Line Troll 3100
Line Troll 3100
User Manual
Rev.
2a
Date:
24.11.06
06.02.08
04.09.08
Description:
Information about the Xenon-flash version added
Ext DC +/GND for relay card corrected
Sign.
TV
TV
TV
0 Contents
CONTENTS
DEFINITIONS
2. FUNCTIONAL DESCRIPTION.
ADAPTIVE DETECTOR
OPERATION CRITERIA
Inrush blocking time:
Fault current passage:
Circuit Breaker (CB) tripping:
INDICATION
LED indication Dual mode:
Relay operation Dual mode:
RESET CRITERIA
Voltage reset
Automatic timer-reset
Manual reset
6
7
7
7
7
8
8
9
9
9
9
9
3. APPLICATIONS
10
10
10
4. APPLICATION NOTES
11
LINE SWITCHING
Connecting a healthy line
Connecting of faulted line when indicator is not indicating
FAULTS
Permanent fault
Second fault while indicating a previous fault
AUTOMATIC RECLOSING
Non-successful reclosing
Successful reclosing
FUSED LINES
MULTIPLE FAULTS
CAPACITIVE DISCHARGES
SETTING AND LOCATION
SENSITIVITY
Earth faults
LineTroll 3100 monitors the resulting
magnetic field under the line.
Short circuit faults
Recommended distances
11
11
11
12
12
12
12
13
13
14
14
14
16
16
16
16
16
16
17
5. PROGRAMMING
18
SENSITIVITY
18
TIMER RESET
CB TRIPPING WITHIN 5 OR 10 SEC.
VOLTAGE RESET.
PARAMETERS
18
18
18
19
6. MAINTENANCE
20
BATTERY MONITORING
REPLACEMENT OF BATTERIES
20
20
21
21
21
21
21
21
22
22
22
22
22
22
22
23
23
23
23
8. DIMENSIONS
23
9. MOUNTING INSTRUCTION
24
GENERAL:
COMMISSIONING
MOUNTING
RESET
TEST
INSTALLATION
24
24
24
25
25
25
26
26
26
Definitions
As the terminology may differ from country to country we will throughout this presentation use the
following definitions:
Short circuit fault
Earth fault
Transient fault
LineTroll
LED
Xenon flash
Circuit breaker
Inrush blocking
Energized
De-energized
Page 4
Userguide LineTroll 3100 February 2008
Page 5
Userguide LineTroll 3100 February 2008
2. Functional Description.
LineTroll 3100s fault sensing is based on detection of the electromagnetic field below the
conductors.
The unit is fully self-contained, no external transformers or connections of any kind are
required.
To determine whether or not the line is faulted, the indicator is looking for a specific sequence
in the line conditions to happen before it starts flashing. The general sequence is as follows:
(ref. fig.2)
1. The line should be energised for at least 5 seconds.
2. The line current should increase rapidly above the value set by the user (the nominal trip
level).
3. The line should be de-energised.
Page 6
Userguide LineTroll 3100 February 2008
NB!
If programmed for voltage reset the indicator reset after 15/30 sec if the line is
not de-energised within this time.
Page 7
Userguide LineTroll 3100 February 2008
LINE
> 10 s
<5s
= INDICATION
CB-trip
enabled
t
CB-trip
disabled
t
Fig. 3. CB-tripping
If LT 3100 is to be used in a network with no tripping due to earth fault the CB-tripping must
be disabled to obtain indication of earth fault.
If these two criteria are met in the correct sequence, the indicator starts indicating.
Indication
Please note that LT3100 are also available with a Xenon-gastube as the main indication. This
is described in next chapter.
NB:
XENON
Fast Auto
Reclosing
Fault
Last
Reclosing
Non-successful
Fault
Fast Auto
Reclosing
Page 8
Userguide LineTroll 3100 February 2008
Last
Reclosing
Non-successful
Fast Auto
Reclosing
Line
current
XENON
INDICATION
Transient
Fault Relay
5 sec
Permanent
Fault Relay
40 sec
The Permanent relay closes if the fault sequence is considered as a permanent fault, and
remains closed until indicator is reset.
Reset Criteria
The indicator can be reset in three
different ways:
1. Voltage reset
Automatic reset on return of voltage:
Voltage reset can be programmed to:
i)
OFF,
ii)
ON, delayed 15 or 30 sec
2. Automatic timer-reset
Programmable to: 1.5, 3, 6 or 12 hours.
3. Manual reset
LineTroll 3100 can be reset by turning the
lens clockwise to "RESET" position. A
magnet is permanently mounted in the
lens.
A special hot-stick-attachable tool is
available for resetting of the indicator from
the ground when mounted on a pole.
Page 9
Userguide LineTroll 3100 February 2008
3. Applications
The application of LineTroll 3100 usually requires a previous line survey so that the best use
of it may be obtained.
For the best economic benefit it is recommended that the indicators are used:
In easily accessibly line points for easy monitoring of the indicator in case of fault, for
instance near the road. It is advisable to take binoculars.
Before and after line points difficult to reach (mountains, woods, etc.) to quickly locate
the fault.
Near line points with sectionalisers to rapidly pinpoint and isolate the fault to facilitate
rapid reconnection the healthy sections.
Page 10
Userguide LineTroll 3100 February 2008
4. Application Notes
The aim of this section is to describe how the LineTroll 3100 indicator behaves in different
service situations and network events.
Line Switching
Connecting a healthy line
As the magnetising inrush current of a line can be very high, the indicator is provided with a 5
seconds blocking of the dB/dt sensor which prevents it from being activated until the line
current is stabilised. Once the blocking time has elapsed, the indicator is enabled for fault
detection.
See fig. 2.
NO INDICATION
Page 11
Userguide LineTroll 3100 February 2008
Faults
Permanent fault
Permanent faults will be indicated by red LEDs.
The time out for the LED can be set by the user to 1.5, 3, 6, or 12 hours.
If the line is restored within the time-out, the LEDs will reset, assuming that the voltage reset
is enabled
Fault
Last
Reclosing
Non-successful
Fast Auto
Reclosing
Line
current
INDICATION
5 sec
Transient
Fault Relay
40 sec
Permanent
Fault Relay
Succesfull
Reclosing
15 sec
24h
INDICATION
Transient
Fault Relay
5 sec
Permanent
Fault Relay
Page 12
Userguide LineTroll 3100 February 2008
Automatic reclosing
An automatic reclosing will not activate a non-flashing indicator.
If the indicator is indicating a previous fault, the operation due to a reclosing depends on
whether the reclosing is successful or not.
Non-successful reclosing
Closing a breaker onto a fault leads to another trip almost instantly. As the activated indicator
needs either 15/30 seconds with the line energised in order to reset, the indicator remain
flashing.
LINE
<30 s
Successful reclosing
The operation due to a successful reclosing depends on the setting of the voltage reset:
Line
current
LED-Indication
Energizing
15 sec.
Transient
Fault Relay
Permanent
Fault Relay
Page 13
Userguide LineTroll 3100 February 2008
Fused lines
One operation criterion is that, after a fault, a three-phase disconnection of the line has to be
carried out. If, instead of a three-phase trip, a fuse operates in one or two phases, the voltage
of the healthy phase might reset the indicator. This is true for indicators placed before the
fuse as well as after it.
When the criterion CB tripping is enabled, LineTroll 3100 is not activated unless the fault
causes a three-phase trip in the feeding within 5 sec (or 10) after the occurrence of the fault.
If CB tripping is disabled, the indicator is activated but will reset after 15/30 sec., unless the
fault causes a three-phase trip in the feeding end within this time.
If the voltage reset is switched off, the indicator will continue flashing until it is reset manually
or after the automatic timer period has elapsed.
Multiple faults
Multiple faults may occur. Defective network components may burn or break due to the
electro-dynamic force of the fault current and cause a second fault.
Another cause of multiple faults in isolated networks is the rise in voltage in the healthy
phases with reference to ground.
The voltage may reach up to 1.7 times the nominal voltage. Weak insulators may not
withstand such a voltage increase, and a second fault may occur.
This kind of fault may be difficult to trace as they often are non-permanent and only appear in
situations like the ones mentioned here.
Capacitive discharges
The LineTroll 3100 indicator is not directional, it therefore detects current without
discriminating its direction. In case of an earth fault, the capacitive energy of the network
discharges in the fault point. It should be checked that the capacitive discharge current
downstream the indicator is below pre-set trip level in order to avoid the indicator erroneously
activating upon earth faults.
If the total capacitive current exceeds the trip level, it is advisable to change the trip level or
install the indicators in the branching points instead of in the main line. The capacitive
discharge of a branching point is limited by its own capacitance, while in the main line the
capacitive current of all the branches downstream the indicator is added. Underground cables
have larger capacitance than overhead lines. This has to be taken into account when an
overhead line feeds an underground cable.
The following simplified formula may be used to estimate the capacitive discharge current of a
line:
Ic =
Ic =
U =
LL =
LC =
K =
U LL
300
U LC
K
Capacitive current in A
Nominal voltage in kV
Overhead line length in km
Cable length in km
10; for oil impregnated cables, 5; for PEX cables, 3; for PVC cables
In order to avoid the LineTroll 3100 being activated by an earth fault upstreams the indicator,
the following criteria have to be met.
Page 14
Userguide LineTroll 3100 February 2008
(1)
Ic < ISET
Ic = capacitive discharge current
ISET = max. sensitivity for
To estimate the capacitive discharge current at any line point, you have to calculate the
contribution from all the overhead lines and underground cables lengths only beyond that
point.
Ic =
Page 15
Userguide LineTroll 3100 February 2008
IC < ISET
IC = Capacitive discharge current behind the indicator.
ISET = maximum sensitivity for earth fault; 4,7,15 or 50A.
To obtain correct indication during earth fault the following criteria have to be met:
(2)
ISET < I0 - IC
I0 = Total earth fault current
in the net.
Comparing (1) and (2) gives the limit for the ISET:
IC < ISET < I0 - IC
Sensitivity
Earth faults
LineTroll 3100 monitors the resulting
magnetic field under the line.
The sensitivity for earth faults is a function of the following variables:
1. The trip level set on the indicator;
4, 7, 15 or 50 A. (See section 2.1)
2. Load current of the line when the fault occurs.
3. Line configuration on the pole where the indicator is located.
4. The distance between the conductors and the indicator.
Page 16
Userguide LineTroll 3100 February 2008
The indicator will indicate the fault by flashing the red (or green) LEDs (or Xenon), and closing
of the fault relays (i.e. same as for earth fault).
Recommended distances
The fault current which is necessary to generate a sufficient increase in magnetic field
depends on; i) the indicators distance from the conductor, ii) the line configuration and iii) the
load current. The distance from the conductors is measured from the lowest conductor.
OK!
LT3100
LT3100
Page 17
Userguide LineTroll 3100 February 2008
5. Programming
Programming of the unit is done from a switch-bank on the printed circuit board located under
the top-cap.
See the figure below for switch ON/OFF definition. Switch combinations which are not shown
should not be used.
SW1
SW2
SW3
Sensitivity
The maximum sensitivity (lowest detectable current) for earth fault current can be set to 1 out
of 4 nominal values of 2.5A*) 7A, 15A or 50A. LT3100K max sensitivity is 4A.
Timer reset
Timer reset can be set from 1.5 to 12 hours.
Voltage reset.
The voltage reset function works after 15 or 30 sec. The line must have been continuously
energised for the programmed period before indicator resets.
The voltage reset can even be disabled.
Page 18
Userguide LineTroll 3100 February 2008
Programming parameters:
SW 1 (1=ON,0=OFF)
Transient fault relay closing time
Threshold Earth Fault (PtG)
*) 4A 2,5A if SW3d7 is ON (1)
Valid for LT3100 only (not 3100K & 3100T)
SW 2 (1=ON, 0=OFF)
CB-trip
Automatic Voltage reset
Delay Voltage reset
SW 3 (1=ON, 0=OFF)
Transient indication 24h Green LED
Extended indication of perm faults
For Xenon only; single Red LED
Short range radio address
Relay card
QuickLink or GSM-modem
Reset of battery counter (see user guide)
default = off (0)
High sensitivity PtG: 2,5A.
**) SW1d3,4must both be in pos off (0)
Always OFF (Debug info)
Values:
1 sec
3 sec
4 A*)
7A
15 A
50 A
100%
200%
100 A
200 A
500 A
1000 A
60 ms
120 ms
60 ms
120 ms
1
0
1
Values:
OFF
ON
OFF
ON
15 sec
30 sec
1,5 h
3h
6h
12 h
40 sec
70 sec
120 sec
180 sec
5 sec
10 sec
1
0
1
Values:
OFF
ON
OFF
ON
1
2
3
4
1
0
1
0
0
1
1
0
1
0
1
0
0
1
1
0
1
0
1
0
1
0
1
0
1
2
0
0
1
1
0
1
0
1
0
0
1
1
0
1
0
1
0
1
0
1
0
1
2
0
0
1
1
0
1
0
1
0
1
0
1
0
4A
2,5A**)
0
1
0
NB!
After programming the indicator must be reset in order to save and initiate the
new settings.
**) NB! This setting (both 4A and 2,5A) is available only for LT-3100 manufactured/delivered
from 2008 and with SW-rev: LT3100_V2.1 & LT3100_V2.1X. Previous versions had 2,5A or
4A setting, not both! LT 3100K do not have 2,5A setting.
Page 19
Userguide LineTroll 3100 February 2008
6. Maintenance
It is advisable to inspect the indicator once a year or 1 year after it was last activated. The
inspection should include a functional test to show that the flashlight frequency is normal.
Battery monitoring
LineTroll3100 is equipped with an internal battery counter that keeps track of battery capacity
used. When the counter excide a predefined number of mAh, the indicators alarms the user
by blinking the yellow LED in a 6 seconds interval.
Low battery warning will be initialized when approximately 80% *) of the total capacity is
used (i.e. two standard lithium batteries).
*) 94% on version v01a.
Replacement of batteries
After replacing the batteries, the internal battery counter must be reset. This is done by
setting dip 6 switch 3 in position ON, followed by a manual reset (i.e. turning the display-unit
clock-wise until it stops and then back to normal position.) The indicator will indicate that the
battery counter has been reset by flashing both green and yellow LEDs.
The indicator will remain in this state until the dip is turned in position OFF, and a new RESET
operation has been performed.
Page 20
Userguide LineTroll 3100 February 2008
7A
0.47
15A
1.00
50A
3.33
(LT3100 only)
If distance is 5m, and setting is 4A => the max sensitivity will be (4A/3m)x5m = 6,7A
Indication criteria:
1) Line energised for more than 5 seconds
- followed by a
2) Line current increasing by at least 100% (or 200%) within 20ms and reaching a level that
exceeds the programmed trip level and fault duration
- followed by a
3) Circuit Breaker tripping within 5 sec (or 10 sec) after the fault occurrence
(can be disabled).
Indication LED
Indication by a cluster of 5 high intensity LEDs:
3 x Red : Permanent Fault Indication
1 x Green
: Transient Fault Indication
1 x Yellow
: Low battery and Installation information
Reset:
1) Voltage reset: 15 or 30 sec.
2) Timer reset: 1.5, 3, 6 or 12 hours
3) Manual reset by rotating the lens.
Battery
o
External dc:
External DC input 10-24 VDC
Battery monitoring:
LT3100 is equipped with an internal battery counter that keeps track of battery capacity used.
The indicator alarms the user by blinking the yellow LED in a 6 seconds interval. Low battery
warning will be initialized when approx. 80%
Event log:
LT 3100 and LT 3100T has built in event LOG that can be read by connecting the unit to a PC
via a cable.
Housing Material
Body & bracket: Polycarbonate (PC) with glass reinforcement.
Top-cap and lens: Transparent Poly carbonate, UV resistant.
Flame retardent grades: (V-0 UL) 750 deg. celsius
Mechanical strength: IK09 (10J impact)
IP: 55 (Cat.2)
Page 22
Userguide LineTroll 3100 February 2008
Test standards:
Protection degree of
enclosures
EN50102
EN60529
Climatical test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-78
IEC 600682-11
Electrical tests
Test to cold
Test to dry heat
Continuous test in humid heat
Salt mist chamber
EN 61000-6-3
EN 61000-6-2
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-8
ENV 50204
98.78
380.11
8. Dimensions
Fig.20. Dimensions
Page 23
Userguide LineTroll 3100 February 2008
9. Mounting Instruction
General:
When the LT 3100 detects a fault current it will indicate this by flashing LEDs or by closing of
relay contacts if connected to an RTU. The LT 3100 will keep flashing until a predetermined
automatic reset condition has been fulfilled.
Commissioning
Check that the batteries or the external DC is connected.
If the LT 3100 is not already programmed, this can be done setting the dipswitches located
under the top-cap.
NB! If switches are changed, RESET the indicator in order to initiate the new settings.
Mounting
The LineTroll 3100 mounts on the pole
typically 3-5 meters below the conductor.
Note!
The indicator must be aligned with
the direction of line, see fig 20.
3-5 meter
When the indicator bracket is mounted on the pole with screws it is recommended to first
screw the lower screw in to the pole and then put the bracket on to this screw before putting
in the second screw.
Page 24
Userguide LineTroll 3100 February 2008
When the bracket has been mounted on the pole with either screws or cable-ties the indicator
housing can be slided down onto the bracket. When the housing is in the correct position a
snap will lock the housing on to the bracket.
RESET
The indicator can be RESET by turning the display-unit clock-wise until it stops and then back
to normal position.
TEST
The indicator can be TESTED by turning the display-unit counter-clockwise until it stops and
then back to normal position.
INSTALLATION
The indicator must be installed on an energized line. After the unit is mounted on the pole,
and any connection to a RTU is done, the unit has to be adapted to the local Electro-magnetic
field, and adjust the internal gain.
1.
Turn the display unit counter-clockwise ( TEST) until it stops. Leave the display
unit in the test position, and then climb down minimum 1 m in order to not
interfere with the EM-field.
2.
After a 10sec with running LEDs the results from the adaption will be indicated by
one or two LEDs:
a. GREEN:
Installation is OK
The green LED flash for approximately 10sec, then it is ready for
detecting faults. Remember to return the lens to normal
position.
b. RED:
c. YELLOW:
E-field too low; the indicator may be installed closer to the lines.
Setting for Absolute Short Circuit Fault level is too low; increase
the level (SW1-5 and SW1-6) and repeat the installation.
Page 25
Userguide LineTroll 3100 February 2008
RL1
J3
RL2
J1
4
1
7
2
J2
NO1
COM.
NO2
JP1
1.
2.
3.
V+
GND
RES
4.
5.
6.
7.
8.
GND
COM.
NO1
COM.
NO2
COM.
RES
V+
GDN
GDN
NORTROLL AS
12 - 24V DC voltage
Ground
External Reset (active when connected to GND)
NB! Do NOT apply any voltage to the rest-input.
Ground
Common
Permanent fault
Common
Transient fault
Page 26