DATA SHEET
Automatic Genset Controller, AGC-4
Single or synchronising gensets
Power plant control
Fast synchronising
Control and protection
Customised logic and control
SW emulation of application
DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 [email protected] www.deif.com
isenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 [email protected] www.deif.com
14 9614 Fax: +45 9614 9615 [email protected] www.deif.com
Document no.: 4921240400K
SW version: 4.4x.x or later
AGC-4 data sheet 4921240400 UK
1. Application information
1.1. General information................................................................................................................................3
1.1.1. Application.....................................................................................................................................3
1.1.2. Application emulation.....................................................................................................................3
1.1.3. Inputs and outputs.........................................................................................................................4
1.1.4. Included functions..........................................................................................................................5
1.1.5. Protections.....................................................................................................................................7
1.1.6. Single line application diagrams....................................................................................................8
1.1.7. Terminal overview .......................................................................................................................10
1.2. Power management applications.........................................................................................................11
1.2.1. Application...................................................................................................................................11
1.2.2. Description...................................................................................................................................11
1.2.3. Power management functions.....................................................................................................12
1.2.4. Easy configuration of single line diagrams..................................................................................13
1.2.5. Safe power management system................................................................................................13
1.2.6. Optional power management applications ..................................................................................14
2. Optional functionality
2.1. Display layouts.....................................................................................................................................16
2.1.1. Option Y1 ....................................................................................................................................16
2.1.2. Option Y3 ....................................................................................................................................16
2.1.3. Option Y4.....................................................................................................................................16
2.1.4. Option Y5.....................................................................................................................................17
2.1.5. Option X3 ....................................................................................................................................17
2.1.6. Option X4 ....................................................................................................................................17
2.2. Available options..................................................................................................................................18
2.2.1. Available variants ........................................................................................................................18
2.2.2. Available software options...........................................................................................................19
2.2.3. Available accessories..................................................................................................................21
2.2.4. Hardware options and slot number location................................................................................22
3. Technical information
3.1. Specifications and dimensions.............................................................................................................25
3.1.1. Technical specifications ..............................................................................................................25
3.1.2. Unit dimensions in mm (inches)...................................................................................................29
4. Ordering information
4.1. Order specifications and disclaimer.....................................................................................................30
4.1.1. Order specifications.....................................................................................................................30
4.1.2. Disclaimer....................................................................................................................................30
DEIF A/S
Page 2 of 30
Application information
AGC-4 data sheet 4921240400 UK
1. Application information
1.1 General information
1.1.1 Application
The Automatic Genset Controller, AGC, is a control unit containing all necessary functions for protection and
control of a genset. It can be used as a single unit for one genset, or a number of AGCs can be connected in
a complete power management system for synchronising projects, islanded or paralleled to the mains. The
AGC contains all necessary 3-phase measuring circuits, and all values and alarms are presented on the sunshine proof LCD display.
The AGC is a compact all-in-one unit designed for the following applications:
Standard plant
modes
Applications
Island mode
Power plant with synchronising generators or a stand-alone generator. Can also
be used in critical power plants.
Automatic Mains Failure
Critical power/emergency standby plants, black start generator.
Fixed power
Power plant with fixed kW setpoint (including building load).
Peak shaving
Power plant where generator supplies peak load demand paralleled to the mains.
Load takeover
Plant mode where the load is moved from mains to generator, e.g. peak demand
periods or periods with risk of power outages.
Mains power export
Power plant with fixed kW setpoint (excluding building load).
Remote maintenance
Used when the generator has to supply the load while a distribution transformer
needs to be disconnected for service.
The plant modes are configurable, and it is possible to change the plant mode on the fly both in single and in
power management applications.
All modes can be combined with Automatic Mains Failure mode (AMF).
Remote maintenance requires a DEIF RMB box (separate product) and a set of cables (option
J8).
The plant/genset is easily controlled from the display unit, or a HMI/scada system can be implemented using
one of the communication options. Three display units can be installed per control unit.
1.1.2 Application emulation
In order to verify and test the functionality of the application, it is possible to use the emulation tool of the
AGC. Being connected to the AGC gives the possibility to test a majority of the functionality, e.g. plant modes
and logics, breaker handling, mains and generator operation.
Application emulation is useful for training, customising plant requirements and testing basic functionality that
needs to be set up or verified.
DEIF A/S
Page 3 of 30
AGC-4 data sheet 4921240400 UK
Application information
In a power management system it is possible to control the entire plant, being connected only to one of the
connected AGC controllers.
1.1.3 Inputs and outputs
The number of inputs and outputs in the AGC can be tailored depending on the option selection. This table
includes the number of I/Os in the standard unit (no options present). The four outputs of the governor/AVR
card in slot #4 are not included in the table.
In-/outputs
Occupied
Available for other configuration
Multi-selectable inputs
Digital inputs
2 for breaker ON/OFF feedbacks (4 if MB is
present)/1 E-stop
9 (7 if MB is present)
RPM (MPU)
Relays for engine control
4 (start prepare/crank/stop/run)
Relays for breaker control
2 (4 if MB is present)
2 (0 if MB is present)
Relay
1 (status/watchdog)
Open collector outputs
DEIF A/S
Page 4 of 30
AGC-4 data sheet 4921240400 UK
Application information
1.1.4 Included functions
General functions
AGC-4
standard
(Y3)
AGC-4 DG
(Y1)
AGC-4
mains (Y4)
AGC-4 BTB
(Y5)
Synchronising
Short time parallel
USB interface to PC
Temperature-dependent cooling down
Time-based cooling down
Emergency cooling down
kWh meter
Day/week/month/total
kVArh meter
Day/week/month/total
x
x
Engine running hours counter, emergency,
normal
Start attempt counter
Maintenance counter
Breaker operation counter
Free PC utility SW (Windows)
Permission settings in PC utility SW for limited
SCADA access
Password-protected setup
Power derate
Nominal settings for rental gensets
Battery test, crank or asymmetry
Lube oil renewal
Mains support (frequency and voltage)
Fan control of 4 fans
Fuel pump logic
Engine block heater control
Customised display views
Command timers
Master clock
Pulse input counters
Current thermal demands
DEIF A/S
Page 5 of 30
AGC-4 data sheet 4921240400 UK
Control functions
Application information
AGC-4
standard
(Y3)
AGC-4 DG
(Y1)
AGC-4
mains (Y4)
AGC-4 BTB
(Y5)
Start/stop sequences
Synchronising
Close before excitation (fast synchro.)
Nos. of breakers/contactors to be controlled
2/1
Run coil
Stop coil with wire break
Relay outputs for speed control
Event log with real-time clock
Alarm log with real-time clock
Battery crank test log with real-time clock
AGC-4
standard
(Y3)
AGC-4 DG
(Y1)
AGC-4
mains (Y4)
AGC-4 BTB
(Y5)
Logic configuration tool for plant customising
Selectable input events, e.g. plant status
Selectable output events, e.g. plant commands
M-Logic
DEIF A/S
Page 6 of 30
AGC-4 data sheet 4921240400 UK
Application information
1.1.5 Protections
Protections
No. of
ANSI
AGC-4
standard
(Y3)
AGC-4 DG
(Y1)
AGC-4
mains (Y4)
Reverse power
x2
Short circuit
32R
x2
50P
Overcurrent
x4
51
Voltage-dependent overcurrent
x1
51V
Overvoltage
x2
59P
Undervoltage
x3
27P
Overfrequency
x3
81O
Underfrequency
x3
81U
Unbalanced voltage
x1
47
Unbalanced current
x1
46
Underexcitation or VAr import
x1
32RV
Overexcitation or VAr import
x1
32FV
Overload
x5
32F
Busbar/mains overvoltage
x3
59P
Busbar/mains undervoltage
x4
27P
Load shed, three levels
via current
via busbar frequency
via overload
via fast overload
x3
x3
x3
x3
51
81
32
32
x
x
x
x
x
x
x
x
x
x
x
x
Busbar/mains overfrequency
x3
81O
Multi-config. inputs with wire
break alarms, three inputs
x2
NA
Emergency stop
x1
Overspeed
x2
12
Low auxiliary supply
x1
27DC
High auxiliary supply
x1
59DC
Generator breaker external trip
x1
Tie/mains breaker external trip
x1
Synchronisation failure alarms
25
Breaker open failure
52BF
Breaker close failure
52BF
Breaker position failure
52BF
Close before excitation failure
x1
48
Phase sequence error
x1
47
DEIF A/S
AGC-4
BTB (Y5)
Page 7 of 30
AGC-4 data sheet 4921240400 UK
Protections
Application information
No. of
ANSI
AGC-4
standard
(Y3)
AGC-4 DG
(Y1)
Deload error
x1
Crank failure
AGC-4
mains (Y4)
AGC-4
BTB (Y5)
34
x1
48
Running feedback error
x1
34
MPU wire break
x1
NA
Start failure
x1
48
Hz/V failure
x1
53
Stop failure
x1
48
Stop coil, wire break alarm
x1
Engine heater
x1
26
Battery test alarm
x1
NA
Max. ventilation/radiator fan
x2
NA
Not in Auto
x1
34
Fuel fill check
x1
NA
1.1.6 Single line application diagrams
Standard, 1 controller
1. Automatic mains failure and
fixed power/base load
2. Island
3. Peak shaving, load takeover
and mains power export
Mains
Display
Display
Transducer
(TAS-331DG)
Mains
Display
Mains
breaker
(MB)
Controller
Mains
breaker
(MB)
Busbar
Consumers
Generator
breaker
(GB)
G
Diesel generator set
DEIF A/S
Controller
Generator
breaker
(GB)
Controller
Consumers
Generator
breaker
(GB)
G
Diesel generator set
G
Diesel generator set
Page 8 of 30
AGC-4 data sheet 4921240400 UK
Application information
Optional
4. Multiple gensets, load sharing (1 controller per genset)
Display 1
Display 2
5.-9. Power managment
See separate page in this data
sheet
Busbar
Analogue
loadsharing
Generator
breaker
(GB 1)
Controller
G
Diesel generator set 1
DEIF A/S
Generator
breaker
(GB 2)
Controller
G
Diesel generator set 2
Page 9 of 30
DEIF A/S
MB OFF
HORN
STATUS
CAN B
OPTION M12/G3
37 38 39 40 41 42
kW SHARE
MB ON
L3
L2
L1
kvar SHARE
OPTION M12
OPTION M14.6
90 91 92 93 94 95 96 97
MULTI INPUTS
10 V DC
LOAD
SHARING EXT SET
COM
85 86 87 88 89
CANbus
Modbus
Profibus
29 30 31 32 33 34 35 36
Hz/kW
79 80 81 82 83 84
CAN A
OPTION M12
43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
COM
73 74 75 76 77 78
GB OFF
MPU
GB ON
+ + POWER
MB OFF
OPTION H2/H3/H8.2
MB ON
A1 A2 A3 B1 B2 B3
TRANSISTOR
OUTPUTS
(MAX 10 mA)
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
GB OFF
U/kvar
8
GB ON
98 99 100 101
OPTION E1
mA OUT
126 127 128 129 130 131 132 133
OPTION M13.8
mA OUT
65 66 67 68 69 70 71 72
+
+
PID
PID
PREPARE
CRANK
RUN
COMMON FOR
E-STOP
E-STOP
108
105
102
119 120 121 122 123 124
STOP
COIL
102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118
AGC-4 data sheet 4921240400 UK
Application information
This terminal strip overview shows the terminals of an AGC with commonly used HW options. The diagram
might not reflect your actual unit due to different option configuration.
1.1.7 Terminal overview
Page 10 of 30
Application information
AGC-4 data sheet 4921240400 UK
1.2 Power management applications
The purpose of the power management system is to implement one control system that controls all breakers
and all gensets. This can for instance be for fuel optimised purposes, for easy implementation of plant logic or
for safety reasons.
1.2.1 Application
The plant modes supported by the power management options are:
Standard plant
modes
Applications
Island mode
Power plant with synchronising generators or a stand-alone generator. Can also
be used in critical power plants with a start signal from an external (ATS) controller
Automatic Mains Failure
Critical power/emergency standby plants, black start generator
Fixed power
Power plant with fixed kW setpoint (including building load)
Peak shaving
Power plant where generator supplies peak demand
Load takeover
Plant mode where the load is moved from mains to generator, e.g. peak demand
periods or periods with risk of power outages
Mains power export
Power plant with fixed kW setpoint (excluding building load)
The plant modes are configurable, and it is possible to change the plant mode on the fly both in single and in
power management applications.
The plant can be divided by one to eight bus tie breakers making it possible to run the plant with different
plant modes, e.g. for test purposes or when splitting up the load in primary and secondary loads.
1.2.2 Description
The AGC can be equipped with a power management option (G4, G5, G7 or G8). Using this possibility, the
AGC will be able to handle simple or advanced applications for a great number of power plant projects within
synchronising gensets, critical power/emergency standby applications or power producing applications.
The following number of units can be controlled:
16 mains feeders with mains and tie breaker
8 bus tie breakers on the generator bus or load bus
16 generators (256 in plant management applications) with generator breakers
The complete power management system can easily be monitored from the PC utility SW through a graphical
supervision page. Running status, hours in operation, breaker status, condition of mains and busbars and fuel
consumption are just some of the values that are presented.
DEIF A/S
Page 11 of 30
AGC-4 data sheet 4921240400 UK
Application information
1.2.3 Power management functions
PM functions
AGC-4 DG
AGC-4 mains
AGC-4 BTB
Multi-master system
Redundant CANbus
Short-time parallel (in same controller (MB/TB))
Load-dependent start/stop
Priority selection, manual and automatic
Running hours
Load profile
Manual
Fuel optimised
Ground relay
ATS control
Safety stop of DG
Load management
Secured mode (start one extra generator)
Quick setup for rental groups
Heavy consumer control/generator request
Asymmetric LS for optimal generator load level
x
x
Plant PF control
Mains feeder control, feeders paralleled
Mains feeder control, main-tie-main for critical power
Base load running for maintenance (island plants)
Analogue load sharing for back-up with option G3
Section power control
DEIF A/S
Page 12 of 30
AGC-4 data sheet 4921240400 UK
Application information
1.2.4 Easy configuration of single line diagrams
The setup of the application is easily configured using a PC and the DEIF PC utility software.
Your PC tool visualises it - the AGC-4 realises it.
The basic plant control is set up by a few basic plant conditions including mains feeder handling and operation of the generators
1.2.5 Safe power management system
Multi-master system
The AGC power management system is designed as a multi-master system for
increased reliability. In a multi-master system all vital data is transmitted between
the AGCs, giving all units knowledge of the present power management status
(calculations and position) in the application. This philosophy makes the application immune to failing master controllers and makes the AGC suitable for all
types of applications, i.e. emergency standby/critical power applications.
Redundant CANbus
In critical power/emergency standby applications requiring extra operation reliability, redundant CANbus communication lines can be used to ensure reliable
CANbus communication for power management if one of the CAN lines are damaged.
Redundant controller
With the Critical Power option (T1) it is possible to have redundant controllers in
the application. The redundant controller is connected on the CAN line as a hot
standby unit and is therefore always updated with the system status and ready to
become the primary controller.
DEIF A/S
Page 13 of 30
AGC-4 data sheet 4921240400 UK
Application information
1.2.6 Optional power management applications
5. Island operation.
6. Parallel with mains.
The tie breaker is selectable depending on applicational needs.
Display 1
Display mains
Display 2
Mains
Busbar
CANbus
Controller
Generator
breaker
(GB 1)
Mains
breaker
(MB)
Controller
Generator
breaker
(GB 2)
Controller
Consumers
Tie
breaker
(TB)
Display 1
Display 2
G
Busbar
CANbus
Diesel generator set 2
Diesel generator set 1
Generator
breaker
(GB 1)
Controller
Generator
breaker
(GB 2)
Controller
Diesel generator set 1
Diesel generator set 2
7. Main - tie - main application.
Ring bus may be used depending on applicational needs.
Display mains 1
Display mains 2
Mains 1
Mains
breaker 1
Display mains 3
Mains 2
Mains
breaker 2
Controller
Consumers
Mains 3
Mains
breaker 3
Controller
Consumers
Consumers
Tie
breaker 3
Display BTB
Bus tie
breaker 1
Display BTB
Display DG 1
Bus tie
breaker 2
Mains 4
Controller
Mains
breaker 4
Controller
Consumers
Tie
breaker 4
Display BTB
Display BTB
Bus tie
breaker 4
Bus tie
breaker 3
CANbus
Controller
Display mains 4
CANbus
Controller
Controller
Controller
Controller
G
Diesel generator set 1
DEIF A/S
Page 14 of 30
AGC-4 data sheet 4921240400 UK
Application information
8. H-coupling.
The tie breaker controlled by the AGC mains is selectable depending on applicational needs.
The bus tie breaker can be present without an AGC controller (open/closed feedbacks are needed).
Display mains 17
Display mains 18
Mains 17
Mains 18
Mains
breaker
(MB 17)
Mains
breaker
(MB 18)
Controller
Consumers
Controller
Consumers
Tie
breaker
(TB 17)
Tie
breaker
TB 18)
Display 1
Display 2
Display BTB 33
Display 3
Display 4
BTB 33
Busbar
BUSBAR
CANbus
Generator
breaker
(GB 1)
Controller
CANBUS
Generator
breaker
(GB 2)
Controller
Controller
Generator
breaker
(GB 3)
Diesel generator set 1
Controller
Diesel generator set 2
Generator
breaker
(GB 4)
Controller
Diesel generator set 3
Diesel generator set 4
9. X mains and 1 DG.
The tie breaker controlled by the AGC mains is selectable depending on applicational needs.
Display mains 17
Mains 17
Mains
breaker
(MB 17)
Display mains 18
Mains
breaker
(MB 18)
Display mains 20
Mains 19
Mains 18
Controller
Display mains 19
Controller
Mains 20
Mains
breaker
(MB 19)
Consumers
Consumers
Consumers
Tie
breaker
(TB 17)
Tie
breaker
(TB 18)
Tie
breaker
(TB 19)
Mains
breaker
(MB 20)
Controller
Consumers
Tie
breaker
(TB 20)
Display mains 21
Mains 21
Controller
Mains
breaker
(MB 21)
Controller
Consumers
Tie
breaker
(TB 21)
Busbar
Display 1
CANbus
Controller
Generator
breaker
(GB 1)
G
Diesel generator set 1
DEIF A/S
Page 15 of 30
AGC-4 data sheet 4921240400 UK
Optional functionality
2. Optional functionality
2.1 Display layouts
2.1.1 Option Y1
Engine and generator breaker control (island). Used for island applications and for synchronising gensets.
Alarm
Automatic Gen-set Controller
Alarm
multi-line AGC
Power
Self check ok
Alarm Inh.
INFO
VIEW
JUMP
LOG
SEL
START
Run
Auto
On
Load
BACK
STOP
MODE
2.1.2 Option Y3
Generator breaker and mains breaker control. Typically used by rental companies or for single genset applications with one mains.
Automatic Gen-set Controller
Alarm
Power
Self check ok
multi-line AGC
Alarm
Alarm Inh.
INFO
VIEW
JUMP
LOG
SEL
Run
On
Auto
On
START
Load
BACK
STOP
MODE
2.1.3 Option Y4
Tie breaker and mains breaker control. Used for AGC mains.
Alarm
Automatic Gen-set Controller
Power
Self check ok
multi-line AGC MAINS
Alarm
Alarm Inh.
INFO
VIEW
JUMP
LOG
SEL
On
Auto
On
START
Load
BACK
STOP
DEIF A/S
MODE
Page 16 of 30
AGC-4 data sheet 4921240400 UK
Optional functionality
2.1.4 Option Y5
Bus tie breaker control. Used for AGC BTBs.
Alarm
Automatic Gen-set Controller
Power
Self check ok
multi-line AGC BUS TIE
Alarm
Alarm Inh.
INFO
VIEW
JUMP
LOG
SEL
Auto
On
BACK
MODE
2.1.5 Option X3
Additional operator's panel - AOP-1. Used for plant and/or genset control and status/alarm indication.
AOP-1
2.1.6 Option X4
Additional operator's panel - AOP-2. Used for plant and/or genset control and status/alarm indication (maximum 5 per AGC).
AOP-2
DEIF A/S
Page 17 of 30
AGC-4 data sheet 4921240400 UK
Optional functionality
2.2 Available options
2.2.1 Available variants
Type
Variant
Description
Item no.
AGC-4
12
AGC-4 without display
2912410040-12
AGC-4
13
AGC-4 w. display + J1
2912410040-13
AGC-4
07
AGC-4 BTB without display + G4
2912410040-07
AGC-4
06
AGC-4 BTB w. display + G4 + J1
2912410040-06
AGC-4
09
AGC-4 Mains without display + A1
+ G5
2912410040-09
AGC-4
08
AGC-4 Mains w. display + A1 + G5
+ J1
2912410040-08
DEIF A/S
Note
One 3 m display cable is included as standard
One 3 m display cable is included as standard
One 3 m display cable is included as standard
Page 18 of 30
AGC-4 data sheet 4921240400 UK
Optional functionality
2.2.2 Available software options
Option
A
Description
Slot
no.
Option
type
Note
Loss of mains protection package
A1
Time-dependent undervoltage (27t)
Undervoltage and reactive power low (27Q)
Vector jump (78)
df/dt (ROCOF) (81)
SW
A4
Positive sequence (mains voltage low) (27)
SW
A5
Directional overcurrent (67)
SW
C2
Negative sequence voltage high (47)
Negative sequence current high (46)
Zero sequence voltage high (59)
Zero sequence current high (50)
Power-dependent reactive power (40)
Inverse time overcurrent (51) (according to IEC 60255-151)
SW
Voltage/VAr/cos phi control
D1
Not available for
AGC mains and
AGC bus tie
Constant voltage control (stand-alone)
Constant reactive power control (parallel with mains)
Constant power factor control (parallel with mains)
Reactive load sharing (island paralleling with other generators)
SW
Load sharing/power management/plant management
G3
Load sharing with analogue lines
HW/
SW
If M12 is
present, G3 is a
software option
G4
Power management, 16 gensets, 8 bus tie breakers
SW
Not with G5 or
G8
G5
Power management, 16 gensets, 8 bus tie breakers, 16 mains
SW
Not with G4 or
G8
G8
Power management, 16 gensets (island mode)
SW
Not with G4 or
G5
SW
Not with H5,
H13 or H6
Serial communication
H7
DEIF A/S
CANbus (J1939):
Page 19 of 30
AGC-4 data sheet 4921240400 UK
Option
Optional functionality
Description
H5
H13
I
Caterpillar
Cummins CM850/570
Detroit Diesel (DDEC)
Deutz (EMR)
Iveco (NEF/CURSOR)
John Deere (JDEC)
MTU SmartConnect
MTU ADEC
MTU MDEC M302/M303
Perkins
Scania (EMS)
Scania (EMS S6)
Volvo Penta (EMS)
Volvo (EMS2)
MTU ADEC M.501
+ same engine types as H5
Slot
no.
Option
type
HW/
SW
HW/
SW
Note
Included in option H5
Application emulation
I1
Emulation, PC-controlled emulation of your application
SW
Special applications
T1
Critical power, redundant controller, short-circiut limitation
SW
Option T1 is only
functional if G4,
G5 or G8 is already selected.
(ANSI# as per IEEE Std C37.2-1996 (R2001) in parenthesis).
Please notice that not all options can be selected for the same unit. Please refer to the chapter
"Hardware overview" in this data sheet for further information about the location of the options
in the unit.
DEIF A/S
Page 20 of 30
AGC-4 data sheet 4921240400 UK
Optional functionality
2.2.3 Available accessories
Accessory
J
Description
Option
type
Note
Cables
J1
Display cable with plugs, 3 m. UL94 (V1) approved
Other
J2
Display cable with plugs, 6 m. UL94 (V1) approved
Other
J4
PC cable for option N-programming (Ethernet cable crossed), 3 m.
UL94 (V1) approved
Other
J6
Display cable with plugs, 1 m. UL94 (V1) approved
Other
J7
PC cable for utility software (USB), 3 m. UL94 (V1) approved
Other
J8
Display CAN cable for DU-2 connection and 2 x plugs for cables
for the Remote Maintenance Box
Other
RMB connector
kit
Documentation
K1
Designer's Reference Handbook (hard copy)
Other
K2
CD-ROM with complete documentation
Other
Display gasket for IP54
Other
Measurement accuracy
Hardware
Verified class 0.5
Other
Q1
X
Standard is
IP52
Additional displays
X2
Additional standard display (DU-2). CANbus comm.
Other
X3
Additional operator's panel (AOP-1): 16 configurable LEDs and 8
configurable push-buttons
Other
X4
Additional operator's panel (AOP-2): 16 configurable LEDs, 8 configurable buttons and 1 status relay. CANbus comm.
Other
Two options X2
can be ordered
for each AGC
unit
Five options X4
can be ordered
for each AGC
unit
Display layout
Hardware
Y1
Engine and generator breaker control (island)
Other
Available for
AGC genset
controller
Y3
Generator breaker and mains breaker control
Other
Available for
AGC genset
controller
Y4
Tie breaker and mains breaker control
Other
Available for
AGC mains
controller
DEIF A/S
Page 21 of 30
AGC-4 data sheet 4921240400 UK
Accessory
Y5
Optional functionality
Description
Option
type
Bus tie breaker control
Other
Note
Available for
AGC BTB controller
2.2.4 Hardware options and slot number location
37 38 39 40 41 42 43 44 45 46 47 48 49 50
CAN A
CAN B
Ethernet
9
51 52 53 54 55 56 57 58 59 60 61 62 63 64
Ethernet
Service port
65 66 67 68 69 70 71 72
Display
Power
Self check ok
Alarm inhibit
73 74 75 76 77 78
79 80 81 82 83 84
85 86 87 88 89
90 91 92 93 94 95 96 97
: The numbers in the drawing above refer to the slot numbers indicated in the table below.
DEIF A/S
Page 22 of 30
AGC-4 data sheet 4921240400 UK
Slot #
Option/standard
Description
Terminal 1-28, power supply
Standard
8-36V DC supply, 11 W; 1 x status output relay; 5 x relay outputs; 2 x pulse outputs (kWh, kVArh or configurable open collector outputs); 5 x digital inputs
Terminal 29-36, communication
H2
Modbus RTU (RS485)
H3
Profibus DP
H9
Modbus RS232 for modem
H8.2
External I/O modules
M13.2
7 x binary inputs
M14.2
4 x relay outputs
Terminal 37-64, in-/outputs/load sharing
M12
13 x digital inputs; 4 x relay outputs (SW option if G3 is present)
G3
Active power load sharing; reactive power load sharing (requires D1) (SW option if M12 is present)
Terminal 65-72, governor, AVR, in-/outputs
Standard
4 x relay
E1
2 x +/-25 mA out
E2
2 x 0(4)...20 mA out
EF2
1 x +/-25 mA out; 1 x 0(4)...20 mA out
EF4
1 x +/-25 mA out; 2 x relay
EF5
1 x +/-25 mA out; 1 x PWM out; 2 x relay
EF6
2 x +/-25 mA out; 1 x PWM out
Terminal 73-89, AC measuring
Standard
DEIF A/S
Optional functionality
3 x generator voltage; 3 x generator current; 3 x busbar/mains voltage
Terminal 90-97, in-/outputs
F1
2 x 0(4)...20 mA out, transducer
M13.6
7 x digital inputs
M14.6
4 x relay outputs
M15.6
4 x 4...20 mA inputs
M16.6
4 x Multi-inputs (4-20mA or 0-5V or PT100)
Page 23 of 30
AGC-4 data sheet 4921240400 UK
Slot #
Option/standard
Optional functionality
Description
Terminal 98-125, engine I/F
Standard
8-36V DC supply, 5 W; 1 x magnetic pick-up (MPU); 3 x multi-inputs; 7 x digital
inputs; 4 x relay outputs
H7
J1939 engine comm. and MTU ADEC
Terminal 126-133, engine communication, in-/outputs
H5
J1939 engine comm. and MTU (ADEC/MDEC)
H13
MTU ADEC M.501 (without SAM module) + J1939 engine comm. and MTU
(ADEC/MDEC)
H6
Cummins GCS
H8.8
External I/O modules
M13.8
7 x digital inputs
M14.8
4 x relay outputs
M15.8
4 x 4...20 mA inputs
M16.8
4 x Multi-inputs (4-20mA or 0-5V or PT100)
LED I/F
N
- Modbus TCP/IP
- EtherNet/IP
- SMS/e-mail alarms
There can only be one hardware option in each slot. It is e.g. not possible to select option H2
and option H3 at the same time, because both options require a PCB in slot #2.
Besides the hardware options shown on this page, it is possible to select the software options
mentioned in the chapter "Available options".
It is possible to have option H7 and option G5 at the same time, but as soon as an engine protocol has been selected in menu 7561, the CAN-A output will be locked for engine communication.
If option H7 is selected, it is not possible to have options H5, H13 and H6 even though slot #8 is
free.
It is only possible to select one of the options H8.2 and H8.8.
DEIF A/S
Page 24 of 30
AGC-4 data sheet 4921240400 UK
Technical information
3. Technical information
3.1 Specifications and dimensions
3.1.1 Technical specifications
Accuracy
Class 1.0
-25...15...30...70C
Temperature coefficient: +/-0.2% of full scale per 10C
Class 0.5 with option Q1
Positive, negative and zero sequence alarms: class 1 within 5% voltage unbalance
Class 1.0 for negative sequence current
Fast overcurrent: 3% of 350%*In
Analogue outputs: class 1.0 according to total range
Option EF4/EF5: class 4.0 according to total range
To IEC/EN60688
Operating
temperature
-2570C (-13...158F)
-25...60C (-13...140F) if Modbus TCP/IP (option N) is available in the controller.
(UL/cUL Listed: max. surrounding air temperature: 55C/131F)
Storage temperature
-4070C (-40...158F)
Climate
97% RH to IEC 60068-2-30
Operating altitude
0-4000 m above sea level
Derating 2001-4000 m above sea level:
Max. 480V AC phase-phase 3W4 measuring voltage
Max. 690V AC phase-phase 3W3 measuring voltage
Measuring
voltage
100-690V AC +/-20%
(UL/cUL Listed: 600V AC phase-phase)
Consumption: max. 0.25 VA/phase
Measuring
current
-/1 or -/5 A AC
(UL/cUL Listed: from CTs 1-5 A)
Consumption: max. 0.3 VA/phase
Current overload
4 x In continuously
20 x In, 10 sec. (max. 75 A)
80 x In, 1 sec. (max. 300 A)
Measuring frequency
30...70 Hz
Aux. supply
Terminals 1 and 2: 12/24V DC (8...36 V continuously, 6 V 1 sec.). Max. 11 W consumption
Terminals 98 and 99: 12/24V DC (8...36 V continuously, 6 V 1 sec.). Max. 5 W consumption
The aux. supply inputs are to be protected by a 2 A slow blow fuse. (UL/cUL Listed:
AWG 24)
DEIF A/S
Page 25 of 30
AGC-4 data sheet 4921240400 UK
Technical information
Binary inputs
Optocoupler, bi-directional
ON: 8...36V DC
Impedance: 4.7 k
OFF: <2V DC
Analogue- inputs
-10...+10V DC: not galvanically separated. Impedance: 100 k (G3)
0(4)...20 mA: impedance 50 . Not galvanically separated (M15.X)
RPM
RPM (MPU): 2...70V AC, 10...10000 Hz, max. 50 k
Multi-inputs
Engine interface board slot
#7
0(4)...20 mA: 0-20 mA, +/-1%. Not galvanically separated
Binary: max. resistance for ON detection: 100 . Not galvanically separated
Pt100/1000: -40...250C, +/-1%. Not galvanically separated. To IEC/EN60751
VDO: 0-1700 , +/-2%. Not galvanically separated
V DC: 0...40V DC, +/-1%. Not galvanically separated
Multi-inputs
(M16.X)
0(4)...20 mA: 0-20 mA, +/-2%. Not galvanically separated
Pt100: -40...250C, +/-2%. Not galvanically separated. To IEC/EN60751
V DC: 0...5V DC, +/-2%. Not galvanically separated
Relay outputs
Electrical rating: 250V AC/30V DC, 5 A. (UL/cUL Listed: 250V AC/24V DC, 2 A resistive
load)
Thermal rating @ 50C: 2 A: continuously. 4 A: ton= 5 sec., toff = 15 sec.
(Unit status output: 1 A)
Open collector outputs
Supply: 8...36V DC, max. 10 mA (terminal 20, 21, 22 (com))
Analogue outputs
0(4)...20 mA and +/-25 mA. Galvanically separated. Active output (internal supply). Load
max. 500 . (UL/cUL Listed: max. 20 mA output)
Update rate: transducer output: 250 ms. Regulator output: 100 ms
Load sharing
lines
-5...0...+5V DC. Impedance: 23.5 k
Galvanic separation
Between AC voltage and other I/Os: 3250 V, 50 Hz, 1 min.
Between AC current and other I/Os: 2200 V, 50 Hz, 1 min.
Between analogue outputs and other I/Os: 550 V, 50 Hz, 1 min.
Between binary input groups and other I/Os: 550 V, 50 Hz, 1 min.
DEIF A/S
Page 26 of 30
AGC-4 data sheet 4921240400 UK
Response
times
(delay set to
min.)
Technical information
Busbar:
Over-/undervoltage: <50 ms
Over-/underfrequency: <50 ms
Voltage unbalance: <250 ms
Generator:
Reverse power: <250 ms
Overcurrent: <250 ms
Fast overcurrent: <40 ms
Directional overcurrent: <150 ms
Over-/undervoltage: <250 ms
Over-/underfrequency: <350 ms
Overload: <250 ms
Current unbalance: <250 ms
Voltage unbalance: <250 ms
Reactive power import: <250 ms
Reactive power export: <250 ms
Voltage-dependent I>: <250 ms
Negative sequence I: <500 ms
Negative sequence U: <500 ms
Zero sequence I: <500 ms
Zero sequence U: <500 ms
Overspeed: <500 ms
Digital inputs: <250 ms
Emergency stop: <200 ms
Multi-inputs: 800 ms
Wire failure: <600 ms
Mains:
df/dt (ROCOF): <130 ms (4 periods)
Vector jump: <40 ms
Positive sequence: <60 ms
Time-dependent undervoltage, Ut<: <50 ms
Undervoltage and reactive power low, UQ<: <250 ms
Mounting
DIN-rail mount or base mount with six screws
Safety
To EN 61010-1, installation category (overvoltage category) III, 600 V, pollution degree 2
To UL 508 and CSA 22.2 no. 14-05, overvoltage category III, 600 V, pollution degree 2
EMC/CE
To EN 61000-6-2, EN 61000-6-4, IEC 60255-26.
Vibration
313.2 Hz: 2 mmpp. 13.2100 Hz: 0.7 g. To IEC 60068-2-6 & IACS UR E10
1060 Hz: 0.15mmpp. 60150 Hz: 1 g. To IEC 60255-21-1 Response (class 2)
10150 Hz: 2 g. To IEC 60255-21-1 Endurance (class 2)
Shock (base
mount)
10 g, 11 ms, half sine. To IEC 60255-21-2 Response (class 2)
30 g, 11 ms, half sine. To IEC 60255-21-2 Endurance (class 2)
50 g, 11 ms, half sine. To IEC 60068-2-27
Bump
20 g, 16 ms, half sine. To IEC 60255-21-2 (class 2)
Material
All plastic materials are self-extinguishing according to UL94 (V1)
DEIF A/S
Page 27 of 30
AGC-4 data sheet 4921240400 UK
Plug connections
Technical information
AC current: 0.2-4.0 mm2 stranded wire. (UL/cUL Listed: AWG 18)
AC voltage: 0.2-2.5 mm2 stranded wire. (UL/cUL Listed: AWG 20)
Relays: (UL/cUL Listed: AWG 22)
Terminals 98-116: 0.2-1.5 mm2 stranded wire. (UL/cUL Listed: AWG 24)
Other: 0.2-2.5mm2 stranded wire. (UL/cUL Listed: AWG 24)
Display: 9-pole Sub-D female
Service port: USB A-B
Protection
Unit: IP20. Display: IP52 (IP54 with gasket: option L). (UL/cUL Listed: Type Complete
Device, Open Type). To IEC/EN 60529
Governors
and AVRs
Multi-line 2 interfaces to all governors and AVRs using analogue, relay control or CANbased J1939 communication
See interfacing guide at www.deif.com
Approvals
UL/cUL Listed to UL508
Applies to VDE-AR-N 4105
UL markings
Wiring: use 60/75C copper conductors only
Mounting: for use on a flat surface of type 1 enclosure
Installation: to be installed in accordance with the NEC (US) or the CEC (Canada)
AOP-2:
Maximum ambient temperature: 60C
Wiring: use 60/75C copper conductors only
Mounting: for use on a flat surface of type 3 (IP54) enclosure. Main disconnect must be
provided by installer
Installation: to be installed in accordance with the NEC (US) or the CEC (Canada)
DC/DC converter for AOP-2:
Tightening torque: 0.5 Nm (4.4 lb-in)
Wire size: AWG 22-14
Weight
DEIF A/S
Base unit: 1.6 kg (3.5 lbs.)
Option J1/J4/J6/J7: 0.2 kg (0.4 lbs.)
Option J2: 0.4 kg (0.9 lbs.)
Option J8: 0.3 kg (0.58 lbs.)
Display: 0.4 kg (0.9 lbs.)
Page 28 of 30
AGC-4 data sheet 4921240400 UK
Technical information
3.1.2 Unit dimensions in mm (inches)
144 (5.669)
165 (6.486)
115 (4.528)
15 (0.59)
115 (4.528)
215(8.465)
115 (4.528)
230 (9.055)
Display or AOP
220 (8.661)
DEIF A/S
20.0 (0.787)
Page 29 of 30
AGC-4 data sheet 4921240400 UK
Ordering information
4. Ordering information
4.1 Order specifications and disclaimer
4.1.1 Order specifications
Variants
Mandatory information
Item no.
Type
Additional options to the standard variant
Variant no.
Option
Option
Option
Option
Option
Example:
Mandatory information
Additional options to the standard variant
Item no.
Type
Variant no.
Option
Option
2912410040-13
AGC-4 w. display + J1
13
C2
M12
Option
Option
Option
The AGC mains unit is only usable with option G5; this option is already included when ordered. The AGC bus tie unit is only usable with option G4 or G5.
Specify the AGC type: DG/mains/BTB unit.
Accessories
Mandatory information
Item no.
Type
Accessory
Example:
Mandatory information
Item no.
Type
Accessory
1022040065
Accessories for AGC-4
USB cable, 3 m (J7)
4.1.2 Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
DEIF A/S