MiCOM C264 LHMI
Configuration
PACiS Technical Training Level 2
CS&P Support Team
PCL
Content
GHU Board Configuration
Bitmaps configuration
LCD configuration
LED assignment
Schneider Electric - CS&P C264 LHMI Configuration E01
Content
GHU Board Configuration
Bitmaps configuration
LCD configuration
LED assignment
Schneider Electric - CS&P C264 LHMI Configuration E01
Configure the GHU board
1) C264 with or without LCD => 2 possible GHU boards
2) GHU attributes
HMI Type :
- Simple : no LCD and LED#4 is not
configurable
- Complete : LCD, LED#4 is configurable and
GHU should be linked to a graphic object
typed Computer Workspace
Schneider Electric - CS&P C264 LHMI Configuration E01
GHU Board Sons & Relations
Board status MPS
Set of LED :
LED#4 not configurable if GHU type = Simple
Relation with graphic configuration :
Completed if GHU type = Complete
Schneider Electric - CS&P C264 LHMI Configuration E01
Content
GHU Board Configuration
Bitmaps configuration
LCD configuration
LED assignment
Schneider Electric - CS&P C264 LHMI Configuration E01
What for?
1) On C264 LCD, in bay panels
= > Single Line Diagrams
- static objects (lines, bitmaps)
- animated objects
2) Graphic table for bitmaps (up to 150)
Note : Starting database is containing bitmap table (IEC)
Schneider Electric - CS&P C264 LHMI Configuration E01
Bitmap Attributes
Short Name :
Rule : put bitmap index in prefix
Bitmap index :
Bitmap index = bitmap identification used at
LCD configuration level
Bitmap type :
-5-uple = animated
-single = non-animated
Schneider Electric - CS&P C264 LHMI Configuration E01
Bitmap Representation (1)
Default
Open*
Closed*
* associated
information in
Closed/Set or
Open/Reset state
Note : bitmap max size = 64x64 pixels
Schneider Electric - CS&P C264 LHMI Configuration E01
Bitmap Representation (2)
Default
Open
Closed
Withdrawn
Open
Withdrawn
Closed
Note : withdrawn = combination of DPS position + withdrawn SPS
Schneider Electric - CS&P C264 LHMI Configuration E01
10
Content
GHU Board Configuration
Bitmaps configuration
LCD configuration
LED assignment
Schneider Electric - CS&P C264 LHMI Configuration E01
11
Add / Configure a Computer Workspace
1) Graphic Part / Computer Workspace
2) Attributes
Short Name
L/R password protection :
Operator has to enter password when
changing bay control mode (Local/Remote)
Schneider Electric - CS&P C264 LHMI Configuration E01
12
Add / Configure a Bay Mimic
1) Graphic Part / Computer Workspace
2) Attributes
Short Name
MV bargraph :
Horizontal / Vertical
Advise to not use
Module Name display
3) Relations => relation with the represented bay
Mimic rank :
one bay can be represented on 1 or 2
mimics
Schneider Electric - CS&P C264 LHMI Configuration E01
13
Add Graphic Objects in Bay Mimic (1)
1) Typical Bay Mimic (128x128 pixels)
Time :
optional
Mandatory :
- Bay L/R
- Interlock bypass (local activation)
- Synchrocheck bypass (local activation)
Controllable devices :
- LHMI Gen Modules
- up to 9 per mimic
Static graphics :
lines, single bitmaps
Note : no graphics outside of area => C264 failure
Schneider Electric - CS&P C264 LHMI Configuration E01
14
Add Animated Objects in Bay Mimic (2)
2) Add a LHMI Gen Module
3) Configure a LHMI Gen Module
Short Name :
different from displayed name
Control availability :
Yes = controllable from LCD
4) LHMI Gen Module Sons
Graphic object with datapoint relation
is managed by SPS or DPS
Displayed name
4 characters
Representing bitmap index
Schneider Electric - CS&P C264 LHMI Configuration E01
15
Add Animated Objects in Bay Mimic (3)
5) Add a LHMI Transformer
6) LHMI Transformer configuration
Graphic object with TPI relation
is managed by TPI
Minimum, Current and
Maximum TPI values
are mandatory
Bitmap index
Schneider Electric - CS&P C264 LHMI Configuration E01
16
Content
GHU Board Configuration
Bitmaps configuration
LCD configuration
LED assignment
Schneider Electric - CS&P C264 LHMI Configuration E01
17
Reminder
1) LED can be animated by SPS or DPS status
13 available LED for Complete HMI
12 available LED for Simple HMI (LED#4 = C264 Local/Remote)
LED can be :
- Off
- On
- Blinking fast
- Blinking slow
Schneider Electric - CS&P C264 LHMI Configuration E01
18
Assign a SPS/DPS to LED
1) Under SPS, add the relation has state displayed on LED
2) Complete the relation
Complete the relation
by selecting LED of
the GHU board
Schneider Electric - CS&P C264 LHMI Configuration E01
19
Assign a SPS/DPS to LED
3) Configure the relation for behaviour of LED :
LED Behaviour :
- For status
- For alarm
LED Behaviour per status :
Closed / OPEN / Invalid behaviour
Off / On / Blinking Slow / Blinking Fast
LED Behaviour for alarm :
Off / On / Blinking Slow / Blinking Fast
Note 1 : 1 LED represents only 1 datapoint
Note 2 : behaviour for alarm will depend on alarm
definition in datapoint profile of this DP.
Schneider Electric - CS&P C264 LHMI Configuration E01
20