Mobile Offshore Drilling Units 2008: Rules For Building and Classing
Mobile Offshore Drilling Units 2008: Rules For Building and Classing
5:
Fire
and
Safety
Measures
and
Copyright 2007
American Bureau of Shipping
ABS Plaza
16855 Northchase Drive
Houston, TX 77060 USA
Features
(1996)
(1995)
(1994)
(1993)
9 May 1996
15 May 1995
9 May 1994
11 May 1993
ii
Title/Subject
Emergency Control Stations
Status/Remarks
To add a cross-reference to 4-3-2/15.5.2. (Incorporates Notice No. 1)
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
PART
Table
of
Contents
5
Fire and Safety Measures and Features
CONTENTS
CHAPTER 1 Passive Fire Protection .........................................................1
Section 1
General .....................................................................3
General ...................................................................13
Section 2
Section 3
Section 4
Section 5
General ...................................................................33
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
iii
PART
Chapter
1:
Passive
Fire
Protection
5
CHAPTER
CONTENTS
SECTION 1
General....................................................................................3
1
General ..................................................................................3
1.1
Administration Review....................................................... 3
1.3
Bureau Review.................................................................. 3
1.5
3.3
3.5
TABLE 1
TABLE 2
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
PART
Section
1:
General
5
CHAPTER
SECTION
General (1993)
General (1993)
All mobile offshore drilling units are to meet the requirements of this Chapter with regard to structural
fire protection, protection of accommodation spaces, service spaces and control stations.
1.1
Administration Review
When a Mobile Offshore Drilling Unit Safety Certificate is issued to a MODU by an Administration
or its agent other than the Bureau, such certificate will be accepted as evidence that the unit is in
accordance with the requirements of this Chapter.
1.3
Bureau Review
In all other cases, the required information and plans are to be submitted to the Bureau for review.
1.5
Vanes used in rotary vane compressors and rotary vane vacuum pumps;
ii)
Watertight joints and linings used for the circulation of fluids when, at high temperature [in
excess of 350C (662F)] or high pressure [in excess of 70.0 bar (71.38 kgf/cm2, 1015.3 psi)],
there is a risk of fire, corrosion or toxicity; and
iii)
Supple and flexible thermal insulation assemblies used for temperatures above 1000C (1832F).
3.1
Construction Materials
These requirements apply to mobile offshore drilling units with their hulls, superstructures, structural
bulkheads, decks and deckhouses constructed of steel.
3.3
Alternate Materials
Construction of other materials may be accepted, provided that they provide an equivalent standard of
safety.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
Part
Chapter
Section
3.5
5
1
1
5-1-1
Class A or Class B divisions and their associated insulation index are as defined in SOLAS Regulation II-2/3.3
or 4, respectively.
TABLE 1
Fire Integrity of Bulkheads Separating Adjacent Spaces (1993)
Spaces
Control Stations
Corridors
1(1)
1(2)
Accommodation Spaces
1(3)
Stairways
1(4)
1(5)
1(6)
1(7)
1(8)
1(9)
(10)
(11)
Notes:
(1)
A-0 (4)
(2)
A-0
C
(3)
A-60
B-00
C
(4)
A-0
B-0
A-0 (2)
B-0
A-0 (2)
B-0
A-0 (2)
(5)
A-15
B-0
(6)
A-60
A-60
(7)
A-15
A-00
(8)
A-60
A-00
(9)
A-60
A-00
(10)
*
*
(11)
A-0
B-0
B-0
A-60
A-00
A-00
A-00
B-0
A-0 (2)
C
A-60
A-0
A-0
A-60
*Note 1
A-0
A-0 (2)
A-0
A-60
A-0
*
A-0
A-60
B-0
A-0 (2)
B-0
A-0
A-0 (1,3)
A-0
A-0
A-0
A-0 (3)
*
*
*
A-0
A-0
A-0
*
C
Where the space contains an emergency power source or components of an emergency power source that adjoins a
space containing a units service generator or the components of a units service generator, the boundary bulkhead
or deck between those spaces is to be an A-60 Class division.
For clarification as to which note applies, see paragraphs 3-4-1/5.1 and 3-4-1/5.5.
Where spaces are of the same numerical category and superscript (3) appears, a bulkhead or deck of the rating
shown in the tables is only required when the adjacent spaces are for a different purpose, e.g., in category (9), a
galley next to a galley does not require a bulkhead, but a galley next to a paint room requires an A-60 bulkhead.
Bulkheads separating the navigation bridge, chart room and radio from each other may be B-0 rating.
When an asterisk appears in the tables, the division is required to be of steel or equivalent material but is not
required to be of A Class standard. However, where a deck is penetrated for the passage of electric cables, pipes
and vent ducts, such penetrations should be made tight to prevent the passage of flame and smoke.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
Part
Chapter
Section
5
1
1
5-1-1
TABLE 2
Fire Integrity of Decks Separating Adjacent Spaces (1993)
Spaces
Below
Space
Above
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
Control Stations
1(1)
A-0
A-0
A-0
A-0
A-0
A-60
A-0
A-0
A-0
A-0
Corridors
1(2)
A-0
A-0
A-60
A-0
A-0
A-0
Accommodation Spaces
1(3)
A-60
A-0
A-0
A-60
A-0
A-0
A-0
Stairways
1(4)
A-0
A-0
A-0
A-0
A-60
A-0
A-0
A-0
A-0
1(5)
A-15
A-0
A-0
A-0
A-60
A-0
A-0
A-0
A-0
Machinery Spaces of
Category A
1(6)
A-60
A-60
A-60
A-60
A-60
*(a)
A-60
A-60
A-60
A-0
1(7)
A-15
A-0
A-0
A-0
A-0
A-0(a)
*(a)
A-0
A-0
A-0
Hazardous Areas
1(8)
A-60
A-0
A-0
A-0
A-0
A-60
A-0
A-0
A-0
1(9)
A-60
A-0
A-0
A-0
A-0
A-0
A-0
A-0
A-0(c)
A-0
Open Decks
(10)
(11)
A-0
A-0
A-0
A-0
A-0
A-0
A-0
Notes:
3.7
Application of Tables
The following requirements govern application of the tables:
3.7.1
5-1-1/Table 1 and 5-1-1/Table 2 apply, respectively, to the bulkheads and decks separating
adjacent spaces.
3.7.2
For determining the appropriate fire integrity standards to be applied to divisions between
adjacent spaces, such spaces are classified according to their fire risk, as shown in Categories
(1) to (11) below. The title of each category is intended to be typical rather than restrictive.
The number in parenthesis preceding each category refers to the applicable column or row in
the tables:
(1)
(2)
(3)
Accommodation Spaces are those used for public spaces, cabins, offices, hospitals,
cinemas, game and hobby rooms and similar spaces. Public spaces are those portions
of the accommodation which are used for meeting halls, dining rooms, lounges and
similar permanently enclosed spaces.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
Part
Chapter
Section
5
1
1
5-1-1
(4)
Stairways are interior stairways, lifts and escalators (other than those wholly contained
within the machinery spaces) and enclosures thereto. In this connection, a stairway
which is enclosed only at one level is regarded as part of the space from which it is
not separated by a fire door.
(5)
(1999) Services Spaces (low risk) are lockers, storerooms and working spaces in which
flammable materials are not stored, drying rooms, laundries, refrigerating, ventilation
and air-conditioning machinery spaces with motors having an aggregate capacity not
greater than 7.5 kW (10 HP).
(6)
Machinery Spaces of Category A are all spaces which contain internal combustion
type machinery used either:
For other purposes where such machinery has in the aggregate a total power of
not less than 375 kw (500 hp) or which contain any oil-fired boiler or oil fuel
unit; and trunks to such spaces.
(7)
(1999) Other Machinery Spaces are those spaces, including trunks to such spaces,
containing propulsion machinery, boilers, oil fuel units, steam and internal combustion
engines, generators and major electrical machinery (SCR, MCC and switchgear), oil
filling station, refrigerating, ventilation and air-conditioning machinery with motors
having an aggregate capacity greater than 7.5 kW (10 HP), and similar spaces, but are
not machinery spaces of Category A.
(8)
Hazardous Areas are all those areas where, due to the possible presence of a flammable
atmosphere arising from the drilling operation, the use without proper consideration of
machinery or electrical equipment may lead to fire hazard or explosion. See Section
4-1-3.
(9)
Services Spaces (high risk) are lockers, storerooms and working spaces in which
flammable materials are stored, galleys, pantries containing cooking appliances, paint
rooms and workshops other than those forming part of the machinery space.
(10)
(11)
Sanitary and Similar Spaces are communal sanitary facilities such as showers, baths,
lavatories, etc., and isolated pantries containing no cooking appliances. Sanitary facilities
which serve a space and with access only from that space shall be considered a portion
of the space in which they are located.
3.9
Continuous B class ceilings or linings in association with the relevant decks or bulkheads will be
accepted as contributing to the required insulation and integrity of a division.
3.11
Structural fire protection details are to avoid the risk of heat transmission at intersections and terminal
points of required thermal barriers. Unless specifically indicated otherwise, an extension of insulation
by 300380 mm (1215 in.) beyond the intersections or terminal points will be acceptable.
3.13
Windows and sidescuttles, with the exception of navigation bridge windows, are to be of the nonopening type. Navigation bridge windows may be of the opening type, provided the design of such
windows permits rapid closure. Windows and sidescuttles outside of hazardous areas may be of the
opening type.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
Part
Chapter
Section
5
1
1
5-1-1
3.15
The fire resistance of doors are, as far as practicable, to be equivalent to that of the division in which
they are fitted. External doors in superstructures and deckhouses are to be self-closing and at least A-0
class standard, where practicable.
3.17 (1999)
Arrangements are to be made to ensure that the fire resistance is not impaired when
i)
A and B class divisions are penetrated for the passage of electrical cables, pipes, trunks,
ducts, etc.
ii)
A class divisions are penetrated for girders, beams or other structural members, or
iii)
B class divisions are penetrated for the fitting of ventilation terminals, lighting fixtures and
similar devices.
3.19 (1999)
Pipes penetrating A or B class divisions are to be of materials approved by the Administration,
having regard to the temperature that such divisions are required to withstand.
5.1
All bulkheads required to be B Class divisions are to extend from deck to deck and to the
deckhouse side or other boundaries, unless continuous B Class ceilings and/or linings are fitted on
both sides of the bulkhead, in which case the bulkhead may terminate at the continuous ceiling or
lining. In corridor bulkheads, ventilation openings are to be provided only in and under the doors of
cabins, public spaces, offices and sanitary spaces. The openings are to be provided only in the lower
half of the door. Any such opening in or under a door is to have a total net opening no larger than
0.05 m2 (0.54 ft2) and is to be fitted with a noncombustible grill. Such openings are not to be provided
in a door in a division forming a stairway enclosure.
5.3
Stairs are to be constructed of steel or other equivalent material.
5.5
Stairways which penetrate only a single deck are to be protected at least at one level by A or B
Class divisions and self-closing doors so as to limit the rapid spread of fire from one deck to another.
Elevator trunks are to be protected by A Class divisions. Stairways and elevator trunks which
penetrate more than a single deck are to be surrounded by A Class divisions and protected by A
Class self-closing doors at all levels. Self-closing doors are not to be fitted with hold-back hooks.
However, hold-back arrangements incorporating remote release fittings of the fail-safe type may be
used.
5.7
Air spaces enclosed behind ceilings, paneling or linings are to be divided by close fitting draft stops
spaced not more than 14 m (46 ft) apart.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
Part
Chapter
Section
5
1
1
5-1-1
5.9
Ceilings, linings, bulkheads and insulation, except for insulation in refrigerated compartments, are to
be of noncombustible material. Vapor barriers and adhesive used in conjunction with insulation, as
well as insulation of pipe fittings for cold service systems need not be noncombustible, but they
should be kept to a minimum and their exposed surfaces are to have low flame spread characteristics.
In spaces where penetration of oil products is possible, the insulation surfaces are to be impervious to
oil or oil vapors.
5.11
The framing, including grounds and the joint pieces of bulkheads, linings, ceilings and draft stops are
to be of noncombustible material.
5.13
In accommodation and service spaces and control stations, the following surfaces are to have low
flame-spread characteristics:
i)
ii)
iii)
5.15
Bulkheads, linings and ceilings may have combustible veneers, provided that the thickness of such
veneers does not exceed 2 mm (0.08 in.) within any space other than corridors, stairway enclosures
and control stations where the thickness is not to exceed 1.5 mm (0.06 in.). Alternately, thicker veneers
of low calorific value [not exceeding 45 mJ/m2 (3960 Btu/ft2)] will be considered.
5.17
Primary deck coverings, if applied, are to be of approved materials which will not readily ignite or
give rise to toxic or explosive hazards at elevated temperatures.
5.19
Paints, varnishes and other finishes used on exposed interior surfaces are not to be of a nature to offer
an undue fire hazard and are not to be capable of producing excessive quantities of smoke or toxic
fumes.
5.21
Ventilation ducts are to be of a noncombustible material, unless they are no more than 2 m (6.6 ft)
long and have a cross-sectional area no more than 0.02 m2 (0.22 ft2) and:
i)
ii)
iii)
Are not situated less than 600 mm (23.5 in.), measured along the duct, from its penetration of
any A or B class division, including continuous B class ceilings.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
Part
Chapter
Section
5
1
1
5-1-1
5.23
Ventilation ducts larger than 0.02 m2 (0.22 ft2) penetrating A class bulkheads or decks are to be
steel or lined with a steel sheet sleeve that:
i)
Are at least 3 mm thick and at least 900 mm (35.4 in.) Long (preferably 450 mm (17.7 in.) On
each side of bulkheads), provided with fire insulation having the same fire integrity as the
bulkhead or deck; and
ii)
Those exceeding 0.075 m2 (0.81 ft2), except those serving hazardous areas, are to also have
automatic fire damper and manual closures from both sides with a position indicator. The fire
dampers are not required for ducts through spaces which have the same fire integrity as the
divisions which they penetrate.
5.25
Ducts provided for ventilation of machinery spaces of Category A, hazardous areas, and galleys are
not to pass through accommodation and service spaces or control stations. However, some relaxation
from this requirement (except for the ducts serving hazardous areas and passing through accommodation
spaces, control stations, and galleys) will be considered, provided that the ducts are:
i)
Constructed of steel at least 3 mm (0.12 in.) Thick for ducts 300 mm (12 in.) Wide or less and
at least 5 mm (0.20 in.) For ducts 760 mm (30 in.) Wide and over. The minimum thickness is
to be interpolated for widths or diameters between 300 and 760 mm (12 and 30 in.);
ii)
Fitted with an automatic fire damper close to the boundaries penetrated; and
iii)
Insulated to A-60 standard from the machinery space or galleys to a point at least 5 m (16.4
ft) beyond each fire damper;
or
iv)
v)
Insulated to A-60 standard throughout the accommodation spaces, service spaces or control
stations.
5.27
Ducts provided for ventilation of accommodation and service spaces or control stations are not to pass
through machinery spaces of Category A hazardous areas or galleys. However, a relaxation from this
requirement, except for the ducts passing through hazardous areas, will be considered, provided:
i)
The ducts where they pass through a machinery space of category A or a galley are constructed
of steel in accordance with 5-1-1/5.25i).
ii)
Automatic fire dampers are fitted close to the boundaries penetrated; and
iii)
The integrity of the machinery space or galley boundaries is maintained at the penetrations;
or
iv)
The ducts where they pass through a machinery space of category A or a galley are constructed
of steel in accordance with 5-1-1/5.25i); and
v)
5.29
Ventilation ducts larger than 0.02 m2 (0.22 ft2) penetrating B class bulkheads are to be steel or lined
with steel sheet sleeves at least 450 mm (17.7 in.) on each side of the bulkhead.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
Part
Chapter
Section
5
1
1
5-1-1
5.31
Exhaust ducts from galley ranges are to be A class fire division integrity or equivalent where they
pass through accommodation spaces or spaces containing combustible materials, and these ducts are
to be fitted with:
i)
ii)
iii)
Arrangements, operable from within the galley, for shutting off the exhaust fans; and
iv)
5.33
All ventilation systems main inlets and outlets are to be capable of being closed from outside the space
being ventilated.
5.35
Power ventilation of accommodation spaces, service spaces, control stations, machinery spaces and
hazardous areas are to be capable of being stopped from an easily accessible position outside the
space being served and in the event of a fire in the space served. The means for stopping the power
ventilation serving machinery spaces or hazardous areas are to be entirely separate from the means
provided for stopping ventilation of other spaces.
5.37
Windows and sidescuttles in boundaries which are required to meet an A-60 standard which face
the drill floor area are to be:
i)
ii)
(1999) Protected by a water curtain system on the exposed wall. The water curtain system
should be designed to provide a discharge rate of 6.0 liters per minute per square meter (0.15
gpm per square foot); or
iii)
5.39
The ventilation of the accommodation spaces and control stations are to be arranged in such a way as
to prevent the ingress of flammable, toxic or noxious gases, or smoke from surrounding areas.
10
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
PART
Chapter
2:
Active
Fire
Protection
Systems
and
Equipment
5
CHAPTER
CONTENTS
SECTION 1
SECTION 2
General..................................................................................13
1
3.3
SECTION 3
3.1
Fire Pumps...................................................................... 15
1.3
1.5
FIGURE 1
3.1
General ........................................................................... 21
3.3
Foam ....................................................................................22
5.1
5.3
11
9.1
General ........................................................................... 23
9.3
9.5
11.3
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
11
SECTION 4
Extinguishers...................................................................25
1.3
Sand ................................................................................25
Firemans Outfit....................................................................25
3.1
SECTION 5
3.3
Breathing Apparatus........................................................25
3.5
Lifeline .............................................................................26
3.7
3.9
3.11
Helmet .............................................................................26
3.13
TABLE 1
TABLE 2
12
Number............................................................................25
1.3
1.5
1.7
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
PART
Section
1:
General
5
CHAPTER
SECTION
General
3.1
General
The following plans together with supporting data and particulars are to be submitted.
Firemans outfits
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
13
Part
Chapter
Section
3.3
5
2
1
5-2-1
14
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
PART
Section
2:
Fixed
Fire
Fighting
Systems
5
CHAPTER
SECTION
1.1
Fire Pumps
1.1.1
Number of Pumps
There are to be at least two independently-driven fire pumps. The pumps, their source of
power, and piping and valves are to be arranged so that a fire in any one compartment will not
put all fire pumps out of action.
1.1.2
Location of Pumps
1.1.2(a) Location. The two main fire pumps are to be in separate compartments having no
direct access between them. Where this is impracticable, special consideration will be given
to accesses as follows,
i)
A watertight door capable of being operated locally from both sides of the bulkhead, and
from a safe and accessible location outside of these spaces. For unattended propulsion
machinery space operation, this door is to be operable from the fire fighting station; or
ii)
An air lock consisting of two gastight steel doors. The doors are to be self closing
without any hold back arrangements.
iii)
Common boundaries are to be at least A-0 construction, except if more than one bulkhead or
deck is common, the boundaries are to be at least A-60 construction.
1.1.2(b) Remote Operation. Valves and pumps in the fire-fighting system which are not
readily accessible are to be provided with means for remote operation.
1.1.3
Type of Pumps
Sanitary, ballast, bilge or general-service pumps may be accepted as one of the fire pumps,
provided that they are not normally used for pumping oil and that if they are subject to
occasional duty for the transfer or pumping of fuel oil, suitable changeover arrangements are
fitted.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
15
Part
Chapter
Section
5
2
2
1.1.4
5-2-2
Pressure (1996)
The pressure for the purpose of determining fire pump capacity in accordance with 4-4-1/7.9.1
is to be at least 3.5 bar (3.5 kgf/cm2, 50 psi) at the hydrant.
The maximum pressure at any hydrant shall be such that the effective control of a fire hose
can be demonstrated.
1.1.5
Pump Capacity
1.1.5(a) General (1996). Each of the fire pumps required by 5-2-2/1.1.1 is to have a capacity
sufficient to deliver, while maintaining the pressure specified in 5-2-2/1.1.4, two jets of water
from nozzles that are connected to the two hydrants at which the pressure drop from the fire
pump discharge pressure will be the greatest.
Where a fire pump is utilized for the foam system provided for helicopter deck protection, the
pump is also to be capable of maintaining a pressure at the foam station as specified in
5-2-3/9.5.2. If the water consumption for any other fire protection or fire-fighting purposes
exceed the rate of the helicopter deck foam installation, this consumption is to be the
determining factor in calculating the required capacity of fire pumps.
In no case is the single pump capacity to be less than 25 m3/hr (110 gal/min.).
1.1.5(b) Ship-Type Drilling Units.
i)
Total Pump Capacity. For ship-type units, the fire pumps required by 5-2-2/1.1.1 are
to be capable of delivering for fire-fighting purposes a quantity of water, at the
appropriate pressure prescribed, not less than four-thirds of the quantity required under
4-5-2/7.3 to be dealt with by each of the independent bilge pumps when employed on
bilge pumping, using in all cases L = length of the unit as defined in 3-1-1/3 of the
Rules for Building and Classing Steel Vessels (Steel Vessel Rules), except that the total
required capacity of the fire pumps need not exceed 180 m3/hr (792 gal/min.).
ii)
Individual Pump. Capacity Each of the fire pumps required by 5-2-2/1.1.1 is to have
a capacity not less than 80% of the total required capacity divided by the number of
required pumps but not less than that required by 5-2-2/1.1.5(a) above. Where more
pumps than required are installed, their capacity will be subject to special consideration.
1.1.6
Relief Valves
In conjunction with all fire pumps, relief valves are to be provided if the pumps are capable of
developing a pressure exceeding the design pressure of the water-service pipes, hydrants and
hoses. These valves are to be so placed and adjusted as to prevent excessive pressure in any
part of the fire main system. In general, the relief valve is to be set to relieve at no greater
than 1.7 bar (1.75 kgf/cm2, 25 psi) in excess of the pump pressure necessary to maintain the
requirements of 5-2-2/1.1.4.
1.1.7
16
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
Part
Chapter
Section
5
2
2
1.1.7(b) Features.
intermediate tank.
1.1.8
1.3
5-2-2
i)
ii)
Two means to replenish water in the intermediate tank are to be provided. Each pump
is to be arranged to deliver at least the amount of water expended under the conditions
of 5-2-2/1.1.4. At least one of the replenishment pumps is to be arranged for
automatic operation. The arrangement of such pumps is to comply with 5-2-2/1.1.1.
iii)
If the drilling unit is intended to operate where the atmospheric temperature is expected
to be 0C (32F) or less, the entire fire-fighting system, including tanks used as water
reservoirs, is to be protected from freezing.
Fire Main
1.3.1
Size
The diameter of the fire main and water-service pipes is to be sufficient for the effective
distribution of the maximum required discharge from two fire pumps operating simultaneously,
except that the diameter need only be sufficient for the discharge of 140 m3/hr (616 gal/min.).
1.3.2
Cocks or Valves
A valve is to be fitted to serve each fire hose so that any fire hose may be removed while the
fire pumps are at work.
1.3.3
Isolation
Isolating valves and other arrangements, as necessary, are to be provided so that if a fire
pump and its associated piping within its compartment are rendered inoperable, the fire main
can be pressurized with a fire pump located in another compartment.
1.3.4
1.3.5
Materials (1997)
Materials readily rendered ineffective by heat are not to be used for fire mains unless
adequately protected. In order to be considered not readily rendered ineffective by heat, a
component is to be certified as having passed an applicable recognized fire test, or the
material is to have a melting temperature higher than the test temperature specified in an
applicable fire test.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
17
Part
Chapter
Section
1.5
5
2
2
5-2-2
Hydrants (1997)
The number and position of the hydrants are to be such that at least two jets of water not
emanating from the same hydrant, one of which is to be from a single length of hose, may
reach any part of the unit normally accessible to the passengers or crew while the unit is being
navigated.
The pipes and hydrants are to be so placed that the fire hoses may be easily coupled to them.
In units where equipment or stores may be carried on deck, the positions of the hydrants are
to be such that they are always readily accessible and the pipes are to be arranged, as far as
practicable, to avoid risk of damage by such equipment or stores.
Materials readily rendered ineffective by heat are not to be used for hydrants. See 5-2-2/1.3.5.
1.5.2
Hoses (1997)
Each of the hydrants required by 5-2-2/1.5.1 is to be provided with a fire hose complete with
couplings and nozzles. Additionally, at least one complete fire hose assembly is to be carried
as a spare.
Fire hoses are to be certified by a competent independent testing laboratory as being constructed
of nonperishable material to recognized standards. The hoses are to be sufficient in length to
project a jet of water to any of the spaces in which they may be required to be used. The
maximum length of hose is not to exceed 23 m (75 ft).
Each hose is to be provided with a dual purpose nozzle in accordance with 5-2-2/1.5.3 and
necessary couplings. Fire hoses together with any necessary fittings and tools are to be kept
ready for use in conspicuous positions near the water-service hydrants of connections.
18
1.5.3
Nozzles (1997)
Dual purpose combined jet spray nozzles are to be fitted throughout the unit with a minimum
nozzle diameter of 12 mm (1/2 in.). Fire hose nozzles of plastic type material such as
polycarbonate may be accepted, subject to review of their capacity and serviceability as
marine use fire hose nozzles.
1.5.4
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
Part
Chapter
Section
5
2
2
5-2-2
FIGURE 1
International Shore Connection
Coupling permanently attached that will
fit the vessel's hydrants and hose.
14.5 mm (9/16 in.)min.
Flat Face
64 mm
(21/2 in.)
132 mm
(51/4 in.)
178 mm
(7 in.)
19 mm
(3/4 in.)
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
19
PART
Section
3:
Additional
Fixed
Fire
Fighting
Systems
5
CHAPTER
SECTION
Main or auxiliary oil-fired boilers and other processes of equivalent thermal rating.
ii)
iii)
iv)
Internal combustion machinery used for purposes other than main propulsion having a total
power output of not less than 750 kW (1000 hp).
v)
Gas Smothering
3.1
General
3.1.1
Storage (2002)
Where the gas smothering medium is stored outside of the protected space, the storeroom is
to be situated in a safe and readily accessible position and is to be effectively ventilated by a
ventilation system independent of all other spaces.
Spaces for storage of cylinders or tanks for extinguishing gas should not be used for other
purposes. These spaces should not be located forward of the forward collision bulkhead.
Access to these spaces should be possible from the open deck. Spaces situated below the deck
should be located no more than one deck below the open deck.
Spaces where entrance from the open deck is not provided or which are located below deck
are to be fitted with mechanical ventilation. The exhaust duct (suction) should be lead to the
bottom of the space. Such spaces should be ventilated with at least six air changes per hour.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
21
Part
Chapter
Section
5
2
3
5-2-3
3.1.2
Design
Containers and associated pressure components are to be designed based upon an ambient
temperature of 55C (131F).
3.1.3
Alarm (1995)
Means are to be provided for automatically giving audible warning of the release of fire
extinguishing gas into any space to which personnel normally have access. The alarm is to
operate for at least a 20-second period before the gas is released. Alarms may be pneumatically
(by the extinguishing medium or by air) or electrically operated.
3.1.3(a) Electric. If electrically operated, the alarms are to be supplied with power from the
main and an emergency source of electrical power.
3.1.3(b) Pneumatic. If pneumatically operated by air, the air supply is to be dry and clean,
and the supply reservoir is to be automatically kept charged at all times and is to be fitted
with a low pressure alarm. The air supply may be taken from the starting air receivers. Any
stop valve fitted in the air supply line is to be locked or sealed in the open position. Any
electrical components associated with the pneumatic system are to be powered from the main
and an emergency source of electrical power.
3.1.4
3.3
Controls
Except as otherwise permitted herein two independent manual control arrangements are to be
provided, one of them being positioned at the storage location and the other in a readily
accessible position outside of the protected space.
Foam
5.1
5.3
22
Reference is made to the International Maritime Organization MSC/Circular 670 Guidelines for the Performance
and Testing Criteria, and Surveys of High-Expansion Foam Concentrates for Fixed Fire-Extinguishing Systems.
Application
Low expansion foam systems may be fitted in machinery spaces in addition to the required
fixed fire extinguishing system.
5.3.2
Design (1998)
In addition to the applicable requirements of the Rules, fixed low expansion foam systems are to
be in accordance with Chapter 6.2.1 and 6.2.2 of the International Code for Fire Safety Systems.
Foam concentrates are to be of an approved type.**
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
Part
Chapter
Section
5
2
3
5-2-3
** Note: Reference is made to the International Maritime Organization MSC/Circular 582 Guidelines for the
Performance and Testing Criteria, and Surveys of Low-Expansion Foam Concentrates for Fixed FireExtinguishing Systems.
9.1
General
Where areas of a unit are designated for helicopter operations, details of the facilities are to be submitted
and the firefighting systems of 5-2-3/9.3 and 5-2-3/9.5 are to be provided and stored near the access to
those areas.
Deckhouse tops directly below helicopter decks are to have no openings. See 4-2-2/25 for helicopter
deck drainage.
9.3
9.5
9.3.2
Portable Extinguishers
The helicopter deck area is to be protected by at least two approved dry powder extinguishers
of a total capacity of not less than 45 kg (100 lb). At least one portable extinguisher is to be
located at each helicopter deck access point.
9.3.3
Back-up System
A back-up firefighting system is to be provided, consisting of CO2 extinguishers of a total capacity
of not less than 18 kg (40 lb) or equivalent, one of these extinguishers being equipped so as to
enable it to reach the engine area of any helicopter using the deck. The back-up system is to
be located so that the equipment would not be vulnerable to the same damage as the dry powder
extinguishers required by 5-2-3/9.3.
Firefighting Systems
A firefighting system as required by 5-2-3/9.3 is to be provided and arranged so as to adequately
protect both the helicopter deck and helicopter fuel storage areas.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
23
Part
Chapter
Section
5
2
3
9.5.2
11
5-2-3
11.1
Lockers of 4 m2 (43 ft2) or More Floor Area and Lockers with Access to
Accommodation Spaces
Paint lockers and flammable liquid lockers of floor area 4 m2 (43 ft2) or more and also such lockers of
any floor area with access to accommodation spaces are to be provided with one of the fixed fireextinguishing systems specified below:
11.3
i)
ii)
Dry powder system, designed for at least 0.5 kg/m3 (0.03 lb/ft3).
iii)
Water spraying system, designed for 5 liters/m2/minute (0.12 gpm/ft2). The water spraying
system may be connected to the units fire main system, in which case the fire pump capacity
is to be sufficient for simultaneous operation of the fire main system as required in 5-2-3/11.9
and the water spray system. Precautions are to be taken to prevent the nozzles from being
clogged by impurities in the water or corrosion of piping, nozzles, valves and pump.
iv)
Systems or arrangements other than those referenced above may be also considered, provided
they are not less effective.
24
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
PART
Section
4:
Portable
Fire
Fighting
Systems
5
CHAPTER
SECTION
1.1
Extinguishers
Portable and semi-portable extinguishers are to be provided in the quantities and locations indicated
in 5-2-4/Table 1 and 5-2-4/Table 2. The fire extinguishers are to be visible and readily accessible.
1.3
Sand
On self-propelled units fitted with main or auxiliary oil-fired boilers, each firing space is to be provided
with a receptacle containing at least 0.28 m3 (10 ft3) of sand, sawdust impregnated with soda or other
dry material suitable for extinguishing oil fires. Alternatively, an approved portable extinguisher may be
substituted therefore.
3.1
Number
At least two firemans outfits consisting of a breathing apparatus, a lifeline, a safety lamp, an axe,
nonconductive boots and gloves, a rigid helmet and protective clothing complying with the requirements
of this paragraph are to be stored so as to be easily accessible and ready for use and are to be stored in
separate positions so that a fire in one location would not block access to both outfits.
3.3
Breathing Apparatus
The breathing apparatus is to be of an approved type and may be one of the following:
i)
A smoke helmet or smoke mask with a suitable air pump and a length of air hose sufficient to
reach from the open deck, well clear of hatch or doorway, to any part of below deck spaces or
machinery spaces. If, in order to comply with this requirement, an air hose exceeding 36 m
(120 ft) in length would be necessary, a self contained breathing apparatus is to be substituted
or provided in addition.
ii)
A self contained breathing apparatus which is capable of functioning for a period of at least
30 minutes. Other periods of time will be specially considered. At least one spare charge is be
carried for each required breathing apparatus carried onboard.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
25
Part
Chapter
Section
3.5
5
2
4
5-2-4
Lifeline
Each breathing apparatus is to have attached to its belt or harness, by means of a snap-hook, a
fireproof lifeline of sufficient length and strength.
3.7
3.9
3.11
Helmet
A rigid helmet is to be supplied which will provide effective protection against impact.
3.13
Protective Clothing
The protective clothing is to be made of material that will protect the skin from the heat of fire and
burns from scalding steam. The outer surface is to be water resistant.
TABLE 1
Classification of Portable and Semi-portable Extinguishers
Fire extinguishers are designated by types as follows: A, for fires in combustible materials such as wood; B, for fires in
flammable liquids and greases; C, for fires in electrical equipment.
Fire extinguishers are designated by size where size I is the smallest and size V is the largest. Sizes I and II are hand portable
extinguishers, and sizes III, IV, and V are semiportable extinguishers.
Classification
Type
Size
Water, liters
(U.S. gallons)
Foam, liters
(U.S. gallons)
Carbon Dioxide,
kg (lb)
Dry Chemical,
kg (lb)
Halon
1211 kg (lb)
A
B
B
B
B
B
C
C
C
C
II
I
II
III
IV
V
I
II
III
IV
9.5 (2.5)
9.5 (2.5)1
4.7 (1.25)
9.5 (2.5)1
45.5 (12)1
76 (20)1
152 (40)1
11.8 (4)
16.7 (15)
15.8 (35)
22.5 (50)
1.45 (100) (1)
11.8 (4)
16.7 (15)
15.8 (35)
22.5 (50)
1.1 (2.5)
4.5 (10) (3)
Notes:
26
For outside use, double the quantity of agent that must be carried.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
Part
Chapter
Section
5
2
4
5-2-4
TABLE 2
Hand Portable Fire Extinguishers and
Semi-portable Fire-Extinguishing Systems
Space
Classification*
Safety areas
Wheelhouse and control room
Stairway and elevator enclosure
Corridors
C-I
A-II
C-I
None required.
1 in each corridor not more than 45 m (150 ft) apart.
(May be located in stairways.)
None required.
2 near the exit. (See Note 1)
Accommodations
Staterooms, toilet spaces, public spaces, offices,
lockers, small storerooms, and pantries, open
decks, and similar spaces.
None required.
B-II or C-II
Service spaces
Galleys
Paint and lamp rooms
Storerooms
B-II
A-II
C-II
Machinery spaces
Oil-fired boilers: Spaces containing oil-fired
boilers, either main or auxiliary, or their fuel
units
Internal combustion or gas turbine machinery
spaces.
B-II
B-V
B-II
1 for each 746 kW (1000 hp) but not less than 2 nor
more than 6 in each space.
1 required in each space. (See Note 3)
1 for each motor or generator.
B-III
C-II
B-II
Auxiliary spaces
Internal combustion engines or gas turbine
Electric emergency motors or generators
C-II
C-II
B-II
(See 4-4-1/37.3)
(See 4-4-1/37.5)
None required.
1 outside the space containing engines or turbines in
vicinity of exit. (See Note 2)
1 outside the space containing motors or generators
in vicinity of exit. (See Note 2)
None required.
None required.
None required.
2 required.
1 required.
Notes:
1
See 4-4-1/Table 1.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
27
PART
Section
5:
Fire
and
Gas
Detection
5
CHAPTER
SECTION
1.1
1.3
General Alarm
Alarm signal devices are to produce a distinctive and loud sound. Attention is directed to the proper
governmental authority concerning the requirements for general alarm systems on units.
1.5
1.7
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
29
Part
Chapter
Section
5
2
5
5-2-5
Cellar deck
ii)
Drill floor
iii)
iv)
v)
Enclosed spaces containing open components of the mud circulation system from the bell
nipple to the mud pits.
The gas detectors are to be connected to an audible and visual alarm system with indicators on the
drill floor and at the required emergency control stations (See 5-3-1/7). The alarm system is to clearly
indicate the location and concentration of the gas hazard. The combustible gas detectors are to alarm
at not more than 25% and at 60% of the lower explosive limit (LEL).
In addition to the fixed automatic gas detection system, two portable combustible gas detectors are to
be provided for operating personnel to locate small leaks.
30
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
PART
Chapter
3:
Outfitting
5
CHAPTER
Outfitting
CONTENTS
SECTION 1
General..................................................................................33
1
5.3
9.3
Other Auxiliaries.............................................................. 35
9.5
9.7
11
13
15
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
31
PART
Section
1:
General
5
CHAPTER
Outfitting
SECTION
General
1.1
The following requirements are to apply to accommodation spaces, service spaces and control stations:
1.1.1
In every general area that is likely to be regularly manned or in which personnel are
accommodated, at least two separate escape routes are to be provided, situated as far apart as
practicable, to allow ready means of escape to the open decks and/or embarkation stations.
Exceptionally, one means of escape may be considered, taking into account the nature and
location of spaces and the number of persons who might normally be accommodated or employed
there.
1.1.2
Stairways are to normally be used for means of vertical escape. However, a vertical ladder
may be used for one of the means of escape from machinery spaces when the installation of a
stairway is shown to be impracticable.
1.1.3
Every escape route should be readily accessible and unobstructed and all exit doors along the
route are to be readily operable from both sides. Dead-end corridors exceeding 7 m (23 ft) in
length are not permitted.
1.3
Two means of escape are to be provided from every machinery space of Category A by either of the
following:
1.3.1
Two sets of steel ladders as widely separated as practicable leading to doors in the upper part
of the space similarly separated and from which access is provided to the open deck. In
general, one of those ladders should provide continuous fire shelter from the lower part of the
space to a safe position outside the space. However, the shelter may not be required if, due to
special arrangements or dimensions of machinery space, a safe escape route from the lower
part of this space is provided. This shelter is to be of steel, insulated, where necessary, and
provided with a self-closing steel door, operated from both sides, at the lower end.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
33
Part
Chapter
Section
5
3
1
5-3-1
1.3.2
One steel ladder leading to a door in the upper part of the space from which access is provided
to the open deck and, additionally, in the lower part of the space and in a position well separated
from the ladder referred to, a steel door capable of being operated from each side and which
provides access to a safe escape route from the lower part of the space to the open deck.
Exceptionally, one means of escape may be permitted, due regard being paid to the nature and
location of spaces and to the number of persons who might normally be employed there.
1.5
From machinery spaces other than those of Category A, escape routes are to be provided having regard
to the nature and location of the space and whether persons are normally employed in that space.
1.7
Elevators are not to be considered as forming one of the required means of escape.
1.9
At least one escape route from the superstructure and deckhouses to the survival craft embarkation
area is to be protected against radiation effects of a drill floor area fire as far as practicable
5.1
5.3
34
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
Part
Chapter
Section
5
3
1
5-3-1
Manually operated contact makers for actuating the general alarm system.
An efficient means of communication between these stations and all locations vital to the safety
of the unit.
9.1
9.3
Other Auxiliaries
Machinery driving forced and induced draft fans, electric motor pressurization fans, oil fuel unit
pumps and other similar fuel pumps are to be fitted with remote controls situated outside of the space
concerned so that they may be manually stopped in the event of a fire arising in the space in which
they are located.
9.5
9.7
11
ii)
iii)
Fixed fire extinguishing system capable of activation from outside the room. The extinguishing
system is to be separate for the room but may be part of the main fire extinguishing system
for the machinery space.
iv)
Means of closing ventilation openings from a position close to where the fire extinguishing
system is activated
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008
35
Part
Chapter
Section
5
3
1
5-3-1
If it is impracticable to locate the fuel oil purifiers in a separate room, special consideration will be
given in regard to location, containment of possible leakage, shielding and ventilation. In such cases, a
local fixed fire extinguishing system is to be provided and arranged to be activated automatically,
where permitted, or manually from the machinery control position or from another suitable location.
If automatic release is provided, additional manual release is also to be arranged.
13
15
36
i)
The surfaces of all internal combustion engines, gas turbines, boilers, exhaust pipes and other
exposed parts which may be heated to a temperature in excess of 220C (428F) and may be
exposed to flammable liquids are to be insulated. Where insulation is oil absorbing and
exposed to penetration of oil, this insulation is to be encased in sheet metal or an equivalent
impervious sheet.
ii)
Drip trays for collecting oil, as required in 4-5-1/9.29, are to be fitted below pumps, burners,
tanks, etc. They are to be of suitable height and provided with suitable drainage to a collecting
tank incorporating a high level alarm.
iii)
Hydraulic pumps, actuators, motors and accessories are to be suitable for the intended duty,
compatible with the working fluid and are to be designed to operate safely at full-power
conditions. In general, the hydraulic fluid is to be nonflammable or have a flash point above
157C (315F).
iv)
For unmanned machinery spaces, fuel oil heaters, purifiers, pumps and filters are to be shielded
or grouped in a special room or location ventilated by suction.
ABS RULES FOR BUILDING AND CLASSING MOBILE OFFSHORE DRILLING UNITS . 2008