethylene coated metal, that has an aluminium core of not less than
0.1 mm thick, is coated both sides with bitumen adhesive enclosed in
polyethylene film of not less than 0.1 m thick on each face, and has a
nominal total thickness of not less than 0.5 mm prior to embossing; or
(iii) bitumen impregnated materials of not less than 2.5 mm thickness, that
meet the requirements of clause 7.5 of AS 2904, when used in walls not
higher than 7.8 m above the level of the damp-proof course; or
(iv) other suitable material.
SA F1.10
(a) (i)
SU
the insertion of a vapour barrier in accordance with AS 2870.1 that has the
following qualities(A) Permeability not greater than 0.02g/N.s; and
(B) Durability:
(B1) Resistance to biological decay in accordance with AS 1157;
and
(B2) Resistance to termite attack in accordance with ASTM D334574; and
(C) Resistance to Damage:
(C1) Puncture resistance test to ASTM E154. Resistance should be
no less than 200 N and 'stretch' no less than 43 mm; and
(C2) Tear strength to ASTM D1922 with a minimum strength of 8 N
in any direction; and
(C3) Falling aggregate impact test to the CSIRO method with
maximum permeance of 0.02 g/N.s after testing; or
SA PART F6
RODENT PROTECTION
SA F6.101
Minimum separation between buildings
Every part of an external wall of a building must be no less than 600 mm from(a) the external wall of any other building on the same site; or
(b) any boundary of the site, unless that wall is on or abutting that boundary,
unless the space between external columns is not infilled.
SA G1.1
ED
Swimming pools
ED
SU
PE
PART G5
SA G5.2
SA Part G8
MISCELLANEOUS PROVISIONS
SU
PE
ED
ED
SA G8.106
Detached incinerators
A detached incinerator must be situated so that no part of that incinerator is less than
2 m from any boundary of the site, and every other building or structure on the site,
or such greater distance as may be required in any area under the Country Fires Act
1989.
************************************************************************************************
CONTENTS
This Appendix contains the BCA provisions that have been varied and additional
provisions for application to Class 1 or Class 10 buildings in Tasmania.
A - GENERAL PROVISIONS
A1.1
Definitions
C - FIRE RESISTANCE
C1.2
Rise in storeys
Tas Specification C1.9 Fire-resistance of Class 1 and 10 Buildings.
Tas F2.102
ED
ED
Tas E1.1
Application of Part
Tas E1.7
Fire and smoke alarms
Tas Specification E1.7 Fire Detection and Alarm Systems
G - ANCILLARY PROVISIONS
Swimming pools
PE
Tas G1.1
SU
INTERPRETATION
A1.1
Definitions
C1.2
ED
ED
PART C1
SU
PE
(a) The rise in storeys is the greatest number of storeys at any part of the external
walls of the building(i) above the finished ground next to that part; or
(ii) if part of the external wall is on the boundary of the allotment, above the
natural ground level at the relevant part of the boundary.
(b) A storey is not counted if(i) it is situated at the top of the building and contains only service units or
equipment; or
(ii) it is situated partly below the finished ground and the underside of the
ceiling is not more than 1m above the average finished level of the ground
at the external wall, or if the external wall is more than 12 m long, the
average for the 12 m part where the ground is lowest.
Tas 101
Roofing
(a) Except as set out in (b) and (c), the roofs of all Class 1 and 10 buildings must
be non-combustible.
(b) Subject to B1.1, and Specification C1.1 Clauses 2.4 and 3.6 excluding
paragraph (a) and (c), PVC, Acrylic, Polycarbonate and GRP sheeting may be
used as a roof covering or canopy over a balcony, verandah, carport, covered
way, swimming pool, barbeque area, or similar open structure which is attached
to a Class 2, 3, 4, 5, 6, 7, 8, or 9 building.
(c) On any land zoned Rural (except Rural Residential) in the Municipality's or
City's sealed Planning Scheme or Effective Interim Order, if a Class 1 or 10
building or a farm building is situated at a distance not less than shown in Tas
Table 101, the roof of that building may be covered with a combustible material.
Tas TABLE 101
Building
Other Building
Allotment Boundary
Class 1 or 10
30
15
30
Farm Building
15
15
ED
ED
(d) Where in accordance with (c) a roof is covered with wood shingles or shakes
over a combustible roof or ceiling, the shingles or shakes must be underlaid
with a material having a Flammability Index not greater than 2.
(e) A roof covered with any of the following materials satisfies (a)(i) metal sheeting or tiles;
(ii) slates;
(iii) terracotta or cement roofing tiles;
(iv) cement fibre sheeting or shingles;
(v) asphalt shingles except on buildings with rise in storeys exceeding 2;
(vi) built-up roofing covered with non-combustible material; or
(vii) concrete, granolithic, terrazzo, cement mortar, or other similar noncombustible materials.
SU
PART E1
PE
Tas E1.1
Application of Part
Tas E1.7
(a) An automatic fire detection and alarm system, designed to ensure the
occupants are given adequate warning so they can evacuate the building in an
emergency, must be installed in(i) a Class 1 building.
2.
Type of system
8.
(a) In a Class 1 building, an automatic smoke detection and alarm system mustDelete the lead-in phrase of Clause 9(b) of Specification E1.7 and insert the
following:
ED
9.
ED
SANITARY FACILITIES
PART F2
PE
SU
Swimming pools
PE
Tas G1.1
PART G1
ED
ED
SU
(e) If the volume of a swimming pool exceeds 15 m3(i) an adequate water recirculation, disinfection and filtration system must be
installed;
(ii) the inlet and outlet openings in a swimming pool for the purpose of water
recirculation must be so located that water movement is continuous from
inlet to outlet;
(iii) inlet and outlet openings, and skimmer boxes where provided, must
comply with AS 1926.3;
(iv) recirculation of water in a swimming pool must be so designed that the
pool contents are recirculated not less than once in the period shown in
Tas Table G1.1(e); and
(v) water filtration rates must not exceed 12 250 L/m2 of sand filter bed per
hour, or an equivalent rate in other filter media.
Tas TABLE G1.1(e)
Pool Type
Period
6 hours
4 hours
Wading Pool
2 hours
Tas G101.1
Construction and location of projections over ways
(a) In this Part the following meanings apply:
Awning means a cover projecting from a building to provide shelter or shade
for people outside the building.
Balcony means a permanent projection from a building, designed to be walked,
stood or sat on, and which is not roofed.
Kerb-line means the line of the carriageway edge of the kerb or, where there is
no kerb, the line of the carriageway edge of the kerb if there was one.
Verandah means a permanent, roofed projection from a building, designed to
be walked, stood or sat on.
(f)
ED
ED
(d)
(e)
(c)
(b)
Awnings
PE
2.7 m
2.4 m
Other projections
3.0 m
SU
non-combustible
(ii)
combustible
Balconies
Other projections(i)
900 mm
600 mm
Note :
(i)
A door, gate, window, sash, or shutter is not deemed to open outwards unless, when open to its
utmost extent, some part of it projects beyond the boundary line of the way.
(ii) The total width of all the oriel windows and turrets projecting on to a way in any wall of any storey
of a building, taken together, must not exceed 3/5of the length of that wall on the level of that
storey.
Tas G101.2
Protection of ways
(a) Every roof of a building, and every verandah, balcony, or other similar
projection or projecting window must be so designed and built as to prevent
stormwater from it from dropping on, running over, or seeping under any way.
(b) The roof of any awning that extends more than 1.0 m over a way must be
drained to a down pipe.
(c) Down-pipes from awnings(i) must not project beyond the boundary of a way; and
(ii) must be of steel or provided with a protective cover to a height of 2 m from
the path.
(d) Any excavation must be protected, by shoring or otherwise, as necessary to
prevent subsidence into the excavation of any part of a way adjoining it.
(e) Footings must not extend beyond the boundary of a way other than as shown in
Tas Table G101.2.
PROJECTION OF FOOTINGS
ED
Nil
450 mm
Exceeding 3.0 m
750 mm
ED
1.3 m to 3.0 m
SU
PE
************************************************************************************************
CONTENTS
This Appendix contains the BCA provisions that have been varied and additional
provisions for application to Class 1 or Class 10 buildings in Victoria.
A - GENERAL PROVISIONS
Vic A1.1
Vic Specification A1.3
Definitions
Standards Adopted by Reference
B - STRUCTURE
Vic B1.3
Construction deemed-to-satisfy
ED
Application
Fire and smoke alarms
Fire Detection and Alarm Systems
ED
Vic E1.1
Vic E1.7
Vic Specification E1.7
PE
Application
Provision of thermal insulation
Chimneys and flues
Installation of reflective foil laminate
SU
Vic F6.1
Vic F6.2
Vic F6.3
Vic F6.4
INTERPRETATION
Vic A1.1
Definitions
No
Title
ED
Table 1
ED
Clause(s)
Vic F6.4
AS 1926
AS 1904
1982 Hardboard
Amdt 1
AS 2701
Part 10
1984
Methods of testing
1984
SU
Part 2
PE
AS 2458
Vic E1.7
Vic F6
Vic B1.3
Supplementary Tables
Timber Promotion Council 1992
Vic B1.3
SECTION B STRUCTURE
PART B1
STRUCTURAL PROVISIONS
Vic B1.3
(f) Timber construction(iv) Timber structures not located in an area subject to snow loads: Timber
Framing Manual and Supplementary Tables.
Add B1.3 (p), (q) and (r) as follows:
Vic B1.3
TABLE B1.3(n)
ED
1 - 1400
100 x 100 or
110 diameter
1401 - 1800
100 x 100 or
110 diameter
1801 - 3000
125 x 125 or
140 diameter
REINFORCEMENT
diameter
ED
LENGTH OF STUMPS
mm
Notes:
PE
SU
(iii) the roof is so constructed that the external walls are not subject to any
thrust therefrom;
(iv) such external walls must not be required to support any load other than
the distributed load of the roof;
(v) cross walls or equivalent buttresses are constructed at not more than 9 m
centres; and
(vi) notwithstanding (o) the mortar mix used is no weaker than the ratio of 1
part cement to 1 part lime to 6 parts fine aggregate volume batched.
ED
Application
ED
Vic E1.1
Vic E1.7
PE
SU
2.
Type of system
8.
Substitute the lead-in phrase of Clause 9(b) and (e)(ii) of Specification E1.7 as
follows:
9.
ED
Thermal Insulation
PART F2
ED
Substitute paragraph (c) of requirements for Class 1 buildings in Table F2.1 with:
CLASS OF BUILDING
(c) Except in a movable unit constructed under section 18 of the Housing Act
1983, on the same allotment as another building, clothes washing facilities,
comprising at least one wash-tub and space in the same room for a
washing machine or wash copper; and
SU
Class 1
PE
PART F5
Vic F5.1
Application of Part
(a) Floors and internal walls separating sole-occupancy units must provide a
reasonable level of acoustic privacy in(i) Class 1 buildings joined by a separating wall as required by Clause 7 of
Specification C1.9; and
(ii) Class 2 and 3 buildings.
(b) Construction satisfies (a) if it complies with the provisions of this Part.
VIC PART F6
Vic F6.1
THERMAL INSULATION
Application
Vic F6.2
(a) R values - In this Part "R" or "R value" means the thermal resistance of an
element of the building measured in m2.K/W.
Table F6.1
ED
ED
OPTION B
Roof or ceiling
R2.2
R2.2
External walls
R1.3
ELEMENT
Ground Floor
R0.4
SU
Table F6.2
PE
(d)
R1.0
R1.7
DESCRIPTION OF ELEMENT
col 1
R VALUE
col 2
Roofs or ceilings
Tiled or metal pitched roof, R2.5 bulk insulation between ceiling joists, lined ceiling
R2.4
Tiled or metal pitched roof, rfl as sarking and insulation over rafters, R2.0 bulk insulation
between ceiling joists, lined ceiling
R2.2
Metal deck roof, rfl as sarking and insulation, 20 mm air gap, R2.0 bulk insulation installed
between joists/beams, rfl as a vapour barrier, ceiling lining on underside of joists/beams
R2.2
Metal deck roof, R2.0 bulk insulation installed between rafters, rfl as a vapour barrier, ceiling
lining on underside of rafters
R2.2
Metal deck roof, R2.0 bulk insulation installed between roof battens, rfl as a vapour barrier,
ceiling lining on top of exposed rafters
R2.2
Tiled roof, rfl as sarking and insulation, R2.0 bulk insulation installed between counter battens,
optional rfl as a vapour barrier, ceiling lining on top of exposed rafters
R2.2
External walls
Brick/masonry veneer with double sided rfl fixed to external face of studs, lined internally
R1.3
Brick/masonry veneer with R1.5 bulk insulation between the studs, lined internally
R1.7
Brick/masonry veneer with R1.0 foam board fixed over the face of the studs, lined internally
R1.7
Weatherboard/fibre-cement, double sided perforated rfl dished between studs lined internally
R1.3
Weatherboard/fibre cement cladding, R1.5 bulk insulation between studs, lined internally
R1.7
R1.3
150 mm concrete panel with R1.0 foam board and lined internally
R1.3
Floors
Concrete/masonry on ground
R1.5
R0.4
Timber framed floor, enclosed perimeter perforated rfl dished between joists
R1.0
Timber framed floor, enclosed perimeter, 13 mm foam board fixed to the underside of floor
joists
R1.0
ED
(e) Exemptions - The requirements of this Part do not apply to the following types
of construction:
(i) concrete panels, cavity brick, earthwall construction, ashlar stone or other
masonry walls which have a thickness (excluding any cavity) of not less
than 180mm if the floor of the building is concrete or masonry in direct
contact with the ground;
(ii) windows, vents and other similar openings in walls, roofs and ceilings; or
(f) Separating walls - For the purposes of (c), a wall which separates a Class 1
building from a Class 10a building is regarded as an external wall.
ED
Vic F6.3
Chimneys and flues from open solid fuel-burning appliances must be provided with a
damper or flap.
Vic F6.4
SU
PE
CONTENTS
This Appendix contains the BCA provisions that have been varied and additional
provisions for application to Class 1 or Class 10 buildings in Western Australia.
B - STRUCTURE
WA B1.3(g)
WA B1.3(m)
WA B1.3(o)
WA Specification B1.3(m)
WA Specification B1.3(o)
Footings
Earth wall construction
Seismic construction: Class 1 buildings
Earth Wall Construction
Seismic Construction- Class 1 Buildings
C - FIRE RESISTANCE
Fire-resistance of Class 1 and 10 buildings
ED
WA Specification C1.9
WA D2.1
WA D2.16
ED
Application of Part
Balustrades
WA F2.5
PE
G - ANCILLARY PROVISIONS
Swimming pools
SU
WA G1.1
SECTION B STRUCTURE
PART B1
STRUCTURAL PROVISIONS
Delete B1.3(g) and (m), and insert WA B1.3(m) and (p) as follows:
WA B1.3
(g)
Construction deemed-to-satisfy
(deleted).
WA Specification B1.3(m)
1.
Scope
This Specification contains the requirements for earth-wall construction.
2.
Definitions
For the purpose of this Specification:
Adobe construction means a type of construction using blocks of sun dried
mud.
Bulletin 5 means CSIRO-NBTC Bulletin 5 Earth Wall Construction 4th Edition
1987.
Earth-wall construction means adobe construction, mechanically pressed-soil
block construction or rammed-earth construction.
Mechanically pressed-soil block construction means a type of construction
using blocks produced by pressed block making machines.
Rammed-earth construction means a type of construction in which damp
earth is tamped in situ between temporary movable framework.
Terrain Category followed by a designation, refers to the terrain category so
designated in AS 1170.2.
ED
3.
Not permitted in certain places
A building must not be of earth-wall construction if it is situated on a site that is
subject to flooding.
ED
4.
Construction generally
(a) A building of earth-wall construction must be constructed in accordance with
the recommendations contained in Bulletin 5 except where varied by this
Specification.
(b) A building of earth-wall construction must not exceed two storeys in height and
walls must be laterally restrained at intermediate floor level.
SU
PE
5.
Sample of test results may be required
Prior to and during construction, Council may require(a) in the case of(i) rammed-earth construction - a sample panel at least 900 mm long by 900
mm high;
(ii) adobe construction - a sample comprising of a least 3 blocks, made of the
materials and by the methods to be used in the construction, to be
provided for inspection on the site; and
(b) in the case of mechanically pressed-soil block construction - the submission to
it of the results of tests, conducted in accordance with Appendix E of Bulletin 5,
made on blocks of the kind to be used in the construction after they have been
moist cured for seven days.
6.
Minimum thickness of walls
In a building of earth-wall construction, the thickness of a wall must be(a) In the case of adobe construction or rammed-earth construction(i) for an external wall, not less than 250 mm; and
(ii) for an internal wall, not less than 200 mm;
(b) In the case of mechanically pressed-soil block construction(i) for an external wall, not less than 250 mm; and
(ii) for an internal wall, not less than 150 mm.
7.
Protection
Every building of earth-wall construction(a) must be provided with a suitable means of protection to prevent water from the
roof running down the face of every wall; and
(b) must, except in the case illustrated in Figure 1.3 of Bulletin 5, have the ground
adjacent to the walls so graded and paved as to prevent any surface water from
reaching those walls.
After WA Specification B1.3(m), insert WA Specification B1.3(p) as follows:
WA Specification B1.3(p)
1.
Scope
Interpretation
ED
2.
Construction
3.
ED
In this Specification (a) timber framing connector means a manufactured connector system for timber
joints formed from 1.2 mm minimum thickness galvanised steel and punched to
take nails; and
(b) acceleration coefficient means an index number determined under AS 1170.4
SU
PE
Application
(a) This Table applies to Class 1 buildings having a rise in storeys no greater than 1 and located in
an area with a coefficient of acceleration of 0.12 or greater but less than 0.15.
(b) This Table does not apply to Class 1 buildings having
(i)
(ii)
2.
(ii)
(iii) to every stump projecting more than 650 mm out of the ground.
(c) Floor beams - fixed to the top of stumps with two M10 diameter bolts or equivalent fixing.
(d) Bottom plates of framed structures where fixed to a concrete raft or strip footing - fixed with M10
bolts or masonry anchors at 1200 mm maximum centres.
(e) Concrete strip footings - continuously reinforced with two layers of reinforcement comprising two
12 mm diameter bars (Grade 400Y) per layer and tied with R6 ligatures at centres not exceeding
2.5 times the depth of the footing.
(f)
3.
(a) Metal framingcomplying with AS 1538 or AS 1884, braced and nogged with welded joints or fixed with
self-tapping fastenings or bolts to give a joint of equal strength.
(ii)
with material used in walls, other than bracing, not to be less than 1.2 mm thick.
ED
(i)
(iii) wall plates - continuous between cross walls or spliced to maintain strength.
(b) Timber framing-
fixed with timber framing connectors nailed with a least three 2.8mm diameter x 30 mm
long nails to each fixing plate or the connector; or
(ii)
constructed of seasoned timber, fixed with at least two 2.8 mm diameter nails, machine
nailed through the top or bottom wall plate into the stud.
ED
(i)
(iii) wall plates - continuous between cross walls or spliced to maintain strength.
Masonry Construction
4.
PE
(a) Internal or external walls 4m in length or greater - stiffened by cross walls, columns or bracing,
certified by a professional engineer as complying with AS 1170.4.
(b) Cross walls - tied to the internal leaf of cavity walls by fully bonding or by metal ties at every
second course.
SU
(f)
(i)
(ii)
to be solid when laid in the top two courses of internal walls and the internal leaf of
external walls.
Reinforcement(i)
both leaves of external walls, reinforced with two R6 bars (Grade 250), or two 3.15 mm
diameter bars (Grade 450), in the course immediately under window sills and over door
and window heads.
(ii)
(iii) to extend a minimum of 300 mm beyond the supporting cross walls or columns.
(iv) in cross walls, turned and lapped 300 mm into the external walls.
(v) splices, not less than 300 mm
(g) Continuous reinforced brick bond beams, comprising two R6 bars (Grade 250), or two 3.15 mm
diameter bars (Grade 450), in each of the top three bed joints, constructed(i)
on the internal leaf of all external walls and on all cross walls; and
(ii)
where the roof is pitched on the external leaf of an external wall, on that external leaf.
(h) Top wall plates - fixed to the second top course of walls by masonry anchors, or equivalent
fixing, at 1 800 mm maximum centres.
5.
(a) Veneers(i)
to comprise an external leaf of masonry and internal walls of timber or metal framing.
(ii)
6.
Roof Construction
WA TABLE B1.3B
1.
Application
ED
(a) This Table applies to Class 1 buildings having a rise in storeys no greater than 1 and located in
an area with a coefficient of acceleration of 0.15 or greater.
a roof clad with concrete or terracotta tile; or
(ii)
2.
ED
(i)
(b) Bracing to stumps - fixed with galvanised M 12 bolt or equivalent to comply with AS1684at intervals not exceeding 8m.
(ii)
(i)
(iii) to every stump projecting more than 500 mm out of the ground.
(c) Floor beams- fixed to the top of stumps with two M10 bolts or equivalent fixing.
PE
(d) Bottom plates of framed structures where fixed to a concrete raft or strip footing - fixed with M10
bolts or masonry anchors at 1 200 mm maximum centres.
(f)
SU
(e) Concrete strip footings - continuously reinforced with two layers of reinforcement comprising two
12 mm diameter bars (Grade 400Y) per layer and tied with R6 ligatures at centres not exceeding
2.5 times the depth of the footing.
Raft slabs- Incorporating monolithic edge beams.
3.
complying with AS 1538 or AS 1664, braced and nogged with welded joints or fixed with
self-tapping fastenings or bolts to give a joint of equal strength.
(ii)
with material used in walls, other than bracing, not be less than 1.2 mm thick.
(iii) wall plates - continuous between cross walls or spliced to maintain strength.
(b) Timber framing(i)
fixed with timber framing connectors nailed with at least three 2.8mm diameter x 30 mm
long nails to each fixing plate or the connector; or
(ii)
constructed of seasoned timber, fixed with at least two 2.8 mm diameter nails, machine
nailed through the top or bottom wall plate into the stud.
(iii) wall plates- continuous between cross walls or spliced to maintain strength.
4.
(a) Veneers(i)
to comprise an external leaf of masonry and internal walls of timber or metal framing.
(ii)
wall plates(A) fixed to transfer lateral loads between frames of external walls and frames of
internal walls.
(B) F8 grade timber minimum dimensions 100 mm x 50 mm where cross walls are
spaced at not greater than 4 800 mm centres.
(ii)
external walls framing in external walls - fixed to supporting cross walls at or near top wall
plate level by at least two timber framing connectors with at least three 2.8 mm diameter
nails to each plate of the connector or by bolting the frames together with M10 minimum
diameter bolts.
wall plates(A) fixed to transfer lateral loads between frames of external walls and frames of
internal walls.
(B) minimum dimensions 78 mm x 31 mm x 1.2 mm where cross walls are spaced at
not greater than 5 500 mm centres, and stiffened by an additional 75 mm x 78 mm
x 1.6 mm plate where the span exceeds 3 500 mm.
external walls - framing in external walls, fixed to supporting cross walls at or near top wall
plate level by at least two framing connectors or by bolting the frames together with M 10
minimum diameter bolts.
ED
(ii)
(d) external walls - 100 mm x 100 mm galvanised steel mesh fixed to the timber or metal framing of
external walls clad with masonry veneer.
6.
ED
(b) Roof framing - fixed to the top wall plate using timber framing connectors nailed with at least
three 2.8 mm diameter x 30 mm long nails to each fixing plate of the connector.
SU
PART C1
PE
CONSTRUCTION OF EXITS
WA D2.1
AppIication of Part
Except for WA D2.16(i), this Part does not apply to(a) a Class 1 or Class 10 building.
After D2.16(h) insert WA D2.16(i) as follows:
WA D2.16
Balustrades
ED
PART F2
ED
WA F2.5
SU
PE
(b) Doors - the door of every fully enclosed closet pan compartment must(i) open outwards; or
(ii) be readily removable from the outside.
WA G1.1
Swimming pools
SU
PE
ED
ED
***********************************************************************************************